712 AMBERJACK MCRS24-0014 TIMOTHY DURBIN - MS156156 FINAL DESIGN stamped_COVER PAGE
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
325 HIGH STREET, METUCHEN, NJ 08840
(732) 902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-1
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
TIMOTHY DURBIN - MS156156
712 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
(904) 903-1224
KJL
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
8/12/2024
SYSTEM SIZE (DC ): 4.92 KW12 MODULES: HANWHA Q.PEAK DUO BLK
ML-G10+ 410
12 INVERTERS: ENPHASE IQ8MC-72-M-US
COVER PAGE
SYSTEM INFORMATION
MODULE HANWHA Q.PEAK DUO BLK ML-G10+ 410
INVERTER ENPHASE IQ8MC-72-M-US
RACKING UNIRAC NXT HORIZON 2-RAIL RACKING
SYSTEM
SYSTEM SIZE (DC)4.92 KW
LOCATION 30.3337665,-81.4095264
HANWHA Q.PEAK DUO BLK ML-G10+ 410
410 WATT MODULE74'' X 41.1'' X 1.26''(SEE DATASHEET)
TABLE R301.2.1.3
WIND SPEED CONVERSIONSa
Vult 110 115 120 130 140 150 160 170 180 190 200
Vasd 85 89 93 101 108 116 124 132 139 147 155
FBC, RESIDENTIAL 2023
For SI: 1 mile per hour = 0.447 m/s.
a.Linear interpolation is
permitted.
CLIMATIC & GEOGRAPHIC DESIGN CRITERIA TABLE
R301.2(1)
SPEED (MPH)130
TOPOGRAPHIC EFFECTS B
SPECIAL WIND REGION NO
WIND BORNE DEBRIS ZONE 2
SEISMIC DESIGN CATEGORY C
CLIMATE ZONE 2A
WIND EXPOSURE CATETORY B
BILL OF MATERIALS
MODULES 12
INVERTERS 12
L-FOOT ATTACHMENT W/
UNIRAC NXT 32
171" RAILS 6
SKIRTS 0
ENPHASE COMBINER BOX 1
EATON 60A FUSIBLE AC
DISCONNECT 1
35A FUSES 2
20A BACKFEED BREAKER 1
PLAN KEY
PV-1 COVER PAGE
PV-1.1 ATTACHMENT DETAIL
PV-1.1(2)ATTACHMENT DETAIL
PV-1.2 INVERTER SPECS
PV-1.3 COMBINER SPECS
PV-1.4 PANEL SPECS
PV-2 PANEL LAYOUT
PV-3 ELETRICAL
PV-3.1 ELECTRICAL CONT.
PV-3.2 EQUIPMENT LABELS
STRUCTURAL STATEMENT:
THE EXISTING STRUCTURE IS ADEQUATE TO SUPPORT THE NEW LOADS IMPOSED BY
THE PHOTOVOLTAIC MODULE SYSTEM INCLUDING UPLIFT & SHEAR.EXISTING RAFTER
SIZES & DIMENSIONS CONFORM TO 8TH EDITION 2023 FLORIDA RESIDENTIAL CODE
MOUNTING BRACKETS AND HARDWARE MEET OR EXCEED FLORIDA CODE
REQUIREMENTS FOR THE DESIGN CRITERIA OF THE TOWN.
GENERAL NOTES:
THIS PV SYSTEM HAS BEEN DESIGNED TO MEET THE MINIMUM DESIGN STANDARDS
FOR BUILDING AND OTHER STRUCTURES OF THE ASCE 7-22, 8TH EDITION 2023
FLORIDA RESIDENTIAL CODE, 8TH EDITION 2023 FLORIDA BUILDING CODE, 8TH
EDITION 2023 FLORIDA FIRE PREVENTION CODE, NEC 2020 AND ALL LOCAL CODES &
ORDINANCES.
ROOF SHALL HAVE NO MORE THAN TWO LAYERS OF COVERING IN ADDITION TO THE
SOLAR EQUIPMENT.
INSTALLATION OF SOLAR EQUIPMENT SHALL BE FLUSH MOUNTED, PARALLEL TO AND
NO MORE THAN 6-INCHES ABOVE THE SURFACE OF THE ROOF.
ANY PLUMBING VENTS ARE NOT TO BE CUT OR COVERED FOR SOLAR EQUIPMENT
INSTALLATION. ANY RELOCATION OR MODIFICATION OF THE VENT REQUIRES A
PLUMBING PERMIT AND INSPECTION.
ALL DESIGN, CALCULATIONS ARE PERFORMED BY MICHAEL S. REZK, P.E.
PROFESSIONAL ENGINEER, WITH LICENCE No. 95844.
INVERTER PLACEMENT:
SYSTEM UTILIZES "ENPHASE" MICRO-INVERTERS WITH RAPID SHUTDOWN CONTROL
LOCATED ON THE BACK SIDE OF EACH MODULE.
FSEC CERTIFICATION STATEMENT:
PER FL. STATUE 377.705 , I, MINA A. MAKAR PE# 86753, CERTIFICATE OF
AUTHORIZATION #33404, AN ENGINEER LICENSED PURSUANT TO CHAPTER
471,CERTIFY THAT THE PV ELECTRICAL SYSTEM AND ELECTRICAL COMPONENTS ARE
DESIGNED AND APPROVED USING THE STANDARDS CONTAINED IN THE MOST RECENT
VERSION OF THE FLORIDA BUILDING CODE. FBC 2023
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2024.08.12 05:08:27 -05:00
1 / 10
ATTACHMENT DETAIL
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
325 HIGH STREET, METUCHEN, NJ 08840
(732) 902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-1.1
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
TIMOTHY DURBIN - MS156156
712 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
(904) 903-1224
KJL
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
8/12/2024
SYSTEM SIZE (DC ): 4.92 KW12 MODULES: HANWHA Q.PEAK DUO BLK
ML-G10+ 410
12 INVERTERS: ENPHASE IQ8MC-72-M-US
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2024.08.12 05:08:27 -05:00
2 / 10
ATTACHMENT DETAIL
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
325 HIGH STREET, METUCHEN, NJ 08840
(732) 902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-1.1 (2)
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
TIMOTHY DURBIN - MS156156
712 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
(904) 903-1224
KJL
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
8/12/2024
SYSTEM SIZE (DC ): 4.92 KW12 MODULES: HANWHA Q.PEAK DUO BLK
ML-G10+ 410
12 INVERTERS: ENPHASE IQ8MC-72-M-US
ATTACHMENT DETAIL FOR SHINGLE ROOF
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2024.08.12 05:08:27 -05:00
3 / 10
INVERTER DETAIL
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
325 HIGH STREET, METUCHEN, NJ 08840
(732) 902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-1.2
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
TIMOTHY DURBIN - MS156156
712 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
(904) 903-1224
KJL
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
8/12/2024
SYSTEM SIZE (DC ): 4.92 KW12 MODULES: HANWHA Q.PEAK DUO BLK
ML-G10+ 410
12 INVERTERS: ENPHASE IQ8MC-72-M-US
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2024.08.12 05:08:27 -05:00
4 / 10
COMBINER DETAIL
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
325 HIGH STREET, METUCHEN, NJ 08840
(732) 902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-1.3
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
TIMOTHY DURBIN - MS156156
712 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
(904) 903-1224
KJL
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
8/12/2024
SYSTEM SIZE (DC ): 4.92 KW12 MODULES: HANWHA Q.PEAK DUO BLK
ML-G10+ 410
12 INVERTERS: ENPHASE IQ8MC-72-M-US
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2024.08.12 05:08:27 -05:00
5 / 10
PANEL DETAIL
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
325 HIGH STREET, METUCHEN, NJ 08840
(732) 902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-1.4
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
TIMOTHY DURBIN - MS156156
712 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
(904) 903-1224
KJL
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
8/12/2024
SYSTEM SIZE (DC ): 4.92 KW12 MODULES: HANWHA Q.PEAK DUO BLK
ML-G10+ 410
12 INVERTERS: ENPHASE IQ8MC-72-M-US
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2024.08.12 05:08:27 -05:00
6 / 10
SCALE: 1/8" = 1'-0"
ROOF LAYOUT
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
325 HIGH STREET, METUCHEN, NJ 08840
(732) 902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-2
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
TIMOTHY DURBIN - MS156156
712 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
(904) 903-1224
KJL
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
8/12/2024
SYSTEM SIZE (DC ): 4.92 KW
12 MODULES: HANWHA Q.PEAK DUO BLK
ML-G10+ 410
12 INVERTERS: ENPHASE IQ8MC-72-M-US
SYMBOL LEGEND
MAIN SERVICE PANEL
UTILITY METER
SKYLIGHT
VENT
CHIMNEY
SUB-PANEL
MSP
SP
M
AC
DISC
UDC
LC
N3R
CB
AC DISCONNECT
LOAD CENTER
NEMA 3R BOX W/ ENVOY-S
COMBINER BOX
PIPE VENT
FAN
SATELLITE DISH
MODULE
FIRE SETBACKS
PITCH DIRECTION
UTILITY DISCONNECT
MIN 3'x3' GROUND ACCESS
POINT
WIND PRESSURE ZONE LINES. REFER TO
PV-2.2 FOR ADDITIONAL INFO
NOTE:
1. ROOF COVERING MATERIAL IS COMPOSED OF SINGLE LAYER ASPHALT COMPOSITE SHINGLE.
2. EXACT ATTACHMENT LOCATION AND QUANTITY OF ATTACHMENTS ARE BASED ON EXISTING RAFTER LOCATIONS
OBTAINED FROM FIELD MEASUREMENTS. THE LOCATION AND QUANTITY OF ATTACHMENTS MAY VARY BASED ON RAFTER
LAYOUT START POINT, SPACING VARIATIONS AND ROOFING TYPE. VERIFY IN THE FIELD ALL RAFTER LOCATIONS AND
ADJUST LAYOUT AS REQUIRED. A TILE ROOF WILL PRODUCE A STAGGERED ATTACHMENT LAYOUT BECAUSE OF EXISTING
STAGGERED TILE JOINT LOCATIONS.
RAFTER SPACING
24" O.C. (TYP)
CLAMPING MAX SPACING IN ZONE 1 48" O.C
AND IN ZONE 2 AND ZONE 3 48" O.C
LANDSCAPE MAX SPAN
(ROOF AREA 1/2/3)
PORTRAIT MAX SPAN
(ROOF AREA 1/2/3)
48 /48 /48 48 /48 /48
48 /48 /48 48 /48 /48
ROOF PANEL COUNT TILT AZIMUTH SHADING
R1 6 7°95°80%
R2 6 7°275°74%
TOTAL SQUARE FOOTAGE OF ROOF: 1719 SQFT
SQUARE FOOTAGE OF SOLAR ARRAY:253.45 SQFT
PERCENTAGE OF SOLAR ROOF COVERAGE: 14.75%
18" RIDGE SETBACK SHALL BE REQUIRED
LANDSCAPE MAX
CANTILEVER
PORTRAIT MAX
CANTILEVER
16 /10 /10 16 /10 /10
16 /10 /10 16 /10 /10
FRONT OF RESIDENCE
AMBERJACK LANE
DRIVEWAY
0'-91
2"
2'-81
2"3'-31
2"RIDGEGUTTERGUTTER3'-0"
R1
R2
M AC
DISC
ELECTRICAL EQUIPMENT
CB
MSP
GROUND ACCESS
(TYP)
FIRE SETBACK
(36" VENTILATION,
36" ROOF ACCESS)
(TYP)
0'-91
2"
3'-0"
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2024.08.12 05:08:27 -05:00
7 / 10
TERMINATION CAP
INSTALLED ON
END OF CABLE
=......10A/15A BREAKER
(MANUFACTURER
SUPPLIED FOR
ENVOY)
20A BREAKER (A)
ENPHASE 80A
AC COMBINER
BOX
1 2 3
==
GND
NEU
ROOF
JUNCTION
BOX
BRANCH CIRCUIT A12 MICRO-INVERTERS
12 HANWHA Q.PEAK DUO BLK ML-G10+ 410 410W MODULES PAIRED WITH
12 ENPHASE IQ8MC-72-M-US MICRO-INVERTERS
GND BUS
NEU BUS
POWER
GROUND
EXISTING GENERAL
ELECTRIC 200A MAIN
SERVICE PANEL 240 V
MAIN BREAKER: 200A
200A
UTILITY
METER
GRID
20A
35A FUSES
GND
NEU
3
EATON 60A FUSIBLE AC
DISCONNECT
35A
35A FUSES
SOLAR CIRCUIT
DISCONNECTING MEANS
Wire Tag Conduit Wire Qty Wire
Gauge Wire Type Temp.
Rating
Wire
Ampacity (A)
Temp.
Derate
Conduit
Fill Derate
Derated
Ampacity (A)
Inverter
Qty NOC (A)NEC
Correction
Design
Current (A)
Ground
Size
Ground Wire
Type
1 OPEN AIR 1 12 AWG Trunk Cable 90°C 30 0.96 1 28.80 12 1.33 1.25 19.95 12 AWG Trunk Cable
2 3/4" PVC 2 10 AWG THWN-2 75°C 35 0.96 1 33.60 12 1.33 1.25 19.95 08 AWG THWN-2
3 3/4" PVC 3 + G 08 AWG THWN-2 75°C 50 0.96 1 48.00 12 1.33 1.25 19.95 08 AWG THWN-2 THREE LINE DIAGRAM
SUB PANEL
BREAKER SIZE
# OF MODULES PV BREAKER
PER BRANCH
UP TO 16 20A
PV MODULE RATINGS
MODULE MAKE HANWHA
MODEL
HANWHA
Q.PEAK DUO BLK
ML-G10+ 410
MAX POWER 410W
OPEN CIRCUIT VOLTAGE 45.37V
MPP VOLTAGE 37.64V
SHORT CIRCUIT CURRENT 11.2A
MPP CURRENT 10.89A
NUMBER OF MODULES 12
UL1703 COMPLIANT YES
INVERTER RATINGS
INVERTER MAKE ENPHASE
MODEL
Enphase
IQ8MC-72-M-U
S
MAX OUTPUT POWER 320W
OPEN DC VOLTAGE 60V
NOMINAL AC VOLTAGE 240V
MAX AC CURRENT 1.33A
CEC INVERTER EFFICIENCY 97%
NUMBER OF INVERTERS 12
UL1703 COMPLIANT YES
VOLTAGE DROP CALCULATIONS
FORMULA USED PER NEC HANDBOOK 215.2(A)(4) WHERE APPLICABLE
WIRE RUN Vmp Imp R L (FT)Vo % Vo WIRE SIZE
BRANCH TO J-BOX 240.00
J-BOX TO LOAD
CENTER 240.00
LOAD CENTER TO AC
DISCONNECT 240.00
AC DISCONNECT TO
INTERCONNECTION 240.00
15.96 1.98 79.00 4.993 2.08%12 AWG
15.96 1.24 50.00 1.979 0.82%10 AWG
19.95 0.778 3.00 0.093 0.04%08 AWG
19.95 0.778 10.00 0.310 0.13%08 AWG
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
325 HIGH STREET, METUCHEN, NJ 08840
(732) 902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
TIMOTHY DURBIN - MS156156
712 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
(904) 903-1224
KJL
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
8/12/2024
SYSTEM SIZE (DC ): 4.92 KW
12 MODULES: HANWHA Q.PEAK DUO BLK
ML-G10+ 410
12 INVERTERS: ENPHASE IQ8MC-72-M-US
NOTE: LETTER "G" IN WIRE QTY TAB STANDS FOR GROUNDING CONDUCTOR.
NEC 705.12(B)(2)(3)(b) 120% RULE
(1.25 x INVERTER OUTPUT) + MAIN OCPD ≤ BUS RATING x 1.20
(1.25 x 15.96) + 200 ≤ 200 x 1.20THIS SOLAR PHOTOVOLTAIC SYSTEM COMPLIES WITH THE 2023
FLORIDA BUILDING CODE AND THE 2020 NATIONAL ELECTRICAL CODE FSEC CERTIFICATION STATEMENT:
PER FL. STATUE 377.705 , I, MINA A. MAKAR PE# 86753,
CERTIFICATE OF AUTHORIZATION #33404, AN ENGINEER
LICENSED PURSUANT TO CHAPTER 471,CERTIFY THAT THE PV
ELECTRICAL SYSTEM AND ELECTRICAL COMPONENTS ARE
DESIGNED AND APPROVED USING THE STANDARDS CONTAINED
IN THE MOST RECENT VERSION OF THE FLORIDA BUILDING
CODE. FBC 2023 Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2024.08.12 05:08:27 -05:00
8 / 10
ELECTRICAL CONT.
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
325 HIGH STREET, METUCHEN, NJ 08840
(732) 902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.1
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
TIMOTHY DURBIN - MS156156
712 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
(904) 903-1224
KJL
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
8/12/2024
SYSTEM SIZE (DC ): 4.92 KW
12 MODULES: HANWHA Q.PEAK DUO BLK
ML-G10+ 410
12 INVERTERS: ENPHASE IQ8MC-72-M-US
ELECTRICAL NOTES:
MAKE MODEL VOLTAGE
RATING
CONDUCTOR
RANGE MAIN
CONDUCTOR
RANGE TAP
ILSCO IPC 4006 600 V 4/0-4 AWG 6-14 AWG
ILSCO IPC 4020 600 V 4/0-2 AWG 2/0-6 AWG
TABLE 1:
INSTRUCTIONS FOR LINE TAPS
FIGURE 1:
1.ADJUST THE CONNECTOR NUT TO
SUITABLE LOCATION
2.PUT THE BRANCH WIRE INTO THE CAP
SHEATH FULLY
3.INSERT THE MAIN WIRE, IF THERE ARE
TWO LAYS OF INSULATED LAY IN THE
MAIN CABLE, SHOULD STRIP A CERTAIN
LENGTH OF THE FIRST INSULATED LAY
FROM INSERTED END
4.TURN THE NUT BY HAND, AND FIX THE
CONNECTOR IN SUITABLE LOCATION.
5.SCREW THE NUT WITH THE SLEEVE
SPANNER.
6.SCREW THE NUT CONTINUALLY UNTIL
THE TOP PART IS CRACKED AND
DROPPED DOWN
1.ALL CALCULATIONS FOR VOC, VMAX, IMP AND ISC HAVE BEEN
CALCULATED USING THE MANUFACTURED STRING CALCULATOR
BASED ON ASHRAE 2% HIGH AND EXTREME MINIMUM TEMPERATURE
COEFFICIENTS.
2.THE ENTIRE ARRAY IS BONDED ACCORDING TO (NEC 690.43(A)
THROUGH (D) WITH 250.134 OR 250.136.
3.THIS SYSTEM COMPLIES WITH NEC 2020
4.BRANCH CIRCUIT CALCULATION FOR WIRE TAG 1 DISPLAYS THE
LARGEST BRANCH CIRCUIT IN SYSTEM. OTHER BRANCH CIRCUITS
SHALL HAVE LOWER DESIGN CURRENT THAN THE ONE SHOWN. IN
ADDITION, VOLTAGE DROP CALCULATIONS FROM PANELS TO THE
COMBINER BOX SHALL BE SHOWN IN A SIMILAR FASHION
5.ALL CONDUCTORS ARE SIZED BASED ON NEC 2020 ARTICLE 310
6.ALL EQUIPMENT INSTALLED IS RATED AT 75°C
7.INVERTER NOC (NOMINAL OPEN CURRENT) OBTAINED FROM
EQUIPMENT DATASHEET
8.CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL
LOCAL AND NATIONAL CODE REQUIREMENTS.
9.EACH MODULE MUST BE GROUNDED ACCORDING TO USER
INSTRUCTIONS
10.ALL EQUIPMENT SHALL BE LISTED PER NEC 690.4(B)
11.PER NEC 690.13, 690.15, PROVIDE A WARNING SIGN AT ALL LOCATIONS
WHERE TERMINALS OF THE DISCONNECTING MEANS MAY BE
ENERGIZED IN THE OPEN POSITION> SIGN SHALL READ *WARNING -
ELECTRIC SHOCK HAZARD - DO NOT TOUCH TERMINALS - OR
EQUIVALENT.
12.PER NEC 705.10, PROVIDE A PERMANENT PLAQUE OR DIRECTORY
SHOWING ALL ELECTRIC POWER SOURCES ON THE PREMISES AT
SERVICE ENTRANCE.
13.INTERCONNECTION METHOD SHALL COMPLY WITH NEC 705.12
14.AND OPTION FOR A SINGLE CIRCUIT BRANCH TO BE SPLIT INTO TWO
SUB-CIRCUIT BRANCHES IS ACCEPTABLE.
15.ALL CONDUCTORS MUST BE COPPER.
16.NEUTRAL AND EQUIPMENT GROUNDING CONDUCTOR BONDED AS PER
NEC 250.24(C).
17.EQUIPMENT GROUNDING CONDUCTOR IS CONNECTED TO A
GROUNDING ELECTRODE SYSTEM PER 250.54(D).
18.FUSES FOR PV DISCONNECT HAVE AIC RATINGS OF 200KA AC AND 20KA
DC.
19.SUPPLY SIDE CONNECTION SHALL BE MADE USING ILSCO INSULATION
PIERCING CONNECTORS (IPC). MAKE, MODEL, AND RATING OF
INTERCONNECTION CAN BE SEEN ON TABLE 1 BELOW.
20.METHOD OF INTERCONNECTION CAN BE SEEN IN FIGURE 1.
21.UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PHOTOVOLTAIC
SYSTEM COMPONENTS LOCATED AT THE SERVICE ENTRANCE.
22.WORKING CLEARANCES AROUND THE EXISTING AND NEW ELECTRICAL EQUIPMENT WILL
BE MAINTAINED IN ACCORDANCE WITH NEC ARTICLE 110.26.
23.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT RESISTANT PER
NEC ARTICLE 300.6 (C)(1) AND ARTICLE 310.8 (D).
24.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE IN WET
LOCATIONS PER NEC ARTICLE 310.10 (C).
25.TOTAL AREA OF ALL CONDUCTORS, SPLICES, AND TAPS INSTALLED AT ANY CROSS
SECTION OF THE WIRING DOES NOT EXCEED 75% OF THE CROSS SECTIONAL AREA OF
THE SPACE. NEC 312.8(A)(2).
26.SYSTEM IS CONSIDERED AN AC MODULE SYSTEM. NO DC CONDUCTORS ARE PRESENT IN
CONDUIT, COMBINER, JUNCTION BOX, DISCONNECT. AND COMPLIES WITH 690.6 - NO DC
DISCONNECT AND ASSOCIATED DC LABELING ARE REQUIRED.
27.SYSTEM COMPLIES WITH 690.12 RAPID SHUTDOWN AND ASSOCIATED LABELING AS PER
690.56(C). AC VOLTAGE AND SYSTEM OPERATING CURRENT SHALL BE PROVIDED 690.51.
28.CONDUCTORS IN CONDUIT ARE AC CONDUCTORS BRANCH CIRCUITS AND NOT PV
SOURCE CIRCUITS. 690.6.
29.ALL GROUNDING SHALL COMPLY WITH 690.47(A) IN THAT THE AC MODULES WILL COMPLY
WITH 250.64.
30.NO TERMINALS SHALL BE ENERGIZED IN THE OPEN POSITION IN THIS AC MODULE
SYSTEM 690.13(B), 690.6.
31. WHERE APPLICABLE: INTERCONNECTION SHALL COMPLY WITH 705.11(A) THROUGH (E)
OR 705.12(B) THROUGH (E)
32.ALL WARNING SIGN(S) OR LABEL(S) SHALL COMPLY WITH 2020 NEC ARTICLE 110.21(B).
LABEL WARNINGS SHALL ADEQUATELY WARN OF THE HAZARD. LABELS SHALL BE
PERMANENTLY AFFIXED TO THE EQUIPMENT, AND LABELS REQUIRED SHALL BE
SUITABLE FOR THE ENVIRONMENT.
33.PV POWER CIRCUIT LABELS SHALL APPEAR ON EVERY SECTION OF THE WIRING SYSTEM
THAT IS SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS.
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2024.08.12 05:08:27 -05:00
9 / 10
ELECTRICAL SHOCK HAZARD
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
15.96
QUANTITY LOCATION
A
LABELTAG
B
C
D
E
F
1
1
JUNCTION BOX
INTERCONNECTION
POINT
1 UTILITY METER
1 COMBINER BOX
1 AC DISCONNECT
(RSD SWITCH)
1 AT ANY COMBINER BOX
1 AT ANY JUNCTION BOX
1 OF EACH AT FUSED AC
DISCONNECT
COMPLETE VOLTAGE AND
CURRENT VALUES ON
DISCONNECT LABEL
1 OF EACH AT BUILDING
INTERCONNECTION POINT AND
ONE DIRECTORY PLACARD
1 AT UTILITY METER AND ONE
DIRECTORY PLACARD
NOTE EXAMPLES
A B
D
REVENUE METER
C
RATED AC
OUTPUT CURRENT
NOMINAL OPERATING
AC VOLTAGE
A
240 V
PHOTOVOLTAIC SYSTEM
AC DISCONNECT
POWER TO THIS SERVICE IS
ALSO SUPPLIED FROM ON-SITE
SOLAR GENERATION
AC SYSTEM DISCONNECT
DUAL POWER SUPPLY
SECOND SOURCE IS
PHOTOVOLTAIC SYSTEM
WARNING
WARNING: PHOTOVOLTAIC
POWER SOURCE
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
RAPID SHUTDOWN SWITCH FOR
SOLAR PV SYSTEM
1
AC SOLAR VOLTAGE
G
12 AC CONDUITS
1 AT EVERY SEPARATION BY
ENCLOSURES / WALLS /
PARTITIONS / CEILINGS / FLOORS
OR NO MORE THAN 10'
F G BACKFEED
DUAL POWER SUPPLY
SECOND SOURCE IS
PHOTOVOLTAIC SYSTEM
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON BOTH LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
NOMINAL OPERATING AC VOLTAGE : 240V
NOMINAL OPERATING AC FREQUENCY : 60HZ
MAXIMUM AC POWER : VA
MAXIMUM AC CURRENT : A
MAXIMUM OVERCURRENT DEVICE RATING FOR
AC MODULE PROTECTION : 20A
AC CURRENT PV
MODULES
1
BACKFEED PANEL
H
CAUTION
CAUTION
POWER SOURCE OUTPUT CONNECTION.
DO NOT RELOCATE THIS OVERCURRENT
DEVICE
WARNING
PHOTOVOLTAIC SYSTEM
INSTALLED BY MOMENTUM SOLAR
3096 B HAMILTON BLVD
S. PLAINFIELD, NJ 07080
PHONE NUMBER:732-902-6224
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
ENTIRE PV SYSTEM
SOLAR ELECTRIC
PV PANELS
SECTIONS OF THE PV SYSTEM THATARE SHUT DOWN WHEN THE RAPIDSHUTDOWN SWITCH IS OPERATED
SECTIONS OF THE PV SYSTEM THATARE NOT SHUT DOWN WHEN THE RAPID
SHUTDOWN SWITCH IS OPERATED
EMERGENCY RESPONDER
THIS SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
EQUIPMENT LABELS
PRO CUSTOM SOLAR LLC D.B.A. MOMENTUM SOLAR
325 HIGH STREET, METUCHEN, NJ 08840
(732) 902-6224
MOMENTUMSOLAR.COM
CUSTOMER INFORMATION
PV-3.2
REV:
REV:
INITIAL
DATE:
DATE:
DATE:
PROJECT INFORMATION
DESIGNER:
DESIGNER:
DESIGNER:
PV SYSTEM INFORMATION
PROFESSIONAL
ENGINEERING
TIMOTHY DURBIN - MS156156
712 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
(904) 903-1224
KJL
CAMERON CHRISTENSEN
CERTIFIED SOLAR CONTRACTOR LICENSE NUMBER: CVC57036
MOMENTUM SOLAR
5728 MAJOR BLVD. SUITE 307, ORLANDO FL. 32819
SOLAR CONTRACTOR
8/12/2024
SYSTEM SIZE (DC ): 4.92 KW
12 MODULES: HANWHA Q.PEAK DUO BLK
ML-G10+ 410
12 INVERTERS: ENPHASE IQ8MC-72-M-US
ALL WARNING SIGN(S) OR LABEL(S) SHALL COMPLY WITH NEC ARTICLE 110.21(B). LABEL WARNINGS SHALL ADEQUATELY WARN OF THE HAZARD. LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT, AND LABELS REQUIRED SHALL BE SUITABLE FOR THE ENVIRONMENT.
Digitally signed by Mina A Makar.
Reason : This item has been
electronically signed and sealed by
[Mina A. Makar, PE 86753, COA #
33404] on the Date and Time Stamp
shown using a digital signature.
Printed copies of this document are
not considered signed and sealed
and the signature must be verified
on any electronic copies
Date: 2024.08.12 05:08:27 -05:00
Powered by TCPDF (www.tcpdf.org)
10 / 10