763 Atlantic Blvd COMM22-0038 DRAWINGS fire approval8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
8/22/22
44 4 4 4
44 4 4 4
WAITING
RECEPTION
CONSULT
RETAIL AREA
SECURE
STORAGE WORK AREA
MENS WOMENS
JANITOR
UTILITY
BREAK AREA
OFFICE
HALLWAY
PANEL "A"
WAITING
A-1,3
A-18
A-5 A-5 A-5 A-7 A-7 A-7
A-38
A-38
A-11
A-11
A-11 A-11
A-17
A-13
+18"
A-19
+18"
GFI
A-13
+18"
GFI
A-13
+18"
GFI
A-13
+18"
GFI
A-23
+18"
A-23
+18"
A-23
+18"
A-23
+48"
GFI
A-23
+48"
A-25+48"A-29+18"
A-35
+18"
A-31
+48"+48" A-31
+48"
+48"
A-35
+18"
A-35+18"
A-35+18"
A-35+18" A-37+48"
+48"
A-37
+48"
+48"
A-41
+18"
A-41+18"
A-41
+18"
A-41
+18"
A-41+18"
RTU-1
ON ROOF
EF-1
ON ROOFA-24
A-20
A-36A-26,28,30 GFI/WP
M/WP
+18"
GFI GFI
C/T
CP-1
A-32
CONTRACT DATE:
BUILDING TYPE:
PLAN VERSION:
BRAND DESIGNER:
SITE NUMBER:
STORE NUMBER:
FLUENT
763 ATLANTIC BLVD.
ATLANTIC BEACH, FL 32233
06/13/22
ARCVISION: 220224
C A N N A B I S C A R E
E1.0
ELECTRICAL
POWER PLAN
)
E 1/4" = 1'-0"POWER PLAN A NOT 86E'
POWER PLAN *ENERAL NOTE6 %POWER PLAN .E<E' NOTE6
A.CONTRACTOR SHALL COORDINATE QUANTITY AND FINAL LOCATION OF ALL TVS
WITH OWNER PRIOR TO CONSTRUCTION.
B.PROVIDE WORKING CLEARANCE AT ALL ELECTRICAL PANELS PER NEC.
C.COORDINATE WITH LOW-VOLTAGE VENDOR FOR EXACT LOCATIONS AND
REQUIREMENTS REGARDING ALL POS, SECURITY, IT, AND OTHER LOW VOLTAGE
ITEMS.
D.REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATIONS AND HEIGHTS OF ALL
FIXTURES.
E.OUTLETS FOR WORKSTATIONS AND POS STATIONS SHOULD BE MOUNTED JUST
UNDER THE MONITOR SHELVES OR UNDER THE TABLES AND PHONE COUNTER.
F.ALL CONDUITS SHALL BE CONCEALED IN WALLS OR ABOVE CEILINGS. WHERE
CONDUIT CAN'T BE CONCEALED IT MUST BE PAINTED TO MATCH WALL COLORS.
G.SEE SYMBOLS LEGEND FOR ADDITIONAL INFORMATION.
H.WHEN REUSING EXISTING PANELS, E.C. SHALL VERIFY THE CONDITION AND
QUANTITY OF ALL EXISTING CIRCUIT BREAKERS. REPLACE DAMAGED BREAKERS
WITH NEW. PROVIDE ANY ADDITIONAL OR BREAKERS OF DIFFERENT AMPERAGE OR
POLE AS REQUIRED TO MEET THE END RESULT INDICATED IN THE PANEL
SCHEDULE. NEW BREAKERS SHALL BE OF THE SAME MFG AND CHARACTERISTICS
OF THE EXISTING. THE SUBMISSION OF THE BID PROPOSALS SHALL BE
CONSIDERED EVIDENCE THAT THE CONTRACTORS HAVE VISITED THE SITE. NO
EXTRA PAYMENTS WILL BE ALLOWED TO THESE CONTRACTORS ON ACCOUNT OF
EXTRA WORK MADE NECESSARY BY HIS FAILURE TO VISIT THE SITE.
I.CONTRACTOR SHALL TRACE OUT ALL EXISTING CIRCUITRY AND DETERMINE IF IS
NEEDED. IF CIRCUIT IS NOT NEEDED CONTRACTOR SHALL REMOVE ALL WIRING
AND DEVICES TO NEAREST JUNCTION BOX, CAP AND LABEL WIRING AND COVER
EXISTING BOX WITH A BLANK PLATE.
J.EXISTING CIRCUITRY SHALL BE VERIFIED IN FIELD PRIOR TO START OF WORK.
A''ITIONAL NOTE6
1.EC TO VERIFY EXISTING EQUIPMENT TO REMAIN. PROTECT EQUIPMENT
DURING CONSTRUCTION.
2.PROVIDE REQUIRED WORKING SPACE/CLEARANCE FOR ELECTRICAL PANEL
PER N.E.C.. CONTRACTOR TO CLEARLY IDENTIFY/INDICATE NOT LESS THAN
30"Wx36"D CLEARANCE AREA/ WORKING SPACE (PER IFC 605.3). IF
EQUIPMENT IS LARGER THAN 30" WIDE, WORKING SPACE/CLEARANCE SHALL
NOT BE LESS THAN EQUIPMENT WIDTH.
3.POS RECEPTACLE AND DATA RAN IN CASEWORK; CONTRACTOR SHALL
COORDINATE WITH ARCHITECT AND OWNER FOR EXACT LOCATION, HEIGHT,
AND REQUIREMENTS PRIOR TO ROUGH IN.
4.RECEPTACLE AND DATA FOR VIDEO SCREEN. CONTRACTOR SHALL
COORDINATE WITH ARCHITECT AND OWNER FOR EXACT LOCATION, HEIGHT,
AND REQUIREMENTS PRIOR TO ROUGH IN.
5.JUNCTION BOX FOR TERMINATION TO FLUENT CANNABIS SIGN. FIELD VERIFY
THE EXACT MOUNTING LOCATION AND CONNECTION REQUIRED, PRIOR TO
ROUGH-IN. PROVIDE SIGN DISCONNECT SWITCH, IF REQUIRED. INSTALL PER
N.E.C. ARTICLE 600 SIGNS.
6.NEW LOCATION FOR EXISTING WATER HEATER. CONTRACTOR SHALL EXTEND
BRANCH CIRCUIT, CONDUIT, AND ALL ASSOCIATED MATERIALS TO MAKE A
SAFE OPERATIONAL SYSTEM AT NEW WATER HEATER LOCATION AND PER
N.E.C. REQUIREMENTS.
7.PROVIDE AN UNDER-FLOOR TRENCH BETWEEN LOW-WALL AND BACK OF
HOUSE WALL, AS SHOWN. COORDINATE WITH OTHER DISCIPLINES WORK AS
NEEDED TO NOT DISTURB OTHERS WORK. CONTRACTOR TO FIELD-VERIFY
THE EXACT NUMBER OF CONDUITS REQUIRED FOR P.O.S.
POWER/COMMUNICATIONS. INSTALL BELOW-GRADE PER BURIAL
REQUIREMENTS IN THE N.E.C. AND SEALED PER THE U.L. LISTING FOR THE
ENVIRONMENT ENCOUNTERED.
8.PROVIDE A 3/4" CONDUIT FOR POWER AND A 3/4" CONDUIT FOR
COMMUNICATION TO COUNTER. PROVIDE TRANSITION AND STUB-UP INTO
COUNTER MILLWORK. EXTEND AND SECURE WIREWAY(S) ALONG THE BACK
OF CABINET. MAKE FINAL CONNECTIONS TO OUTLETS AT JUNCTION BOXES.
COORDINATE WITH MILLWORK CONTRACTOR FOR "STUB-THRU" LOCATIONS.
9.NEW ROOFTOP UNIT (RTU-1). EC TO PROVIDE 60A, 208V, 3P, NON-FUSED,
WEATHERPROOF DISCONNECT SWITCH. SEE PANEL SCHEDULE ON SHEET
E3.0 FOR WIRE SIZES. COORDINATE ALL REQUIREMENTS WITH HVAC
CONTRACTOR PRIOR TO BID.
10.EC TO PROVIDE GFI WEATHERPROOF DUPLEX RECEPTACLE AT HVAC
EQUIPMENT.
11.PROVIDE CONNECTION FROM AIR DUCT SMOKE DETECTORS TO MECHANICAL
CONTROL CIRCUIT. COORDINATE ALL REQUIREMENTS WITH HVAC
CONTRACTOR PRIOR TO BID.
12.PROVIDE 20A, 120V, WEATHERPROOF TOGGLE SWITCH DISCONNECT FOR
EF-1. COORDINATE LOCATION WITH MANUFACTURER. CIRCUIT THROUGH
TIMECLOCK FOR OPERATION ONLY DURING OCCUPIED HOURS.
13.PROVIDE A TIMECLOCK FOR CIRCULATING PUMP CONTROL AND TOGGLE
SWITCH DISCONNECT. TIMECLOCK SHALL BE WIRED AHEAD OF DISCONNECT.
MOUNT ON WALL ADJACENT TO WATER HEATERS.
C
N
TRUE
N
PROJECT
'NOT 86E'
FIRE ALARM:
AS REQUIRED, IT SHALL BE THE GENERAL CONTRACTORS RESPONSIBILITY TO
ENGAGE THE SERVICES OF AN APPROVED FIRE ALARM CONTRACTOR. THE FIRE
ALARM CONTRACTOR SHALL BE REQUIRED TO PROVIDE DRAWINGS, SPECIFICATIONS
& INSTALLATION ACCORDING TO MUNICIPALITIES GUIDELINES. FIRE ALARM SERVICE
MAY ALSO INCLUDE PROVIDING FIRE ALARM MONITORING TO BUILDING'S INSTALLED
FIRE ALARM CONTROL SYSTEM. FIRE ALARM CONTRACTOR TO PROVIDE COMPATIBLE
DEVICES & ALL BRACING, WIRING, ETC. COORDINATE WITH LANDLORD'S FIRE ALARM
CONTRACTOR FOR DETAILS.
EQUIPMENT:
THE EQUIPMENT AND DIMENSIONED LOCATIONS FOR CONNECTIONS ARE ACCURATE
TO THE BEST OF OUR KNOWLEDGE, BUT SHALL BE VERIFIED WITH THE EQUIPMENT
SUPPLIER, EQUIPMENT ROUGH-IN DRAWINGS, AND/OR THE OWNER. IN SOME
INSTANCES, THE OWNER OR SUPPLIER MAY MAKE SUBSTITUTIONS OR THE
EQUIPMENT MAY VARY FROM WHAT IS SHOWN ON THE PLAN. THE
ARCHITECT/ENGINEER SHALL BE IMMEDIATELY NOTIFIED, PRIOR TO CONSTRUCTION,
OF ANY DEVIATIONS FROM WHAT IS SHOWN OR IMPLIED ON THESE DRAWINGS.
FAILURE OF THE APPROPRIATE CONTRACTOR TO VERIFY ROUGH-INS OR THEIR
LOCATIONS SHALL PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION
AND/OR ADDITIONAL ROUGH-INS DIRECTLY UPON THE CONTRACTOR.
FLORIDA BUILDING CODE REQUIREMENT - ENERGY CONSERVATION:
WITHIN 30-DAYS AFTER DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE
ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER, INCLUDING: 1.
A SINGLE-LINE DIAGRAM OF BUILDING ELECTRICAL SYSTEM AND 2. FLOOR PLAN
INDICATING LOCATION AND AREA SERVED FOR ALL DISTRIBUTION. AN OPERATIONS
MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING OWNER, THE
MANUALS SHALL INCLUDE AT MINIMUM, THE FOLLOWING: 3. SUBMITTAL DATA STATING
THE EQUIPMENT RATINGS AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT
REQUIRING MAINTENANCE. 4. OPERATIONS MANUAL AND MAINTENANCE MANUAL FOR
EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE
MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED. 5. NAMES AND ADDRESS OF
AT LEAST ONE QUALIFIED SERVICE AGENCY. PRIOR TO PASSING FINAL INSPECTION,
THE REGISTERED DESIGN PROFESSIONAL/INSTALLER SHALL PROVIDE EVIDENCE
THAT THE LIGHTING CONTROL SYSTEM HAVE BEEN TESTED TO ENSURE THAT
CONTROL HARDWARE AND SOFTWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED
AND IN PROPER WORKING CONDITION IN ACCORDANCE WITH THE CONSTRUCTION
DOCUMENTS AND MANUFACTURES INSTRUCTIONS. FUNCTIONAL TESTING SHALL BE
IN ACCORDANCE WITH SECTIONS C408.3.1.1 & C408.3.1.3 FOR APPLICABLE CONTROL
TYPE.
8/22/22
WAITING
RECEPTION
CONSULT
RETAIL AREA
SECURE
STORAGE WORK AREA
MENS WOMENS
JANITOR
UTILITY
WAITING
BREAK AREA
OFFICE
HALLWAY
A1
A-12
A1
A-12
A1
A-12
A1
A-12
A1
A-12
A1
A-12
A1
A-12
A1,f
A-12
A1,e
A-12
A1,f
A-12
A1,e
A-12 A1,f
A-12
A1,e
A-12
A1,e
A-12
A1,f
A-12
A1,e
A-12
A1
A-12
A1
A-12
A1,f
A-12
A1,e
A-12
A1,f
A-12
A1,e
A-12
A1,d
A-8
A1,c
A-8
A1,d
A-8
A1
A-8
A1
A-8
A1
A-8
A1
A-8
A1,b
A-6
A1,a
A-6
A1,b
A-6
A1,a
A-6
A1,b
A-6
A1,a
A-6
A1,b
A-6
A1,a
A-6
A1,b
A-6
A1,a
A-6
A1,b
A-6
A1,a
A-6
A1,b
A-6
A1,a
A-6
A1,b
A-6
A1,a
A-6
A1,b
A-6
A1,a
A-6
A1,b
A-6
A1,a
A-6
A1,b
A-6
A1,d
A-8
A1,c
A-8
A1,c
A-8
A1,d
A-8
A1,d
A-8
A1,c
A-8
A1,c
A-8
A1,d
A-8
A1,d
A-8
A1,c
A-8
A1,c
A-8
A1,d
A-8
A1
A-12
A1/NL
A-12
A1
A-12
A1
A-12
A1,a
A-6
A1,b
A-6
A1,a
A-6
A1,b
A-6
C1,g
A-6
C1,g
A-6
C1,g
A-6
C1,g
A-6
(TYP)
(TYP)
A1
A-12
A1
A-12
PANEL "A"
abcdef
A-2
OS
OS
A1
A-12
OS
OS
OS
A-14 A-14 A-14 A-14 A-14 A-14 A-14 A-14 A-14 A-14 A-14 A-14 A-14
OS
A1
A-12
OS
EX1 A-8
EX1 A-6
EX1 A-12
A-8EM1 A-8EM1
A-12
EM1
A-12
EM1
A-12
EM1
A1
A-12A-12
EM1
A1
A-12
A-6
EM1
A-6EM1 A-6EM1
A1,a
A-6
A-12EM1
A-8EM1
A-12EM1
A-12EM1
A-12
EM1
A-12
EM1
PS
CONTRACT DATE:
BUILDING TYPE:
PLAN VERSION:
BRAND DESIGNER:
SITE NUMBER:
STORE NUMBER:
FLUENT
763 ATLANTIC BLVD.
ATLANTIC BEACH, FL 32233
06/13/22
ARCVISION: 220224
C A N N A B I S C A R E
E2.0
ELECTRICAL
LIGHTING
PLAN
G
E
1/4" = 1'-0"LIGHTINGPLAN A
6:ITCH%AN.'ETAIL
LIGHTINGPLANGENERALN2TE6 %LIGHTINGPLAN.E<E'N2TE6
A.EMERGENCY LIGHTS/EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED HOT
CONDUCTOR OF CIRCUIT INDICATED.
B.REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATIONS OF ALL FIXTURES.
C.REFER TO LIGHTING FIXTURE SCHEDULE.
D.SEE SYMBOLS LEGEND FOR ADDITIONAL INFORMATION.
E.CONTRACTOR SHALL UTILIZE EXISTING LIGHTING CIRCUITRY FOR RELOCATED
LIGHTING FIXTURES. CONTRACTOR SHALL VERIFY CIRCUIT LOAD PRIOR TO START
OF WORK AND WORK TO NOT OVERLOAD CIRCUITRY.
LIGHTING)I;T8RE6CHE'8LE
1.E.C. TO VERIFY EXISTING CEILING MOUNTED DEVICES (SPEAKERS, REMOTE
TEST SWITCH, SMOKE DETECTORS, OCCUPANCY SENSORS, ETC;) FOR REUSE,
REMOVE (AS NEEDED), PROTECT AND CLEAN (SAND AND REFINISH AS
NEEDED), PROVIDE ADDITIONAL BRACING, AS NEEDED FOR RELOCATION OF
DEVICES. EXTEND CIRCUITING, JUNCTION BOX, ETC; TO NEW LOCATIONS
(INDICATED ON SHEETS OR PER ON-SITE FLUENT CANNABIS
REPRESENTATIVE), NEW DEVICE MOUNTING BASE SHALL BE FLUSH WITH
BOTTOM OF CEILING.
2.PROVIDE REQUIRED WORKING SPACE/CLEARANCE FOR ELECTRICAL PANEL
PER N.E.C.. CONTRACTOR TO CLEARLY IDENTIFY/INDICATE NOT LESS THAN
30"Wx36"D CLEARANCE AREA/ WORKING SPACE (PER IFC 605.3). IF
EQUIPMENT IS LARGER THAN 30" WIDE, WORKING SPACE/CLEARANCE SHALL
NOT BE LESS THAN EQUIPMENT WIDTH.
3.DAYLIT ZONE SHOWN FOR REFERENCE PER ENERGY CODE C103.2.
4.NEW RECESSED CAN. SEE LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL
INFORMATION. CONTRACTOR TO PROVIDE LED FIXTURE WITH WHITE FINISH.
VERIFY SPECIFICATION WITH OWNER PRIOR TO INSTALLATION. CONNECT
LIGHT FIXTURE TO NEW CIRCUIT INDICATED.
5.NEW LED LINEAR LIGHT. SEE LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL
INFORMATION. VERIFY SPECIFICATION WITH OWNER PRIOR TO INSTALLATION.
PROVIDE JUNCTION BOX FOR CONNECTION FROM FIXTURE TO REMOTE
DRIVER. PROVIDE ADDITIONAL STRUCTURAL BRACING, INDEPENDENT FROM
DROP CEILING AS NEEDED.
6.CONTRACTOR TO PROVIDE AND INSTALL NEW EMERGENCY EGRESS LIGHTING
FIXTURE. SEE LIGHTING SCHEDULE FOR ADDITIONAL INFORMATION. PROVIDE
A SEPARATE HOT LEAD FROM LOCAL AREA LIGHTING CIRCUIT TO EM
CONTROL IN FIXTURE, BY-PASSING ALL SWITCHING AND LIGHTING CONTROL.
CONTRACTOR TO PROVIDE BREAKER IDENTIFICATION OF EMERGENCY
SYSTEM(S) ON THAT CIRCUIT. SEE LIGHTING FIXTURE SCHEDULE AND
GENERAL NOTES, THIS SHEET. (NOTE: CONTRACTOR TO PROVIDE ADDITIONAL
CODE COMPLIANT EMERGENCY EGRESS LIGHTING FIXTURES IF REQUIRED BY
THE A.H.J.).
7.NEW FLUSH, CEILING MOUNTED DUAL-TECHNOLOGY OCCUPANCY SENSOR.
SET TIMING AND LOADS PER OWNERS RECOMMENDATION. MANUFACTURER:
WATTSTOPPER CX-100 OR CI-100.
8.LOCAL LIGHTING CONTROL SWITCH SHALL BE MOUNTED AT 48" AFF. ONLY AS
REQUIRED BY ENERGY CODE.
9.PROPOSED MAIN SWITCH BANK LOCATION FOR NEW LIGHTING CONTROL
(COORDINATE EXACT SWITCH BANK LOCATION WITH OWNER IN FIELD).
CONTRACTOR TO PROVIDE SWITCH INDICATION AND LABEL FOR THEIR
INTENDED USE. SEE DETAIL E, THIS SHEET FOR ADDITIONAL INFORMATION.
(NOTE: CONTRACTOR TO FIELD VERIFY EACH THE LIGHTING AREA BEING
CONTROLLED BY SWITCH LOCATED WITHIN SWITCH BANK, IS WITHIN THE LINE
OF SIGHT (VISIBLE) FROM THE CONTROLLING DEVICE LOCATION (SWITCH
BANK). ANY SWITCH CONTROLLING LIGHTING IN AREAS, NOT WITHIN THE LINE
OF SITE, FROM THE CONTROLLING DEVICE LOCATION (SWITCH BANK), SHALL
BE PROVIDED WITH A SWITCH WITH AN ANNUNCIATOR DEVICE (I.E. SWITCH
WITH PILOT LIGHT), SO WHEN THE AREA BEING CONTROLLED IS LIT, THE
CONTROLLING DEVICE IS ANNUNCIATED.
10.TIMECLOCK AND LIGHTING CONTROLS. SEE DETAIL D, THIS SHEET, FOR
ADDITIONAL INFORMATION. PROVIDE A 120-VOLT, 20-AMP DEDICATED BRANCH
CIRCUIT FROM A 1-POLE SPACE IN EXISTING PANEL FOR POWER SUPPLY.
WALL MOUNT DEVICES (IN CLEAR AREA) IN BREAKROOM OR ADJACENT TO
LIGHTING PANEL, NO HIGHER THAN 6'-0" A.F.F.. INTERCEPT ONLY EXISTING
RETAIL AREA LIGHTING BRANCH CIRCUIT(S) FROM LIGHTING PANEL AND
REROUTE THROUGH NEW LIGHTING CONTROLS.
11.NEW EXTERIOR RECESSED LIGHT. CONTRACTOR SHALL PROVIDE MATCHING
MODEL TO DEMOLISHED LIGHT FIXTURE AND REPLACE ANY MATERIALS
NEEDED FOR FIXTURE TO WORK PROPERLY AS PER CONSTRUCTION
DOCUMENTS.
12.NIGHT LIGHT. PROVIDE A SEPARATE HOT LEAD FROM LOCAL AREA LIGHTING
CIRCUIT, BY-PASSING ALL SWITCHING AND LIGHTING CONTROL.
13.AUTOMATIC DAYLIGHTING CONTROL TO BE MOUNTED FLUSH WITH CEILING.
COORDINATE EXACT QUANTITIES AND PLACEMENT WITH MANUFACTURERS
REQUIREMENTS FOR COMPLETE ZONE COVERAGE. SYMBOL SHOWN FOR
REFERENCE ONLY. DO NOT WIRE WITH EMERGENCY LIGHT FIXTURES.
PROVIDE CONNECTION TO CONTROL CIRCUIT AFTER TIMECLOCK AND LOCAL
SWITCHING. ALL GENERAL LIGHTING WITHIN ZONES (AS SHOWN) SHALL BE
CAPABLE OF CONTINUOUS DIMMING AND BE WIRED THROUGH DAYLIGHTING
CONTROL SENSORS. CONTROLLER SHALL PERCEIVE INCOMING (OUTDOOR)
LIGHTING AND ADJUST GENERAL LIGHTING ILLUMINANCE TO COMPENSATE
FOR ADDED DAYLIGHT PER ENERGY CODE REQUIREMENTS.
DAYLIGHTING/DIMMING LIGHTING CONTROL PACKAGE SHALL BE INSTALLED
PER ENERGY CODE AND PER MANUFACTURER'S SPECIFICATION. COORDINATE
WITH FLUENT REPRESENTATIVE FOR FINAL CONTROL DESIGN AND DEVICE
APPROVAL. SEE DETAIL F, THIS SHEET FOR ADDITIONAL INFORMATION.
1.CONTRACTOR TO CONSULT WITH LIGHTING MANUFACTURERS TO PROVIDE FIXTURE LAMPS & UL LABELING TO REFLECT ACTUAL LAMP WATTAGE USED, NOT MAX FIXTURE
WATTAGE.
2.RECESSED FIXTURES INSTALLED IN AN INSULATED CEILING SHALL BE I.C. RATED.
NO.QTY.LOCATION MFR / CATALOG NUMBER DESCRIPTION LAMP BALLAST
TYPE#TYPE
MOUNTING
TYPE HT.
VOLT WATT
A1 77 ALL HALO
H750TML712830TUNVD010 RECESSED LED DOWNLIGHT NA 120 141LEDRECESSED
DROP CLG -
C1 4 RETAIL AREA ALCON
12160-P-6-40K-RMT 6'-0" LED LINEAR PENDANT NA 120 421LEDPENDANT
DROP CLG -
C
N
TRUE
N
PROJECT
*=PROVIDE BY-PASS FOR
CIRCUITS REQUIRING 24HR
OPERATION.1.PROVIDE LOCAL SWITCHING AS REQUIRED, PER MUNICIPALITY'S ADOPTED VERSION OF THE ENERGY CODE
2.120-VOLT, 30-AMP CONTINUOUS DUTY CONTACTOR (TYPICAL). PROVIDE IN CONFIGURATION, AS SHOWN.
3.SEE DETAIL F, THIS SHEET FOR REQUIRED LIGHTING CONTROL IN THESE AREAS.
C
LIGHTING
RETAIL AREA
**
LIGHTING
OFFICE/
WORK AREA/
BREAK AREA/
SECURE
STORAGEOR
H N
TC 120 VAC, 2HR (MAXIMUM) TIMER
SWITCH (OVERRIDE). SEE PLANS
FOR LOCATION.
CHANNEL
OUTPUT #2
CHANNEL
OUTPUT #1
MULTI-CHANNEL ELECTRONIC
PROGRAMMABLE TIMECLOCK
120-VAC
HVAC
EF-1 SPARE
**
LIGHTING
RECEPTION/
CONSULT/
WAITING
*
OR
C
LIGHTING
EXTERIOR
BUILDING SPARE
SIGN
INTERIOR
BUILDING SPARE
'LIGHTINGC2NTR2L'IAGRA0
NOTES:
CONTRACTOR TO VERIFY EXACT CONFIGURATION REQUIRED WITH
SPACE AVAILABLE. PROVIDE LABELS AS DIRECTED BY OWNER.
SWITCHES SHALL NOT BE MOUNTED HIGHER THAN 48".
RETAIL AREA
A
c
RETAIL AREA
B
RECEPTION/
WAITING
A
d
RECEPTION/
WAITING
B
e
WORK AREA/
BREAK AREA/
HALLWAY
A
f
WORK AREA/
BREAK AREA/
HALLWAY
B
ba
REMARKS
-
-
EM1 15 ALL E-LITE
ELM-809-W
2-HEAD EMERGENCY LIGHT FROG
EYE - WHITE EM 120 1025W/
MR16 WALL
6"
BELOW
CLG.
EX1 3 RETAIL AREA,
ENTRANCES
LITHONIA
ECC M6
COMBO EXIT / EMERGENCY LIGHT
UNIT. UNIVERSAL MOUNT -120 3--WALL -
-
LEAD CALCIUM BATTERY
(90 MIN)
#nSP5
PCD
ELV
#nPS80
BLK
RED
WHT
H N
120V
20A
1P
BLK
WHT
LIGHTING
EMERG.
LIGHTING
PCAT5
#nCM-ADCX-DZ CEILING
MOUNTED, DUAL-ZONE
PHOTOCELL
WALL-SWITCH AT
SWITCHBANK. SEE DETAIL E.
PROVIDE UN-SWITCHED HOT
TO EMERGENCY LIGHTING
BATTERY. PROVIDE SWITCHED
HOT TO CONTROL IN DRIVER.
FIXTURES WITH ELECTRONIC
LOW VOLTAGE DRIVERS IN
PRIMARY DAYLIGHTING ZONE.CAT5NOTE: POWER PACK, RELAY PACK, AND
PHOTOCELL MANUFACTURED BY ACUITY
BRANDS SENSOR SWITCH. COORDINATE ALL
REQUIREMENTS WITH MANUFACTURER.
PROVIDE UN-SWITCHED HOT TO
DEVICE POWER PACKS.
(SEE PLAN)
PHOTOCELL AND DIMMING RELAYS SHALL BE PROGRAMMED TO
PROVIDE THE FOLLOWING FUNCTIONALITY:
CONTROLS SHALL PROVIDE CONTINUOUS DIMMING.
FOR THE PRIMARY AND SECONDARY ZONES IN EACH SPACE, THE
COMBINED ILLUMINANCE FROM THE CONTROLLED LIGHTING AND
DAYLIGHT SHALL NOT BE LESS THAN THE ILLUMINANCE FROM
CONTROLLED LIGHTING WHEN NO DAYLIGHT IS AVAILABLE. IN THE
DARKEST PORTION OF THE DAYLIT ZONE (FURTHEST AWAY FROM
WINDOWS OR SKYLIGHTS) THE CONTROL SHOULD NOT OVER-DIM
THE LIGHTS; THIS SECTION OF THE DAYLIGHTED AREA SHOULD
NOT GET DARKER AS DAYLIGHT LEVELS INCREASE, DUE TO AN
INCORRECT CALIBRATION OF THE CONTROLS.
IN AREAS SERVED BY LIGHTING THAT IS DAYLIGHT CONTROLLED,
WHEN THE ILLUMINANCE RECEIVED FROM THE DAYLIGHT IS
GREATER THAN 150 PERCENT OF THE ILLUMINANCE RECEIVED
FROM THE GENERAL LIGHTING SYSTEM AT FULL POWER, THE
GENERAL LIGHTING POWER IN THAT DAYLIGHT ZONE SHALL BE
REDUCED BY A MINIMUM OF 65 PERCENT. E.C. SHALL FIELD
MEASURE ACTUAL GENERAL LIGHTING LEVELS AND ADJUST
DAYLIGHT SENSOR ACCORDINGLY.
)'A<LITC2NTR2L6EN62R'IAGRA0
g
P.O.S.
PENDANTS
125V, 20-AMP, 1-POLE
DIMMER SWITCH (450
MILLIAMP (MAX.) CONTROL)
8/22/22
ELECTRICAL RISER DIAGRAM NOTES:
1.ELECTRICAL DISTRIBUTION EQUIPMENT SHOWN DASHED OR LIGHTWEIGHT IS EXISTING.
2.INFORMATION ON PLANS REGARDING ELECTRICAL DISTRIBUTION EQUIPMENT WAS BASED
ON AVAILABLE INFORMATION AT THE TIME OF DESIGN. E.C. SHALL VERIFY EXISTING
CONDITIONS. NOTIFY CONSTRUCTION PROJECT MANAGER IMMEDIATELY OF ANY
DISCREPANCY AFFECTING THE INTENT OF THE DESIGN CONVEYED HEREIN.
EXISTING EXTERIOR WALLINTERIOR
GRADEFLOOR
SEE PANEL SCHEDULES
FOR SIZE AND RATINGS
EX.
PANEL
"A"
EXISTING
PENETRATION INTO
BUILDING
EXISTING METER CENTER,
VERIFY IN FIELD.
EXISTING UTILITY SERVICE
” ”
MM
M
M
TO
ADJACENT
TENANTS
CONTRACT DATE:
BUILDING TYPE:
PLAN VERSION:
BRAND DESIGNER:
SITE NUMBER:
STORE NUMBER:
FLUENT
763 ATLANTIC BLVD.
ATLANTIC BEACH, FL 32233
06/13/22
ARCVISION: 220224
C A N N A B I S C A R E
E3.0
ELECTRICAL
ONE-LINE
AND PANEL
SCHEDULE
8/22/22
CONTRACT DATE:
BUILDING TYPE:
PLAN VERSION:
BRAND DESIGNER:
SITE NUMBER:
STORE NUMBER:
FLUENT
763 ATLANTIC BLVD.
ATLANTIC BEACH, FL 32233
06/13/22
ARCVISION: 220224
C A N N A B I S C A R E
E4.0
ELECTRICAL
SPECIFICATIONS
8/22/22
8/22/22
8/22/22