Baptist Primary Care Atlantic Beach Final Reportjf
Baptist Primary Care Atlantic Beach
Test and Balance Report
Table of Contents
Project Details 1
Certification Page 2
Abbreviation Page 3
Instrument Calibration Report 4
Project Summary 5
Plan Layout 6
Building Pressure Analysis 7
Unit Sheet AHU-1 8
AHU-1 OA CFM Test 9
AHU-1 Diffuser Report 10
Unit Sheet AHU-2 11
AHU-2 OA CFM Test 12
AHU-2 Diffuser Report 13
Unit Sheet AHU-3 14
AHU-3 OA CFM Test 15
AHU-3 Diffuser Report 16
Unit Sheet AHU-4 17
AHU-4 OA CFM Test 18
AHU-4 Diffuser Report 19
Fan Test Report 20
Project: Baptist Primary Care
Mechanical Engineer: Gregory Engineering
Architect: Lilly Haynes Architecture, Inc.
HVAC Contractor: Accu Air
TAB Firm: Holistic Test and Balance
TAB CT : Shawn Berlinghoff
Project Details
NCI Certified Test and Balance Report
Report Date: 10/25/2021
Page 1
CerUUed Commercial Air Balancer SHAWN BERLINGHOFF
Has successfully completed the required training and passed the written exam by the
to perform HVAC commercial system balancing up to 20 tons
according to NCI practical standards and procedures.
�rnfo
I l �
nal Candon Inst/tu•• g
rtifi /
Certified Since: January 28, 2021
Certification# 21-016-07
Expires: January 28, 2023
�� Rob Falke, President, National Comfort Institute, Inc.
Page 2
AC or ACU Air Conditioner or Air Conditioning Unit TDH Pressure Difference across the entering
AH or AHU Air Handler or Air Handling Unit and leaving side of a pump.
AVG Average HEPA High Efficiency Particulate Arrestance
BHP Brake Horsepower HP Horsepower
CAV Constant Air Volume HVAC Heating Ventilation and Air Conditioning
CBV Calbirated Balancing Valve HWS Heating Water Supply
(Circuit Setter)HWR Heating Water Return
CC Cooling Coil HX Heat Exchanger
CD Ceiling Diffuser HZ Hertz, cycle per second
in.inches
CFM Cubic Feet per Minute in.w.g.inches of water gauge
CH Chiller Kfactor Correction factor to the free area need to
CHWS Chilled Water Supply calculate CFM.
CHWR Chilled Water Return KW Kilowatts
LAT Leaving Air Temperature
CP Circulating Pump LWG Low Wall Grille
CR Ceiling Register LWR Low Wall Register
CRAC Computer Room Air Conditioner LWT Leaving Water Temperature
CRU Computer Room Unit MAU Make-up Air Hangling Unit
CT Cooling Tower MBH 1,000 BTUH
CU Condenser Unit
CUH Cabinet Unit Heater
CWS Condenser Water Supply
N/A Not Applicable
NV Not Visible
NS Not Specified
CWR Condenser Water Return ∆P Pressure Drop.
DAT Discharge Air Temperature PH Phase
DB Dyr Bulb PSI Pounds per Square Inch
DD Direct Drive RA Return Air
DDC Direct Digital Controls: EMS Control RAT Return Air Temperature
System for the HVAC RF Return Fan
Des.Design RH Relative Humidity
Dia.Diameter RHC Reheat Coil
Disch.Discharge RPM Revolutions per Minute
EA Exhaust Air RTU Roof Top Unit
EAT Entering Air Temperature SA Supply Air
Economizer Controls and components that allow an SAT Supply Air Temerature
air handler to logically utilize outdoor air S.F.Service Factor
for cooling as opposed to the use of SF Supply Fan
mechanical cooling.SFD Smoke/Fire Damper
EF Exhaust Fan SP Static Pressure
EG Exhaust Grille sq.ft.square feet
EMCS Energy Management Control System Suct.Suction
ERU Energy Recovery Unit SWG Sidewall Grille
E.S.P.External Static Pressure SWR Sidewall Register
HRC Heat Recovery Coil TAB Test; Adjust; and Balance
EWT Entering Water Temperature TSP Total Static Pressure: Difference
FCU Fan Coil Unit between the entering and leaving
FD Fire Damper static pressure of a fan.
FLA Full Load Amperage: Maximum UH Unit Heater
amperage a motor can draw.VAV Variable Air Volume; box that
Flow Hood Instrument that captures air and contains a motorized damper that
converts the reading to CFM.modulates airflow.
FHT VD Volume Damper
FPB Fan Powered Box VFD Variable Frequency Drive
FPM Feet per Minute Velgrid Instrument that reads used to read
FR Field Report velocity in feet per minute.
FT Foot, Feet VVT Variable Volume Terminal
FTU Fan Terminal Unit WC Water Column
GPM Gallons per Minute W.G.Water Gauge
HC Heating Coil WB Wet Bulb
Fume Hood Test
Common Test and Balance Terms
Page 3
www.htbjax.com Holistic Test and Balance, Inc.Phone (904)-900-1484
Fax (904)-900-1485
Velgrid: 1 Total Velgrid a 12"x12" square and accurately measures 25-2500 fpm face velocity grid for coil, filter, fume hood, outside air louver, and clean
room testing)
Pitot Tube Sizes:12", 18", 24", 36", 48"
Evergreen Flow Hood Sizes: 15" Base (NIST-traceable accuracy from 100 CFM to 2500 supply, 2000 exhaust), 8" Base (accurate readings of
bathroom grilles and similar diffusers. Readings as low as 24 CFM can be made accurately due to the small cross-sectional area of this base)
Shawn Berlinghoff Instrument
Calibration Report
Instrument
10/8/2021Testo4205.06075E+11 Digital Direct Reading
Capture Hood 10/8/2020
2/25/2022
2/25/2021 2/25/2022
2/25/2022
Evergreen Telemetry S-H-3-5 2100099 Humidity 2/25/2021 2/25/2022
Evergreen Telemetry S-PVF-1 1700121 Air Pressure 2/25/2021
Evergreen Telemetry S-PVF-1 1700121
Evergreen Telemetry S-PVF-1 1700121 FHT Air Velocity
Air Velocity Instrument 2/25/2021
2/25/2022
Evergreen Telemetry PR-T-1 1700283 Temperature Probe 2/25/2021 2/25/2022
Evergreen Telemetry RM-T-1 2100099 Temperature Module 2/25/2021
Klein CL120 0520U-A1 Amperage Measurement 2/25/2021
2/25/2022
Extech 461920 201001990 Tachometer/Counter 2/25/2021 2/25/2022
Evergreen Telemetry S-H-3-5 2100098 Humidity 2/25/2021
Model #Serial #Application Calibration Test Date Calibration End Date
2/25/2022
Klein CL120 0520U-A1 Voltage Measurement 2/25/2021 2/25/2022
Page 4
Date:SB
Remark
7
8
Technician:
5
2
3
4
6
9
Project Summary
Item #
1 For reference supply air is numbered blue, return air is numbered pink, exhaust air is numbered green, and finally
outside air where applicable is highlighted orange. This is done to emphasize drawings and locations of diffusers/duct
better.
Project:Baptist Primary Care
10/25/2021
All diffusers read using a direct reading flowhood. Diffusers totaled specifically for each unit and ensured within design
airflow.
Diffusers correlated from plan layout to diffuser report to show the exact diffuser being read and where it is located on
the drawings.
Building pressure is slightly positive at 137 cfm at the front entry with all systems running.
Cooling and heating test taken on all units, this shows units are within design capacity.
AHU's read by testing and then performing balance on each grille to ensure each grille is within design airflow
parameters. Grilles then totaled and ensured within design airflow tolerance. Once airflow balance is done, pressure
drops across unit components then taken and final cooling and heating test taken.
OA read using a pitot tube to convert velocity to OA cfm. Appropriate damper position then set to achieve design cfm.
EF's read with a direct reading flowhood to ensure each fan is set to within design airflow tolerance. There are multiple
EF-1 types, these have been numbered by TAB tech to properly correlate.
AHU-4 is designed for 1850 cfm total, however diffusers total 1860 cfm total. Diffusers able to be balanced to within
design airflow tolerance.
Page 5
NO
.
RE
V
I
S
I
O
N
D
E
S
C
R
I
P
T
I
O
N
DA
T
E
TH
I
S
D
R
A
W
I
N
G
I
S
A
N
I
N
S
T
R
U
M
E
N
T
O
F
S
E
R
V
I
C
E
A
N
D
S
H
A
L
L
R
E
M
A
I
N
T
H
E
P
R
O
P
E
R
T
Y
O
F
L
I
L
L
Y
H
A
Y
N
E
S
A
R
C
H
I
T
E
C
T
U
R
E
,
I
N
C
.
T
H
E
U
S
E
O
F
T
H
I
S
D
R
A
W
I
N
G
I
S
L
I
M
I
T
E
D
T
O
T
H
E
O
R
I
G
I
N
A
L
P
R
O
J
E
C
T
A
N
D
P
U
R
P
O
S
E
F
O
R
W
H
I
C
H
I
T
W
A
S
P
R
E
P
A
R
E
D
.
58
E
v
a
n
s
D
r
i
v
e
.
J
a
c
k
s
o
n
v
i
l
l
e
B
e
a
c
h
,
F
L
3
2
2
5
0
Co
r
p
o
r
a
t
e
L
i
c
e
n
s
e
N
o
.
A
A
2
6
0
0
2
4
2
8
.
P
h
o
n
e
N
o
.
9
0
4
.
2
0
7
.
1
8
7
1
4567 Deep River Place
Jacksonville, FL 32224
FBPE Certificate # 28163
(904) 714-5188
YROGERG
L E A H C
I
M
M
A
I
L
L
I
W P R O F E S S I O N A
L
E
N
G
I
N
E
E
R
F L O R
I
D
A
L
I
C
E N S E
No
.
4
6
6
0
7
ST
A
T
E
O
F
PROJECT NO.:
DATE: 08.11.20
20.002
ME
D
I
C
A
L
O
F
F
I
C
E
B
U
I
L
D
I
N
G
AT
L
A
N
T
I
C
B
O
U
L
E
V
A
R
D
.
A
T
L
A
N
T
I
C
B
E
A
C
H
,
F
L
3
2
2
3
3
AT
L
A
N
T
I
C
B
E
A
C
H
BA
P
T
I
S
T
Pr
i
m
a
r
y
C
a
r
e
ME
C
H
A
N
I
C
A
L
F
L
O
O
R
P
L
A
N
M1.1
1
2
34
5
6
7
8
9
10
1
2
345
1
2 3 45
6
1
2
3
4
5
6 7
8
9 10
11
12
13 14
15
16
17
1
2
3
Page 6
Technician:
Total Building Pressure Analysis
Date:
Building Static Pressure NA Building CFM Difference
Total CFM 610 Total CFM
Total Exhaust
137
473
68
74
73
52
206
231
EF-3
Exhaust Airflow Tested
127 EF-1(1)
EF-1(2)
EF-1(3)
EF-2
OA Airflow Tested Unit
125
127
Total Outside Air
Unit
10/25/2021SB
AHU-1
AHU-2
AHU-3
AHU-4
Page 7
Motor Make
HP
Frame
Full Load Amps 5.46
Service Factor
Volts/Phase 208 1PH 209
Corrected FLA
Fan RPM
DB:85.5°WB:Motor RPM
BHP
Total Fan CFM
Outlet CFM
Traverse CFM
Return Air CFM
Outside Air CFM
Embedded OA Ratio %
208 1PH Embedded TSP In. of W.C.
ESP In. of W.C.
Coil Pressure Differential
Entering Fan Pressure
Supply Duct Pressure
0.11
NA
NA
NA
0.48
0.42
HVAC Unit Test Report
Motor Design and Test
Test
1500
Design
NS
1500
1500
1375
125
Embedded
3/4
Embedded
Direct Drive
6
Direct Drive
Direct Drive
1
Miscellaneous Info
Direct Drive
NS
NS
46.00
81.2
NS10/25/2021
Coil Test Report
Filter Quantity
50.0
Fan Sheave
NS
Cooling LAWB F°52.4°Filter Model/Size
Cooling EAWB F°
Date:
Design
Cooling EADB F°75.0°
63.0°
OA Temp DB/WB
Test
NA
1517
NS
NS
Seasonal Test
Seasonal Test
Test
1517
Cooling MBH
27.9
1390
127
CFM 1517
Sensible MBH
Duct Detector Test
CFM and Pressure Test
NA46.00 Seasonal Test
1500
34.60
Design
Type
Area Served
Location
Unit Designation
Manufacturer
Model #
Serial #
6
Embedded
Embedded
Static Pressure Profile
0.530.6
Return Duct SP:
Mixing OA and RA SP:
Filter Pressure Differential
Unit and Nameplate Data
AHU-1
Carrier
FX4DNF049
1721F00053
HP
Multiple Areas
Atlantic Beach, Florida
Electric Heat Report
SBTested By:
HP
Test
71.2°
63.5°
Designation
8%
Design
Heating MBH
Direct Drive
NS High SpeedServiceSupply/Return
KW 10.0
Amps
Volts/Phase
NS
0.9
Belt Size/ Quantity
Motor Sheave
Center to Center
1.1
Heating EADB
Heating LADB
Cooling LADB F°54.2°
24x24x1
8%
Page 8
Type
1
620
675
1 628 670 689 651
642
607
127
Area 0.20
Total Velocity:
637
125
5182
Pitot TubeBaptist Primary Care
102%
Date
Design Velocity
Design CFM
Velocity Readings
0.20
Average Velocity
Damper Position:
Remarks
VFD Speed
25-Oct
Round Duct Traverse Test
System
Instrument Used
Outside AirAHU-1
Project
NA
6''
Area
648
Louver/Duct Size
% Variance
CFM Tested
10%
Page 9
VEL CFM VEL CFM
1 A 10''24"x24"Hood 375 368 98%
2 A 10''24"x24"Hood 375 379 101%
3 A 20"x6"20"x6"Hood 250 255 102%
4 A 20"x6"20"x6"Hood 250 263 105%
5 A 20"x6"20"x6"Hood 250 252 101%
1500 1517 101%
Technician:Date:
SupplyDuct Type:
# VarianceDesign
Diffuser Test Report
SYSTEM: AHU-1
101
Supply Air
Final
101
101
Test 1
101
AK or
HoodFace Size
101
Type Neck Size
10/25/2021
Area Served #
SB
Page 10
Motor Make
HP
Frame
Full Load Amps 3.34
Service Factor
Volts/Phase 208 1PH 211
Corrected FLA
Fan RPM
DB:86.4°WB:Motor RPM
BHP
Total Fan CFM
Outlet CFM
Traverse CFM
Return Air CFM
Outside Air CFM
Embedded OA Ratio %
208 1PH Embedded TSP In. of W.C.
ESP In. of W.C.
7%
Design
Heating MBH
Direct Drive
NS Medium SpeedServiceSupply/Return
KW 10.0
Amps
Volts/Phase
NS
0.83
Belt Size/ Quantity
Motor Sheave
Center to Center
0.7
Heating EADB
Heating LADB
Cooling LADB F°53.6°
22x20x1
11%
Embedded
Static Pressure Profile
0.470.6
Return Duct SP:
Mixing OA and RA SP:
Filter Pressure Differential
Unit and Nameplate Data
AHU-2
Carrier
FX4DNF037
1021F22257
HP
Multiple Areas
Atlantic Beach, Florida
Electric Heat Report
SBTested By:
HP
Test
70.3°
63.2°
Designation
Design
Type
Area Served
Location
Unit Designation
Manufacturer
Model #
Serial #
4.1
Embedded
Test
NA
1138
NS
NS
Seasonal Test
Seasonal Test
Test
1138
Cooling MBH
20.5
1013
125
CFM 1138
Sensible MBH
Duct Detector Test
CFM and Pressure Test
NA46.00 Seasonal Test
1100
26.00
36.00
81.9
NS10/25/2021
Coil Test Report
Filter Quantity
34.9
Fan Sheave
NS
Cooling LAWB F°52.9°Filter Model/Size
Cooling EAWB F°
Date:
Design
Cooling EADB F°75.0°
63.0°
OA Temp DB/WB
HVAC Unit Test Report
Motor Design and Test
Test
1100
Design
NS
1100
1100
1025
75
Embedded
1/2
Embedded
Direct Drive
4.1
Direct Drive
Direct Drive
1
Miscellaneous Info
Direct Drive
NS
NS
Coil Pressure Differential
Entering Fan Pressure
Supply Duct Pressure
0.09
NA
NA
NA
0.45
0.38
Page 11
Type
1
642
664
1 619 647 658 613
643
621
125
Area 0.20
Total Velocity:
637
125
5107
Pitot TubeBaptist Primary Care
100%
Date
Design Velocity
Design CFM
Velocity Readings
0.20
Average Velocity
Damper Position:
Remarks
VFD Speed
25-Oct
Round Duct Traverse Test
System
Instrument Used
Outside AirAHU-2
Project
NA
6''
Area
638
Louver/Duct Size
% Variance
CFM Tested
10%
Page 12
VEL CFM VEL CFM
1 A 8''24"x24"Hood 230 238 103%
2 A 6''24"x24"Hood 75 77 103%
3 A 8''24"x24"Hood 145 150 103%
4 A 8''24"x24"Hood 275 283 103%
5 A 8''24"x24"Hood 240 251 105%
6 A 8''24"x24"Hood 135 139 103%
1100 1138 103%
Technician:Date:
SupplyDuct Type:
# VarianceDesign
Diffuser Test Report
SYSTEM: AHU-2
109
Supply Air
107
Final
106
109
Test 1
106
AK or
HoodFace Size
104
Type Neck Size
10/25/2021
Area Served #
SB
Page 13
Motor Make
HP
Frame
Full Load Amps 5.54
Service Factor
Volts/Phase 208 1PH 211
Corrected FLA
Fan RPM
DB:86.9°WB:Motor RPM
BHP
Total Fan CFM
Outlet CFM
Traverse CFM
Return Air CFM
Outside Air CFM
Embedded OA Ratio %
208 1PH Embedded TSP In. of W.C.
ESP In. of W.C.
7%
Design
Heating MBH
Direct Drive
NS Medium SpeedServiceSupply/Return
KW 10.0
Amps
Volts/Phase
NS
0.94
Belt Size/ Quantity
Motor Sheave
Center to Center
1.1
Heating EADB
Heating LADB
Cooling LADB F°55.2°
24x24x1
7%
Embedded
Static Pressure Profile
0.550.6
Return Duct SP:
Mixing OA and RA SP:
Filter Pressure Differential
Unit and Nameplate Data
AHU-3
Carrier
FX4DNF061
2121F07356
HP
Multiple Areas
Atlantic Beach, Florida
Electric Heat Report
SBTested By:
HP
Test
74.0°
64.3°
Designation
Design
Type
Area Served
Location
Unit Designation
Manufacturer
Model #
Serial #
6
Embedded
Test
NA
1910
NS
NS
Seasonal Test
Seasonal Test
Test
1910
Cooling MBH
38.7
1783
127
CFM 1910
Sensible MBH
Duct Detector Test
CFM and Pressure Test
NA58.00 Seasonal Test
1850
43.20
60.00
82.0
NS10/25/2021
Coil Test Report
Filter Quantity
64.1
Fan Sheave
NS
Cooling LAWB F°53.1°Filter Model/Size
Cooling EAWB F°
Date:
Design
Cooling EADB F°75.0°
63.0°
OA Temp DB/WB
HVAC Unit Test Report
Motor Design and Test
Test
1850
Design
NS
1850
1850
1725
125
Embedded
3/4
Embedded
Direct Drive
6
Direct Drive
Direct Drive
1
Miscellaneous Info
Direct Drive
NS
NS
Coil Pressure Differential
Entering Fan Pressure
Supply Duct Pressure
0.14
NA
NA
NA
0.53
0.41
Page 14
Type
1
611
638
1 634 672 685 633
670
648
127
Area 0.20
Total Velocity:
637
125
5191
Pitot TubeBaptist Primary Care
102%
Date
Design Velocity
Design CFM
Velocity Readings
0.20
Average Velocity
Damper Position:
Remarks
VFD Speed
25-Oct
Round Duct Traverse Test
System
Instrument Used
Outside AirAHU-3
Project
NA
6''
Area
649
Louver/Duct Size
% Variance
CFM Tested
10%
Page 15
VEL CFM VEL CFM
1 A 12''24"x24"Hood 420 432 103%
2 A 6''24"x24"Hood 100 106 106%
3 A 8''24"x24"Hood 180 176 98%
4 A 8''24"x24"Hood 180 188 104%
5 A 8''24"x24"Hood 180 182 101%
6 A 8''24"x24"Hood 180 192 107%
7 A 8''24"x24"Hood 180 186 103%
8 A 8''24"x24"Hood 180 188 104%
9 B 6''12"x12"Hood 50 53 106%
10 A 8''24"x24"Hood 200 207 104%
1850 1910 103%
Technician:Date:
SupplyDuct Type:
# VarianceDesign
Diffuser Test Report
SYSTEM: AHU-3
120
Supply Air
121
Final
115
116
Test 1
112
AK or
HoodFace Size
114
Type Neck Size
123
125
122
124
10/25/2021
Area Served #
SB
Page 16
Motor Make
HP
Frame
Full Load Amps 5.13
Service Factor
Volts/Phase 208 1PH 210
Corrected FLA
Fan RPM
DB:86.5°WB:Motor RPM
BHP
Total Fan CFM
Outlet CFM
Traverse CFM
Return Air CFM
Outside Air CFM
Embedded OA Ratio %
208 1PH Embedded TSP In. of W.C.
ESP In. of W.C.
12%
Design
Heating MBH
Direct Drive
NS Medium SpeedServiceSupply/Return
KW 10.0
Amps
Volts/Phase
NS
0.96
Belt Size/ Quantity
Motor Sheave
Center to Center
1.0
Heating EADB
Heating LADB
Cooling LADB F°55.3°
24x24x1
12%
Embedded
Static Pressure Profile
0.580.6
Return Duct SP:
Mixing OA and RA SP:
Filter Pressure Differential
Unit and Nameplate Data
AHU-4
Carrier
FX4DNF061
2121F10771
HP
Multiple Areas
Atlantic Beach, Florida
Electric Heat Report
SBTested By:
HP
Test
70.8°
63.4°
Designation
Design
Type
Area Served
Location
Unit Designation
Manufacturer
Model #
Serial #
6
Embedded
Test
NA
1898
NS
NS
Seasonal Test
Seasonal Test
Test
1898
Cooling MBH
31.8
1667
231
CFM 1898
Sensible MBH
Duct Detector Test
CFM and Pressure Test
NA58.00 Seasonal Test
1900
43.20
60.00
81.4
NS10/25/2021
Coil Test Report
Filter Quantity
59.9
Fan Sheave
NS
Cooling LAWB F°52.6°Filter Model/Size
Cooling EAWB F°
Date:
Design
Cooling EADB F°75.0°
63.0°
OA Temp DB/WB
HVAC Unit Test Report
Motor Design and Test
Test
1900
Design
NS
1900
1900
1675
225
Embedded
3/4
Embedded
Direct Drive
6
Direct Drive
Direct Drive
1
Miscellaneous Info
Direct Drive
NS
NS
Coil Pressure Differential
Entering Fan Pressure
Supply Duct Pressure
0.12
NA
NA
NA
0.5
0.46
Page 17
Type
1
653
689
1 644 702 660 647
668
632
NA
8''
Area
662
Louver/Duct Size
% Variance
CFM Tested
10%
Remarks
VFD Speed
25-Oct
Round Duct Traverse Test
System
Instrument Used
Outside AirAHU-4
Project Pitot TubeBaptist Primary Care
103%
Date
Design Velocity
Design CFM
Velocity Readings
0.35
Average Velocity
Damper Position:
231
Area 0.35
Total Velocity:
645
225
5295
Page 18
VEL CFM VEL CFM
1 A 12''24"x24"Hood 460 461 100%
2 A 6''24"x24"Hood 150 158 105%
3 A 6''12"x12"Hood 75 77 103%
4 A 8''24"x24"Hood 80 75 94%
5 A 8''24"x24"Hood 150 148 99%
6 A 8''24"x24"Hood 35 36 103%
7 D 12"x6"12"x6"Hood 175 182 104%
8 A 8''24"x24"Hood 85 83 98%
9 D 12"x6"12"x6"Hood 175 184 105%
10 A 8''24"x24"Hood 75 79 105%
11 A 8''24"x24"Hood 80 85 106%
12 A 8''24"x24"Hood 85 88 104%
13 A 8''24"x24"Hood 85 86 101%
14 A 8''24"x24"Hood 80 84 105%
15 A 8''12"x12"Hood 35 35 100%
16 A 8''12"x12"Hood 35 37 106%
1860 1898 102%
Technician:Date:
SupplyDuct Type:
# Variance
110
Design
Diffuser Test Report
SYSTEM: AHU-4
Corridor
Supply Air
102
Corridor
102
102
Final
130
Corridor
Test 1
127
AK or
HoodFace Size
126
Type Neck Size
102
111
119
118
119
Corridor
10/25/2021
Area Served #
TAB
Page 19
ManufacturerModelSerial
CFMSPMotor MakeRPMHPVolts/Phase 120 1 124 120 1 123 120 1 124 120 1 124 120 1 124Amperage0.19 0.20 0.19 0.26 1.68Frame
Service FactorBHPOverload SizeMotor SheaveFan SheaveBelt
NS NS
0.02 0.03
Remarks:
Direct Drive Direct Drive Direct Drive Direct Drive
Date: 10/25/2021Baptist Primary Care
NS NS
NS NS NSNS
NA
Project:
Fan Test Report
Fan #
NS
Direct Drive
NS NS
NA0.25
Embedded
720 1291
158 Watts
2.1
NS NS NS
NS
925
Embedded
0.25
52 Watts
NS
NS
NS
NS
Direct Drive
Direct Drive
Direct Drive
0.02
Direct Drive
NA
74 73
NA
Direct DriveDirect Drive
38 Watts
0.3
206
Direct Drive
Embedded
50 200
52 Watts
0.25
Direct Drive Direct Drive
0.02
Embedded
925 Direct Drive
0.20
Design
Embedded
Embedded
Embedded
TEST DATA
70 68
EF-1(1)
70 70
Embedded Embedded
Embedded Embedded
Embedded
925
52 Watts
0.25
NS
0.25 0.25 0.25 0.25
52
NA
Embedded 990722994A
TEST DATA TEST DATA TEST DATA TEST DATA
Broan CAS
Embedded Embedded AE80B-B CFA250
EF-1(2)EF-1(3)EF-2 EF-3
Design Design Design Design
Direct Drive
Direct Drive Direct Drive Direct Drive Direct Drive
Technician:SB
email: nuffelman@htbjax.com www.htbjax.com
Phone 9049001484
Fax 9049001485Page 20