808 Amberjack Ln RES24-0044 Approved Revision5/8" O.A. INSULATED GLASSGLAZING DETAILINTERIOREXTERIOR1/2" MIN. GLASSBITEGENERAL NOTES:1. THE PRODUCT SHOWN HEREIN IS DESIGNED AND MANUFACTURED TO COMPLY WITH THECURRENT EDITION FLORIDA BUILDING CODE (FBC), EXCLUDING HVHZ AND HAS BEEN EVALUATEDACCORDING TO THE FOLLOWING:·AAMA/WDMA/CSA 101/I.S.2/A440-172. ADEQUACY OF THE EXISTING STRUCTURAL CONCRETE/MASONRY, 2X FRAMING, AND METALFRAMING AS A MAIN WIND FORCE RESISTING SYSTEM CAPABLE OF WITHSTANDING ANDTRANSFERRING APPLIED PRODUCT LOADS TO THE FOUNDATION IS THE RESPONSIBILITY OF THEENGINEER OR ARCHITECT OF RECORD FOR THE PROJECT OF INSTALLATION.3. 1X AND 2X BUCKS (WHEN USED) SHALL BE DESIGNED AND ANCHORED TO PROPERLY TRANSFERALL LOADS TO THE STRUCTURE. BUCK DESIGN AND INSTALLATION IS THE RESPONSIBILITY OF THEENGINEER OR ARCHITECT OF RECORD FOR THE PROJECT OF INSTALLATION.4. THE INSTALLATION DETAILS DESCRIBED HEREIN ARE GENERIC AND MAY NOT REFLECT ACTUALCONDITIONS FOR A SPECIFIC SITE. IF SITE CONDITIONS CAUSE INSTALLATION TO DEVIATE FROMTHE REQUIREMENTS DETAILED HEREIN, A LICENSED ENGINEER OR ARCHITECT SHALL PREPARESITE SPECIFIC DOCUMENTS FOR USE WITH THIS DOCUMENT IN NON-HVHZ AREAS.5. APPROVED IMPACT PROTECTIVE SYSTEM IS REQUIRED ON THIS PRODUCT IN AREAS REQUIRINGIMPACT RESISTANCE.6. WINDOW FRAME MATERIAL: PVC7. GLASS SHALL MEET THE REQUIREMENTS OF ASTM E 1300 GLASS CHARTS. SEE SHEET 1 FORGLAZING DETAILS.AMERICAN CRAFTSMAN WINDOWSSILVER LINE WINDOWS AND DOORS 50 SERIES / V1 SERIES / (2000) SINGLE-HUNG WINDOWS(NON-HVHZ)(NON-IMPACT) GENERAL NOTES & GLAZING DETAILSSHEET:DWG. #:1SWD017 BUILDING DROPS, INC.
398 E. DANIA BEACH BLVD., STE. 338
DANIA BEACH, FL 33004
PH: (954)399-8478
FAX: (954)744.4738
WEB: www.buildingdrops.comOFSCALE:NTSCLDWG. BY:DATE:09.19.17CHK. BY:HFNREMARKSTITLE:BY DATE
50 SERIES/ V1 SERIES/ (2000)
SINGLE-HUNG WINDOWS
(NON-HVHZ)(NON-IMPACT)6FL14911FL #:PREPARED BY:6TH FBC EDITION FM 10/17THE INSTALLATION DETAILS DESCRIBED HEREIN ARE GENERICAND MAY NOT REFLECT ACTUAL CONDITIONS FOR A SPECIFICSITE. IF SITE CONDITIONS CAUSE INSTALLATION TO DEVIATEFROM THE REQUIREMENTS DETAILED HEREIN, A LICENSEDENGINEER OR ARCHITECT SHALL PREPARE SITE SPECIFICDOCUMENTS FOR USE WITH THIS DOCUMENT.AMERICAN CRAFTSMAN WINDOWSSILVER LINE WINDOWS AND DOORSONE SILVER LINE DRIVENORTH BRUNSWICK, NJ 08902PH: (888) 741-03547TH FBC EDITION NUS10/14/208th FBC EDITIONLH09/23TABLE OF CONTENTSSHEET REVISIONSHEET DESCRIPTION1 -GENERAL NOTES & GLAZING DETAILS2-ELEVATIONS & ANCHOR LAYOUTS3 -VERTICAL SECTIONS4-HORIZONTAL SECTIONS5 -ANCHOR DETAIL & SCHEDULEDESIGN PRESSURE TABLEPRODUCTMODELWINDOW SIZE CONFIGURATION DESIGN PRESSURE GLASS TYPE MISSILE IMPACT RATING2001 36.0"X 62.0"O/X+35/-35 PSFSS/SSNON IMPACT2001 48.0" X 80.0"O/X+15/-15 PSFSS/SSNON IMPACT2001 36.0" X 62.0"O/X+50/-50 PSFDS/DSNON IMPACT2001 45.0" X 62.0"O/X+40/-40 PSFDS/DSNON IMPACT2001 48.0" X 73.0"O/X+30/-30 PSFDS/DSNON IMPACT2002 72.0" X 62.0"O/X-O/X+35/-35 PSFSS/SSNON IMPACT2002 96.0" X 62.0"O/X-O/X+20/-20 PSFSS/SSNON IMPACT2002 72.0" X 80.0"O/X-O/X+20/-20 PSFSS/SSNON IMPACT2002 96.0" X 80.0"O/X-O/X+15/-15 PSFSS/SSNON IMPACT2003 108.0" X 80.0"O/X-O/X-O/X+25/-25 PSFSS/SSNON IMPACT2003 108.0" X 62.0"O/X-O/X-O/X+35/-35 PSFSS/SSNON IMPACTGLAZING NOTES:1. GLASS TYPE & THICKNESS SHALL COMPLY WITH ASTM E1300 REQUIREMENTS AS WELL ASAPPLICABLE SAFETY GLAZING REQUIREMENTS PER THE FBC. TEMPER AND SAFETY GLAZINGREQUIREMENTS SHALL BE REVIEWED ON A SITE SPECIFIC BASIS.2. SETTING BLOCK DUROMETER HARDNESS OF 70-90 (SHORE A) AS REFERENCED IN FBC CHAPTER 24.3. SETTING BLOCKS TO BE LOCATED AT 1/4 SPAN LENGTH FOR GLASS WIDER THAN 36" AS PER FBCCHAPTER 24.4. D.L.O. AND DESIGN PRESSURES MAY NOT EXCEED MAX VALUES IN GLASS CHARTS.Digitally signed by Hermes F. Norero, P.E. Reason: I am approving this document Date: 2023.10.18 15:27:53 -04'00'
ELEVATIONELEVATION"O""X""O""X""O""X""O""X" UNIT MAX.WIDTH 48.0"D.L.O MAX.WIDTH 43.69"UNITMAX.HEIGHT80.0"D.L.O. MAX.HEIGHT37.0" UNIT MAX.WIDTH 108.0"D.L.O MAX.WIDTH 31.69"UNITMAX.HEIGHT80.0""O""X"ANCHOR LAYOUTTHROUGH FRAME"O""X""O""X""O""X"ANCHOR LAYOUTTHROUGH FRAME6.0" FROMCORNER (TYP.)6.0" (TYP.)6.0" FROMCORNER (TYP.)6.0" (TYP.)4.0" (TYP.)4.0" (TYP.)6.0" (TYP.)6" FROMCORNER (TYP.)6" (TYP.)6" (TYP.)"O""X"3.0" (TYP.)3.0" (TYP.)A3NOTE: 1) APPLIES TO TWIN UNITS OF EQUIVALENT ORLESSER PANEL DIMENSIONS.℄6" FROMCORNER (TYP.)6" FROMCORNER (TYP.)A34A4C4B4A4C14.0" MAX.(TYP)ELEVATION"O""X""O""X""O""X" UNIT MAX.WIDTH 108.0"D.L.O MAX.WIDTH 31.69"UNITMAX.HEIGHT80.0"D.L.O. MAX.HEIGHT37.0"A34B4CELEVATIONS & ANCHOR LAYOUTSSHEET:DWG. #:2SWD017 BUILDING DROPS, INC.
398 E. DANIA BEACH BLVD., STE. 338
DANIA BEACH, FL 33004
PH: (954)399-8478
FAX: (954)744.4738
WEB: www.buildingdrops.comOFSCALE:NTSCLDWG. BY:DATE:09.19.17CHK. BY:HFNREMARKSTITLE:BY DATE
50 SERIES/ V1 SERIES/ (2000)
SINGLE-HUNG WINDOWS
(NON-HVHZ)(NON-IMPACT)6FL14911FL #:PREPARED BY:6TH FBC EDITION FM 10/17THE INSTALLATION DETAILS DESCRIBED HEREIN ARE GENERICAND MAY NOT REFLECT ACTUAL CONDITIONS FOR A SPECIFICSITE. IF SITE CONDITIONS CAUSE INSTALLATION TO DEVIATEFROM THE REQUIREMENTS DETAILED HEREIN, A LICENSEDENGINEER OR ARCHITECT SHALL PREPARE SITE SPECIFICDOCUMENTS FOR USE WITH THIS DOCUMENT.AMERICAN CRAFTSMAN WINDOWSSILVER LINE WINDOWS AND DOORSONE SILVER LINE DRIVENORTH BRUNSWICK, NJ 08902PH: (888) 741-03547TH FBC EDITION NUS10/14/208th FBC EDITIONLH09/23
ELEVATION"O""X""O""X" UNIT MAX.WIDTH 96.0"D.L.O MAX.WIDTH 42.25"UNITMAX.HEIGHT80.0"D.L.O. MAX.HEIGHT37.0"A34B4A4C"O""X""O""X"6" FROMCORNER (TYP.)6" (TYP.)6" (TYP.)6.0" FROMCORNER (TYP.)6.0" (TYP.)6.0" (TYP.)4.0" (TYP.)6.0" (TYP.)ANCHOR LAYOUTTHROUGH FRAMEELEVATIONS & ANCHOR LAYOUTSSHEET:DWG. #:3SWD017 BUILDING DROPS, INC.
398 E. DANIA BEACH BLVD., STE. 338
DANIA BEACH, FL 33004
PH: (954)399-8478
FAX: (954)744.4738
WEB: www.buildingdrops.comOFSCALE:NTSCLDWG. BY:DATE:09.19.17CHK. BY:HFNREMARKSTITLE:BY DATE
50 SERIES/ V1 SERIES/ (2000)
SINGLE-HUNG WINDOWS
(NON-HVHZ)(NON-IMPACT)6FL14911FL #:PREPARED BY:6TH FBC EDITION FM 10/17THE INSTALLATION DETAILS DESCRIBED HEREIN ARE GENERICAND MAY NOT REFLECT ACTUAL CONDITIONS FOR A SPECIFICSITE. IF SITE CONDITIONS CAUSE INSTALLATION TO DEVIATEFROM THE REQUIREMENTS DETAILED HEREIN, A LICENSEDENGINEER OR ARCHITECT SHALL PREPARE SITE SPECIFICDOCUMENTS FOR USE WITH THIS DOCUMENT.AMERICAN CRAFTSMAN WINDOWSSILVER LINE WINDOWS AND DOORSONE SILVER LINE DRIVENORTH BRUNSWICK, NJ 08902PH: (888) 741-03547TH FBC EDITION NUS10/14/208th FBC EDITIONLH09/23
3VERTICAL SECTIONASEE GLAZINGDETAIL SHEET 1MAX FRAME HEIGHT D.L.O.D.L.O.EXTERIORINTERIOR3SEE GLAZINGDETAIL SHEET 1SHEET:DWG. #:4SWD017 BUILDING DROPS, INC.
398 E. DANIA BEACH BLVD., STE. 338
DANIA BEACH, FL 33004
PH: (954)399-8478
FAX: (954)744.4738
WEB: www.buildingdrops.comOFSCALE:NTSCLDWG. BY:DATE:09.19.17CHK. BY:HFNREMARKSTITLE:BY DATE
50 SERIES/ V1 SERIES/ (2000)
SINGLE-HUNG WINDOWS
(NON-HVHZ)(NON-IMPACT)6FL14911FL #:PREPARED BY:6TH FBC EDITION FM 10/17THE INSTALLATION DETAILS DESCRIBED HEREIN ARE GENERICAND MAY NOT REFLECT ACTUAL CONDITIONS FOR A SPECIFICSITE. IF SITE CONDITIONS CAUSE INSTALLATION TO DEVIATEFROM THE REQUIREMENTS DETAILED HEREIN, A LICENSEDENGINEER OR ARCHITECT SHALL PREPARE SITE SPECIFICDOCUMENTS FOR USE WITH THIS DOCUMENT.AMERICAN CRAFTSMAN WINDOWSSILVER LINE WINDOWS AND DOORSONE SILVER LINE DRIVENORTH BRUNSWICK, NJ 08902PH: (888) 741-03547TH FBC EDITION NUS10/14/208th FBC EDITIONLH09/23VERTICAL SECTIONS
EXTERIORINTERIORSEE GLAZINGDETAIL SHEET 1SEE GLAZINGDETAIL SHEET 1SEE GLAZINGDETAIL SHEET 1MAX. FRAME WIDTHD.L.O.D.L.O.34HORIZONTAL SECTIONMULLIONB4HORIZONTAL SECTIONOPERABLE JAMBA4HORIZONTAL SECTIONFIXED JAMBCSEE GLAZINGDETAIL SHEET 1SHEET:DWG. #:5SWD017 BUILDING DROPS, INC.
398 E. DANIA BEACH BLVD., STE. 338
DANIA BEACH, FL 33004
PH: (954)399-8478
FAX: (954)744.4738
WEB: www.buildingdrops.comOFSCALE:NTSCLDWG. BY:DATE:09.19.17CHK. BY:HFNREMARKSTITLE:BY DATE
50 SERIES/ V1 SERIES/ (2000)
SINGLE-HUNG WINDOWS
(NON-HVHZ)(NON-IMPACT)6FL14911FL #:PREPARED BY:6TH FBC EDITION FM 10/17THE INSTALLATION DETAILS DESCRIBED HEREIN ARE GENERICAND MAY NOT REFLECT ACTUAL CONDITIONS FOR A SPECIFICSITE. IF SITE CONDITIONS CAUSE INSTALLATION TO DEVIATEFROM THE REQUIREMENTS DETAILED HEREIN, A LICENSEDENGINEER OR ARCHITECT SHALL PREPARE SITE SPECIFICDOCUMENTS FOR USE WITH THIS DOCUMENT.AMERICAN CRAFTSMAN WINDOWSSILVER LINE WINDOWS AND DOORSONE SILVER LINE DRIVENORTH BRUNSWICK, NJ 08902PH: (888) 741-03547TH FBC EDITION NUS10/14/208th FBC EDITIONLH09/23HORIZONTAL SECTIONS
PERIMETER SEALANT BY OTHERSINTERIOREXTERIOR3/8" MAX.SHIM SPACEMIN. EDGE DISTANCEMIN. EMB.SUBSTRATE BY OTHERS5ANCHOR DETAILTHROUGH FRAME (HEAD)A43/8" MAX. SHIM SPACEMIN.EDGE DISTANCEMIN. EMB.5ANCHOR DETAILTHROUGH FRAME (JAMB)BINTERIOREXTERIORPERIMETER SEALANT BY OTHERSSUBSTRATE BY OTHERS5ANCHOR SCHEDULEMETHODSUBSTRATE ANCHOR SCHEDULE MIN EMBEDMENTMIN. EDGEDISTANCETHROUGH FRAMEWOOD: MIN. SG = 0.55 #10 WOOD SCREW1.5"0.75"METAL: 18 GAUGESteel, MIN. Fy = 33KSI#10 TEK SCREW3 THREADS MINPENETRATION BEYONDMETAL0.75"CONCRETE:f'c=3000PSI1/4" ITW TAPCON1.75"2.5"MASONRY: CMU perASTM C90 f'c=2000PSI1/4" ITW TAPCON1.75"2.5" TO BE INSTALLEDABOVE MEETING RAIL(FLAT HEAD SCREW)TO BE INSTALLEDBELOW MEETING RAIL.INSTALLATION NOTES1. ONE (1) INSTALLATION ANCHOR IS REQUIRED AT EACH ANCHOR LOCATION SHOWN.2. THE NUMBER OF INSTALLATION ANCHORS DEPICTED IS THE MINIMUM NUMBER OFANCHORS TO BE USED FOR PRODUCT INSTALLATION OF THE MAXIMUM SIZE LISTED.3. INSTALL INDIVIDUAL INSTALLATION ANCHORS WITHIN A TOLERANCE OF ±1.000INCH THE DEPICTED LOCATION & SPACING IN THE ANCHOR LAYOUT DETAILS (I.E.,WITHOUT CONSIDERATION OF TOLERANCES). TOLERANCES ARE NOT CUMULATIVEFROM ONE INSTALLATION ANCHOR TO THE NEXT.4. SHIM AS REQUIRED AT EACH INSTALLATION ANCHOR WITH LOAD BEARING SHIM(S).MAXIMUM ALLOWABLE SHIM STACK TO BE 3/8 INCH. SHIM WHERE SPACE OF 1/16INCH OR GREATER OCCURS. SHIM(S) SHALL BE CONSTRUCTED OF HIGH DENSITYPLASTIC OR BETTER.5. MINIMUM EMBEDMENT AND EDGE DISTANCE EXCLUDE WALL FINISHES, INCLUDINGBUT NOT LIMITED TO STUCCO, FOAM, BRICK VENEER, AND SIDING.6. INSTALLATION ANCHORS AND ASSOCIATED HARDWARE MUST BE MADE OFCORROSION RESISTANT MATERIAL OR HAVE A CORROSION RESISTANT COATING.7. FOR MASONRY OR CONCRETE OPENINGS, A 1X WOOD BUCK MAY BE USED(OPTIONAL) AS LONG AS THE MINIMUM EMBEDMENT AND EDGE DISTANCEREQUIREMENTS ARE STILL MET WITHIN THE CORRESPONDING HOST SUBSTRATE. SEEGENERAL NOTE #3 ON SHEET 1 FOR MORE INFORMATION.8. FOR HOLLOW BLOCK AND GROUT FILLED BLOCK, DO NOT INSTALL INSTALLATIONANCHORS INTO MORTAR JOINTS. EDGE DISTANCE IS MEASURED FROM FREE EDGE OFBLOCK OR EDGE OF MORTAR JOINT INTO FACE SHELL OF BLOCK.9. INSTALLATION ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH ANCHORMANUFACTURER'S INSTALLATION INSTRUCTIONS, AND ANCHORS SHALL NOT BE USEDIN SUBSTRATES WITH STRENGTHS LESS THAN THE MINIMUM STRENGTH SPECIFIED BYTHE ANCHOR MANUFACTURER.SHEET:DWG. #:6SWD017 BUILDING DROPS, INC.
398 E. DANIA BEACH BLVD., STE. 338
DANIA BEACH, FL 33004
PH: (954)399-8478
FAX: (954)744.4738
WEB: www.buildingdrops.comOFSCALE:NTSCLDWG. BY:DATE:09.19.17CHK. BY:HFNREMARKSTITLE:BY DATE
50 SERIES/ V1 SERIES/ (2000)
SINGLE-HUNG WINDOWS
(NON-HVHZ)(NON-IMPACT)6FL14911FL #:PREPARED BY:6TH FBC EDITION FM 10/17THE INSTALLATION DETAILS DESCRIBED HEREIN ARE GENERICAND MAY NOT REFLECT ACTUAL CONDITIONS FOR A SPECIFICSITE. IF SITE CONDITIONS CAUSE INSTALLATION TO DEVIATEFROM THE REQUIREMENTS DETAILED HEREIN, A LICENSEDENGINEER OR ARCHITECT SHALL PREPARE SITE SPECIFICDOCUMENTS FOR USE WITH THIS DOCUMENT.AMERICAN CRAFTSMAN WINDOWSSILVER LINE WINDOWS AND DOORSONE SILVER LINE DRIVENORTH BRUNSWICK, NJ 08902PH: (888) 741-03547TH FBC EDITION NUS10/14/208th FBC EDITIONLH09/23ANCHOR DETAIL & SCHEDULE
Revision Request/Correction to Comments **ALL INFORMATION
HIGHLIGHTED IN
GRAY IS REQUIRED.City of Atlantic Beach Building Department
800 Seminole Rd, Atlantic Beach, FL 32233
Phone: (904) 247-5826 Email: Building-Dept@coab.us PERMIT #: _____________________
**ALL REVISION SUBMITTALS MUST BE EMAILED AS A PDF ATTACHMENT ONLY**
Revision to Issued Permit OR Corrections to Comments Date: ________________
Project Address: ____________________________________________________________________________________
Contractor/Contact Name: ____________________________________________________________________________
Contact Phone: ______________________________ Email: _________________________________________________
Description of Proposed Revision / Corrections:
__________________________________________________________________________________________________
__________________________________________________________________________________________________
__________________________________________________________________________________________________
__________________________________________________________________________________________________
_______________________________ affirm the revision/correction to comments is inclusive of the proposed changes.
(Printed name)
x Will proposed revision/corrections add additional square footage to original submittal?
No Yes (additional s.f. to be added: _____________________________)
x Will proposed revision/corrections add additional increase in building value to original submittal?
No *Yes (additional increase in building value: $____________________) (Contractor must sign if increase in valuation)
*Signature of Contractor/Agent: _______________________________________________________
__________________________________________________________________________________________________
(Office Use Only)
Approved Denied Not Applicable to Department Permit Fee Due $_______________
Revision/Plan Review Comments_______________________________________________________________________
__________________________________________________________________________________________________
Department Review Required:
Building _____________________________________________
Planning & Zoning Reviewed By
Tree Administrator
Public Works
Public Utilities _____________________________________________
Public Safety Date
Fire Services
RES24-0044
X 08/19/2024
808 AMBERJACK LANE ATLANTIC BEACH FL 32233
T.M CONSTRUCTION & ROOFING
904-662-7228 tmconstructionroofing@gmail.com
IM UPDATING THE PRODUCT APPROVAL FORM BECAUSE THE WINDOW AND DOOR BRAND CHANGED
TRAVIS MOSS
n n
n
City of Jacksonville - Planning and Development
Building Inspection Division Permit Number:
PRODUCT APPROVAL INFORMATION SHEET (PAIS)
(revised July 30, 2015)
Project Name:
Project Address:
Contractor:
Manufacturer Product Description Code Version FL# (include suffix)Expiration
ACME 36" Exterior Widget 2017 12345.01 12/31/2017
A.Exterior Doors
1.Swinging
2.Sliding
3.Sectional
4.Roll-up
5.Automatic
6. Other
B.Windows
1.Single Hung
2.Horizontal Slider
3.Casement
4.Double Hung
5.Fixed
6.Awning
7.Pass-through
8.Projected
9.Mullion
10.Wind Breaker
11.Dual Action
12.Other
Category/Subcategory
EXAMPLE
As required by Florida Statute 553.842 and Florida Administrative Code 9B-72, please provide the information and product approval number(s) for the building components listed
below as applicable to the building construction project for the permit number listed above. You should contact your product supplier if you do not know the product approval
number for any of the applicable listed products. Information regarding statewide product approval may be obtained at: www.floridabuilding.org.
Ply Gem Steel Doors 2020 229.1 09/15/2024
Ply Gem windows Sliding Glass Door 2020 14634.1 12/31/2022
Ply Gem windows Single Hung Non Impact 2020 16103.1 12/31/2022
Garage Door Wayne-Dalton Garage Door 2020 9174.2 12-31-2035
12/21/25
11/30/2026
2020WAYNE DALTON 9174.2 12-31-2035
PLY GEM SLIDING GLASS DOOR 2020 14634.1
GARAGE DOOR
2023 14634.2
2023
2023
Masonite 2023 5465.1 12/31/2026
RES24-0044
Amberjack Home
808 Amberjack Lane Atlantic Beach FL 32233
T.M Construction & Roofing
Masonite Fiberglass door 2023 22363.5 05/31/2027
07/23/203114911American Craftsman
C. Panel Wall
1. Siding
2. Soffits
3. EIFS
4. Storefront
5. Curtain Walls
6. Wall Louvers
7. Glass Block
8. Membrane
9. Greenhouse
10. Synthetic Stucco
11. Other
D. Roofing Products
1. Asphalt Shingles
2. Underlayments
3. Roofing Fasteners
5. Built-up Roofing
6. Modified Bitumen
7. Single-ply Roofing
8. Roofing Tiles
9. Roofing Insulation
10. Water-proofing
12. Roofing Slate
15. Roof Tile Adhesive
17. Other
14. Cement-adhesive
coats
16. Spray-applied
Polyurethane Roofing
13. Liquid-applied
Roofing
4. Non-structural Roof
Metal
11. Wood
Shingles/Shakes
James Hardie Hardie Plank Lap Siding 2020 13192.2 12/31/2023
Ply Gem Siding Vinyl Soffit Mastic 2020 32502.1 12/31/2023
GAF ASphalt Shingles 2020 10124.1 12/16/2022
12/31/2023Owens Corner Roof Underlayments 2020 15216.1
12/16/25
2023 13192.2 03/31/2026
Petersen Aluminum 2023 23157.1 09/22/2026
2023
2023 12/31/2026
12/16/2025
E. Shutters
1. Accordion
2. Bahama
3. Storm Panels
4. Colonial
5. Roll-up
6. Equipment
7. Other
F. Structural Components
2. Truss plates
3. Engineered Lumber
4. Railing
5. Coolers/Freezers
6. Concrete Admixtures
7. Material
8. Insulation Forms
9. Plastics
10. Deck-roof
11. Wall
12. Sheds
13. Other
G. Skylights
1. Skylight
2. Other
1.
2.
In addition to completing the above list of manufacturers, product description and State approval number for the products
used on this project, it is the Contractor's or Authorized Agent's responsibility to have a legible copy of each manufacturer's
printed instructions, along with the list above, on the job site available to the inspector.
1. Wood
Connector/Anchor
H. New Exterior Envelope
Products
MITEK Threaded Rod 2020 578.1 12/31/2023
12/31/2022MitekHigh Strength Connector Plate 2020 2197.2 12/16/2025
2023
2023 01/01/2027
01/01/2027