1021 ATLANTIC BLVD 971 COMM24-0042 - approved by fireABBREVIATIONS 971 ATLANTIC BLVD. - TECH HOSPITAL REMODEL INDEX OF DRAWINGS C, IT 'r -449 4� 4 ■ ,� AFF- ABOVE FINISHED FLOOR RO- ROUGH OPENING ALUM- ALUMINUM - a U_ SHEET # SHEET TITLE G1 ARCH- ARCHITECT SECT- SECTION GENERAL SHT- SHEET BLDG- BUILDING SHTG- SHEATHING BLKG- BLOCKING SIM-- SIMILAR " - ` • v a - A001 COVER SHEET X BRG- BEARING SPEC- SPECIFIED° BSMT- BASEMENT STD- STANDARD STOR- STORAGE . 1 F T w - „_ s s .' 0 A � A002 ADA NOTES AND DETAILS x A003 GENERAL NOTES LEGENDS SPECS X AOQ4 LIFE SAFETY PLAN x CLG- CEILING coNc- CONCRETE T- TREAD ^ _ a `; : .� A + 4 p- a G 0 U � � lbi ,- ARCHITECTURAL CONSTR- CONSTRUCTION T&G- TONGUE AND GROVE - `J I - ` + a Oil` • ~ • 4 r r THIS CONFIDENCE. WITH0UT ARCHITECTURAL DRAWINGS NO USE OR DISSEMINATION PRIOR WRITTEN CONSENT IS GIVEN IN MAY BE MADE OF THE ARCHITECT. CONT- CONTINUOUS TEMP- TEMPORARY CONTR- CONTRACT THK- THICK - + • j —mom*— * r ` f ALL OTHERWISE COMMON LAW RIGHTS OF COPYRIGHT ARE HERBY SPECIFICALLY AND RESERVED. A300 MISC BUILDING SECTION/ DETAILS x CTR- CENTER TRTD- TOP OF READO D Ir`- DP- DEEP TV- TELEVISION DBL- DOUBLE TYP- TYPICAL DET- DETAIL c#_ # _ DIA- DIAMETER UNO UNLESS NOTED OTHERWISE DIM- DIMENSION DN- DOWN VP- VAPOR BARRIER _ �r/ '�+ �^ ^4, 9 '•"� '� �'rls ��•yry� DR- DOOR VCT- VINYL COMPOSITE LUMBER �- [�I - • � - � or ,� � !� vp W J DS- DOWNSPOUT VEN- VENEER r . DWG- DRAWING W_ WIDE EA- EACH WI- WIDTH w� + - ... ft.ION �'• ~ "" T r * z ELEC- ELECTRICAL WD- WOOD . f 'jr ! 7 *r _�;• ` . a ` ` 1 ' _ T qp Tf W U] LLI ELEV- ELEVATION WIN- WINDOW � '� = U ❑ EP- ELECTRICAL PANEL W10- WITH OUT EXT- EXTERIOR WP- WEATHERPROOF I �' r Z (rj O m WWF- WELDED WIRE FABRIC. �� or < FG- FIRE CODE ,.r4r.- r C FD- FLOOR DRAIN &- AND�/ FDN- FOUNDATION @- AT FIN- FINISHED CL- CENTERLINE ,e qk le _ C w 0 N FLR- FLOOR O- DIAMETER FT- FOOT OR FEET41 FTG- FOOTING vw, 6 GC- GENERAL CONTRACTOR GYP- GYPSUM j 3,. Z W HT- HEIGHT n 0 — Q m HC- HANDICAP �-- -'* '' -- - "' m 01 V) c) O HDR- HEADER HR- HOUR HVAC- HEATING, VENTING & AIR CONDITIONING INCL- INCLUDING .�.Awe - - + ' ` ` ��+...,. _mw ` -"'"' �' ,w R aw r w T CD y INSUL- INSULATION J W �3 Q INT- INTERIOR �. WWAM- _ _ _� AL._i _AL ik� i- _ T- - 'A - t F-> W JST- JOIST LU LT- LIGHT PSL- PARALLEL STRUCTURE LUMBER MAX- MAXIMUM - Royal PalmlVilf6ge V11me Tapas MECH- MECHANICAL 41 Ya MET- METAL MFR- MANUFACTURER do �1! MIN- MINIMUM MISG- MISCELLANEOUS i NIC- NOT IN CONTRACT w I NO- NUMBER NONCOM- NONCOMBUSTIBLE ♦ „. _ �� .r NTS- NOT TO SCALE TIM OI- ON OR OVER OC- ON CENTER y 0 • OPNG- OPENING' OPP- OPPOSITE s ' OVHD- OVERHEAD s o v I >� f z O F- PLY- PLYWOOD dn ftlaim PROP- PROPERTY PT- POINT PVMT- PAVEMENT N ` f j i , U L PWR- POWER R- RISER MIL- C • W E � � ■ � RAD- RADIUS REFRIG- REFRIGERATOR REINF- REINFORCING 5 READ- REQUIRED REV- REVISION RM- ROOM T ` . ' ■ ' Ilk A ita As ARM j LL] GENERAL CONSTRUCTION NOTES BUILDING INFORMATION ARCHITECT AND CONSULTANT INFO. CID 1. THE USE OF THESE DOCUMENTS IS RESTRICTED TO THE ORIGINAL SITE PLAN FOR WHICH PERMITTING AUTHORITY HAVING JURISDICTION: CODE REFERENCES: CITY OF ATLANTIC BEACH FLORIDA BUILDING CODE (FBC) 2023z ARCHITECT: O THEY WERE PREPARED. REUSE OR REPRODUCTION OF THE DOCUMENTS (WHOLE OR IN PART) FOR ANY OTHER PURPOSE IS PROHIBITED. 800 SEMINOLE BLVD FLORIDA RESIDENTIAL BUILDING CODE (FBC) 2023 ATLANTIC BEACH, FL 32233 FLORIDA PLUMBING CODE (FBC) 2023 ISLANDS ARCHITECTURE AND DESIGN, LLC REVISIONS 2- THE CONTRACTOR AND SUB -CONTRACTORS SHALL BE SOLELY RESPONSIBLE FOR FLORIDA MECHANICAL CODE (FBC) 2023 COMPLYING WITH ALL FEDERAL STATE, AND LOCAL, SAFETY REQUIREMENTS TOGETHER PROPERTY LOCATION: NATIONAL ELECTRIC CODE (NECO) 2020 JOSH B U NO PERMIT SET WITH EXERCISING PRECAUTIONS AT ALL TIMES FOR THE PROTECTION OF PERSONS INCLUDING EMPLOYEES AND PROPERTY. IT IS THE SOLE RESPONSIBILITY OF THE 971 ATLANTIC BEACH, ATLANTIC BEACH, FLORIDA 32233 NFPA LIFE SAFETY CODE NFPA 101, 2023 ANSI- AMERICAN NATIONAL STANDARD FOR BUILDINGS 173 ARUBA LANE CONTRACTOR AND SUB -CONTRACTOR'S TO INITIATE, MAINTAIN, AND SUPERVISE ALL CLASSIFICATION BY OCCUPANCY: FLORIDA FIRE PREVENTION CODE 2023 SAFETY REQUIREMENTS, PRECAUTIONS, AND PROGRAMS IN CONNECTION WITH THE WORK BUILDING TYPE: B - RETAIL STRIP CENTER FLORIDA ACCESSIBILITY CODE (ADA) 2023 PANTE VED RA BEACH, FL 3��82 3. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE ALL WORK AND FOR OCCUPANCY LOAD: 60 GROSS 813.413.9901 THE MEANS, METHODS, PROCEDURES, TECHNIQUES, AND SEQUENCE OF CONSTRUCTION. CLASSIFICATION BY CONSTRUCTION TYPE: 4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SCHEDULING AND MONITORING BUILDING TYPE: TYPE 2-B - NOWSPRINKLERED pp n J ©U O N O. BAC a@G MAI L. C O M OF ON SITE TESTING AND INSPECTION SERVICES AS LISTED IN THE GENERAL CONDITIONS. 5. THE GENERAL CONTRACTOR IS TO VERIFY ALL EXISTING FIELD CONDITIONS. GENERAL ALLOWABLE HEIGHT AND BUILDING AREAS: CONTRACTOR IS TO REPORT IMMEDIATELY TO THE ARCHITECT ANY VARIANCES IN FIELD CONDITIONS THAT MAY CAUSE CONSTRUCTION PROBLEMS PRIOR TO COMMENCING WORK. MAXIMUM HEIGHT ALLOWED (TABLE 503): EXISTING UNCHANGED 6. DO NOT SCALE DRAWINGS, WRITTEN DIMENSIONS GOVERN. ALL PARTITION LOCATIONS, MAXIMUM HEIGHT PROVIDED: EXISTING UNCHANGED ALL DOOR AND OPENING LOCATIONS SHALL BE SHOWN ON FLOOR PLANS. IN CASE OF CONFLICT NOTIFY THE ARCHITECT. FLOOR PLAN BY THE ARCHITECT SUPERSEDES ALL MAXIMUM NUMBER OF FLOORS ALLOWED: EXISTING UNCHANGED OTHER PLANS. ALL DIMENSIONS MARKED "CLEAR" SHALL BE MAINTAINED AND SHALL MAXIMUM NUMBER OF OF FLOORS PROVIDED - EXISTING UNCHANGED ALLOW FOR THICKNESS OF ALL FINISHES. 7. ALL DIMENSIONS SHOWN ARE FROM FACE STUD TO FACE STUD EXCEPT WHEN MAXIMUM AREA ALLOWED (PER FLOOR): EXISTING UNCHANGED DIMENSIONING MAJOR STRUCTURAL ELEMENTS (SUCH AS COLUMNS OR TUNNEL FORM MAXIMUM AREA PROVIDED NEW AUXILIARY STRUCTURE: EXISTING UNCHANGED WALLS) OR ARCHITECTURAL MILLWORK (SUCH AS CABINETS, SHELVING, ETC...} OCCUPANCY SEPARATION REQUIREMENTS: Digitally signed by Joshua Michael Buono DN: E=jbuono.bac@gmail.com, CN=Joshua EXISTING TO REMAIN - 1 HOUR CURRENTLY PROVIDED. Michael Buono, SERIALN U MBER=AATL20240220337232, FIRE RESISTANCE RATINGS: REQUIRED PROTECTION FOR TYPE II -B CONSTRUCTION FOR C=US Date: 2024.10.11 13:27:02-04'00' STRUCTURAL COLUMNSP GIRDERS, ROOFS, ROOF/ TO THE BEST OF OUR KNOWLEDGE, THESE PLANS AND CEILING ASSEMBLIES AND BEAMS 0 HOURSSS, EXTERIOR BEARING WALLS: 0 HOURS SPECIFICATIONS COMPLY WITH THE APPLICABLE INTERIOR BEARING WALLS: 0 HOURS CHECKED BY: JMB FLOORING CONSTRUCTION: 0 HOURS BUILDING CODES AND THE APPLICABLE MINIMUM FIRE DRAWN BY: JMB,JPB,SMB ISSUE DATE.10.10.2024 SAFETY STANDARDS AS DETERMINED IN ACCORDANCE WITH CHAPTERS 553 AND 653, FLORIDA STATUTES. AOO1 NERAL THIS PROJECT SHALL COMPLY WITH ALL LOCAL, STATE & FEDERAL ACCESSIBILITY CODES/STANDARDS. IF A CONFLICT EXISTS BETWEEN ANY OF THESE STANDARDS, THEN THE MOST STRINGENT CODE SHALL APPLY. ENTRANCES 2. WHERE URINALS ARE PROVIDED, AT LEAST ONE WITH A RIM PROJECTING A MINIMUM OF 13.5" FROM THE WALL 7 AND AT A MAXIMUM OF 17" ABOVE THE FLOOR SHALL BE PROVIDED. 3. FLUSH CONTROLS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST AND SHALL BE MOUNTED NO MORE THAN 44" ABOVE THE FLOOR. THE FORCE REQUIRED TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5 POUNDS PER FOOT. WHEN PERMANENT IDENTIFICATION IS PROVIDED FOR ROOMS AND SPACES, RAISED LETTERS SHALL BE PROVIDED AND SHALL BE ACCOMPANIED BY BRAILLE. SIGNS SHALL BE INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE OF THE DOOR. WHERE THERE IS NO WALL SPACE ON THE LATCH SIDE, INCLUDING AT DOUBLE LEAF DOORS, SIGNS SHALL BE PLACED ON THE NEAREST ADJACENT WALL. MOUNTING HEIGHT SHALL BE 60" ABOVE THE FINISHED FLOOR TO THE CENTERLINE OF THE SIGN. SIGN SHALL BE MOUNTED SO THAT A CLEAR FLOOR SPACE OF 18"x18" MINIMUM, CENTER ON THE TACTILE CHARACTERS, IS PROVIDED BEYOND THE ARC OF ANY DOOR SWING BETWEEN THE CLOSED POSITION & 45 DEGREE OPEN POSITION. IF ALL PUBLIC ENTRANCES ARE NOT ACCESSIBLE, PROVIDE AN INTERNATIONAL SYMBOL OF ACCESSIBILITY SIGN 4. LAVATORIES SHALL BE MOUNTED WITH A CLEARANCE OF AT LEAST 29" FROM THE FLOOR TO THE BOTTOM OF AT THE ACCESSIBLE ENTRANCE AND ADDITIONAL DIRECTIONAL SIGNS, AS REQUIRED, VISIBLE FROM THE APRON WITH KNEE CLEARANCE UNDER THE FRONT LIP EXTENDING A MINIMUM OF 30" IN WIDTH WITH 8" TABLES AND SEATING DISTRIBUTION NOTES: APPROACHING PEDESTRIAN WAYS TO THE INACCESSIBLE ENTRANCE. MINIMUM DEPTH AT THE TOP. TOE CLEARANCE SHALL BE THE SAME WIDTH AND SHALL BE A MINIMUM OF 9" HIGH FROM THE FLOOR AND A MINIMUM OF 17" DEEP FROM THE FRONT OF THE LAVATORY. 1. AT LEAST 5% OF ALL SEATING AND STANDING SPACES ARE TO BE ACCESSIBLE AND LOCATED ON AN EVERY REQUIRED ENTRANCE OR PASSAGE DOORWAY SHALL BE OF A SIZE AS TO PERMIT THE INSTALLATION OF ACCESSIBLE ROUTE. THE ACCESSIBLE TABLES ARE ALSO REQUIRED TO BE DISTRIBUTED THROUGHOUT ALL A DOOR NOT LESS THAN YIN WIDTH AND NOT LESS THAN U-8" IN HEIGHT. DOORS SHALL BE CAPABLE OF 5. A PROJECTION OF A LAVATORY BOWL INTO THE 8" CLEAR SPACE THEREBY REDUCING THE CLEAR HEIGHT DINING AREAS. OPENING AT LEAST 90 DEGREES AND SHALL BE SO MOUNTED THAT THE CLEAR WIDTH OF THE DOORWAY IS NOT BELOW THE LAVATORY TO NO LESS THAN 27" AT 8" BACK FROM THE APRON, MEETS THE REQUIREMENT FOR LESS THAN 32". PROVIDING KNEE CLEARANCE. A MAXIMUM HEIGHT OF 34" TO THE TOP OF THE LAVATORY IS REQUIRE. 2. ACCESSIBLE ROUTE TO SEATING LOCATIONS WHERE A PAIR OF DOORS IS UTILIZED, AT LEAST ONE OF THE DOORS SHALL PROVIDE A CLEAR UNOBSTRUCTED 6. HOT WATER AND DRAIN PIPES UNDER LAVATORIES SHALL BE INSULATED OR OTHERWISE COVERED. THERE A. A 36" MINIMUM WIDE ACCESSIBLE ROUTE IS REQUIRED TO CONNECT THE ACCESSIBLE TABLES TO EACH OF THE OPENING WIDTH OF 32" WITH THE LEAF POSITIONED AT AN ANGLE OF 900 DEGREES FROM ITS CLOSED POSITION. SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER LAVATORIES. RESTAURANT ELEMENTS. 7. FAUCET CONTROLS AND OPERATING MECHANISMS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT B. THE 36" ROUTE SHOULD TAKE INTO ACCOUNT CUSTOMERS SEATED AT THE TABLES. IT SHOULD NOT BE LATCHING AND LOCKING DOORS THAT ARE HAND ACTIVATED AND WHICH ARE IN A PATH OF TRAVEL SHALL BE REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE MEASURED WITH THE SEATS PUSHED COMPLETELY UNDER THE TABLES. OPERABLE WITH A SINGLE EFFORT BY LEVER TYPE HARDWARE, PANIC BARS, PUSH-PULL ACTIVATING BARS, OR CONTROLS SHALL BE NO MORE THAN 5 POUNDS. LEVER OPERATED, PUSH TYPE AND ELECTRONICALLY OTHER HARDWARE DESIGNED TO PROVIDE PASSAGE WITHOUT REQUIRING THE ABILITY TO GRASP THE OPENING CONTROLLED MECHANISMS ARE EXAMPLES OF ACCEPTABLE DESIGNS. SELF-CLOSING VALVES ARE ALLOWED IF 3. MINIMUM NUMBER OF ACCESSIBLE TABLES HARDWARE. THE FAUCET REMAINS OPEN FOR AT LEAST 10 SECONDS. HAND ACTIVATED DOOR OPENING HARDWARE SHALL BE CENTERED BETWEEN 30" AND 44" ABOVE THE FLOOR. GRAB BARS A. A MINIMUM OF 5% OF SEATING AND STANDING LOCATIONS ARE REQUIRED TO BE ACCESSIBLE. THIS IS CALCULATED BY ADDING THE TOTAL NUMBER OF SEATS OR STANDING TABLE SPACES AND MULTIPLYING BY .05. THE MINIMUM REQUIRED MANEUVERING CLEARANCES ON EACH SIDE OF AN ENTRANCE OR PASSAGE DOOR 1. GRAB BARS SHALL BE LOCATED ON EACH SIDE, OR ONE SIDE AND THE BACK OF THE PHYSICALLY DISABLED 4. SEATING DISPERSION SHALL BE CLEAR, AND THE FLOOR SLOPE SHALL NOT EXCEED 2%. TOILET STALL OR COMPARTMENT AND SHALL BE SECURELY ATTACHED 33"-36" ABOVE AND PARALLEL TO THE TYPICAL ACCESSIBILITY NOTE: DIMENSIONS SHOWN APPLY WHEN X<48" DETAILS NOTE: X=12" IF DOOR HAS NOTE: Y=48" MIN. IF DOOR HAS NOTE: Y=48" MIN. IF CHARACTERS ARE PERMITTED. FOR SIGNS SUSPENDED OR PROJECTED ABOVE THE FINISH FLOOR THE MINIMUM FLOOR TO THE TOP OF THE BAR. GRAB BARS SHALL NOT ROTATE WITHIN THEIR FITTINGS. NOTE: AREAS INCLUDING PLAYPLACE SEATING AND PARTY ROOMS. THE FLOOR OR LANDING SHALL BE NOT MORE THAN 112" LOWER THAN THE THRESHOLD OF THE DOORWAY, }( IF OUTLETS ARE PROVIDED IN DINING AREA FOR CUSTOMERS USE, AN OUTLET MUST BE PROVIDED AT AN CHANGE IN LEVEL BETWEEN 114" AND 112" SHALL BE BEVELED WITH A SLOPE NO GREATER THAN 1:2, 2. GRAB BARS AT THE SIDE SHALL BE AT LEAST 42" LONG, INSTALLED 12" FROM THE REAR WALL, AND GRAB BARS BETWEEN THE CLOSED POSITION AND 45' OPEN POSITION. MOUNTING HEIGHT SHALL BE 60" ABOVE THE ACCESSIBLE TABLE. DARK BACKGROUND OR DARK CHARACTERS ON A LIGHT BACKGROUND. AT THE BACK SHALL BE NOT LESS THAN 36" LONG, & EXTENDING 12" MINIMUM ON ONE SIDE OF THE WATER C. BOTH CLOSER AND LATCH BOTH LATCH AND CLOSER DOOR HAS CLOSERY THE BOTTOM 10" OF ALL DOORS EXCEPT AUTOMATIC AND SLIDING SHALL HAVE A SMOOTH UNINTERRUPTED CLOSET CENTERLINE AND 24" MINIMUM ON THE OTHER SIDE. X AN ACCESSIBLE TABLE. SHALL BE 48" MAX WHEN X IS 20" MAX; LETTERS AND NUMBERS ON SIGNS SHALL BE RAISED 1132" MINIMUM AND SHALL BE SANS -SERIF UPPERCASE D. THE OPEN SPACE AT THE ENDS OF BOOTHS IS NOT AN ACCEPTABLE ACCESSIBLE SEATING LOCATION. HAZARDOUS CONDITION. WHERE NARROW FRAME DOORS ARE USED, A 10" HIGH SMOOTH PANEL SHALL BE 3. THE DIAMETER OR WIDTH OF THE GRIPPING SURFACES OF A GRAB BAR SHALL BE 1-1/4" TO 1-112" OR THE SHAPE E. MOVEABLE CHAIRS MAY BE POSITIONED AT ACCESSIBLE SEATING LOCATION FOR USE BY AMBULATORY INSTALLED ON THE PUSH SIDE OF THE DOOR WHICH WILL ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR SHALL PROVIDE AN EQUIVALENT GRIPPING SURFACE. C. 24" 48" 24" FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. PLACED DIRECTLY BELOW THE PICTOGRAM. THE BORDER DIMENSION OF THE PICTOGRAM SHALL BE A MINIMUM Y SHALL BE 44" MAX WHEN X IS X20-25" MAX MAX. MIN. MAX.58 1. TOILET FLUSH CONTROLS SHALL BE OPERABLE WITH ONE HAND, AND SHALL NOT REQUIRE TIGHT GRASPING, z t 6. CONTRACTED GRADE 2 BRAILLE SHALL BE USED WHEREVER BRAILLE SYMBOLS ARE SPECIFICALLY REQUIRED IN SIDE OF THE TOILET AREAS, NO MORE THAN 44" ABOVE THE FLOOR. THE FORCE REQUIRED TO ACTIVATE ` OTHER PORTIONS OF THESE REGULATIONS. DOTS SHALL BE .1" ON CENTERS IN EACH CELL WITH .3" SPACE MIN. ,-IF DOOR HAS BETWEEN CELLS. DOTS SHALL BE RAISED .3" ABOVE THE BACKGROUND. �� - ��1 X z p0 ti ti 12" BOTH MIN -LATCH K 24" MIN - w K w �, - - w - - 1' 1 1, I j y PUSH X ? z AND z` SIDE ` 01 = z = z � - N = z z �� �� CLOSER � z � � 4 4 X NOTE: IF X=10" MAX., THEN Y=48" MAX = z 48" MAX CLEAR WIDTH OF AN 36" 48" 36" 42" X 42" PULL � SIDE `INT. DR 18"MIN o = 24" MIN _ �_ HIGH AND IF X 10-24 EN Y=46 MAX.,, LOW MAXIMUM SIDE REACH MAXIMUM FORWARD REACH UNOBSTRUCTED "MIN SIDE ACCESSIBLE ROUTE EXT. DRS ? � � REACH LIMITS OVER OBSTRUCTION. OVER A HIGH FORWARD REACH BSTRUCTION MIN MIN MIN MIN MIN 90° TURN 180° TURN ? NOTE: �� _ Q IF Y=54", THEN X=42 MAX SIDE REACH FRONT REACH NOTE: DIMENSIONS SHOWN APPLY WHEN X<48" 12" 36" MIN 1 " PULL SIDE IF Y=60", THEN X=36" NOTE: Y=54" IF DOOR MIK MIK HAS CLOSER 30" MIN y �yy FRONT APPROACHES- HINGE SIDE LATCH SIDE 7C ; SWINGING APPROACHES -SWINGING APPROACHES -SWINGING w a' DOORS DOORS DOORS - J - z o! �_ zw CHANGES IN LEVEL � x 2 1 z �� �� 4$« MIN. �+ I O° ` �[ j 3011 IIZE OF 60 IN LE 60" MIN L L 36" X 36" 48" MIN. 60" MIN MIN DIAMETER FLOOR T -SHAPED FOR � � MIN. SPACE SPACE 180° TURNS BEVELED CHANGES IN LEVEL 180° TURN (EXCEPTION} TWO HINGED ODORS IN SERIES TWO HINGED DOORS IN SERIES TWO HINGED DOORS IN SERIES ACCESSIBLE SEATING NERAL THIS PROJECT SHALL COMPLY WITH ALL LOCAL, STATE & FEDERAL ACCESSIBILITY CODES/STANDARDS. IF A CONFLICT EXISTS BETWEEN ANY OF THESE STANDARDS, THEN THE MOST STRINGENT CODE SHALL APPLY. ENTRANCES 2. WHERE URINALS ARE PROVIDED, AT LEAST ONE WITH A RIM PROJECTING A MINIMUM OF 13.5" FROM THE WALL 7 AND AT A MAXIMUM OF 17" ABOVE THE FLOOR SHALL BE PROVIDED. 3. FLUSH CONTROLS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST AND SHALL BE MOUNTED NO MORE THAN 44" ABOVE THE FLOOR. THE FORCE REQUIRED TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5 POUNDS PER FOOT. WHEN PERMANENT IDENTIFICATION IS PROVIDED FOR ROOMS AND SPACES, RAISED LETTERS SHALL BE PROVIDED AND SHALL BE ACCOMPANIED BY BRAILLE. SIGNS SHALL BE INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE OF THE DOOR. WHERE THERE IS NO WALL SPACE ON THE LATCH SIDE, INCLUDING AT DOUBLE LEAF DOORS, SIGNS SHALL BE PLACED ON THE NEAREST ADJACENT WALL. MOUNTING HEIGHT SHALL BE 60" ABOVE THE FINISHED FLOOR TO THE CENTERLINE OF THE SIGN. SIGN SHALL BE MOUNTED SO THAT A CLEAR FLOOR SPACE OF 18"x18" MINIMUM, CENTER ON THE TACTILE CHARACTERS, IS PROVIDED BEYOND THE ARC OF ANY DOOR SWING BETWEEN THE CLOSED POSITION & 45 DEGREE OPEN POSITION. IF ALL PUBLIC ENTRANCES ARE NOT ACCESSIBLE, PROVIDE AN INTERNATIONAL SYMBOL OF ACCESSIBILITY SIGN 4. LAVATORIES SHALL BE MOUNTED WITH A CLEARANCE OF AT LEAST 29" FROM THE FLOOR TO THE BOTTOM OF AT THE ACCESSIBLE ENTRANCE AND ADDITIONAL DIRECTIONAL SIGNS, AS REQUIRED, VISIBLE FROM THE APRON WITH KNEE CLEARANCE UNDER THE FRONT LIP EXTENDING A MINIMUM OF 30" IN WIDTH WITH 8" TABLES AND SEATING DISTRIBUTION NOTES: APPROACHING PEDESTRIAN WAYS TO THE INACCESSIBLE ENTRANCE. MINIMUM DEPTH AT THE TOP. TOE CLEARANCE SHALL BE THE SAME WIDTH AND SHALL BE A MINIMUM OF 9" HIGH FROM THE FLOOR AND A MINIMUM OF 17" DEEP FROM THE FRONT OF THE LAVATORY. 1. AT LEAST 5% OF ALL SEATING AND STANDING SPACES ARE TO BE ACCESSIBLE AND LOCATED ON AN EVERY REQUIRED ENTRANCE OR PASSAGE DOORWAY SHALL BE OF A SIZE AS TO PERMIT THE INSTALLATION OF ACCESSIBLE ROUTE. THE ACCESSIBLE TABLES ARE ALSO REQUIRED TO BE DISTRIBUTED THROUGHOUT ALL A DOOR NOT LESS THAN YIN WIDTH AND NOT LESS THAN U-8" IN HEIGHT. DOORS SHALL BE CAPABLE OF 5. A PROJECTION OF A LAVATORY BOWL INTO THE 8" CLEAR SPACE THEREBY REDUCING THE CLEAR HEIGHT DINING AREAS. OPENING AT LEAST 90 DEGREES AND SHALL BE SO MOUNTED THAT THE CLEAR WIDTH OF THE DOORWAY IS NOT BELOW THE LAVATORY TO NO LESS THAN 27" AT 8" BACK FROM THE APRON, MEETS THE REQUIREMENT FOR LESS THAN 32". PROVIDING KNEE CLEARANCE. A MAXIMUM HEIGHT OF 34" TO THE TOP OF THE LAVATORY IS REQUIRE. 2. ACCESSIBLE ROUTE TO SEATING LOCATIONS WHERE A PAIR OF DOORS IS UTILIZED, AT LEAST ONE OF THE DOORS SHALL PROVIDE A CLEAR UNOBSTRUCTED 6. HOT WATER AND DRAIN PIPES UNDER LAVATORIES SHALL BE INSULATED OR OTHERWISE COVERED. THERE A. A 36" MINIMUM WIDE ACCESSIBLE ROUTE IS REQUIRED TO CONNECT THE ACCESSIBLE TABLES TO EACH OF THE OPENING WIDTH OF 32" WITH THE LEAF POSITIONED AT AN ANGLE OF 900 DEGREES FROM ITS CLOSED POSITION. SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER LAVATORIES. RESTAURANT ELEMENTS. 7. FAUCET CONTROLS AND OPERATING MECHANISMS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT B. THE 36" ROUTE SHOULD TAKE INTO ACCOUNT CUSTOMERS SEATED AT THE TABLES. IT SHOULD NOT BE LATCHING AND LOCKING DOORS THAT ARE HAND ACTIVATED AND WHICH ARE IN A PATH OF TRAVEL SHALL BE REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE MEASURED WITH THE SEATS PUSHED COMPLETELY UNDER THE TABLES. OPERABLE WITH A SINGLE EFFORT BY LEVER TYPE HARDWARE, PANIC BARS, PUSH-PULL ACTIVATING BARS, OR CONTROLS SHALL BE NO MORE THAN 5 POUNDS. LEVER OPERATED, PUSH TYPE AND ELECTRONICALLY OTHER HARDWARE DESIGNED TO PROVIDE PASSAGE WITHOUT REQUIRING THE ABILITY TO GRASP THE OPENING CONTROLLED MECHANISMS ARE EXAMPLES OF ACCEPTABLE DESIGNS. SELF-CLOSING VALVES ARE ALLOWED IF 3. MINIMUM NUMBER OF ACCESSIBLE TABLES HARDWARE. THE FAUCET REMAINS OPEN FOR AT LEAST 10 SECONDS. HAND ACTIVATED DOOR OPENING HARDWARE SHALL BE CENTERED BETWEEN 30" AND 44" ABOVE THE FLOOR. GRAB BARS A. A MINIMUM OF 5% OF SEATING AND STANDING LOCATIONS ARE REQUIRED TO BE ACCESSIBLE. THIS IS CALCULATED BY ADDING THE TOTAL NUMBER OF SEATS OR STANDING TABLE SPACES AND MULTIPLYING BY .05. THE MINIMUM REQUIRED MANEUVERING CLEARANCES ON EACH SIDE OF AN ENTRANCE OR PASSAGE DOOR 1. GRAB BARS SHALL BE LOCATED ON EACH SIDE, OR ONE SIDE AND THE BACK OF THE PHYSICALLY DISABLED 4. SEATING DISPERSION SHALL BE CLEAR, AND THE FLOOR SLOPE SHALL NOT EXCEED 2%. TOILET STALL OR COMPARTMENT AND SHALL BE SECURELY ATTACHED 33"-36" ABOVE AND PARALLEL TO THE A. THE ACCESSIBLE TABLES ARE REQUIRED TO BE DISPERSED THROUGHOUT THE VARIOUS TYPES OF DINING CHARACTERS ARE PERMITTED. FOR SIGNS SUSPENDED OR PROJECTED ABOVE THE FINISH FLOOR THE MINIMUM FLOOR TO THE TOP OF THE BAR. GRAB BARS SHALL NOT ROTATE WITHIN THEIR FITTINGS. AREAS INCLUDING PLAYPLACE SEATING AND PARTY ROOMS. THE FLOOR OR LANDING SHALL BE NOT MORE THAN 112" LOWER THAN THE THRESHOLD OF THE DOORWAY, B. IF OUTLETS ARE PROVIDED IN DINING AREA FOR CUSTOMERS USE, AN OUTLET MUST BE PROVIDED AT AN CHANGE IN LEVEL BETWEEN 114" AND 112" SHALL BE BEVELED WITH A SLOPE NO GREATER THAN 1:2, 2. GRAB BARS AT THE SIDE SHALL BE AT LEAST 42" LONG, INSTALLED 12" FROM THE REAR WALL, AND GRAB BARS BETWEEN THE CLOSED POSITION AND 45' OPEN POSITION. MOUNTING HEIGHT SHALL BE 60" ABOVE THE ACCESSIBLE TABLE. DARK BACKGROUND OR DARK CHARACTERS ON A LIGHT BACKGROUND. AT THE BACK SHALL BE NOT LESS THAN 36" LONG, & EXTENDING 12" MINIMUM ON ONE SIDE OF THE WATER C. IF TELEVISIONS ARE PROVIDED IN DINING AREA, A LINE OF SIGHT MUST BE PROVIDED TO THE TELEVISION FROM THE BOTTOM 10" OF ALL DOORS EXCEPT AUTOMATIC AND SLIDING SHALL HAVE A SMOOTH UNINTERRUPTED CLOSET CENTERLINE AND 24" MINIMUM ON THE OTHER SIDE. WHEN RAISED CHARACTERS OR SYMBOLS ARE USED, THEY SHALL CONFORM TO THE FOLLOWING: AN ACCESSIBLE TABLE. SURFACE TO ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR LETTERS AND NUMBERS ON SIGNS SHALL BE RAISED 1132" MINIMUM AND SHALL BE SANS -SERIF UPPERCASE D. THE OPEN SPACE AT THE ENDS OF BOOTHS IS NOT AN ACCEPTABLE ACCESSIBLE SEATING LOCATION. HAZARDOUS CONDITION. WHERE NARROW FRAME DOORS ARE USED, A 10" HIGH SMOOTH PANEL SHALL BE 3. THE DIAMETER OR WIDTH OF THE GRIPPING SURFACES OF A GRAB BAR SHALL BE 1-1/4" TO 1-112" OR THE SHAPE E. MOVEABLE CHAIRS MAY BE POSITIONED AT ACCESSIBLE SEATING LOCATION FOR USE BY AMBULATORY INSTALLED ON THE PUSH SIDE OF THE DOOR WHICH WILL ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR SHALL PROVIDE AN EQUIVALENT GRIPPING SURFACE. C. CUSTOMERS. FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. PLACED DIRECTLY BELOW THE PICTOGRAM. THE BORDER DIMENSION OF THE PICTOGRAM SHALL BE A MINIMUM 4, IF THE GRAB BARS ARE MOUNTED ADJACENT TO A WALL, THE SPACE BETWEEN THE WALL AND THE GRAB BARS 5, REQUIRED KNEE SPACE UNDER ACCESSIBLE TABLES TO BE MINIMUM OF 27" HIGH, 30" WIDE AND 19" DEEP. MAXIMUM EFFORT TO OPERATE DOORS SHALL NOT EXCEED 8.5 POUNDS FOR EXTERIOR DOORS AND 5 POUNDS SHALL BE 1-112". TABLE TOP HEIGHT TO BE BETWEEN 28" & 34"AFF. FOR INTERIOR DOORS, SUCH PULL OR PUSH EFFORT BEING APPLIED AT RIGHT ANGLES TO DOORS AND AT THE CENTER PLANE OF SLIDING OR FOLDING DOORS, COMPENSATING DEVICES OR AUTOMATIC DOOR OPERATORS 5. A GRAB BAR AND ANY WALL OR OTHER SURFACE ADJACENT TO IT SHALL BE FREE OF ANY SHARP OR ABRASIVE MAY BE UTILIZED TO MEET THE ABOVE STANDARDS. WHEN FIRE DOORS ARE REQUIRED, THE MAXIMUM EFFORT ELEMENTS. TO OPERATE THE DOOR MAY BE INCREASED NOT TO EXCEED 15 POUNDS. RS 10. PROVIDE DOOR (LEVER) HARDWARE ON ALL DOORS. 11. PROVIDE PANIC HARDWARE ON EXIT DOORS FROM PUBLIC ASSEMBLY AREAS. OORS AND LEVELS 6. GRAB BARS SHALL NOT ROTATE WITHIN THEIR FITTINGS. 7. EDGES SHALL HAVE A MINIMUM RADIUS OF 118"- 8. GRAB BAR, TUB AND SHOWER SEATS, FASTENERS AND MOUNTING DEVICES SHALL BE DESIGNED FOR 250 POUNDS PER LINEAR FOOT LOAD. 9. THE SPACE BETWEEN THE GRAB BAR & PROJECTING OBJECTS BELOW SHALL BE 1 1/2" MINIMUM. THE SPACE BETWEEN THE GRAB BAR & PROJECTING OBJECTS ABOVE SHALL BE 12" MINIMUM. 1. IN BUILDINGS AND FACILITIES, FLOORS OF A GIVEN STORY SHALL BE A COMMON LEVEL THROUGHOUT, OR SHALL BE CONNECTED BY PEDESTRIAN RAMPS, PASSENGER ELEVATORS OR SPECIAL ACCESS LIFTS. ADDITIONAL REQUIREMENTS FLOOR SURFACES SHALL BE SLIP -RESISTANT. CORRIDORS AND AISLES 1. THE CENTER OF RECEPTACLE OUTLETS SHALL BE NOT LESS THAN 15" ABOVE THE FLOOR OR WORKING PLATFORM. 1. EVERY CORRIDOR SERVING AN OCCUPANT LOAD OF 10 OR MORE SHALL BE NOT LESS IN WIDTH THAN 44". 2. 2. EVERY PORTION OF EVERY BUILDING IN WHICH ARE INSTALLED SEATS, TABLES, MERCHANDISE, EQUIPMENT OR SIMILAR MATERIALS SHALL BE PROVIDED WITH WITH AISLES LEADING TO AN EXIT, 3. EVERY AISLE SHALL BE NOT LESS THAN T WIDE IF SERVING ONLY ONE SIDE, AND NOT LESS THAN T-6" WIDE IF 3. SERVING BOTH SIDES. SUCH MINIMUM WIDTH SHALL BE MEASURED AT THE POINT FARTHEST FROM AN EXIT, CROSS AISLE OR FOYER AND SHALL BE INCREASED BY 1-112" FOR EACH 5' IN LENGTH TOWARD THE EXIT, CROSS AISLE OR FOYER. 4. SANITARY FACILITIES WHEN SANITARY FACILITIES ARE LOCATED ON ACCESSIBLE FLOORS OF A BUILDING, THEY SHALL BE MADE ACCESSIBLE TO THE PHYSICALLY DISABLED. WHERE SEPARATE FACILITIES ARE PROVIDED FOR NON -DISABLED PERSONS OF EACH SEX, SEPARATE FACILITIES SHALL BE PROVIDED FOR DISABLED PERSONS OF EACH SEX ALSO. WHERE UNISEX FACILITIES ARE PROVIDED FOR NON -DISABLED PERSONS, SUCH UNISEX FACILITIES MAY BE PROVIDED FOR THE THE DISABLED. ALL DOORWAYS LEADING TO SANITARY FACILITIES SHALL HAVE 32" CLEAR UNOBSTRUCTED OPENINGS. PROVIDE SIGNAGE AS SHOWN IN THIS SET. THE CENTER OF THE GRIP OF THE OPERATING HANDLE OF SWITCHES INTENDED TO BE USED BY THE OCCUPANT OF THE ROOM OR AREA TO CONTROL LIGHTING AND RECEPTACLE OUTLETS, APPLIANCES, OR COOLING, HEATING AND VENTILATING EQUIPMENT SHALL BE NOT LESS THAN 36" NOR MORE THAN 48" ABOVE THE FLOOR OR WORKING PLATFORM. THE CENTER OF FIRE ALARM INITIATING DEVICES (BOXES) SHALL BE INSTALLED PER BUILDING CODE & FIRE DEPARTMENT REQUIREMENTS. IF EMERGENCY WARNING SYSTEMS ARE REQUIRED, THEY SHALL ACTIVATE A MEANS OF WARNING THE HEARING IMPAIRED. FLASHING VISUAL WARNING SHALL BE A FREQUENCY OF NOT MORE THAN 60 FLASHES PER MINUTE. SIGNS & IDENTIFICATION NOTE 1. THE INTERNATIONAL SYMBOL OF ACCESSIBILITY SHALL BE THE STANDARD USED TO IDENTIFY FACILITIES THAT ARE ACCESSIBLE TO AND USABLE BY PHYSICALLY DISABLED PERSONS AS SET FORTH IN ADA AND AS SPECIFICALLY REQUIRED IN THIS SECTION.THE INTERNATIONAL SYMBOL OF ACCESSIBILITY SHALL CONSIST OF A WHITE FIGURE ON A BLUE BACKGROUND. THE BLUE SHALL BE EQUAL TO COLOR NO. 15090 IN FEDERAL STANDARD 5998. 2. LETTERS AND NUMBERS ON SIGNS SHALL HAVE A WIDTH -TO -HEIGHT RATIO OF BETWEEN 3:5 AND 1:1 AND A STROKE WIDTH -TO -HEIGHT RATIO BETWEEN 1:5 AND 1:10. L OF TACTILE CHARACTERS 1 kTION ALT. ADP IDENTIFII SIGN, SE LL. a z w U) m z_ 00 W U 0 W J H L) H PLAN 3. CHARACTERS AND NUMBERS ON SIGNS SHALL BE SIZED ACCORDING TO THE VIEWING DISTANCE FROM WHICH 5. ON THE WALL ADJACENT TO THE MEN'S AND WOMEN'S SANITARY FACILITIES BRAILLE SIGNAGE SHALL BE TION THEY ARE TO BE READ. THE MINIMUM HEIGHT IS MEASURED USING AN UPPER CASE X. LOWER CASE PROVIDED. LETTERS BE RAISED 1132", UPPER CASE AND ACCOMPANIED WITH GRADE 2 BRAILLE. RAISED CHARACTERS ARE PERMITTED. FOR SIGNS SUSPENDED OR PROJECTED ABOVE THE FINISH FLOOR THE MINIMUM CHARACTERS SHALL BE MINIMUM 518" HIGH, PICTOGRAMS MINIMUM 6" HIGH, CHARACTERS AND SYMBOLS SHALL CHARACTER HEIGHT SHALL BE 3". CONTRAST WITH THEIR BACKGROUND. THE SIGN SHALL BE LOCATED SO THAT A MINIMUM CLEAR FLOOR SPACE OF 18"X18", CENTERED ON THE TACTILE CHARACTERS, IS PROVIDED BEYOND THE ARC OF ANY DOOR SWING 4. CHARACTERS AND SYMBOLS SHALL CONTRAST WITH THEIR BACKGROUND, EITHER LIGHT CHARACTERS ON A BETWEEN THE CLOSED POSITION AND 45' OPEN POSITION. MOUNTING HEIGHT SHALL BE 60" ABOVE THE DARK BACKGROUND OR DARK CHARACTERS ON A LIGHT BACKGROUND. FINISHED FLOOR TO THE CENTER OF THE SIGN. Q 5. WHEN RAISED CHARACTERS OR SYMBOLS ARE USED, THEY SHALL CONFORM TO THE FOLLOWING: 6. WATER CLOSET COMPARTMENTS SHALL BE EQUIPPED WITH A DOOR THAT IS SELF CLOSING, AND SHALL HAVE A A. LETTERS AND NUMBERS ON SIGNS SHALL BE RAISED 1132" MINIMUM AND SHALL BE SANS -SERIF UPPERCASE CLEAR UNOBSTRUCTED OPENING WIDTH OF 32" WHEN LOCATED AT THE END AND 34" WHEN LOCATED AT THE CHARACTERS ACCOMPANIED BY GRADE 2 BRAILLE. SIDE WITH THE DOOR POSITIONED AT AN ANGLE OF 90 DEGREES FROM ITS CLOSED POSITION. B. RAISED CHARACTERS OR SYMBOLS SHALL BE A MINIMUM OF 518" HIGH. C. PICTORIAL SYMBOL SIGNS (PICTOGRAMS) SHALL BE ACCOMPANIED BY THE EQUIVALENT VERBAL DESCRIPTION TOILET ROOM FIXTURES AND ACCESSORIES PLACED DIRECTLY BELOW THE PICTOGRAM. THE BORDER DIMENSION OF THE PICTOGRAM SHALL BE A MINIMUM OF 6" IN HEIGHT. 1. TOILET FLUSH CONTROLS SHALL BE OPERABLE WITH ONE HAND, AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST. CONTROLS FOR THE FLUSH VALVES SHALL BE MOUNTED ON THE WIDE 6. CONTRACTED GRADE 2 BRAILLE SHALL BE USED WHEREVER BRAILLE SYMBOLS ARE SPECIFICALLY REQUIRED IN SIDE OF THE TOILET AREAS, NO MORE THAN 44" ABOVE THE FLOOR. THE FORCE REQUIRED TO ACTIVATE OTHER PORTIONS OF THESE REGULATIONS. DOTS SHALL BE .1" ON CENTERS IN EACH CELL WITH .3" SPACE CONTROLS SHALL BE NO GREATER THAN 5 POUNDS. BETWEEN CELLS. DOTS SHALL BE RAISED .3" ABOVE THE BACKGROUND. L OF TACTILE CHARACTERS 1 kTION ALT. ADP IDENTIFII SIGN, SE LL. a z w U) m z_ 00 W U 0 W J H L) H PLAN I` PREFFERED LOCATION OF ADA ROOM IDENTIFICATION SIGN RESTROOM go- LATCH SIDE OF DOOR - KICKPLATE ON BOTH SIDES ADA RESTROOM SIGNAGE 112" = 1'-O" ADA SIGN vr� MEN ] [ WOMEN ,fl. GRADE 2 BRAILLE ADA SIGNAGE NOTES 1. WHITE CHARACTERS AND SYMBOLS ON A CONTRASTING CHARCOAL GRAY BACKGROUND. IDENTIFICATION SYMBOLS ARE TO BE 2. DISTINCTLY DIFFERENT FROM THE DOOR IN COLOR AND CONTRAST. 3. PROVIDE ROOM IDENTIFICATION SIGN ON LATCH SIDE OF DOOR. ALTERNATE SIGN LOCATION OF NO ROOM LATCH SIDE, IS ADJACENT WALL OR ON PUSH SIDE OF DOOR WITH CLOSER AND WITHOUT HOLD OPEN DEVICE. 4. SIGNS CONTAINING TAC TILE CHARACTERS SHALL BE LOCATED SO THAT A CLEAR FLOOR SPACE OF 18"X18" MIN, CENTER LINE OF TACTILE CHARACTERS, IS PROVIDED BEYOND THE ARC OF ANY DOOR SWING BETWEEN THE CLOSED POSITION AND 450 OPEN POSITION. 5. LETTERS AND NUMBERS ON SIGNS SHALL BE RAISED 112" MIN. SHALL BE 518" MIN. HIGH AND SHALL BE SANS -SERIF UPPERCASE CHARACTERS ACCOMPANIED BY GRADE 2 BRAILLE. 6. ADA RESTROOM SIGNAGE - GC TO CONFIRM SPECIFICATION WITH CM AND DM PRIOR TO ORDERING/INSTALLING. 1 � ADA RESTROOM SIGNAGE SCALE: N.T.S THIS ARCHITECTURAL DRAWINGS IS GIVEN IN CONFIDENCE. NO USE OR DISSEMINATION MAY BE MADE WITH0UT PRIOR WRITTEN CONSENT OF THE AR"TECT. ALL COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HERBY SPECIFICALLY RESERVED. 06 VJrn LU W J J F- LU w ZLU LU z 0 I - a U U) LU a op Digitally signed by Joshua Michael Buono DN: E=jbuono.bac@gmail.com, CN=Joshua Michael Buono, S ERIALN U M B ER=AATL20240220337232, C=US Date: 2024.10.11 13:26:41-04'00' CHECKED BY: JMB DRAWN BY: JMB,JPB,SMB ISSUE DATE: 10110!2024 A002 ROOM / TION NOTE 3. f Q T I` PREFFERED LOCATION OF ADA ROOM IDENTIFICATION SIGN RESTROOM go- LATCH SIDE OF DOOR - KICKPLATE ON BOTH SIDES ADA RESTROOM SIGNAGE 112" = 1'-O" ADA SIGN vr� MEN ] [ WOMEN ,fl. GRADE 2 BRAILLE ADA SIGNAGE NOTES 1. WHITE CHARACTERS AND SYMBOLS ON A CONTRASTING CHARCOAL GRAY BACKGROUND. IDENTIFICATION SYMBOLS ARE TO BE 2. DISTINCTLY DIFFERENT FROM THE DOOR IN COLOR AND CONTRAST. 3. PROVIDE ROOM IDENTIFICATION SIGN ON LATCH SIDE OF DOOR. ALTERNATE SIGN LOCATION OF NO ROOM LATCH SIDE, IS ADJACENT WALL OR ON PUSH SIDE OF DOOR WITH CLOSER AND WITHOUT HOLD OPEN DEVICE. 4. SIGNS CONTAINING TAC TILE CHARACTERS SHALL BE LOCATED SO THAT A CLEAR FLOOR SPACE OF 18"X18" MIN, CENTER LINE OF TACTILE CHARACTERS, IS PROVIDED BEYOND THE ARC OF ANY DOOR SWING BETWEEN THE CLOSED POSITION AND 450 OPEN POSITION. 5. LETTERS AND NUMBERS ON SIGNS SHALL BE RAISED 112" MIN. SHALL BE 518" MIN. HIGH AND SHALL BE SANS -SERIF UPPERCASE CHARACTERS ACCOMPANIED BY GRADE 2 BRAILLE. 6. ADA RESTROOM SIGNAGE - GC TO CONFIRM SPECIFICATION WITH CM AND DM PRIOR TO ORDERING/INSTALLING. 1 � ADA RESTROOM SIGNAGE SCALE: N.T.S THIS ARCHITECTURAL DRAWINGS IS GIVEN IN CONFIDENCE. NO USE OR DISSEMINATION MAY BE MADE WITH0UT PRIOR WRITTEN CONSENT OF THE AR"TECT. ALL COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HERBY SPECIFICALLY RESERVED. 06 VJrn LU W J J F- LU w ZLU LU z 0 I - a U U) LU a op Digitally signed by Joshua Michael Buono DN: E=jbuono.bac@gmail.com, CN=Joshua Michael Buono, S ERIALN U M B ER=AATL20240220337232, C=US Date: 2024.10.11 13:26:41-04'00' CHECKED BY: JMB DRAWN BY: JMB,JPB,SMB ISSUE DATE: 10110!2024 A002 ABBREVIATIONS LEGEND SYMBOLS LEGEND 3 GENERAL CONDITIONS NOTES �GN►TECTQ P 4 A 1. PERMITS: CONTRACTOR 15 RESPONSIBLE FOR ALL PERMITS. ARCHITECT WILL SUPPORT THE PROCESS. �4 AFF ABOVE FINISHED FLOOR q ACT ACOUSTICAL CEILING TILE 1 �. r.` ) ALT ALTERNATE 2. QUALITY: CONTRACTOR SHALL PERFORM ALL WORK AND INSTALL ALL COMPONENTS INA PROFESSIONAL co -' ALUM ALUMINUM NORTH ARROW MANNER. ALL FINISH WORK TO BE TRUE, LEVEL AND PLUMB. ALL JOINTS TO BE TIGHT AND CLEAN. ;• yl� z APPROX APPROXIMATE(LY) ARCH ARCHITECT{URAL} 3, CODE COMPLIANCE: WORK SHALL CONFORM TO ALL APPLICABLE LOCAL, STATE, AND FEDERAL CODES 1. B VIEW NAME INCLUDING NFPA; AND USE TESTED AND CERTIFIED ASSEMBLIES, AS REQUIRED BY CODE. BLKG BLOCKING PLAN, DETAIL OR ELEVATION TITLE BLDG BUILDING_ , ��$„ _ „ 4. HANDICAP ACCESSIBILITY: CONTRACTOR SHALL COMPLY WITH ACCESSIBILITY GUIDELINES 36 GFR PART 1191 OF BD BOARD THE FEDERAL REGISTER, ITS REV IS10NS TO ANSI STANDARD A117.1, AND TITLE II10 F THE AMERICAN'S WITH DISABILITY ACT (ADA), AND LOCAL ORDINANCES C CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED y 5. WARRANTY: ALL CONSTRUCTION, MATERIALS, PRODUCTS AND WORK TO BE WARRANTED FOR A PERIOD OF ONE THIS ARCHITECTURAL DRAWINGS IS GIVEN IN C CENTERLINE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE CLIENT. CONFIDENCE. NO OR DISSEMINATION MAY BE MADE CLG CEILING wlTHaur RIrEN cONseNT PRIOR WR OF THE ARCH lTecr. CT CERAMIC TILEALL CLR CLEAR ,'� COLUMN LINE DESIGNATION 6, CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS. NO MEASUREMENTS SHALL BE SCALED FROM THE DRAWINGS. CONTRACTOR SHALL OBTAIN CLARIFICATION FROM ARCHITECT BEFORE PROCEEDING WITH CONSTRUCTION IF A OTHERWISE COMMON LAW RIGHTS OF COPYRIGHT ARE HERBY SPECIFICALLY AND RESERVED- CONC CONCRETE CONT CONTINUE, CONTINUOUS DIMENSION(S) IS IN QUESTION. CJ CONTROL JOINT CORR CORRIDOR 7. CONTRACTOR IS ADVISED THAT PORTIONS OF THIS DOCUMENT MAY BE BASED ON UNFIELD VERIFIED INFORMATION PROVIDED BY OTHERS IN ACCORDANCE WITH THE OWNERS DIRECTIONS. CONTRACTOR TO D DIA DIAMETER SIM BUILDING SECTION ADVISE ARCHITECT OF ANY EXISTING CONDITION DIFFERENT FROM THAT NOTED WHICH MAY IMPACT DIM DIMENSION(S) 1 DETAIL NUMBER CONSTRUCTION PRIOR TO EXECUTION. M {) SHEET NUMBER L1J E 8, DIMENSIONS AND NOTES ON ENLARGED PLANS AND DETAILS ARE TO OVERRULE SMALLER SCALE DRAWINGS. J FA EACH ELEC ELECTRIC(AL) ALL DIMENSIONS ARE TO FACE OF DRYWALL UNLESS NOTED OTHERWISE. ELEV ELEVATION EQ EQUAL SIM WALL SECTION 1 9. TURN OVER TO CLIENT OR SAVE FOR REUSE THE FOLLOWING ITEMS WHEN DISMANTLED: z J EQUIP EQUIPMENT EXP EXPANSION DETAIL NUMBER 101 A. DOORS, FRAMES, & DOOR HARDWARE AS INDICATED. U) Uj SHEET NUMBER B. THERMOSTATS. EJ EXPANSION )DINT EXIST EXISTING C. SUPPLY AND RETURN AIR GRILLES. U EXT EXTERIOR D. ADDITIONAL ITEMS INDICATED ON PLAN. 00 0 co E. EXISTING LIGHT FIXTURES INDICATED ON PLAN. F ^ DETAIL MARKS N N FIN FINISH(ED) FIN FLR FINISHED FLOOR S1M❑ETAIL NUMBER 10. CLEAN UP: REMOVE ALL DEBRIS, PACKING MATERIAL, DEMOLISHED MATERIAL, AND EXTRANEOUS TRASH a FE FIRE EXTINGUISHER iQ GENERATED BY CONSTRUCTION FROM BUILDING & SITE UNLESS NOTED, TO BE TURNED OVER TO OWNER. ALL LU FEC FIRE EXTINGUISHER CABINET sxEET NUMBER DEMOLISHED MATERIAL NOT TO BE TURNED OVER TO THE CLIENT SHALL BECOME THE PROPERTY OF GENERAL m ��// J J FLR FLOOR CONTRACTOR. L.L LL FD FLOOR DRAIN FLUOR FLUORESCENT ROOM NAME 1 NUMBER 11. BUILDING STANDARDS: ALL MATERIAL, HARDWARE, FIXTURES, AND FINISHES TO BE BUILDING STANDARD FRT FIRE -RETARDANT TREATED ROOM NAME ROOM NAME UNLESS NOTED OTHERWISE. BUILDING STANDARD INFORMATION IS AVAILABLE THROUGH THE TENANT'S U G ROOM REPRESENTATIVES, AND TYPICALLY MATCHES EXISTING INTERIOR CONSTRUCTION. GA GAUGE NUMBER s Z GYP BD GYPSUM BOARD 12. SITE VISIT; ALL GENERAL CONTRACTORS & SUBCONTRACTORS ARE TO VISIT SITE PRIOR TO COMPLETING BID TOrn Q m 4 VERIFY EXISTING CONDITION. GENERAL CONTRACTOR & SUBCONTRACTORS TO PROVIDE WRITTEN V J J H HCP HANDICAPPED EXTERIOR ELEVATION DOCUMENTATION OF ANY DISCREPANCY BETWEEN SITE CONDITIONS & DOCUMENTS. SUBMISSION OF BID IS U) 0 r� r HDW HARDWARE 1 <JA3 ELEVATION NUMBER CONFIRMATION THAT EXISTING CONDITIONS HAVE BEEN FULLY TAKEN INTO CONSIDERATION & ARE REFLECTED HT HEIGHT IN THE COSTS PROVIDED. W W HC HOLLOW CORE SHEET 2 NUMBER n r HM HOLLOW METAL HOR HORIZONTAL 13. CONTRACTOR TO PROVIDE OWNER WITH COPIES OF DELIVERY, AND CONSTRUCTION SCHEDULES. L.L 0 C HR HOUR 4 CONTRACTOR TO COORDINATE ALL SCHEDULES WITH OWNER. J J INTERIOR ELEVATION 1 14. IF EXTERIOR WINDOWS ARE BEING ENCLOSED CONTRACTOR IS TO CLEAN ALL WINDOWS, SHADES, CAVITY AREA 1JJZ 06 1 A101 3 ELEVATION NUMBER INCL INCLUDE(D) SHEET NUMBER FROM CONSTRUCTION DUST AND DEBRIS PRIOR TO ENCLOSING EXTERIOR WINDOWS. INSUL INSULATION INT INTERIOR 2 15. CUTTING & PATCHING: CONTRACTOR TO PATCH, REPAIR, & REFINISH WORK DAMAGED AS A RESULT OF F _ _^Uj = ¢ rV1 J1 DEMOLITION OR REMOVAL OF CONSTRUCTION TO MATCH ADJACENT FINISH. PATCH THRU-WALL1 THRU-FLOOR 0 JT JOINT DETAIL REFERENCE PENETRATIONS TO MAINTAIN EXISTING BUILDING INTEGRITY. L.L SI 1 DETAIL NUMBER + Uj L LAM LAMINATE 101 SHEET NUMBER 16. ALL NEW CONCRETE FLOORING SECTIONS TO BE DOWELED AND PINNED TO EXISTING CONCRETE SLAB WITH A Z W MINIMUM MINIMUM OF 12 " MAX MAXIMUM AREA OF DETAIL � F I Fj MECH MECHANICAL 17. ALL ROOF WORK TO BE COMPLETED BY CLIENT'S APPROVED ROOFING CONTRACTOR A� i . [`�] W MEP MECHANICAL, ELECTRICAL, AND PLUMBING EXISTING CONSTRUCTION TO 18. CONTRACTOR TO MAINTAIN CLEAR ACCESS TO ALL DRIVE & ENTRANCES WHILE ON SITE. MEPFP MECHANICAL, ELECTRICAL, PLUMBING REMAIN AND FIRE PROTECTION MTL METAL j j EXISTING ❑ppR TO REMAIN AND 19. CONTRACTOR TO STORE & INSTALL AS NECESSARY ANY OWNER -PROVIDED EQUIPMENT. REFER TO MIN MINIMUM TAG DOCUMENTS FOR FURTHER DETAIL. MISC MISCELLANEOUS EXISTING CONSTRUCTION TO BE 20. EXISTING CONDITIONS DOCUMENTS PROVIDED FOR REFERENCE ONLY. ANY WORK INDICATED HAS ALREADY N REMOVED BEEN COMPLETED. NIC NOT IN CONTRACT EXISTING DOOR TO BE NTS NOT TO SCALE REMOVED 21. ALL AREAS MUST BE COMPLETELY CLEAN & CLEAR OF ANY CONSTRUCTION MATERIALS AT THE END OF THE ❑ WORK DAY. OFCI OWNER FURNISHED, NEW CONSTRUCTION CONTRACTOR INSTALLED 22. WOOD DOORS: REFER TO DOCUMENTS FOR FURTHER DETAIL. OFOI OWNER FURNISHED, 101 NEW DOOR AND TAG Z OWNER INSTALLED 0 Oc ON CENTER 23. METAL DOORS: REFER TO DOCUMENTS FOR FURTHER DETAIL, OH OPPOSITE HAND OPG OPENING EXISTING PARTITIONS 24. FRAMES: REFER TO DOCUMENTS FOR FURTHER DETAIL. OPP OPPOSITE OSB ORIENTED STRAND BOARD EXISTING PARTITIONS TO BE REMOVED 25. HARDWARE STANDARD: PROVIDE DOOR HARDWARE IN ACCORDANCE W/ SCHEDULE. ALL LOCKSET/LATCHSET Lu P HARDWARE COMPLY WITITLE III OF AMERICANS WITH DISABILITIES ACT (ADA). GENERAL CONTRACTOR TO PLAM PLASTIC LAMINATE NEW PARTITIONS (REF PARTITION COORDINATE KEYING WITH OWNER REPRESENTATIVE. PT PAINT(ED) SHEET) PTN PARTITION NEW PARTITIONS WI R-11 SOUND BATT 26. DRYWALL: REFER TO PARTITION DETAILS FOR FURTHER INFORMATION. PWD PLYWOOD Q COOLER 1 FREEZER WALL 27. PAINT: PROVIDE 2 COATS OF ALKYD SEMI -GLOSS ENAMEL FINISH COLOR ON METAL DOORS & FRAMES AS aTy QUANTITY INDICATED ON DRAWINGS. 112 HEIGHT WALL (HEIGHT VARIES) R REF REFERENCE 28. PAINT: PROVIDE 2 COATS OF PREMIUM PAINT, EGGSHELL FINISH COLOR ON ALL NEW SURFACES AS INDICATED REINF REINFORCE(D) }( KEYED NOTE ON DRAWINGS. PRIME NEW/EXISTING SURFACES & PATCH AS REQUIRED. W REQ REQUIRED REV REVISION 29. SOUND BATT INSULATION (WALLS ONLY): SHALL BE UNFACED GLASS FIBER ACOUSTICAL INSULATION RB RESILIENT BASE COMPLYING WITH ASTM C665, TYPE 1, SIZED AS INDICATED IN DETAILS. MAXIMUM FLAME SPREAD: 10, STC S ABOVE 55. SAB SOUND ATTENUATION BATTS 2a REVISION CLOUD AND TAG m SC SOLID CORE 30. SOUND ATTENUATION (ABOVE CEILINGS) SHALL BE 3" UNFACED, LIGHTWEIGHT, RESILIENT FIBERGLASS z SF SQUARE FOOT [FEET] REVISION NUMBER AREA OF REVISION DESIGNED TO ABSORB SOUND AND SPECIFICALLY MANUFACTURED FOR USE ABOVE CEILINGS. MAXIMUM FLAME 51M SIMILAR SPREAD: 25 STC ABOVE 55. NO SOUND ATTENUATION INSULATION IS TO BE USED ABOVE FINISHED CEILING IN SLNT SEALANT SPEC SPECIFICATION lt� WINDOW NUMBER SYMBOL FOOD PREPARATION AREAS. REVISIONS SQ SQUARE L_1 SQ FT SQUARE FOOT (FEET) 31. ALL FLOORING PRODUCTS TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS & PERMIT SET SS, SSTL STAINLESS STEEL STL STEEL SPECIFICATIONS. CONTRACTOR IS RESPONSIBLE FOR ALL FLOOR LEVELING THAT MAY BE REQUIRED IN ORDER TO COMPLY WITH PROPER INSTALLATION PROCEDURE. 1i WALL PARTITION TYPE SUSP SUSPENDED] SYM SYMMETRICAL 32. HVAC: REFERENCE MECH. DOCUMENTS FOR INFORMATION AND LAYOUT. G.C. IS RESPONSIBLE FOR T SCHEDULING AND PROVIDING A TEST AND BALANCE REPORT TO THE CLIENT PRIOR TO TURNOVER. GC SHALL TEL TELEPHONE USE AN AABC OR NEBB INDEPENDENT THIRD PARTY AIR BALANCE COMPANY. THE REPORT SHALL BE AVAILABLE TEMP TEMPERED ON JOB SITE PRIOR TO FINAL INSPECTION. TOS TOP OF STRUCTURE Tow TOP OF WALL TYP TYPICAL 33. PLUMBING: FIXTURES LOCATED ON ARCHITECTURAL SHEETS FOR GENERAL REFERENCE ONLY. REFER TO PLUMBING SHEETS FOR ROUGH -IN DETAILS_ U UL UNDERWRITERS LABORATORIES, INC. 34. ALL ELECTRICAL RECEPTACLES TO BE MOUNTED AT MIN. 18" A.F.F. U.N.O. TO CENTERLINE. ALL LIGHT SWITCHES UNO UNLESS NOTED OTHERWISE AND THERMOSTATS TO BE MOUNTED AT 48" A.F.F. TO CENTERLINE. v VERT VERTICAL 35, ELECTRICAL, DATA, AND COMMUNICATIONS OUTLETS ARE PROVIDED FOR REFERENCE ONLY. REFERENCE ELEC. DOCUMENTS FOR ADDITIONAL ELECTRICAL INFORMATION ON SWITCHING, ADDITIONAL OUTLETS, EQUIPMENT w ROOM REQUIREMENTS, ETC, WC WALL COVERING W1 WITH WIO WITHOUT WD WOOD Digitally signed by Joshua Michael Buono DN: E=jbuono.bac@gmail.com, CN=Joshua Michael Buono, SERIALNUMBER=AATL20240220337232, C=US Date: 2024.10.11 13:26:20-04'00' CHECKED BY: JMB DRAWN BY: JMB,JPB,SMB ISSUE DATE: 10/10/2024 A003 APPLICABLE BUILDING CODES 4 SCALE: NOT TO SCALE �G�1ITECr[ljp� P �a BUILDING CODE FLORIDA BUILDING CODE (FBC) 2023 �Q PLUMBING CODE FLORIDA PLUMBING CODE (FBC) 2023 J ELECTRICAL CODE NATIONAL ELECTRIC CODE (MECO) 2020 G7 co GM1 Y z MECHANICAL CODE FLORIDA MECHANICAL CODE (FBC) 2023 EXISTING WATER HEATER ENERGY CODE FLORIDA ENERGY CODE (FBC) 2023 FIRE CODE NFPA LIFE SAFTY CODE NFPA 101, 2023 pop EXISTING EXIST SIGN FLORIDA FIRE PREVENTION CODE (FFPC) 2023 EXISTING ELECTRICAL ACCESSIBILITY CODE FLORIDA ACCESSIBILITY CODE (ADA) 2023 PANEL BUILDING INFORMATIONARCH EXISTING FIRE 5 EXTINGUISHER SCALE: NOT TO SCALE CON CONFIDENCE. CONFIl7ENCE. WITHOUT NO U L OR DISSEMINATION 7V0 USE OR OISSEMINAtIQN PRIOR WRITTEN CONSENT IS GIVEN M MAY BE MADE OF THE ARCHITECT. CONSTRUCTION TYPE TYPE II - B ALL OTHERWISE COMMON LAW RIGHTS OF ARE HERBY SPECIFICALLY COPYRIGHT AND RESERVED. SPRINKLERED BUILDING IS NON-SPRINKLERED L E G E N D S TRAVEL DISTANCE - 10'0" E; SCALE .NOT TO SCALE � 01 MERCANTILE AREA'0.0 W AREA: 964 SQ.FT, J ALLOWABLE AREA SCALE: NOT TO SCALE 0 J w J U) PER 2023 IBC 1030.7 o v TRAVEL DISTANCE - 21`5" PRIMARY OCCUPANCY M 1 MERCANTILE Z CY7 ■ MAXIMUM ALLOWABLE BUILDING AREA 964 SQ.FT. • O co TRAVEL DISTANCE 75 FT ALLOWED (NON -SPRINKLED) 42'4" FT ACTUAL LU 8 OCCUPANT LOAD m � J LL m SCALE: NOT TO SCALE U iL OCCUPANT LOAD COUNT TABLE PER 2023 FBC TABLE 1004.5 U Q FUNCTION OF SPACE OCCUPANT AREA (SQ.FT.) OCCUPANTS ' LOAD FACTOR � , Z W Q n m TRAVEL DISTANCE - 357" , MERCANTILE UNCONCENTRATED 0 60 17 7 LrnL TOTAL INTERIOR OCCUPANTS: 1 i' < O Q ■� • EXIT REQUIREMENTS _ _ r Z TRAVEL DISTANCE -42'4" ------- -- SCALE NOT TO SCALE >__ ' PER 2023 FBC IL r y LONGEST INTERIOR DIAGONAL DIMENSION 631-811�j I­_LJJ IJ MIN. DISTANCE BETWEEN DOORWAYS (NON -SPRINKLED) 31'-10" LU r ACTUAL DISTANCE BETWEEN CLOSEST DOORWAYS 59'-61, ! ALLOWABLE EGRESS WIDTH SCALE: NOT TO SCALE W r PER 2023 FBC LL aft OCCUPANTS FACTOR (IN.) (IN.) INTERIOR NON -SPRINKLER SYSTEM 17 .20 3.4 _ 0 r EXTERIOR PATIO SPACE W/OUT SPRINKLER SYSTEM - - - TRAVEL DISTANCE - 32`3" 1co MINIMUM EGRESS OPENING WIDTH REQUIRED 31.75 ! MINIMUM DOOR SIZE CLEAR OPENING 32 MAIN EXIT (IN.) SECONDARY TOTAL (IN.) N ' _ ❑ I ) _�jf ACTUAL EGRESS OPENING WIDTH PROVIDED 36 36 72 z� r ti o PLUMBING CALCULATIONS �� z o 1 ■ � � ALE TO SCALE SC � .NOT ' ■Q PER 2023 FLORIDA PLUMBING CODE U) ! BUILDING OCCUPANCY (TOTAL) 17 � CI] � TOTAL MEN/WOMEN 17 1 WATER CLOSETS LAVATORIES OTHER cq ■ ! MALE FEMALE MALE FEMALE 1 ■ MERCANTILE 1:500 1:750 1 SERVICESINK REQUIRED 1 1 1 ! PROVIDED 1 1 1 r 1 Lu ■ 1 } m ' r o . REVISIONS . r EXISTING EXIST SIGN l PERMIT SET 1 Ir ■ Digitally signed by Joshua Michael Buono DN: E=jbuono.bac@gmail.com, CN=Joshua Michael Buono, S E RIALN U M BER=AATL20240220337232, C=US Date: 2024.10.11 13:25:59-04'00' CHECKED BY: JMB DRAWN BY: JMB,JPB,SMB ISSUE DATE: 10/1012024 A004 E SAFETY PLAN LS�IFALE: rr_ 'Ir0rr 1/4 - GC TO ROUTE NEW LINES FROM EXISTING LINES AND SYSTEMS TO PROVIDE REQUIRED SERVICE. GC TO INSTALL NEW PLUMBING FOR SINK AND REFRIDGERATOR PER CODE GC TO INSTALL NEW ELECTRIC OUTLETS TO EXISTING PANEL PER CODE H� EXISTING GLASS STORE FRONT TO REMAIN GC TO INSTALL ALL ELECTRICAL OUTLETS NEAR SINK WITH GFI PER CODE GC TO COORDINATE WITH CLIENT FOR CABINET STYLE AND SPACING X11 II II GC TO COORDINATE WITH CLIENT FOR REFRIGERATOR AND SPACING ELEVATION - STORE FRONT 7 ELEVATION - KITCHENETTE SCALE: 3/8 - 1'011 SCALE: 3/8 - 1'011 Z� ❑ Uj C� C) I- F �0 7 EXISTING GLASS STORE FRONT TO REMAIN GC TO INSTALL ALL ELECTRICAL OUTLETS NEAR SINK WITH GFI PER CODE GC TO COORDINATE WITH CLIENT FOR CABINET STYLE AND SPACING X11 II II GC TO COORDINATE WITH CLIENT FOR REFRIGERATOR AND SPACING R 13 BATT INSULATION TYP. IN ALL WALLS. r9W GYP. BOARD TVP. UNLESS OTHERWISE NOTED. W GYP. SOARD TYP-UNLESS OTHERWISE NOTED. 2 X a WOOD STUD HEADER WI 117 PLY SPACER AS NEEDED WOODEN DOOR TRIWCASING STANDARD DOUBLE RABBET WOODEN DOOR FRAME W1 SHIMS TO BE INSTALLED PER MFG. SPEC. WOODEN DOOR TRIMI CASING RUBBER GASKET SILENCER. TYP ON ALL DOORS. HOLLOW CORE WOOD rNT. DOOR. GC TO COORDINATE WITH CL IE NT FOR HARDWARE - OL LOW ARDWARE. OLLOW CORE WOOD INT. DOOR IN 2 x 4 WOOD STUD CONSTRUCTION WITH 5f3 GYP. 80A R G FI NISH EA. SIDE 23 HEADER SCALE: 111/2"=110" 51B' GYP. BOARD TYP. UNLESS OTHERWISE NOTED. SV GYP BOARD TYP. UNLESS OTHERWISE NOTED R 13 BATT ASULATICN TYP. IN ALL WALLS. WOODEN DOOR TRIWCASING DOUBLE 2X4 WOOD STUD JVQ- STANDARD DOUBLE RABBET WOODEN DOOR FRAME W! SHIMS TO BE INST%LED PER MFG. SPEC. WOODEN DOOR T RIMrCASI NG HOLLOW CORE WOOD INT. DOOR. GC TO COORDI NATE WITH CU ENT FOR HARDWARE. HOLLOW CORE WOODINT. DOOR IN 2 %4 WOOD STUD CONSTRUCTION WITH M GYP. BOARD FINISH EA. SIDE. JAMB ,I,_ 1 11 4 CALE.1112-1� HOLLOW CORE YIOOD rNT. DOOR. GC TO COORDINATE WITH CLIENT FOR HARDWARE.. HOLLCW CORE WOOD INT. DOOR IN 2 X 4 WOOD STUD CON STRUCTrON WITH 515 GYP. BOARD FINISH EA. SIDE. REPRE SENTATIONAL FLOOR SYSTEM ON FIR$T FLOOR SLOPE CONCRETE AWAYFROM DOOR TO PREVENT WATER INFILTRATION. SILL 116 CALE . 1'1/2"=1'0 I112}I-1,0 0 0 GC TO REPAIR DAMAGED TILE, AS NEEDED REPAIR DETAILS SCALE :11411 = 11011 CJ\ GC TO REPAIR LIGHTS, AS NEEDED GC TO REPAIR HVAC VENT, AS NEEDED GC TO REPAIR CEILING TILES, AS NEEDED GC TO REPAIR DAMAGED TILE AS NEEDED 5GENERAL NOTES SCALE . NOT TO SCALE 1. DIMENSIONS ARE FROM FACE OF STUD TO FACE OF STUD UNLESS OTHERWISE NOTED. 2. ALL ANGLES ARE ASSUMED TO BE AT A 45' ANGLE UNLESS OTHERWISE NOTED. 3. ABBREVIATIONS ARE REFERENCED FROM VERSION 3.1 OF THE US NATIONAL CAD STANDARDS 4. LARGE DASHED LINES REPRESENT ITEMS OF IMPORTANCE LOCATED ABOVE THE CUT PLANE (I.E. ROOF LINE) 5. SMALL DASHED LINES REPRESENT ITEMS THAT ARE SIGNIFYING CLEAR FLOOR SPACES OR ARCHITECTURAL MILLWORK NOT IMMEDIATELY CUT BY THE CUT PLANE. 6. IF A DISCREPANCY IS FOUND OR INFORMATION IS NOT SUFFICIENT TO COMPLETE THE SCOPE OF WORK, THE GC IS TO SUBMIT A FORMAL RFI FOR REVIEW AND RESPONSE. 7. SEE SHEET A002 FOR ADA PLACEMENT AND REQUIREMENTS 8. SEE SHEET A700 FOR EQUIPMENT FINISH SCHEDULE 6 LEGEND SCALE:NOT EXISTING CEILING TO REMAIN ELEVATION - STORE FRONT 7 ELEVATION - KITCHENETTE SCALE: 3/8 - 1'011 SCALE: 3/8 - 1'011 R 13 BATT INSULATION TYP. IN ALL WALLS. r9W GYP. BOARD TVP. UNLESS OTHERWISE NOTED. W GYP. SOARD TYP-UNLESS OTHERWISE NOTED. 2 X a WOOD STUD HEADER WI 117 PLY SPACER AS NEEDED WOODEN DOOR TRIWCASING STANDARD DOUBLE RABBET WOODEN DOOR FRAME W1 SHIMS TO BE INSTALLED PER MFG. SPEC. WOODEN DOOR TRIMI CASING RUBBER GASKET SILENCER. TYP ON ALL DOORS. HOLLOW CORE WOOD rNT. DOOR. GC TO COORDINATE WITH CL IE NT FOR HARDWARE - OL LOW ARDWARE. OLLOW CORE WOOD INT. DOOR IN 2 x 4 WOOD STUD CONSTRUCTION WITH 5f3 GYP. 80A R G FI NISH EA. SIDE 23 HEADER SCALE: 111/2"=110" 51B' GYP. BOARD TYP. UNLESS OTHERWISE NOTED. SV GYP BOARD TYP. UNLESS OTHERWISE NOTED R 13 BATT ASULATICN TYP. IN ALL WALLS. WOODEN DOOR TRIWCASING DOUBLE 2X4 WOOD STUD JVQ- STANDARD DOUBLE RABBET WOODEN DOOR FRAME W! SHIMS TO BE INST%LED PER MFG. SPEC. WOODEN DOOR T RIMrCASI NG HOLLOW CORE WOOD INT. DOOR. GC TO COORDI NATE WITH CU ENT FOR HARDWARE. HOLLOW CORE WOODINT. DOOR IN 2 %4 WOOD STUD CONSTRUCTION WITH M GYP. BOARD FINISH EA. SIDE. JAMB ,I,_ 1 11 4 CALE.1112-1� HOLLOW CORE YIOOD rNT. DOOR. GC TO COORDINATE WITH CLIENT FOR HARDWARE.. HOLLCW CORE WOOD INT. DOOR IN 2 X 4 WOOD STUD CON STRUCTrON WITH 515 GYP. BOARD FINISH EA. SIDE. REPRE SENTATIONAL FLOOR SYSTEM ON FIR$T FLOOR SLOPE CONCRETE AWAYFROM DOOR TO PREVENT WATER INFILTRATION. SILL 116 CALE . 1'1/2"=1'0 I112}I-1,0 0 0 GC TO REPAIR DAMAGED TILE, AS NEEDED REPAIR DETAILS SCALE :11411 = 11011 CJ\ GC TO REPAIR LIGHTS, AS NEEDED GC TO REPAIR HVAC VENT, AS NEEDED GC TO REPAIR CEILING TILES, AS NEEDED GC TO REPAIR DAMAGED TILE AS NEEDED 5GENERAL NOTES SCALE . NOT TO SCALE 1. DIMENSIONS ARE FROM FACE OF STUD TO FACE OF STUD UNLESS OTHERWISE NOTED. 2. ALL ANGLES ARE ASSUMED TO BE AT A 45' ANGLE UNLESS OTHERWISE NOTED. 3. ABBREVIATIONS ARE REFERENCED FROM VERSION 3.1 OF THE US NATIONAL CAD STANDARDS 4. LARGE DASHED LINES REPRESENT ITEMS OF IMPORTANCE LOCATED ABOVE THE CUT PLANE (I.E. ROOF LINE) 5. SMALL DASHED LINES REPRESENT ITEMS THAT ARE SIGNIFYING CLEAR FLOOR SPACES OR ARCHITECTURAL MILLWORK NOT IMMEDIATELY CUT BY THE CUT PLANE. 6. IF A DISCREPANCY IS FOUND OR INFORMATION IS NOT SUFFICIENT TO COMPLETE THE SCOPE OF WORK, THE GC IS TO SUBMIT A FORMAL RFI FOR REVIEW AND RESPONSE. 7. SEE SHEET A002 FOR ADA PLACEMENT AND REQUIREMENTS 8. SEE SHEET A700 FOR EQUIPMENT FINISH SCHEDULE 6 LEGEND SCALE:NOT EXISTING CEILING TO REMAIN DEMENSIONED FLOOR PLAN SCALE: 114 = 1 R 13 BATT INSULATION TYP. IN ALL WALLS. r9W GYP. BOARD TVP. UNLESS OTHERWISE NOTED. W GYP. SOARD TYP-UNLESS OTHERWISE NOTED. 2 X a WOOD STUD HEADER WI 117 PLY SPACER AS NEEDED WOODEN DOOR TRIWCASING STANDARD DOUBLE RABBET WOODEN DOOR FRAME W1 SHIMS TO BE INSTALLED PER MFG. SPEC. WOODEN DOOR TRIMI CASING RUBBER GASKET SILENCER. TYP ON ALL DOORS. HOLLOW CORE WOOD rNT. DOOR. GC TO COORDINATE WITH CL IE NT FOR HARDWARE - OL LOW ARDWARE. OLLOW CORE WOOD INT. DOOR IN 2 x 4 WOOD STUD CONSTRUCTION WITH 5f3 GYP. 80A R G FI NISH EA. SIDE 23 HEADER SCALE: 111/2"=110" 51B' GYP. BOARD TYP. UNLESS OTHERWISE NOTED. SV GYP BOARD TYP. UNLESS OTHERWISE NOTED R 13 BATT ASULATICN TYP. IN ALL WALLS. WOODEN DOOR TRIWCASING DOUBLE 2X4 WOOD STUD JVQ- STANDARD DOUBLE RABBET WOODEN DOOR FRAME W! SHIMS TO BE INST%LED PER MFG. SPEC. WOODEN DOOR T RIMrCASI NG HOLLOW CORE WOOD INT. DOOR. GC TO COORDI NATE WITH CU ENT FOR HARDWARE. HOLLOW CORE WOODINT. DOOR IN 2 %4 WOOD STUD CONSTRUCTION WITH M GYP. BOARD FINISH EA. SIDE. JAMB ,I,_ 1 11 4 CALE.1112-1� HOLLOW CORE YIOOD rNT. DOOR. GC TO COORDINATE WITH CLIENT FOR HARDWARE.. HOLLCW CORE WOOD INT. DOOR IN 2 X 4 WOOD STUD CON STRUCTrON WITH 515 GYP. BOARD FINISH EA. SIDE. REPRE SENTATIONAL FLOOR SYSTEM ON FIR$T FLOOR SLOPE CONCRETE AWAYFROM DOOR TO PREVENT WATER INFILTRATION. SILL 116 CALE . 1'1/2"=1'0 I112}I-1,0 0 0 GC TO REPAIR DAMAGED TILE, AS NEEDED REPAIR DETAILS SCALE :11411 = 11011 CJ\ GC TO REPAIR LIGHTS, AS NEEDED GC TO REPAIR HVAC VENT, AS NEEDED GC TO REPAIR CEILING TILES, AS NEEDED GC TO REPAIR DAMAGED TILE AS NEEDED 5GENERAL NOTES SCALE . NOT TO SCALE 1. DIMENSIONS ARE FROM FACE OF STUD TO FACE OF STUD UNLESS OTHERWISE NOTED. 2. ALL ANGLES ARE ASSUMED TO BE AT A 45' ANGLE UNLESS OTHERWISE NOTED. 3. ABBREVIATIONS ARE REFERENCED FROM VERSION 3.1 OF THE US NATIONAL CAD STANDARDS 4. LARGE DASHED LINES REPRESENT ITEMS OF IMPORTANCE LOCATED ABOVE THE CUT PLANE (I.E. ROOF LINE) 5. SMALL DASHED LINES REPRESENT ITEMS THAT ARE SIGNIFYING CLEAR FLOOR SPACES OR ARCHITECTURAL MILLWORK NOT IMMEDIATELY CUT BY THE CUT PLANE. 6. IF A DISCREPANCY IS FOUND OR INFORMATION IS NOT SUFFICIENT TO COMPLETE THE SCOPE OF WORK, THE GC IS TO SUBMIT A FORMAL RFI FOR REVIEW AND RESPONSE. 7. SEE SHEET A002 FOR ADA PLACEMENT AND REQUIREMENTS 8. SEE SHEET A700 FOR EQUIPMENT FINISH SCHEDULE 6 LEGEND SCALE:NOT EXISTING CEILING TO REMAIN 0 1 1 A#I## 1 1 ELEVATION CALL OUT GC TO DEMO UTILITY SINK AND ALL PLUMBING ID GC TO DEMO UTILITY SINK AND ALL PLUMBING DEMO DETIALS SCALE: 111 11011 SECTION CALL OUT NOTES �1 KEYED NOTE DOOR TAG L1 WINDOW TAG FINISH TAG E1 EOUIPMENT TAG THIS ARCHITECTURAL DRAWINGS IS GIVEN IN CONFIDENCE. NO USE OR DISSEMINATION MAY BE MADE WITHOUT PRIOR WRI'T'TEN CONSENT OF THE ARCHITECT. ALL CGMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HERBY SPECIFICALLY RESERVED. WALL SECTION 11 _ , 11 SCALE.1 -1a 0 1 1 A#I## 1 1 ELEVATION CALL OUT GC TO DEMO UTILITY SINK AND ALL PLUMBING ID GC TO DEMO UTILITY SINK AND ALL PLUMBING DEMO DETIALS SCALE: 111 11011 SECTION CALL OUT NOTES �1 KEYED NOTE DOOR TAG L1 WINDOW TAG FINISH TAG E1 EOUIPMENT TAG THIS ARCHITECTURAL DRAWINGS IS GIVEN IN CONFIDENCE. NO USE OR DISSEMINATION MAY BE MADE WITHOUT PRIOR WRI'T'TEN CONSENT OF THE ARCHITECT. ALL CGMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HERBY SPECIFICALLY RESERVED. z 0 F_ a Of C) w J W ❑ co 0 co CSI 0 co W > _J m U_ Q U Z Q n w m rI..L VJ V r I Q Digitally signed by Joshua Michael Buono DN: E=jbuono.bac@gmail.com, CN=Joshua Michael Buono, S ERIALN U M B E R=AATL20240220337232, C=US Date: 2024.10.11 13:25:39-04'00' CHECKED BY: JMB DRAWN BY: JMB,JPB,SMB ISSUE DATE: 10110l2D24 A3oo U) _j Z� ❑ Uj LU J J C) I- F w _+ I1J gym■ 1� = � 7 L 0 rU �J rW V ) z 0 F_ a Of C) w J W ❑ co 0 co CSI 0 co W > _J m U_ Q U Z Q n w m rI..L VJ V r I Q Digitally signed by Joshua Michael Buono DN: E=jbuono.bac@gmail.com, CN=Joshua Michael Buono, S ERIALN U M B E R=AATL20240220337232, C=US Date: 2024.10.11 13:25:39-04'00' CHECKED BY: JMB DRAWN BY: JMB,JPB,SMB ISSUE DATE: 10110l2D24 A3oo