FIRE Returned for CorrectionsReturned for Corrections: The plans submitted for review have been returned for corrections. Please correct and or provide the additional requested information to obtain plans approval. When resubmitting corrected sheets, provide a type written itemized narrative letter responding to our comments and directing the plans reviewer to the sheets the changes have taken place. FAILURE TO SUPPLY RESPONSE LETTER “WILL” RESULT IN A RETURNED FOR CORRECTIONS PERMIT STATUS. Revised sheets should be clouded, clearly showing areas were changes or corrections have occurred and re-inserted with the original set of drawings with old sheets removed. Unbound plans will not be reviewed. If this is an electronic submission please make sure that written narrative is submitted under correspondence along with a “complete set” (not just the revised sheets) of electronic documents. When submitting electronic plans, each discipline shall upload a single PDF file containing multiple sheets rather than separate PDFs for each sheet. Please re-upload in this fashion. 1.nfpa 101-6.1.1.14.1 business to mercantile needs 2 hr rate wall 10 unit to 9unit. 2.nfpa 101-A6.1.10.1 (4) restaurant with less than 50 people is MERCANTILE 3.nfpa 101-7.3.1.2 occupany load is 30 Miguel Di Pierri 214 Hogan St 2 Floor # 2116 Jacksonville FL. 32202 Plan Review Spanish Advocate Dipierri@coj.net off ; 904-255-8561 cell ; 904-763-1290