1021 ATLANTIC BLVD COMM21-0047 - MECH COMcheck_1COMcheck Software Version COMcheckWeb
Mechanical Compliance Certificate
Project Title:
2020 Florida Building Code, Energy Conservation
Project Type:Alteration
Location:Jacksonville, Florida
Climate Zone:2a
Construction Site:
961 Atlantic BLVD
Jacksonville, Florida 32233
Owner/Agent:Designer/Contractor:
Jesse Lee
Pursuit Engineering
323 E Glenn Ave
Auburn, Alabama 36801
334-246-1369
info@pursuitengineering.com
Project Information
Energy Code:
NFCU - Atlantic Village
Mechanical Systems List
QuantitySystem Type & Description
Heating: 1 each - Other, Electric, Capacity = 40 kBtu/h
No minimum efficiency requirement applies
Cooling: 1 each - Single Package DX Unit, Capacity = 44 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 17.00 SEER, Required Efficiency: 14.00 SEER
Fan System: FAN SYSTEM 1 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 1600 CFM, 1.0 motor nameplate hp, 1.00 fan energy index
1 EX-RTU-2 (Single Zone):
Heating: 1 each - Central Furnace, Electric, Capacity = 40 kBtu/h
No minimum efficiency requirement applies
Cooling: 1 each - Single Package DX Unit, Capacity = 35 kBtu/h, Air-Cooled Condenser, Unknown Economizer
Proposed Efficiency = 17.00 SEER, Required Efficiency: 14.00 SEER
Fan System: FAN SYSTEM 2 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 2 Supply, Constant Volume, 1200 CFM, 0.5 motor nameplate hp, 1.00 fan energy index
1 EX-RTU-3 (Single Zone):
Heating: 1 each - Central Furnace, Electric, Capacity = 40 kBtu/h
No minimum efficiency requirement applies
Cooling: 1 each - Single Package DX Unit, Capacity = 50 kBtu/h, Air-Cooled Condenser, Unknown Economizer
Proposed Efficiency = 14.00 SEER, Required Efficiency: 14.00 SEER
Fan System: FAN SYSTEM 3 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 3 Supply, Constant Volume, 1400 CFM, 0.8 motor nameplate hp, 1.00 fan energy index
1 RTU-4 (Single Zone):
Cooling: 1 each - Split System, Capacity = 12 kBtu/h, Air-Cooled Condenser, Unknown Economizer
Proposed Efficiency = 14.00 SEER, Required Efficiency: 14.00 SEER
Fan System: FAN SYSTEM 4 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes
Fans:
FAN 4 Supply, Constant Volume, 400 CFM, 0.3 motor nameplate hp, 1.00 fan energy index
1 DSS-1 (Single Zone):
Electric Storage Water Heater, Capacity: 20 gallons
1 PL-14:
Project Title:
Data filename:
NFCU - Atlantic Village 09/10/21Report date:
91 ofPage
QuantitySystem Type & Description
No minimum efficiency requirement applies
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building
plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2020 Florida Building Code, Energy Conservation requirements in COMcheck Version COMcheckWeb and to
comply with any applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Project Title:
Data filename:
NFCU - Atlantic Village 09/10/21Report date:
92 ofPage
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version COMcheckWeb
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2020 Florida Building Code, Energy Conservation
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Complies
Does Not
Not Observable
Not Applicable
C103.2
[PR3]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the service water
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
NFCU - Atlantic Village 09/10/21Report date:
93 ofPage
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C403.2.4.
5
[FO9]3
Snow/ice melting system and freeze
protection systems have sensors and
controls configured to limit service for
pavement temperature and outdoor
temperature. future connection to
controls.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
NFCU - Atlantic Village 09/10/21Report date:
94 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C402.2.6
[ME41]3
Thermally ineffective panel surfaces of
sensible heating panels have
insulation >= R-3.5.
Complies
Does Not
Not Observable
Not Applicable
C403.2.10
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.2.10.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
C403.2.12
.4
[ME142]2
Motors for fans that are not less than
1/12 hp and less than 1 hp are
electronically commutated motors or
have a minimum motor efficiency of
70 percent. These motors have the
means to adjust motor speed.
Complies
Does Not
Not Observable
Not Applicable
C403.2.12
.4
[ME142]2
Motors for fans that are not less than
1/12 hp and less than 1 hp are
electronically commutated motors or
have a minimum motor efficiency of
70 percent. These motors have the
means to adjust motor speed.
Complies
Does Not
Not Observable
Not Applicable
C403.2.12
.4
[ME142]2
Motors for fans that are not less than
1/12 hp and less than 1 hp are
electronically commutated motors or
have a minimum motor efficiency of
70 percent. These motors have the
means to adjust motor speed.
Complies
Does Not
Not Observable
Not Applicable
C403.2.12
.4
[ME142]2
Motors for fans that are not less than
1/12 hp and less than 1 hp are
electronically commutated motors or
have a minimum motor efficiency of
70 percent. These motors have the
means to adjust motor speed.
Complies
Does Not
Not Observable
Not Applicable
C403.2.12
.5
[ME143]2
Each DX cooling system > 65 kBtu
and chiller water/evaporative cooling
system with fans > 1/4 hp are
designed to vary the indoor fan airflow
as a function of load and comply with
detailed requirements of this section.
Complies
Does Not
Not Observable
Not Applicable
C403.2.12
.5
[ME143]2
Each DX cooling system > 65 kBtu
and chiller water/evaporative cooling
system with fans > 1/4 hp are
designed to vary the indoor fan airflow
as a function of load and comply with
detailed requirements of this section.
Complies
Does Not
Not Observable
Not Applicable
C403.2.12
.5
[ME143]2
Each DX cooling system > 65 kBtu
and chiller water/evaporative cooling
system with fans > 1/4 hp are
designed to vary the indoor fan airflow
as a function of load and comply with
detailed requirements of this section.
Complies
Does Not
Not Observable
Not Applicable
C403.2.12
.5
[ME143]2
Each DX cooling system > 65 kBtu
and chiller water/evaporative cooling
system with fans > 1/4 hp are
designed to vary the indoor fan airflow
as a function of load and comply with
detailed requirements of this section.
Complies
Does Not
Not Observable
Not Applicable
C403.2.3
[ME55]2
HVAC equipment efficiency verified.Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
NFCU - Atlantic Village 09/10/21Report date:
95 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.2.6
[ME59]1
Natural or mechanical ventilation is
provided in accordance with Florida
Building Code Chapter 4. Mechanical
ventilation has capability to reduce
outdoor air supply to minimum per
Florida Building Code Chapter 4.
Complies
Does Not
Not Observable
Not Applicable
C403.2.6.
1
[ME59]1
Demand control ventilation provided
for spaces >500 ft2 and >25
people/1000 ft2 occupant density and
served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
Complies
Does Not
Not Observable
Not Applicable
C403.2.6.
2
[ME115]3
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50% or less of design capacity.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
8
[ME141]3
HVAC systems serving guestrooms in
Group R-1 buildings with > 50
guestrooms: Each guestroom is
provided with controls that
automatically manage temperature
setpoint and ventilation (see sections
C403.2.4.8.1 and C403.2.4.8.2).
Complies
Does Not
Not Observable
Not Applicable
C403.2.7
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.2.7(1)
and C403.2.7(2).
Complies
Does Not
Not Observable
Not Applicable
C403.2.8
[ME116]3
Kitchen exhaust systems comply with
replacement air and conditioned
supply air limitations, and satisfy hood
rating requirements and maximum
exhaust rate criteria.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1,
C403.2.9.
2
[ME60]2
HVAC ducts and plenums insulated in
accordance with C403.2.9.1 and
constructed in accordance with
C403.2.9.2, verification may need to
occur during Foundation Inspection.
Complies
Does Not
Not Observable
Not Applicable
C403.4.6
[ME35]1
Hot gas bypass limited to: <=240
kBtu/h – 50% >240 kBtu/h – 25%
Complies
Does Not
Not Observable
Not Applicable
C403.4.6
[ME35]1
Hot gas bypass limited to: <=240
kBtu/h – 50% >240 kBtu/h – 25%
Complies
Does Not
Not Observable
Not Applicable
C403.4.6
[ME35]1
Hot gas bypass limited to: <=240
kBtu/h – 50% >240 kBtu/h – 25%
Complies
Does Not
Not Observable
Not Applicable
C403.4.6
[ME35]1
Hot gas bypass limited to: <=240
kBtu/h – 50% >240 kBtu/h – 25%
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
NFCU - Atlantic Village 09/10/21Report date:
96 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C408.2.2.
1
[ME53]3
Air outlets and zone terminal devices
have means for air balancing.
Complies
Does Not
Not Observable
Not Applicable
C403.5,
C403.5.1,
C403.5.2
[ME123]3
Refrigerated display cases, walk-in
coolers or walk-in freezers served by
remote compressors and remote
condensers not located in a
condensing unit, have fan-powered
condensers that comply with Sections
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
NFCU - Atlantic Village 09/10/21Report date:
97 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.1
[FI50]3
HVAC systems and equipment design
loads calculated in accordance with
ANSI/ASHRAE/ACCA Standard 183 or
by an approved equivalent
computational procedure
Complies
Does Not
Not Observable
Not Applicable
C403.2.2
[FI27]3
HVAC systems and equipment
capacity does not exceed calculated
loads.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1.2
[FI38]3
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1.3
[FI20]3
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2
[FI39]3
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.1,
C403.2.4.
2.2
[FI40]3
Automatic Controls: Setback to 55°F
(heat) and 85°F (cool); 7-day clock, 2-
hour occupant override, 10-hour
backup
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls as a function of space
temperature, occupied setpoint
temperature, outdoor temperature
and amount of time prior to
occupancy.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
NFCU - Atlantic Village 09/10/21Report date:
98 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls as a function of space
temperature, occupied setpoint
temperature, outdoor temperature
and amount of time prior to
occupancy.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls as a function of space
temperature, occupied setpoint
temperature, outdoor temperature
and amount of time prior to
occupancy.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls as a function of space
temperature, occupied setpoint
temperature, outdoor temperature
and amount of time prior to
occupancy.
Complies
Does Not
Not Observable
Not Applicable
C404.3
[FI11]3
Heat traps installed on supply and
discharge piping of non-circulating
systems.
Complies
Does Not
Not Observable
Not Applicable
C408.2.1
[FI28]1
Commissioning plan developed by
registered design professional or
approved agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
1
[FI31]1
HVAC equipment has been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
2
[FI10]1
HVAC control systems have been
tested to ensure proper operation,
calibration and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
C408.2.4
[FI29]1
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
1
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
3
[FI43]1
An air and/or hydronic system
balancing report is provided for HVAC
systems.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
4
[FI30]1
Final commissioning report due to
building owner within 90 days of
receipt of certificate of occupancy.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
NFCU - Atlantic Village 09/10/21Report date:
99 ofPage