763 Atlantic Blvd COMM22-0038 DRAWINGS reduced 1844 4 4 4
44 4 4 4
WAITING
RECEPTION
CONSULT
RETAIL AREA
SECURE
STORAGE WORK AREA
MENS WOMENS
JANITOR
UTILITY
BREAK AREA
OFFICE
HALLWAY
PANEL "A"
WAITING
A-1,3
A-18
A-5 A-5 A-5 A-7 A-7 A-7
A-38
A-38
A-11
A-11
A-11 A-11
A-17
A-13
+18"
A-19
+18"
GFI
A-13
+18"
GFI
A-13
+18"
GFI
A-13
+18"
GFI
A-23
+18"
A-23
+18"
A-23
+18"
A-23
+48"
GFI
A-23
+48"
A-25+48"A-29+18"
A-35
+18"
A-31
+48"+48" A-31
+48"
+48"
A-35
+18"
A-35+18"
A-35+18"
A-35+18" A-37+48"
+48"
A-37
+48"
+48"
A-41
+18"
A-41+18"
A-41
+18"
A-41
+18"
A-41+18"
RTU-1
ON ROOF
EF-1
ON ROOFA-24
A-20
A-36A-26,28,30 GFI/WP
M/WP
+18"
GFI GFI
C/T
CP-1
A-32
CONTRACT DATE:
BUILDING TYPE:
PLAN VERSION:
BRAND DESIGNER:
SITE NUMBER:
STORE NUMBER:
FLUENT
763 ATLANTIC BLVD.
ATLANTIC BEACH, FL 32233
06/13/22
ARCVISION: 220224
C A N N A B I S C A R E
E1.0
ELECTRICAL
POWER PLAN
)
E 1/4" = 1'-0"POWER PLAN A NOT 86E'
POWER PLAN *ENERAL NOTE6 %POWER PLAN .E<E' NOTE6
A. CONTRACTOR SHALL COORDINATE QUANTITY AND FINAL LOCATION OF ALL TVS
WITH OWNER PRIOR TO CONSTRUCTION.
B. PROVIDE WORKING CLEARANCE AT ALL ELECTRICAL PANELS PER NEC.
C. COORDINATE WITH LOW-VOLTAGE VENDOR FOR EXACT LOCATIONS AND
REQUIREMENTS REGARDING ALL POS, SECURITY, IT, AND OTHER LOW VOLTAGE
ITEMS.
D. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATIONS AND HEIGHTS OF ALL
FIXTURES.
E. OUTLETS FOR WORKSTATIONS AND POS STATIONS SHOULD BE MOUNTED JUST
UNDER THE MONITOR SHELVES OR UNDER THE TABLES AND PHONE COUNTER.
F. ALL CONDUITS SHALL BE CONCEALED IN WALLS OR ABOVE CEILINGS. WHERE
CONDUIT CAN'T BE CONCEALED IT MUST BE PAINTED TO MATCH WALL COLORS.
G. SEE SYMBOLS LEGEND FOR ADDITIONAL INFORMATION.
H. WHEN REUSING EXISTING PANELS, E.C. SHALL VERIFY THE CONDITION AND
QUANTITY OF ALL EXISTING CIRCUIT BREAKERS. REPLACE DAMAGED BREAKERS
WITH NEW. PROVIDE ANY ADDITIONAL OR BREAKERS OF DIFFERENT AMPERAGE OR
POLE AS REQUIRED TO MEET THE END RESULT INDICATED IN THE PANEL
SCHEDULE. NEW BREAKERS SHALL BE OF THE SAME MFG AND CHARACTERISTICS
OF THE EXISTING. THE SUBMISSION OF THE BID PROPOSALS SHALL BE
CONSIDERED EVIDENCE THAT THE CONTRACTORS HAVE VISITED THE SITE. NO
EXTRA PAYMENTS WILL BE ALLOWED TO THESE CONTRACTORS ON ACCOUNT OF
EXTRA WORK MADE NECESSARY BY HIS FAILURE TO VISIT THE SITE.
I. CONTRACTOR SHALL TRACE OUT ALL EXISTING CIRCUITRY AND DETERMINE IF IS
NEEDED. IF CIRCUIT IS NOT NEEDED CONTRACTOR SHALL REMOVE ALL WIRING
AND DEVICES TO NEAREST JUNCTION BOX, CAP AND LABEL WIRING AND COVER
EXISTING BOX WITH A BLANK PLATE.
J. EXISTING CIRCUITRY SHALL BE VERIFIED IN FIELD PRIOR TO START OF WORK.
A''ITIONAL NOTE6
1. EC TO VERIFY EXISTING EQUIPMENT TO REMAIN. PROTECT EQUIPMENT
DURING CONSTRUCTION.
2. PROVIDE REQUIRED WORKING SPACE/CLEARANCE FOR ELECTRICAL PANEL
PER N.E.C.. CONTRACTOR TO CLEARLY IDENTIFY/INDICATE NOT LESS THAN
30"Wx36"D CLEARANCE AREA/ WORKING SPACE (PER IFC 605.3). IF
EQUIPMENT IS LARGER THAN 30" WIDE, WORKING SPACE/CLEARANCE SHALL
NOT BE LESS THAN EQUIPMENT WIDTH.
3. POS RECEPTACLE AND DATA RAN IN CASEWORK; CONTRACTOR SHALL
COORDINATE WITH ARCHITECT AND OWNER FOR EXACT LOCATION, HEIGHT,
AND REQUIREMENTS PRIOR TO ROUGH IN.
4. RECEPTACLE AND DATA FOR VIDEO SCREEN. CONTRACTOR SHALL
COORDINATE WITH ARCHITECT AND OWNER FOR EXACT LOCATION, HEIGHT,
AND REQUIREMENTS PRIOR TO ROUGH IN.
5. JUNCTION BOX FOR TERMINATION TO FLUENT CANNABIS SIGN. FIELD VERIFY
THE EXACT MOUNTING LOCATION AND CONNECTION REQUIRED, PRIOR TO
ROUGH-IN. PROVIDE SIGN DISCONNECT SWITCH, IF REQUIRED. INSTALL PER
N.E.C. ARTICLE 600 SIGNS.
6. NEW LOCATION FOR EXISTING WATER HEATER. CONTRACTOR SHALL EXTEND
BRANCH CIRCUIT, CONDUIT, AND ALL ASSOCIATED MATERIALS TO MAKE A
SAFE OPERATIONAL SYSTEM AT NEW WATER HEATER LOCATION AND PER
N.E.C. REQUIREMENTS.
7. PROVIDE AN UNDER-FLOOR TRENCH BETWEEN LOW-WALL AND BACK OF
HOUSE WALL, AS SHOWN. COORDINATE WITH OTHER DISCIPLINES WORK AS
NEEDED TO NOT DISTURB OTHERS WORK. CONTRACTOR TO FIELD-VERIFY
THE EXACT NUMBER OF CONDUITS REQUIRED FOR P.O.S.
POWER/COMMUNICATIONS. INSTALL BELOW-GRADE PER BURIAL
REQUIREMENTS IN THE N.E.C. AND SEALED PER THE U.L. LISTING FOR THE
ENVIRONMENT ENCOUNTERED.
8. PROVIDE A 3/4" CONDUIT FOR POWER AND A 3/4" CONDUIT FOR
COMMUNICATION TO COUNTER. PROVIDE TRANSITION AND STUB-UP INTO
COUNTER MILLWORK. EXTEND AND SECURE WIREWAY(S) ALONG THE BACK
OF CABINET. MAKE FINAL CONNECTIONS TO OUTLETS AT JUNCTION BOXES.
COORDINATE WITH MILLWORK CONTRACTOR FOR "STUB-THRU" LOCATIONS.
9. NEW ROOFTOP UNIT (RTU-1). EC TO PROVIDE 60A, 208V, 3P, NON-FUSED,
WEATHERPROOF DISCONNECT SWITCH. SEE PANEL SCHEDULE ON SHEET
E3.0 FOR WIRE SIZES. COORDINATE ALL REQUIREMENTS WITH HVAC
CONTRACTOR PRIOR TO BID.
10. EC TO PROVIDE GFI WEATHERPROOF DUPLEX RECEPTACLE AT HVAC
EQUIPMENT.
11. PROVIDE CONNECTION FROM AIR DUCT SMOKE DETECTORS TO MECHANICAL
CONTROL CIRCUIT. COORDINATE ALL REQUIREMENTS WITH HVAC
CONTRACTOR PRIOR TO BID.
12. PROVIDE 20A, 120V, WEATHERPROOF TOGGLE SWITCH DISCONNECT FOR
EF-1. COORDINATE LOCATION WITH MANUFACTURER. CIRCUIT THROUGH
TIMECLOCK FOR OPERATION ONLY DURING OCCUPIED HOURS.
13. PROVIDE A TIMECLOCK FOR CIRCULATING PUMP CONTROL AND TOGGLE
SWITCH DISCONNECT. TIMECLOCK SHALL BE WIRED AHEAD OF DISCONNECT.
MOUNT ON WALL ADJACENT TO WATER HEATERS.
C
N
TRUE
N
PROJECT
'NOT 86E'
FIRE ALARM:
AS REQUIRED, IT SHALL BE THE GENERAL CONTRACTORS RESPONSIBILITY TO
ENGAGE THE SERVICES OF AN APPROVED FIRE ALARM CONTRACTOR. THE FIRE
ALARM CONTRACTOR SHALL BE REQUIRED TO PROVIDE DRAWINGS, SPECIFICATIONS
& INSTALLATION ACCORDING TO MUNICIPALITIES GUIDELINES. FIRE ALARM SERVICE
MAY ALSO INCLUDE PROVIDING FIRE ALARM MONITORING TO BUILDING'S INSTALLED
FIRE ALARM CONTROL SYSTEM. FIRE ALARM CONTRACTOR TO PROVIDE COMPATIBLE
DEVICES & ALL BRACING, WIRING, ETC. COORDINATE WITH LANDLORD'S FIRE ALARM
CONTRACTOR FOR DETAILS.
EQUIPMENT:
THE EQUIPMENT AND DIMENSIONED LOCATIONS FOR CONNECTIONS ARE ACCURATE
TO THE BEST OF OUR KNOWLEDGE, BUT SHALL BE VERIFIED WITH THE EQUIPMENT
SUPPLIER, EQUIPMENT ROUGH-IN DRAWINGS, AND/OR THE OWNER. IN SOME
INSTANCES, THE OWNER OR SUPPLIER MAY MAKE SUBSTITUTIONS OR THE
EQUIPMENT MAY VARY FROM WHAT IS SHOWN ON THE PLAN. THE
ARCHITECT/ENGINEER SHALL BE IMMEDIATELY NOTIFIED, PRIOR TO CONSTRUCTION,
OF ANY DEVIATIONS FROM WHAT IS SHOWN OR IMPLIED ON THESE DRAWINGS.
FAILURE OF THE APPROPRIATE CONTRACTOR TO VERIFY ROUGH-INS OR THEIR
LOCATIONS SHALL PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION
AND/OR ADDITIONAL ROUGH-INS DIRECTLY UPON THE CONTRACTOR.
FLORIDA BUILDING CODE REQUIREMENT - ENERGY CONSERVATION:
WITHIN 30-DAYS AFTER DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE
ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER, INCLUDING: 1.
A SINGLE-LINE DIAGRAM OF BUILDING ELECTRICAL SYSTEM AND 2. FLOOR PLAN
INDICATING LOCATION AND AREA SERVED FOR ALL DISTRIBUTION. AN OPERATIONS
MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING OWNER, THE
MANUALS SHALL INCLUDE AT MINIMUM, THE FOLLOWING: 3. SUBMITTAL DATA STATING
THE EQUIPMENT RATINGS AND SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT
REQUIRING MAINTENANCE. 4. OPERATIONS MANUAL AND MAINTENANCE MANUAL FOR
EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE
MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED. 5. NAMES AND ADDRESS OF
AT LEAST ONE QUALIFIED SERVICE AGENCY. PRIOR TO PASSING FINAL INSPECTION,
THE REGISTERED DESIGN PROFESSIONAL/INSTALLER SHALL PROVIDE EVIDENCE
THAT THE LIGHTING CONTROL SYSTEM HAVE BEEN TESTED TO ENSURE THAT
CONTROL HARDWARE AND SOFTWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED
AND IN PROPER WORKING CONDITION IN ACCORDANCE WITH THE CONSTRUCTION
DOCUMENTS AND MANUFACTURES INSTRUCTIONS. FUNCTIONAL TESTING SHALL BE
IN ACCORDANCE WITH SECTIONS C408.3.1.1 & C408.3.1.3 FOR APPLICABLE CONTROL
TYPE.
8/22/22