725 ATLANTIC BLVD 6 PPI24-0004 .Atlantic Coast Appliance - Mechanical PlansMECHANICAL GENERAL NOTES SYMBOL LEGEND ABBREVIATIONS 1.ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN DUCTS, AND TRANSITION AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COSTS. 2.LOCATE ALL RTU's, EF's, AND OTHER SERVICEABLE MECHANICAL EQUIPMENT A MINIMUM OF 10 FT FROM THE ROOF EDGE. GUARDS SHALL BE PROVIDED WHERE SERVICEABLE MECHANICAL EQUIPMENT IS LOCATED WITHIN 10 FT. OF A ROOF EDGE. THE GUARD SHALL EXTEND NOT LESS THAN 30 IN. BEYOND EACH END OF SUCH EQUIPMENT, AND THE TOP OF THE GUARD SHALL BE LOCATED NOT LESS THAN 42 IN. ABOVE THE ELEVATED SURFACE ADJACENT TO THE GUARD. 3.PROVIDE CONICAL TAKE-OFFS FOR ALL TAPS INTO DUCTWORK WITH VOLUME DAMPERS AT EACH TAKE-OFF FOR CFM ADJUSTMENT. 4.COORDINATE DIFFUSER BOXES, SUPPLY, RETURN GRILLES AND OTHER MECHANICAL DEVICES WITH LIGHT FIXTURES WHERE THE AIR DISCHARGES DIRECTLY ON THE FIXTURE. ENGINEER MUST BE NOTIFIED IN ALL CASES WHERE COORDINATION IS IN QUESTION. 5.HORSEPOWER RATINGS ON MOTORS ARE BASED ON SCHEDULED EQUIPMENT AND DESIGN CONDITIONS. ACTUAL FIELD CONDITIONS OR SUBSTITUTIONS FROM SCHEDULED EQUIPMENT MAY REQUIRE DIFFERENT HORSEPOWER. IF LARGER MOTOR SIZES ARE REQUIRED OR CHANGES OCCUR IN VOLTAGES, COORDINATE ELECTRICAL SERVICE TO ENSURE PROPER WIRE SIZES AND DEVICES AT NO ADDITIONAL COMPENSATION (DUE TO THESE CHANGES) ASKED FOR OR REQUESTED BY ANOTHER CONTRACTOR OR TRADE. ADDITIONAL COMPENSATION RESULTING FROM EQUIPMENT SUBMITTED FOR REASONS OF CONTRACTOR PREFERENCE OR AVAILABILITY, SHALL BE PAID BY THIS CONTRACTOR WITH NO ADDITIONAL EXPENSE TO THE OWNER. 6.CONTRACT DRAWINGS ARE BASED ON THE EQUIPMENT SPECIFIED. MAKE ADJUSTMENTS, MODIFICATIONS OR CHANGES REQUIRED, DUE TO USE OF OTHER EQUIPMENT, WITH NO ADDITIONAL COMPENSATION EXPECTED FOR OR DEMANDED BY THIS CONTRACTOR OR ANY OTHER CONTRACTOR OR TRADE. ANY ADDITIONAL COMPENSATION AS A RESULT OF CHANGES IN EQUIPMENT, STRUCTURAL FRAMING, CONCRETE FOUNDATION, OR OTHER PHYSICAL CHANGES SHALL BE BORE BY THIS CONTRACTOR, WITH NO ADDITIONAL EXPENSE TO THE OWNER. 7.PROVIDE THERMOSTATS FOR ALL RTU's WHETHER SHOWN OR NOT. IF LOCATION IS NOT SHOWN ON DRAWINGS, CHECK WITH ENGINEER FOR EXACT PLACEMENT. LOCATIONS SHOWN ARE APPROXIMATE, AND MAY NEED TO BE ADJUSTED DUE TO FURNITURE LOCATIONS OR OTHER OBSTRUCTIONS. THERMOSTATS LOCATED IN PUBLIC AREAS SHALL BE IN A LOCKABLE CASE. 8.PROVIDE SMOKE DETECTORS IN SUPPLY DUCTS FOR ALL RTU'S THAT DELIVER GREATER THAN 2000 CFM OF SUPPLY AIR FOR UNIT SHUTDOWN. CONTRACTOR SHALL PROVIDE AUDIBLE AND VISUAL ALARM IN A CONSTANTLY OCCUPIED LOCATION. ALARM SHALL BE LABELED "DUCT TROUBLE". 9.ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE 2023 FLORIDA MECHANICAL CODE, WITH ALL REVISIONS, NFPA 90A AND ASHRAE 62.1-2016. 10.GENERAL CONTRACTOR SHALL OBTAIN SERVICES OF A TEST AND BALANCE AGENCY THAT SPECIALIZES IN AND WHOSE BUSINESS IS LIMITED TO THE TESTING AND BALANCING OF AIR CONDITIONING SYSTEMS AND IS A TRUE THIRD PARTY OF THE MECHANICAL CONTRACTOR. THE AGENCY SELECTED SHALL BE A FULLY CERTIFIED MEMBER OF THE ASSOCIATED AIR BALANCE COUNCIL (AABC) OR NATIONAL ENVIRONMENTAL BALANCING BUREAU. (NEBB) TEST AND BALANCE ENTIRE HVAC SYSTEM IN ACCORDANCE WITH LATEST AABC OR NEDD STANDARDS. SUBCONTRACTOR SHALL PROVIDE SUFFICIENT TIME BEFORE THE SUBSTANTIAL COMPLETION DATE SO THAT TESTS AND BALANCING CAN BE ACCOMPLISHED. 10.A.NAME OF TEST AND BALANCE AGENCY SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL WITHIN 20 DAYS AFTER RECEIPT OF CONTRACT. TEST AND BALANCE AGENCY SHALL NOTIFY ENGINEER OF ANY ADDITIONAL REQUIRED TEST COCK LOCATIONS, BALANCING DAMPER LOCATIONS, ETC. WITHIN 30 DAYS AFTER APPROVAL OF THE AGENCY. ANY ADDITIONAL BALANCING DEVICES REQUIRED BY THE TEST AND BALANCE AGENCY AFTER THIS PERIOD WILL BE INSTALLED AT NO EXPENSE TO THE OWNER BY THE CONTRACTOR. 10.B.TEST AND BALANCE AGENCY SHALL INCLUDE AN EXTENDED WARRANTY OF 90 DAYS, AFTER COMPLETION OF TEST AND BALANCE WORK, DURING WHICH TIME THE ENGINEER, AT THEIR DISCRETION, MAY REQUEST A RECHECK OR RESETTING OF ANY ITEMS INCLUDED IN THE AIR DISTRIBUTION SYSTEMS. IN THE EVENT THE REPORT IS REJECTED, ALL SYSTEMS SHALL BE READJUSTED AND TESTED, NEW DATA RECORDED, NEW CERTIFIED REPORTS SUBMITTED, AND NEW INSPECTION TESTS MADE.THE AGENCY SHALL PROVIDE TECHNICIANS TO ASSIST THE ENGINEER IN MAKING ANY TEST THEY MAY REQUIRE DURING THIS PERIOD OF TIME. 11.FOR ANY UNITS WITH HOT GAS REHEAT, VAV CONTROLS, BAS INTERFACES,ETC., MECHANICAL CONTRACTOR NEEDS TO COMMISSION THE UNIT AFTER INSTALLATION. 12.MAINTAIN A MINIMUM OF 10'-0" BETWEEN ALL OUTDOOR INTAKES AND ANY VENTS OR EXHAUSTS. 13.ALL DUCTWORK LOCATED IN UNCONDITIONED SPACES SHALL BE INSULATED WITH A MINIMUM R-6. 14.RTU's SHALL HAVE AN OUTDOOR AIR INTAKE BALANCED TO SCHEDULED VALUES. 15.ROUTE CONDENSATE FROM RTU'S TO NEAREST ROOF DRAINS. 16.RTU CONCEALED DUCTWORK SHALL BE CONSTRUCTED WITH SHEET METAL OR DUCTBOARD. EXPOSED DUCT SHALL BE SHEET METAL AND INTERNAL INSULATED OR INSULATED SPIRAL DUCT PER LATEST SMACNA STANDARDS. 17.ALL RTU'S AND ROOF MOUNTED EF'S SHALL BE INSTALLED ON FACTORY INSULATED ROOF CURBS. CONTRACTOR TO PROVIDE ROOF CURB ANGLES FOR ALL ROOF PENETRATIONS INCLUDING KITCHEN EQUIPMENT. 18.ALL ROOF CURBS SHALL BE FABRICATED SO THAT THE TOP OF CURB IS LEVEL WITH THE HORIZON REGARDLESS OF ROOF PITCH. 19.ALL UNITS SHALL HAVE INSULATED DRAIN PANS AND SHALL BE INTERNALLY INSULATED AND WATERPROOFED. CONDENSATE SHALL BE SIZED AND TRAPPED PER MANUFACTURER'S RECOMMENDATIONS. 20.RTU CASINGS SHALL BE DIEFORMED STEEL WITH SMOOTH PANEL CONSTRUCTION WITHOUT SHARP ANGLES OR EDGES. ALL COMPONENT SECTIONS SHALL HAVE REMOVABLE PANELS FOR ACCESS TO THE INTERIOR. 21.PROVIDE ENGINEER OF RECORD WITH HVAC EQUIPMENT CUT SHEETS. CUT SHEETS SHALL BE APPROVED PRIOR TO INSTALLATION. 22.THE MECHANICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID FOR THE PROJECT. THE MECHANICAL CONTRACTOR SHALL COORDINATE DUCTWORK LOCATIONS DESIGNED BY THE MECHANICAL ENGINEER AND FIELD VERIFY ANY OBSTACLES OR CONFLICTS AND NOTE THEM IMMEDIATELY TO THE ENGINEER. NO DUCTWORK SHALL BE FABRICATED PRIOR TO FIELD VERIFYING ALL EXISTING CONDITIONS. NOTE: SOME SYMBOLS SHOWN DO NOT PERTAIN TO THIS PROJECT THERMOSTAT/SENSOR SUPPLY AIRFLOW RETURN/ EXHAUST AIRFLOW DEHUMIDISTAT AIR DEVICE TYPE CFM AMOUNT SMOKE DETECTOR DUCT TEMPERATURE SENSOR CEILING RETURN AIR GRILLE CEILING EXHAUST AIR GRILLE MANUAL VOLUME DAMPER CEILING SUPPLY AIR DIFFUSERNEW RECTANGULAR DUCT (INSIDE DIMENSIONS; WIDTH X DEPTH) FLEX DUCT (INSIDE DIMENSION) NEW ROUND DUCT (INSIDE DIMENSION) EXISTING DUCT TO REMAIN EXISTING DUCT TO BE REMOVED CONNECT NEW DUCT TO EXISTING DUCT TRUNCATE DUCT - LIMIT OF DEMOLITION VANED ELBOW RADIUS ELBOW TRANSITION - CONCENTRIC TRANSITION - ECCENTRIC SQUARE TEE SUPPLY DUCT (UP & DOWN) RETURN DUCT (UP & DOWN) EXHAUST DUCT (UP & DOWN) ROUND DUCT (UP & DOWN) STANDARD BRANCH TAKE-OFF DUCT / WALL MOUNTED SUPPLY REGISTER / GRILLE DUCT / WALL MOUNTED RETURN/ EXHAUST REGISTER / GRILLE ABV ABOVE AFF ABOVE FINISH FLOOR AHU AIR HANDLING UNIT BDD BACKDRAFT DAMPER BHP BRAKE HORSEPOWER BTU BRITISH THERMAL UNIT CFM CUBIC FEET PER MINUTE CIRC CIRCULAR CU CONDENSING UNIT DCI DUCTLESS CEILING-CASSETTE INDOOR DCO DUCTLESS CEILING-CASSETTE OUTDOOR DN DOWN DWI DUCTLESS WALL-MOUNTED INDOOR DWO DUCTLESS WALL-MOUNTED OUTDOOR EAT ENTERING AIR TEMPERATURE EDB ENTERING DRY-BULB (TEMPERATURE) EER ENERGY EFFICIENCY RATIO EF EXHAUST FAN ESP EXTERNAL STATIC PRESSURE EWB ENTERING WET-BULB (TEMPERATURE) EX EXISTING FD FIRE DAMPER FF FLY FAN (AIR CURTAIN) FLA FULL LOAD AMPS FPM FEET PER MINUTE FT FEET GPM GALLON PER MINUTE HE HEATER HP HEAT PUMP HP HORSEPOWER HUM HUMIDIFIER IN INCHES IRH INFRARED HEATERS KEF KITCHEN EXHAUST FAN KW KILOWATT L LOUVER LAT LEAVING AIR TEMPERATURE MBH THOUSANDS BTUs PER HOUR MCA MINIMUM CIRCUIT AMPS MOCP MAXIMUM OVER CURRENT PROTECTION MOD MOTOR OPERATED CONTROL DAMPER MUA MAKE-UP AIR UNIT NA NOT APPLICABLE NC NOISE CRITERIA NC NORMALLY CLOSED NO NORMALLY OPEN NTS NOT TO SCALE OA OUTSIDE AIR OD OUTSIDE DIAMETER PSI POUNDS PER SQUARE INCH RA RETURN AIR RECT RECTANGULAR RH RELATIVE HUMIDITY RLA RUN LOAD AMPERE RTU ROOFTOP AIR HANDLING UNIT RPM REVOLUTION PER MINUTE SA SUPPLY AIR SEER SEASONAL ENERGY EFFICIENCY RATIO SF SUPPLY FAN SS STAINLESS STEEL SP STATIC PRESSURE TYP TYPICAL UC UNDERCUT DOOR UNO UNLESS NOTED OTHERWISE UTR UP THROUGH ROOF V/PH VOLTS/PHASE VCD VOLUME CONTROL DAMPER VAV VARIABLE AIR VOLUME VD VOLUME DAMPER (MANUAL OPPOSED BLADE) VFD VARIABLE FREQUENCY DRIVE W WATTS WEF WALL EXHAUST FAN HEATER MECHANICAL NOTES, LEGEND AND ABBREVIATIONSM-1SHEET TITLE:SHEET DATE:NO.DRAWN BY: CHECKED BY:CMDREVISIONDATE 04-02-24370 15th Ave S; Units A & BJacksonville Beach, FL 32250904.249.0698 pDOHERTY SOMMERSARCHITECTS ENGINEERS, INC.904.241.0691 fwww.dsae.netFlorida Certificate of Auth No: 00009393Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS. THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUT EXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.ATLANTIC COASTAPPLIANCECAREN M. DOHERTY, P.E.FL. P.E. #55021CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THISITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 05/16/23USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDEREDSIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.TENANT BUILDOUT725 ATLANTIC BOULEVARDATLANTIC BEACH, FLORIDA 3222305-16-24 ABS BRANCH & FLEX DUCT SCHEDULE 0 - 160 CFM -6"Ø 165 - 250 CFM -8"Ø 255 - 380 CFM -10"Ø 385 - 470 CFM -12"Ø 475 - 700 CFM -14"Ø 705 - 1100 CFM -16"Ø NOTE : BRANCH RUNOUT SIZE REFLECTS SUPPLY DIFFUSER NECK SIZE UNLESS OTHERWISE NOTED. ELECTRIC ROOFTOP UNIT SCHEDULE MARK TONS INDOOR FAN DATA COOLING CAPACITY HEAT PUMP CAPACITY (BTU/HR) SEE R MCA (A) MOCP (A) HEATER RATING (KW) ELECTRICAL DATA UNIT WEIGHT (LBS) BASIS OF DESIGN NOTESTOTAL FLOW (CFM) 0/A (CFM) ESP (W.G.) MOTOR (BHP) EDB (°F) EWB (°F) AMBIENT (°F) TOTAL (BTU/HR) SENSIBLE (BTU/HR) VOLT S HZ PHASE RTU-1 6 2350 500 0.75 --80 67 95 78,190 57,390 73,580 15.5 42 50 7.5 208 60 3 927 TRANE WHC074H3R0A 1-6 NOTES: 1. UNITS PROVIDED SHALL MEET ALL SCHEDULED VALUES REGARDLESS OF MODEL OR TYPE, UNLESS APPROVED BY THE ENGINEER. 2. PROVIDE PROGRAMMABLE THERMOSTATS FOR ALL RTU'S. MOUNT @ 48" AFF. 3. PROVIDE DUCT MOUNTED SMOKE DETECTOR IN SUPPLY AIR, WIRED TO SHUT DOWN RTU. POWER WIRING BY ELECTRICAL CONTRACTOR, CONTROL (24VAC) WIRING BY MECHANICAL CONTRACTOR. TIE INTO BUILDING FACP IF BUILDING FACP EXISTS. FOR UNITS WITH OVER 2000 CFM OF SUPPLY AIR 4. ELECTRICAL CONTRACTOR TO INSTALL DISCONNECT AND CONVENIENCE OUTLETS ON BOTH UNITS. 5. INSTALL AQUAGUARD AG-3180E SENSOR W/ CORRESPONDING AQUAGUARD AUDIO & VISUAL REMOTE ALARM. 6. PROVIDE SYSTEM ECONOMIZER. AIR DISTRIBUTION DEVICE SCHEDULE MARK DESCRIPTION MOUNTING FACE SIZE BASIS OF DESIGN NOTES A 4-WAY SUPPLY LAY-IN 24"x 24" / 12"x 12"TITUS TMS-AA 1,2 B EGGCRATE RETURN LAY-IN 24"x 24"TITUS 50F 2 NOTES: 1. LOUVER FACE. 2. WITH OPTIONAL DAMPER. EXHAUST FAN SCHEDULE MARK SERVICE TOTAL AIR (CFM) E.S.P. (W.G)UNIT TYPE DRIVE POWER (W)FLA VOLTS/PH/HZ MANUFACTURER MODEL NUMBER NOTES EF-1 TOILET ROOM 70 0.13 CEILING DIRECT 15 0.27 115/1/60 GREENHECK SP-A70 1,2 NOTES: 1. INTERLOCK WITH LIGHT SWITCH. 2. PROVIDE BACKDRAFT DAMPER.MECHANICAL SCHEDULESM-2SHEET TITLE:SHEET DATE:NO.DRAWN BY: CHECKED BY:CMDREVISIONDATE 04-02-24370 15th Ave S; Units A & BJacksonville Beach, FL 32250904.249.0698 pDOHERTY SOMMERSARCHITECTS ENGINEERS, INC.904.241.0691 fwww.dsae.netFlorida Certificate of Auth No: 00009393Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS. THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUT EXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.ATLANTIC COASTAPPLIANCECAREN M. DOHERTY, P.E.FL. P.E. #55021CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THISITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 05/16/23USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDEREDSIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.TENANT BUILDOUT725 ATLANTIC BOULEVARDATLANTIC BEACH, FLORIDA 3222305-16-24 ABS K-1728CHESAPEAKEC_LAVATORYVITREOUS CHINA EF-1 A 50 A 50 RTU-1 4"Ø UP T0 ROOF W/ CAP A 225 B 925 B 925 A 225 A 225 A 225 A 225 A 225 A 225 A 225 A 225 16"x14"16"x14" 16"x16" NOT IN SCOPE 14"x12"12"x12" SD MERCANTILE 2,381 SF TOILET ROOM JAN CLOSET A 225 MECHANICAL PLANSCALE:1/4"=1'-0" MECHANICAL PLAN M-3SHEET TITLE:SHEET DATE:NO.DRAWN BY: CHECKED BY:CMDREVISIONDATE 04-02-24370 15th Ave S; Units A & BJacksonville Beach, FL 32250904.249.0698 pDOHERTY SOMMERSARCHITECTS ENGINEERS, INC.904.241.0691 fwww.dsae.netFlorida Certificate of Auth No: 00009393Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS. THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUT EXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.ATLANTIC COASTAPPLIANCECAREN M. DOHERTY, P.E.FL. P.E. #55021CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THISITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 05/16/23USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDEREDSIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.TENANT BUILDOUT725 ATLANTIC BOULEVARDATLANTIC BEACH, FLORIDA 3222305-16-24 ABS MECHANICAL DETAILSM-4 SCALE:N.T.S. DUCT HANGER DETAIL SCALE:N.T.S. RADIUS ELBOW - RECT. DUCT SCALE:N.T.S. ELBOW DETAIL - RECT. DUCT SCALE:N.T.S. FLEX DUCT CONNECTION DETAIL SCALE:N.T.S. RTU CONNECTION DETAIL SCALE:N.T.S. RTU CURB DETAIL SCALE:N.T.S. DUCT OFFSET SCALE:N.T.S. TYPICAL BRANCH TAKE-OFF DETAIL SCALE:N.T.S. TOILET EXHAUST DETAIL SHEET TITLE:SHEET DATE:NO.DRAWN BY: CHECKED BY:CMDREVISIONDATE 04-02-24370 15th Ave S; Units A & BJacksonville Beach, FL 32250904.249.0698 pDOHERTY SOMMERSARCHITECTS ENGINEERS, INC.904.241.0691 fwww.dsae.netFlorida Certificate of Auth No: 00009393Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS. THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUT EXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.ATLANTIC COASTAPPLIANCECAREN M. DOHERTY, P.E.FL. P.E. #55021CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THISITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 05/16/23USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDEREDSIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.TENANT BUILDOUT725 ATLANTIC BOULEVARDATLANTIC BEACH, FLORIDA 3222305-16-24 ABS