447 ATLANTIC BLVD SIGN24-0005 Gateway Vision CALCSDESIGN CALCULATIONS FOR GATEWAY VISION WALL-MOUNTED SIGNS 447 Atlantic Blvd – Atlantic Beach Index: Pg 1 Cover Pg 2 Wind Loads Pg 3 Anchor Design PE # 67382 Easy Seals Cert Auth # 31124 Engineer's signature and seal valid for pages 1 through 3 Jun 05 2024 Christian Langley GENERAL NOTES: 1.Design is in accordance with the Florida Building Code 8th Edition (2023) for use within and outside the High Velocity Hurricane Zone (HVHZ). 2.Wind loads have been calculated per the requirements of ASCE 7-22 as shown herein. 3.These engineering calculations pertain only to the structural integrity of those systems, components, and/or other construction explicitly specified herein and/or in accompanying engineering drawings. The existing host structure (if any) is assumed to be in good condition, capable of supporting the loaded system, subject to building department approval. No warranty, either expressed or implied, is contained herein. 4.System components shall be as noted herein. All references to named components and installation shall conform to manufacturer's or industry specifications as summarized herein. 5.Where site conditions deviate from those noted herein, revisions may be required or a separate site-specific engineering evaluation performed. 6.Aluminum components in contact with steel or embedded in concrete shall be protected as prescribed in the 2020 Aluminum Design Manual. Steel components in contact with, but not encased in, concrete shall be coated, painted, or otherwise protected against corrosion. 7.Engineer seal affixed hereto validates structural design as shown only. Use of this specification by contractor, et. Al, indemnifies and saves harmless this engineer for all costs & damages including legal fees & apellate fees resulting from deviation from this design. This item has been digitally signed and sealed by Christian Langley PE onthe date adjacentto the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on anyelectroniccopies. Serial:4A49 8F53 221830 0D229D96 67 1200 N Federal Hwy, #200 Boca Raton, FL 33432 Easy Seals .com Page 1 CALCULATIONS FOR WALL-MOUNTED SIGNS ASCE 7-22 Design Wind Loads WALL-MOUNTED SIGNS Building Specs V =130 mph Basic wind speed (Vult)ASD Load Combo Coeff:0.6 Exposure C Risk Category:II ←Tornado load eval not req'd Ae =N/A Effective plan area (sqft) VT =N/A Tornado speed (Vult) VT/V = N/A Calculations α =9.8 3-sec gust speed power law exponent Kd =0.85 Directionality factor zg =2460'Nominal ht. of atmos. boundary layer Kzt =1.0 Topographic factor Gcpi =0 Internal pressure coeff Ke =1.0 Ground elevation factor A =10 sq ft Tributary area CENTER (Zone 4) CORNER (Zone 5)Kh = Kz qz GCp (4)GCp (5) 15 ft 20.7 psf 26.3 psf 0.85 22.1 -1.10 -1.40 20 ft 21.9 psf 27.9 psf 0.90 23.4 -1.10 -1.40 25 ft 22.9 psf 29.2 psf 0.94 24.5 -1.10 -1.40 30 ft 23.8 psf 30.3 psf 0.98 25.5 -1.10 -1.40 35 ft 24.6 psf 31.3 psf 1.01 26.3 -1.10 -1.40 40 ft 25.2 psf 32.1 psf 1.04 27.0 -1.10 -1.40 45 ft 25.9 psf 32.9 psf 1.07 27.6 -1.10 -1.40 50 ft 26.4 psf 33.6 psf 1.09 28.2 -1.10 -1.40 55 ft 26.9 psf 34.3 psf 1.11 28.8 -1.10 -1.40 60 ft 27.4 psf 34.9 psf 1.13 29.3 -1.10 -1.40 70 ft 23.1 psf 46.3 psf 1.17 30.3 -0.90 -1.80 80 ft 23.8 psf 47.6 psf 1.20 31.1 -0.90 -1.80 90 ft 24.4 psf 48.7 psf 1.23 31.8 -0.90 -1.80 100 ft 24.9 psf 49.8 psf 1.25 32.5 -0.90 -1.80 110 ft 25.4 psf 50.8 psf 1.28 33.2 -0.90 -1.80 120 ft 25.8 psf 51.7 psf 1.30 33.8 -0.90 -1.80 130 ft 26.3 psf 52.5 psf 1.32 34.3 -0.90 -1.80 140 ft 26.7 psf 53.3 psf 1.34 34.9 -0.90 -1.80 150 ft 27.0 psf 54.1 psf 1.36 35.3 -0.90 -1.80 175 ft 27.9 psf 55.8 psf 1.41 36.5 -0.90 -1.80 200 ft 28.7 psf 57.4 psf 1.44 37.5 -0.90 -1.80 250 ft 30.0 psf 60.0 psf 1.51 39.2 -0.90 -1.80 130 mph - Exp ''C'' WALL-MOUNTED SIGNS SIGN HEIGHT ASD WIND PRESSURES Page 2 CALCULATIONS FOR WALL-MOUNTED SIGNS Wall Sign Anchor Design Structure Dimensions & Loading Design wind pressure:P =30.3 psf Sign type: Sign size:A =25.6 sqft (entire letterset) Wall material:CDX or equiv, thickness to match Min Embed Anchor type/size: Ref: Min Embedment:Full Min edge dist:1.5"Min Spacing:1.5" Anchor tensile capacity:Tcap =1014.8 lb (per anchor) Check Anchors for Pullout Total Reaction:Rt =774 lb … = P*A (entire letterset) No. of anchors req'd:n =0.8 total anchors … = Rt/cap Total anchors required:1 total anchors balanced over letterset OK, use (2) each tube frame = (12) bolts total. AAMA TIR-A9-1991 Letterset Wood 3/8" Bolt + Nut Page 3