299 ATLANTIC BLVD COMM22-0013 AB Kitchen COMcheck Signed.COMcheck Software Version COMcheckWeb
Interior Lighting Compliance Certificate
Project Title:
2020 Florida Building Code, Energy Conservation
Project Type:Alteration
Construction Site:
299 ATLANTIC BLVD
ATLANTIC BEACH, Florida 32233
Owner/Agent:
Florida
Designer/Contractor:
MIKE KLEINSCHMIDT
DESIGN COOPERATIVE, LLC
1032 HENDRICKS AVE
JACKSONVILLE, Florida 32207
904-200-5673
MIKE@DCOOP.COM
Project Information
Energy Code:
AB KITCHEN
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed
Watts
1-RESTAURANT (Common Space Types:Dining Area - Family Restaurant)2095 0.71 1487
1487Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixture
RESTAURANT (Common Space Types: Dining Area - Family Restaurant, 2095 sq.ft.)
LED: HL36AR13FL927ED010TAT-TL3RMW: RECESS CAN LIGHT: LED A Lamp 13W:1 4 13 52
LED: PR620FS12D010-PR6M12MD827MW: RECESS CAN LIGHT: LED A Lamp 25W:1 16 21 336
LED: HCC4S20D010MW-HM412827-41WDWWF: SURFACE CAN LIGHT: LED A Lamp
25W:
1 8 20 160
Track Lighting: STT25XM-13L-27K-WD-BLU-TM48V-PS: TRACK LIGHT: Wattage
based on 4 feet of track
0 0 32 32
Track Lighting: OPTICS ARTS: MB-KMSC-A-SA; LINE: LED TAPE LIGHT: Wattage
based on 9 feet of track
0 0 72 72
LED: MIST LED PENDANT S/L; SIZE:SL; : DECORATIVE PENDANT LIGHT: LED Other
Fixture Unit 60W:
1 5 50 250
LED: SATELISE PENDANT; FOR-20440; FR: DECORATIVE PENDANT LIGHT: LED A
Lamp 2.5W:
1 12 9 108
LED: AZORES 4 LIGHT 25" WIDE BATH BA: DECORATIVE WALL SCONE: LED A Lamp
3.2W:
2 2 3 6
1016Total Proposed Watts =
Interior Lighting Compliance
Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting
systems have been designed to meet the 2020 Florida Building Code, Energy Conservation requirements in COMcheck Version
COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist.
Interior Lighting PASSES
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
131 ofPage
Name - Title Signature Date
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
132 ofPage
Ian G. Vega P.E., Mechanical Engineer 3-4-2022
Ian G Vega
Marina
Digitally signed by
Ian G Vega Marina
Date: 2022.03.04
17:25:23 -05'00'
COMcheck Software Version COMcheckWeb
Mechanical Compliance Certificate
Project Title:
2020 Florida Building Code, Energy Conservation
Project Type:Alteration
Location:Jacksonville, Florida
Climate Zone:2a
Construction Site:
299 ATLANTIC BLVD
ATLANTIC BEACH, Florida 32233
Owner/Agent:
Florida
Designer/Contractor:
MIKE KLEINSCHMIDT
DESIGN COOPERATIVE, LLC
1032 HENDRICKS AVE
JACKSONVILLE, Florida 32207
904-200-5673
MIKE@DCOOP.COM
Project Information
Energy Code:
AB KITCHEN
Mechanical Systems List
QuantitySystem Type & Description
Single Package Heat Pump
Heating Mode: Capacity = 180 kBtu/h,
Proposed Efficiency = 3.20 COP, Required Efficiency = 3.20 COP
Cooling Mode: Capacity = 180 kBtu/h, , Air Economizer
Proposed Efficiency = 10.60 EER, Required Efficiency: 10.60 EER + 11.6 IEER
1 HVAC System (Single Zone):
Cooling: 1 each - Room AC With Louvered Sides, Capacity = 24 kBtu/h, Air-Cooled Condenser, Unknown Economizer
Proposed Efficiency = 9.40 CEER, Required Efficiency: 9.40 CEER
1 HVAC System (Single Zone):
Gas Instantaneous Water Heater, Capacity: 1 gallons, Input Rating: 199 kBtu/h w/ Circulation Pump
Proposed Efficiency: 0.93 UEF, Required Efficiency: 0.81 UEF
2 Water Heater:
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building
plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2020 Florida Building Code, Energy Conservation requirements in COMcheck Version COMcheckWeb and to
comply with any applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
133 ofPage
Ian G. Vega P.E., Mechanical Engineer 3-4-2022
Inspection Checklist
Requirements: 100.0% were addressed directly in the COMcheck software
COMcheck Software Version COMcheckWeb
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2020 Florida Building Code, Energy Conservation
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C103.2
[PR3]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the service water
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C103.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
134 ofPage
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C403.2.4.
5
[FO9]3
Snow/ice melting system and freeze
protection systems have sensors and
controls configured to limit service for
pavement temperature and outdoor
temperature. future connection to
controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
135 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.6.1,
C404.6.2
[PL3]1
Automatic time switches installed to
automatically switch off the
recirculating hot-water system or heat
trace.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
136 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C402.2.6
[ME41]3
Thermally ineffective panel surfaces of
sensible heating panels have
insulation >= R-3.5.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.12
.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
C403.2.12
.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
C403.2.12
.3
[ME117]2
Fans have energy index (FEI) >= 1.00
in accordance with AMCA 208. Fans
for VAV systems shall have an FEI >=
0.95.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.12
.3
[ME117]2
Fans have energy index (FEI) >= 1.00
in accordance with AMCA 208. Fans
for VAV systems shall have an FEI >=
0.95.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.3
[ME55]2
HVAC equipment efficiency verified.Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.2.4.
7
[ME113]2
Fault detection and diagnostics
installed with air-cooled unitary DX
units having economizers.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.6
[ME59]1
Natural or mechanical ventilation is
provided in accordance with Florida
Building Code Chapter 4. Mechanical
ventilation has capability to reduce
outdoor air supply to minimum per
Florida Building Code Chapter 4.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.6.
1
[ME59]1
Demand control ventilation provided
for spaces >500 ft2 and >25
people/1000 ft2 occupant density and
served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.6.
2
[ME115]3
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50% or less of design capacity.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.4.
8
[ME141]3
HVAC systems serving guestrooms in
Group R-1 buildings with > 50
guestrooms: Each guestroom is
provided with controls that
automatically manage temperature
setpoint and ventilation (see sections
C403.2.4.8.1 and C403.2.4.8.2).
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.7
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.2.7(1)
and C403.2.7(2).
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
137 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.2.8
[ME116]3
Kitchen exhaust systems comply with
replacement air and conditioned
supply air limitations, and satisfy hood
rating requirements and maximum
exhaust rate criteria.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.9.
1,
C403.2.9.
2
[ME60]2
HVAC ducts and plenums insulated in
accordance with C403.2.9.1 and
constructed in accordance with
C403.2.9.2, verification may need to
occur during Foundation Inspection.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.3,
C403.3.1,
C403.3.2
[ME62]1
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high-limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.3.3.
3
[ME124]1
Air economizers automatically reduce
outdoor air intake to the design
minimum outdoor air quantity when
outdoor air intake will not reduce
cooling energy usage. See Table
C403.3.3.3 for applicable device types
and climate zones.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.3.3.
4
[ME125]1
System capable of relieving excess
outdoor air during air economizer
operation to prevent overpressurizing
the building. The relief air outlet
located to avoid recirculation into the
building.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.3.3.
5
[ME126]1
Return, exhaust/relief and outdoor air
dampers used in economizers have
motorized dampers that automatically
shut when not in use and meet
maximum leakage rates. Reference
section C403.2.4.3 for details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.2.
1
[ME53]3
Air outlets and zone terminal devices
have means for air balancing.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.5,
C403.5.1,
C403.5.2
[ME123]3
Refrigerated display cases, walk-in
coolers or walk-in freezers served by
remote compressors and remote
condensers not located in a
condensing unit, have fan-powered
condensers that comply with Sections
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
138 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.2.
2
[EL22]1
Spaces required to have light-
reduction controls have a manual
control that allows the occupant to
reduce the connected lighting load in
a reasonably uniform illumination
pattern >= 50 percent.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.1,
C405.2.1.
1
[EL18]1
Occupancy sensors installed in
classrooms/lecture/training rooms,
conference/meeting/multipurpose
rooms, copy/print rooms,
lounges/breakrooms, enclosed offices,
open plan office areas, restrooms,
storage rooms, locker rooms,
warehouse storage areas, and other
spaces <= 300 sqft that are enclosed
by floor-to-ceiling height partitions.
Reference section language
C405.2.1.2 for control function in
warehouses and section C405.2.1.3
for open plan office spaces.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.2.1.
2
[EL19]1
Occupancy sensors control function in
warehouses: In warehouses, the
lighting in aisleways and open areas is
controlled with occupant sensors that
automatically reduce lighting power
by 50% or more when the areas are
unoccupied. The occupant sensors
control lighting in each aisleway
independently and do not control
lighting beyond the aisleway being
controlled by the sensor.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.2.1.
3
[EL20]1
Occupant sensor control function in
open plan office areas: Occupant
sensor controls in open office spaces
>= 300 sq.ft. have controls 1)
configured so that general lighting can
be controlled separately in control
zones with floor areas <= 600 sq.ft.
within the space, 2) automatically turn
off general lighting in all control zones
within 20 minutes after all occupants
have left the space, 3) are configured
so that general lighting power in each
control zone is reduced by >= 80% of
the full zone general lighting power
within 20 minutes of all occupants
leaving that control zone, and 4) are
configured such that any daylight
responsive control will activate space
general lighting or control zone
general lighting only when occupancy
for the same area is detected.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.2.2,
C405.2.2.
1,
C405.2.2.
2
[EL21]2
Each area not served by occupancy
sensors (per C405.2.1) have time-
switch controls and functions detailed
in sections C405.2.2.1 and C405.2.2.2.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
139 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.3,
C405.2.3.
1,
C405.2.3.
2
[EL23]2
Daylight zones provided with
individual controls that control the
lights independent of general area
lighting. See code section C405.2.3
Daylight-responsive controls for
applicable spaces, C405.2.3.1 Daylight
responsive control function and
section C405.2.3.2 Sidelit zone.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.2.4
[EL26]1
Separate lighting control devices for
specific uses installed per approved
lighting plans. 1. Display and accent
lighting, lighting in display cases,
supplemental task lighting and
lighting equipment for sale shall have
occupancy sensor control. 2) Sleeping
units shall have auto off controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.6
[EL26]2
Low-voltage dry-type distribution
electric transformers meet the
minimum efficiency requirements of
Table C405.6.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.7
[EL27]2
Electric motors meet the minimum
efficiency requirements of Tables
C405.7(1) through C405.7(4).
Efficiency verified through certification
under an approved certification
program or the equipment efficiency
ratings shall be provided by motor
manufacturer (where certification
programs do not exist).
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.8.2,
C405.8.2.
1
[EL28]2
Escalators and moving walks comply
with ASME A17.1/CSA B44 and have
automatic controls configured to
reduce speed to the minimum
permitted speed in accordance with
ASME A17.1/CSA B44 or applicable
local code when not conveying
passengers.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.5.3
[EL29]2
Total voltage drop across the
combination of feeders and branch
circuits <= 5%.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
1310 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C408.2.5.
2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.1
[FI50]3
HVAC systems and equipment design
loads calculated in accordance with
ANSI/ASHRAE/ACCA Standard 183 or
by an approved equivalent
computational procedure
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.2
[FI27]3
HVAC systems and equipment
capacity does not exceed calculated
loads.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1.1
[FI42]3
Heat pump controls prevent
supplemental electric resistance heat
from coming on when not needed.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1.2
[FI38]3
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1.3
[FI20]3
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
2
[FI39]3
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
2.1,
C403.2.4.
2.2
[FI40]3
Automatic Controls: Setback to 55°F
(heat) and 85°F (cool); 7-day clock, 2-
hour occupant override, 10-hour
backup
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.3
[FI11]3
Heat traps installed on supply and
discharge piping of non-circulating
systems.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.4
[FI25]2
All recirculation piping, first 8 feet of
outlet or branch piping, inlet piping
and piping that is externally heated
shall be insulated in accordance with
section details and Table C403.2.10
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
1311 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C404.6.1
[FI12]3
Controls are installed that limit the
operation of a recirculation pump
installed to maintain temperature of a
storage tank. System return pipe is a
dedicated return pipe or a cold water
supply pipe.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C405.3.2
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
C408.1.1
[FI57]1
Building operations and maintenance
documents will be provided to the
owner. Documents will cover
manufacturers' information,
specifications, recommendations,
programming procedures and means
of illustrating to owner how building,
equipment and systems are intended
to be installed, maintained, and
operated. Regular maintenance
actions shall be clearly stated on
accessible label.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.1
[FI28]1
Commissioning plan developed by
registered design professional or
approved agency.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.3.
1
[FI31]1
HVAC equipment has been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.3.
2
[FI10]1
HVAC control systems have been
tested to ensure proper operation,
calibration and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.3.
3
[FI32]1
Economizers have been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.4
[FI29]1
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
1
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
3
[FI43]1
An air and/or hydronic system
balancing report is provided for HVAC
systems.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
4
[FI30]1
Final commissioning report due to
building owner within 90 days of
receipt of certificate of occupancy.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
1312 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C408.3
[FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
AB KITCHEN 03/04/22Report date:
1313 ofPage