1816 Atlantic Beach Dr ERES24-0275 Proposed Riser Diagram -200 A Main Lug Panel RESIDENTIAL LOAD CALCULATION / RISER DIAGRAM 1816 AtlanƟc Beach Drive, AtlanƟc Beach , FL 32233 200 Amp Meter Main 200 Amp MLO Panel Total Square Feet Approx. 3000 Total Demand Load 196 Amps Neutral Demand 81 Amps LighƟng Load 5,100 VA Appliance Load 15,103 VA Heat Demand Load 11,600 VA Total Load CalculaƟon 47,003 VA Exterior of Residence American Electrical ContracƟng, Inc. 9016 Philips Highway—Jacksonville, FL 32256 Telephone 904-737-7770 EC13010299 UƟlity Service 3 ” Conduit UƟlity Meter Encl Proposed 200A AutomaƟc Transfer Switch 26KW Generac Generator 200 A 100A Interior of Residence Exterior Panel of Residence 60A 60A 60 A Pool Panel ERES24-0275