893 AMBERJACK LN RES24-0285 ARCH DWGS 1-15-25ABBREVIATIONS
& AND
ANGLE
@ AT
C CENTERLINE
CHANNEL
Ø DIAMETER
# NUMBER, POUND(S)
AC AIR CONDITIONING
ACB ACOUSTICAL BAFFLE
ACM ARHITECTURAL CONCRETE MASONRY
ACOUS ACOUSTIC(AL)
ACP ACOUSTICAL CEILING PANEL
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADJ ADJUSTABLE/ADJACENT
ADR ACCESS DOOR
AFF ABOVE FINISH FLOOR
ANC ANCHOR
AHU AIR HANDLING UNIT
AL/ALUM ALUMINUM
ALT ALTERNATE
ANNUN ANNUNCIATOR
ANOD ANODIZED
AP ACCESS PANEL
APC ARCHITECTURAL PRECAST CONCRETE
APPROX APPROXIMATE(LY)
ARCH ARCHITECT(URAL)
ARGWB ABUSE RESISTANT GYPSUM WALL BOARD
AVG AVERAGE
AWP ACOUSTIC WALL PANEL
BC BOTTOM OF CURB
BD BOARD
BITUM BITUMINOUS
BLDG BUILDING
BLK BLOCK
BLKBD BLACK BOARD
BLKG BLOCKING
BLKHD BULKHEAD
BM BEAM
BOT BOTTOM
BRG PL BEARING PLATE
BRG BEARING
BRK BRICK
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT UP ROOFING
C COURSE(S) / CARPET
CAB CABINET
CBB CEMENTITIOUS BACKER BOARD
CEM CEMENT
CER CERAMIC
CI CAST IRON
CIF CHANGE IN FLOORING
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLKG CAULKING
CLL CONTRACT LIMIT LINE
CLO CLOSET
CLR CLEAR
CM CONSTRUCTION MANAGER
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CLEAN OUT
COL COLUMN
COMB COMBINATION
COMP COMPACT(ED)
CONC CONCRETE
CONSTR CONSTRUCTION
CONT CONTINUOUS
COP COPPER
CORR CORRIDOR
CPT CARPET
CRFS COLD ROLLED FORMED STEEL
CS LINT CAST STONE LINTEL
CS CAST STONE
CT CERAMIC TILE
CTR CENTER
CU CUSPIDOR
CW COLD WATER
CWS CURTAIN WALL SYSTEM
D DEEP/DEPTH/DRAIN
DB DECIBEL
DBL DOUBLE
DEMO DEMOLITION
DET DETAIL
DF DRINKING FOUNTAIN
DH DOUBLE HUNG
DIA DIAMETER
DIAG DIAGONAL(LY)
DIM DIMENSION
DISP DISPENSER
DIV DIVISION
DMPF DAMPROOFING
DN DOWN
DR DOOR
DS DOWNSPOUT/DIVIDER STRIP
DSP DRY STANDPIPE
DW DISTILLED WATER
DSWR DISHWASHER
DWG DRAWING
DWR DRAWER
E EAST
EA EACH
EEW EMERGENCY EYE WASH
EIFS EXTERIOR INSULATION
& FINISHING SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC(AL)
EMERG EMERGENCY
EMR ELEVATOR MACHINE ROOM
ELEV ELEVATOR
ENG ENGINEER
ENCL ENCLOSURE
ENT ENTRANCE
EOS EDGE OF SLAB
EPB ELECTRICAL PANEL BOARD
EQ EQUAL
EQUIP EQUIPMENT
ES EXPOSED STRUCTURE
EV EXHAUST VENT
EWC ELECTRIC WATER COOLER
EXP EXPANED/EXPANSION
EXST EXISTING
EXT EXTERIOR
EXTR EXTRUDED
F FAHRENHEIT
FA FIRE ALARM/GAUGE
FCU FAN COIL UNIT
FD FLOOR DRAIN/FIRE DAMPER
FDN FOUNDATION
FDV FIRE DEPARTMENT VALVE
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FACE
FFE FINISH FLOOR ELEVATION
FHC FIRE HOSE CABINET
FHVC FIRE HOSE VALVE CABINET
FHMS FLAT HEAD MACHINE SCREW
FHS FLAT HEAD SCREW
FHWS FLAT HEAD WOOD SCREW
FIN FINISH
FL FLASHING
FLEX FLEXIBLE
FLG FLOORING
FLR FLOOR
FLUOR FLUORESCENT
FO FACE OF
FOS FACE OF STUD/SLAB/STRUCTURE
FRPF FIREPROOF(ING)
FS FULL SIZE/FLOOR SINK
FT FOOT OR FEET
FTG FOOTING
FURR FURRING
FVC FIRE VALVE CABINET
FXTR FIXTURE
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GCMU GLAZED CMU
GEN GENERAL
GFCMU GROUND FACE CMU
GL GLASS/GLAZING
GND GROUND
GR GRADE
GV GAS VENT
GWB GYPSUM WALL BOARD
GYP GYPSUM
H HIGH
HT HEIGHT
HB HOSE BIB
HC HOLLOW CORE
HDCP HANDICAP(PED)
HDWD HARDWOOD
HDWE HARDWARE
HK HOUSEKEEPING
HM HOLLOW METAL
HMF HOLLOW METAL FRAME
HORIZ HORIZONTAL(LY)
HPT HIGH POINT
HR HOUR
HTG HEATING
HVAC HEATING/VENTILATION/AIR CONDITIONING
HW HOT WATER
ICCMU INTEGRALLY COLORED CMU
ID INSIDE DIAMETER
IN INCH
INCAND INCANDESCENT
INSUL INSULATION
INT INTERIOR
INTRM INTERMEDIATE
INV INVERT
JAN JANITOR
JST JOIST
JT JOINT
KD KNOCKED DOWN
KIT KITCHEN
KO KNOCK OUT
KP KICK PLATE
L LONG/LENGTH
LAB LABORATORY
LAM LAMINATE(D)
LAV LAVATORY
LB(S) POUND(S)
LC LEAD COATED
LCKR LOCKER
LEV LEVEL
LF LINEAR FOOT (FEET), LIGHT FIXTURE
LFT LEFT
LG LONG/LENGTH
LH LEFT HANDED
LIN LINOLEUM
LOW LIMIT OF WORK
LP LIGHT POLE
LPT LOW POINT
LT LIGHT
LT WT LIGHT WEIGHT
LVR LOUVER
MACH MACHINE
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MDF MEDIUM DENSITY FIBERBOARD
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL/ELECTRICAL/PLUMBING
MET/MTL METAL
MEZZ MEZZANINE
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODIFIED
MR MOISTURE RESISTANT
MTD MOUNTED
MTG MOUNTING
MULL MULLION
MW MICROWAVE
N NORTH
NIC NOT IN CONTACT
NO NUMBER
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
OA OVERALL/OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER/OVERFLOW DRAIN
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OH OPPOSITE HAND
OHMS OVAL HEAD MACHINE SCREW
OHWS OVAL HEAD WOOD SCREW
OPER OPERABLE
OPNG OPENING
OPP OPPOSITE
ORB OIL RUBBED BRONZE
OSD OPEN SITE DRAIN
OZ OUNCE
PA PLANTING AREA
PBD PARTICLE BOARD
PC PRECAST
PCP PARTICLE CEMENT PLASTER
PERF PERFORATED
PG PIPE GUARD
PL PLATE/PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PNL PANEL
POL POLISHED
PR PAIR
PRCST PRECAST
PROJ PROJECT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTD PAINTED
PTN PARTITION
PVC POLYVINYL CHLORIDE
PVG PAVING
PWD PLYWOOD
QT QUARRY TILE
QTY QUANTITY
R RISER/REGISTER
RA RETURN AIR
RAD/R RADIUS
RBR RUBBER
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RECPT RECEPTACLE
REFRIG REFRIGERATOR
REG REGISTER
REINF REINFORCE(MENT)(ING)
REQD REQUIRED
RESIL RESILIENT
RET RETURN
RETG RETAINING
REV REVISION, REVERSE
RFG ROOFING
RH ROBE HOOK/RIGHT HAND
RL RAIN LEADER
RM ROOM
RO ROUGH OPENING/ROUND
RT RIGHT
RTU ROOF TOP UNIT
RV RANGE VENT
RWC RAIN WATER CONDUCTOR
S SOUTH/SINK
SA SUPPLY AIR
SAB SOUND ATTENUATION BLANKETS
SAD SEE ARCHITECTURAL DRAWINGS
SC SEALED CONCRETE/SOLID CORE
SCH SCHEDULE
SD STORM DRAIN/SOAP DISPENSER/
SMOKE DETECTOR
SED SEE ELECTRICAL DRAWINGS
SECT SECTION
SF SQUARE FOOT (FEET)
SFT STRUCTURAL FACING TILE
SHR SHOWER
SHT SHEET
SHTG SHEATHING
SHVLG SHELVING
SIM SIMILAR
SLNT SEALANT
SM SHEETMETAL
SMD SEE MECHANICAL DRAWINGS
SMS SHEET METAL SCREW
SPD SEE PLUMBING DRAWINGS
SPEC SPECIFICATION(S)
SPKR SPEAKER
SQ SQUARE
SS/ST STAINLESS STEEL
SSD SEE STRUCTURAL DRAWINGS
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SV STACK VENT
SUSP SUSPEND(ED)/SUSPENSION
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
TB TOWEL BAR
TBD TACKBOARD
TEL TELEPHONE
TEMP TEMPERED
TF TRANSPARENT FINISH
TG/T&G TONGUE & GROOVE
THK THICK(NESS)
THRES THRESHOLD
TL TILE
TO TOP OF
TOC TOP OF CONCRETE/CURB
TOS TOP OF SLAB/STEEL
TOW TOP OF WALL
TPO THERMOPLASTIC POLYOLEFIN
TV TELEVISION
TWP TRANSLUSCENT WALL PANEL
TYP TYPICAL
TZ/TER TERRAZZO
UC UNDERCUT
UH UNIT HEATER
UL UNDERWRITER'S LABORATORIES INC.
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
UR URINAL
VAR VARIES
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL(LY)
VEST VESTIBULE
VIF VERIFY IN FIELD
VRB VENTED RUBBER BASE
VIN VINYL
VT VINYL TILE
VWC VINYL WALL COVERING
W WEST/WIDE/WIDTH
W/ WITH
W/O WITHOUT
WOM WOMEN
WC WATER CLOSET
WD WOOD
WG WIREGLASS
WH WALL HYDRANT/WATER HEATER
WP WATERPROOFING
WRB WATER RESISTIVE BARRIER
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
CODE COMPLIANCE
LOCATION: JACKSONVILLE, FLORIDA
DUVAL COUNTY
BUILDING CODE: FBC 8TH EDITION (2023) - BUILDING
FBC 8TH EDITION (2023) - RESIDENTIAL
NEC - 2020
OCCUPANCY CLASS.: GROUP R-3 RESIDENTIAL
OCCUPANCY SUB-CAT.: N/A
BUILDING DESCRIPTION: PRIVATE RESIDENCE
TYPE OF CONSTRUCTION: VB
ALLOWED PROPOSED
MAXIMUM HEIGHT: 35' +/- 20'-4" TOP OF ROOF
MAXIMUM STORIES: 3 2
MAXIMUM AREA: UL SEE PLANS FOR SF
AREA CALCULATIONS
NOTE:
SQUARE FOOTAGE CALCULATIONS ARE FROM EXTISTING PLUS NEW.
FLOOR HEATED AND COOLED 2,331 SF
TOTAL NEW HEATED AND COOLED 2,331 SF
NEW 2 CAR GARAGE 442 SF
NEW REAR OPEN PORCH 139 SF
NEW FRONT OPEN PORCH 29 SF
TOTAL NEW UNDER ROOF 2,941 SF
VICINITY MAP
DISCLAIMER:
VICINITY MAP IS FOR LOCATION REFERENCE
ONLY. TRUE NORTH AND PLAN NORTH ARE
DEPICTED TO THE RIGHT OF THIS NOTE.
PLAN
NORTH
PROJECT
LOCATION
SYMBOL LEGED
SYMBOL DESCRIPTION
101
ROOM NAME
101
1t
A13
4
2
3 1
1
A101
SIM
1 VIEW NAME
1/8" = 1'-0"
1/A101
ROOM DESIGNATION AND NUMBER
DOOR NUMBER
WINDOW DESIGNATION
INTERIOR ELEVATION
SECTION CALLOUT
DETAIL CALLOUT
DRAWING VIEW TITLE
DETAIL REFERENCE
COPYRIGHTED MATERIAL
ALL HOME PLANS SOLD THROUGH AA & ASSOCIATES OF FLORIDA ARE PROTECTED
BY COPYRIGHT HELD BY THE A/EOR. REPRODUCTION OF THESE PLANS, EITHER IN
WHOLE OR IN PART; INCLUDING ANY FORM AND/OR PREPARATION OR DERIVATIVE
WORKS, FOR ANY REASON WITHOUT PRIOR WRITTEN PERMISSION IS STRICTLY
PROHIBITED.
WILLFUL INFRINGEMENT COULD CAUSE SETTLEMENTS FOR STATUTORY DAMAGES
UP TO $100,000.00 PLUS ATTORNEY FEES, DAMAGES, AND LOSS OF PROFITS. META
CONTRACTORS WHEN SELLING PLANS LICENSES THE OWNER TO USE
THE PLANS FOR THE SPECIFIC ADDRESS OF THE SPECIFIC PROJECT. IF THE
OWNER WISHES TO REUSE THE PLANS A REUSE FEE MUST BE NEGOTIATED AND
PAID PRIOR TO THE ADDITIONAL USE OF THE PLANS.
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A000
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
COVER SHEET
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
DRAWING INDEX SHEET LIST
A000 COVER SHEET
A001 GENERAL NOTES
A002 EXISTING AND NEW SITE / PLOT PLANS, AND NOTES
A100 FLOOR PLAN
A140 ROOF PLAN
A150 FLASHING LOCATION DIAGRAM, DETAILS, AND NOTES
A201 EXTERIOR ELEVATIONS
A202 EXTERIOR ELEVATIONS
A301 BUILDING SECTIONS
A302 BUILDING SECTIONS AND WALL SECTIONS
A501 TYPICAL DETAILS
A502 TYPICAL ROOF DETAILS
A601 WINDOW AND DOOR TYPICAL DETAILS
E101 ELECTRICAL FIRST FLOOR PLAN AND NOTES
S001 GENERAL NOTES
S002 GENERAL NOTES AND COMPONENTS AND CLADDING DIAGRAM
S003 SCHEDULES AND TABLES
S110 FOUNDATION AND SLAB PLAN
S111 SHEARWALL, WALL FRAMING, HEADERS, AND HOLD-DOWN PLAN
S140 ROOF FRAMING PLAN
S501 TYPICAL CONCRETE DETAILS AND SECTIONS
S502 TYPICAL MASONRY DETAILS AND SECTION
S601 TYPICAL WOOD FRAMING DETAILS
S602 WOOD FRAMING, BEARING AND SHEARWALL SECTIONS AND DETAILS
NEW CONSTRUCTION
-LUNDGREN RESIDENCE
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
SITE INFORMATION:
ZONING:ARS-1
FLOOD ZONE: FLOOD ZONE X
FRONT SETBACK:25 FEET
SIDE SETBACK:7.5 FEET
REAR SETBACK:20 FEET
SITE PLAN NOTES:
1.IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO STAKE-OUT PERIMETER OF
STRUCTURE AND FIELD VERIFY ALL SETBACKS PRIOR TO COMMENCEMENT OF ANY CONSTRUCTION.
2.VERIFY EXISTING FLOOD ZONES AND COORDINATE ALL REQUIRED DOCUMENTS/REQUIREMENTS
WITH SCOPE OF WORK APPLICABLE.
3.VERIFY ALL CODES AND RESTRICTIONS WITH STATE AND LOCAL MUNICIPALITIES PRIOR TO
CONSTRUCTION.
4.GENERAL CONTRACTOR TO VERIFY ANY EXISTING STRUCTURES, SEPTIC, GAS, SHEDS, AND ETC.
DEMOLISH AND RELOCATE AS REQUIRED PER LOCAL CODES.
5.ALL UTILITIES, F.F.E. AND DRAINAGE TO BE VERIFIED BY BUILDER.
6.THE APPLICANT/OWNER/CONTRACTOR SHALL IMMEDIATELY CONTACT ST. JOHN'S COUNTY LOT
GRADING STAFF SHOULD MODIFICATIONS TO THE DRAINAGE PLAN BE REQUIRED DURING SITE
DEVELOPMENT, BASED ON ACTUAL FIELD CONDITIONS.
BUILDING DESIGN CRITERIA
(REFER TO STRUCTURAL DRAWINGS)
LEGAL DESCRIPTIONS:
PARCEL ID:171178-0000
LOCATION ADDRESS:893 AMBERJACK LANE, ATLANTIC BEACH, FLORIDA 32233
USE DESCRIPTION:RES LD 3-7 UNITS PER AC
LEGAL DESCRIPTION:30-60 17-2S-29E ROYAL PALMS UNIT 1 LOT 24 BLK 4
PROPERTY USE CODE:SINGLE FAMILY (0100)
SUBDIVISION:03120 ROYAL PALMS UNIT 01
NO. DESCRIPTION DATE
R302.5.1 OPENING PROTECTION:
1. OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM USED FOR SLEEPING PURPOSES SHALL NOT
BE PERMITED. OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE EQUIPPED WITH
SOLID WOOD DOORS NOT LESS THAN 1 3/8" IN THICKNESS, SOLID OR HONEYCOMP CORE STEEL DOORS
NOT LESS THAN 1 3/8" THICK, OR 20-MINUTE FIRE-RATED DOORS. NOTE: DOOR TO BE SELF-CLOSING.
R302.11 FIREBLOCKING:
1. IN COMBUSTIBLE CONSTRUCTION, FIREBLOCKING SHALL BE PROVIDED TO CUT OFF ALL CONCEALED DRAFT
OPENINGS (BOTH VERTICAL AND HORIZONTAL) AND TO FORM AN EFFECTIVE FIRE BARRIER BETWEEN
STORIES, AND BETWEEN A TOP STORY AND THE ROOF SPACE.
2. FIREBLOCKING SHALL BE PROVIDED IN WOOD-FRAME CONSTRUCTION IN THE FOLLOWING LOCATIONS.
(a) IN CONCEALED SPACES OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES AND
PARALLEL ROWS OF STUDS OR STAGGERED STUDS AS FOLLOWS:
(a.1) VERTICALLY AT THE CEILING AND FLOOR LEVELS.
(a.2) HORIZONTALLY AT INTERVALS NOT EXCEEDING 10 FEET.
(b) AT ALL INTERCONNECTIONS BETWEEN CONCEALED VERTICAL AND HORIZONTAL SPACES SUCH AS
OCCUR AT SOFFITS, DROP CEILINGS AND COVE CEILINGS.
(c) IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT THE TOP AND BOTTOM OF THE RUN.
ENCLOSED SPACES UNDER STAIRS SHALL COMPLY WITH SECTION R302.7.
(d) AT OPENINGS AROUND VENTS, PIPES, DUCTS, CABLES, AND WIRES AT CEILING AND FLOOR LEVEL,
WITH AN APPROVED MATERIAL TO RESIST THE FREE PASSAGE OF FLAME AND PRODUCTS OF
COMBUSTION. THE MATERIAL FILLING THIS ANNULAR SPACE SHALL NOT BE REQUIRED TO MEET THE
ASTM E 136 REQUIREMENTS.
(e) FOR THE FIREBLOCKING OF CHIMNEYS AND FIREPLACES, SEE SECTION R1003.19.
(f) FIREBLOCKING OF CORNICES OF A TWO-FAMILY DWELLING IS REQUIRED AT THE LINE OF DWELLING
UNIT SEPARATION.
R302.7 UNDER-STAIR PROTECTION:
1. ECLOSED ACCESSIBLE SPACE UNDER THE STAIRS SHALL HAVE WALLS, UNDER STAIR SURFACE AND ANY
SOFFITS PROTECTED ON THE ECLOSED SIDE WITH 1/2" GYPSUM BOARD.
R302.12 DRAFTSTOPPING:
1. IN COMBUSTIBLE CONSTRUSTION WHERE THERE IS USEABLE SPACE BOTH ABOVE AND BELOW THE
CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED SO THAT THE AREA
OF THE CONCEALED SPACE DOES NOT EXCEED 1.000 SF.
2. DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREA. WHERE THE
ASSEMBLY IS ECLOSED BY A FLOOR MEMBRANE ABOVE AND A CEILING MEMBRANE BELOW, DRAFTSTOPPING
SHALL BE PROVIDED IN FLOOR/CEILING ASSEMBLIES UNDER THE FOLLOWING CIRCUMSTANCES.
(a) CEILING IS SUSPENDED UNDER THE FLOOR FRAMING.
(b) FLOOR FRAMING IS CONSTRUCTED OF TRUSS TYPE OPEN WEB OR PERORATED MEMBERS.
R310 EMERGENCY EXAPE AND RESCUE OPENINGS:
1. R310.1: EMERGENCY ESCAPE AND RESCUE REQUIRED. BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING
ROOF SHALL HAVE AT LEAST ONE OPERABLE EMERGENCY ESCAPE AND RESCUE OPENING. WHERE
BASEMENTS CONTAIN ONE OR MORE SLEEPING ROOMS, EMERGENCY EGRESS AND RESCUE OPENINGS SHALL
BE REQUIRED IN EACH SLEEPING ROOM. WHERE EMERGENCY ESCAPE AND RESCUE OPENING ARE PROVIDED
THEY SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44" ABOVE THE FLOOR. WHERE A DOOR OPENING
HAVING A THRESHOLD BELOW THE ADJACENT GROUND ELEVATION SERVES AS AN EMERGENCY ESCAPE
AND RESCUE OPENING AND IS PROVIDED WITH A BULKHEAD ENCLOSURE, THE BULKHEAD ENCLOSURE SHALL
COMPLY WITH SECTION R310.3.
2. THE NET CLEAR OPENING DIMENSIONS REQUIRED BY THIS SECTION SHALL BE OBTAINED BY THE NORMAL
OPERATION OF EMERGENCY ESCAPE AND RESCUE OPENINGS FROM THE INSIDE. EMERGENCY ESCAPE AND
RESCUE OPENINGS WITH A FINISHED SILL HEIGHT BELOW THE ADJACENT GROUND ELEVATIONS SHALL BE
PROVIDED WITH A WINDOW WELL IN ACCORDANCE WITH SECTION R310.2. EMERGENCY ESCAPE AND
RESCUE OPENINGS SHALL OPEN DIRECTLY INTO A PUBLIC WAY, OR TO A YARD OR COURT THAT OPENS TO
A PUBLIC WAY.
EXCEPTIONS:
(a) BASEMENTS USED ONLY TO HOUSE MECHANICAL EQUIPMENT AND NOT EXCEEDING TOTAL FLOOR AREA
OF 200 SF.
(b) THE EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE PERMITTED TO OPEN INTO A SCREEN
ENCLOSURE, OPEN TO THE ATMOSPHERE, WHERE A SCREEN DOOR IS PROVIDED LEADING AWAY FROM
THE RESIDENCE.
(c) R310.1.1. MINIMUM OPENING AREA: ALL EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE A
MINIMUM NET CLEAR OPENING OF 5.7 SF. EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A
MINIMUM NET CLEAR OPENING OF 5 SF.
(d) R310.1.2. MINIMUM OPENING HEIGHT: THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24".
(e) R310.1.3. MINIMUM OPENING WIDTH: THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20".
(f) R310.1.4. OPERATIONAL CONSTRAINTS: EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE
OPERATIONAL FROM THE INSIDE OF THE ROOM WITHOUT THE USE OF KEYS, TOOLS OR SPECIAL
KNOWLEDGE.
R302.6 DWELLING/GARAGE FIRE SEPARATION:
1. THE GARAGE SHALL BE SEPARATED AS REQUIRED BY TABLE R302.6. OPENINGS IN GARAGE WALLS SHALL
COMPLY WCOITH SECTION R302.5. THIS PROVISION DOES NOT APPLY TO GARAGE WALLS THAT ARE
PERPENDICULAR TO THE ADJACENT DWELLING UNIT WALL.
TABLE R302.6
DWELLING/GARAGE SEPARATION
SEPARATION MATERIAL
FROM THE RESIDENCE AND ATTICS
FROM THE HABITABLE ROOMS ABOVE THE GARAGE
STRUCTURE(S) SUPPORTING FLOOR/CEILING ASSEMBLIES
USED FOR SEPARATION REQUIRED BY THIS SECTION
GARAGES LOCATED LESS THAN 3 FEET FROM A DWELLING
UNIT ON THE SAME LOT
NOT LESS THAN 1/2" GYPSUM BOARD OR EQUIVALENT
APPLIED TO THE GARAGE SIDE.
NOT LESS THAN 1/2" TYPE X GYPSUM BOARD OR
EQUIVALENT
NOT LESS THAN 1/2" GYPSUM BOARD OR EQUIVALENT
NOT LESS THAN 1/2" GYPSUM BOARD OR EQUIVALENT
APPLIED TO THE INTERIOR SIDE OF EXTERIOR WALLS THAT
ARE WITHIN THIS AREA
R302.5.2. DUCT PENETRATION:
1. DUCTS IN THE GARAGE AND DUCTS PENETRATING THE WALLS OR CEILINGS SEPARATING THE DWELLING
FROM THE GARAGE SHALL BE CONSTRUCTED OF A MINIMUM NO. 26 GAGE SHEET STEEL, 1" MINIMUM RIGID
NONMETALLIC CLASS 0 OR CLASS 1 DUCT BOARD, OR OTHER APPROVED MATERIAL AND SHALL HAVE NO
OPENINGS INTO THE GARAGE.
FBC-R-E3902 AFCI PROTECTION REQUIRED:
1. ALL 120 VOLT, SINGLE PHASE, 15-20 AMPHERE BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED IN
DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
SUN ROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS SHALL BE
PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER, COMBINATION-TYPE.
FBC-R-E3901.7, NEC 210, E3901.7 AND E3902.3 GFCI PROTECTION REQUIRED:
1. BATHROOMS, GARAGES, BOATHOUSES AND ACCESSORY STRUCTURES NOT INTENDED AS HABITABLE
ROOMS AND LIMITED TO STORAGE, WORK, AND SIMILAR USES. OUTDOORS, CRAWL SPACES, UNFINISHED
BASEMENTS, KITCHEN COUNTERTOPS. OUTLETS WITHIN 6 FEET OF LAUNDRY, UTILITY OR WET SINKS.
BALCONY, DECK OR PORCH GREATER THAN 20 SF. ONE AT THE FRONT AND BACK OF THE DWELLING AND AT
THE CONDENSER UNITS.
CONSTRUCTION DOCUMENTS:
1. THE PURPOSE OF THESE DOCUMENTS IS TO CONVEY DESIGN INTENT ONLY. THE CONTRACTOR SHALL A) BE
SOLELY RESPONSIBLE FOR COMPLIANCE WITH ORDERS OF ANY PUBLIC AUTHORITY BEARING ON THE
PERFORMANCE OF THE WORK, B) PROMPTLY NOTIFY ARCHITECT IF THE DRAWINGS AND SPECIFICATIONS ARE
AT VARIANCE THERWITH, AND C) OBTAIN ALL REQUISITE BUILDING AND OTHER PERMITS REQUIRED IN
CONNECTION WITH THE WORK.
2. THE CONTRACTOR WILL BE PRESUMED TO HAVE INSPECTED THE SITE AND TO HAVE READ AND TO BE
THOROUGHLY FAMILIAR WITH THE DRAWINGS AND SPECIFICATIONS. THE FAILURE OR OMISSION OF ANY
CONTRACTOR TO EXAMINE ANY FORM, INSTRUMENT OR DOCUMENT SHALL IN NO WAY RELIEVE THE
CONTRACTOR FROM ANY OBLIGATION IN RESPECT TO HIS WORK.
3. THE CONTRACTOR SHALL PERFORM NO PORTION OF THE WORK AT ANY TIME WITHOUT CONTRACT
DOCUMENTS, OR WHERE REQUIRED, APPROVED SHOP DRAWINGS, PRODUCT DATA OR SAMPLE FOR SUCH
PORTION OF THE WORK.
4. THESE DRAWINGS DO NOT NECESSARILY INDICATE OR DESRIBE ALL WORK REQUIRED FOR FULL
PERFORMANCE AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. ON THE BASIS OF
THE GENERAL SCOPE INDICATED OR DESCRIBED, THE CONTRACTOR SHALL FURNISH ALL ITEMS REQUIRED FOR
THE PROPER EXECUTION AND COMPLETION OF THE WORK. DECISIONS OF ARCHITECT AS TO THE ITEMS OF WORK
INCLUDED WITHIN THE SCOPE OF THESE DOCUMENTS SHALL BE FINAL AND BINDING ON THE CONTRACTOR AND
THE OWNER.
5. THE ARCHITECT RESERVES THE RIGHT TO REJECT ITEMS INCORPORATED INTO THE WORK WHICH FAIL TO MEET
THE SPECIFIED MINIMUM REQUIREMENTS. THE ARCHITECT FURTHER RESERVES THE RIGHT, AND WITHOUT
PREJUDICE TO OTHER RECOURSE. ARCHITECT MAY OR MAY NOT ACCEPT NON-COMPLYING ITEMS SUBJECT TO ANY
ADJUSTMENT IN THE CONTRACT AMOUNT AS APPROVED BY THE ARCHITECT AND/OR THE OWNER.
PERMITS, FEES, TAXES AND NOTICES:
1. THE CONTRACTOR SHALL PAY ALL SALES, CONSUMER, AND OTHER SIMILAR TAXES FOR THE WORK OR
PORTIONS THEREOF PROVIDED BY THE CONTRACTOR WHICH ARE LEGALLY ENACTED AT THE TIME OF
CONSTRUCTION.
2. UNLESS OTHERWISE PROVIDED IN THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL SECURE ANY PAY
FOR THE BUILDING PERMIT AND FOR ALL OTHER PERMITS AND GOVERNMENTAL FEES, LICENSES AND
INSPECTIONS NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THE WORK.
3. THE CONTRACTOR SHALL GIVE ALL NOTICES AND COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS,
AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY BEARING ON THE PERFORMANCE OF THE WORK.
4. THE CONTRACTOR SHALL EXERCISE REASONABLE EFFORT TO MAKE CERTAIN THAT THE CONTRACT
DOCUMENTS ARE IN ACCORDANCE WITH APPLICABLE LAWS, STATUTES, BUILDING CODES AND REGULATIONS. IF
THE CONTRACTOR OBSERVES THAT ANY OF THE CONTRACT DOCUMENTS ARE AT VARIANCE THEREWITH IN ANY
RESPECT, HE SHALL PROMPTLY NOTIFY ARCHITECT IN WRITING, AND ANY NECESSARY CHANGES SHALL BE
ACCOMPLISHED BY APPROPRIATE MODIFICATION.
5. IF THE CONTRACTOR PERFORMS ANY WORK KNOWING IT TO BE CONTRARY TO SUCH LAWAS, ORDINANCES,
RULES AND REGULATIONS, AND WITHOUT SUCH NOTICE TO THE DESIGNER, THE CONTRACTOR SHALL ASSUME
FULL RESPONSIBILITY THEREFORE AND SHALL BEAR ALL COSTS ATTRIBUTABLE THERETO.
COORDINATION AND SUPERVISION:
1. ALL WORK TO BE SCHEDULED DURING REGULAR BUSINESS HOURS UNLESS NOTED OTHERWISE.
2. CONTRACTOR TO PROVIDE ADVANCE NOTIFICATION TO TENANTS REPRESENTATIVE WHEN TENANT OR THEIR
CONTRACTOR(S) ARE REQUIRED AT JOB SITE FOR COORDINATION MEETINGS OR INSTALLATIONS.
3. UPON COMPLETION OF THE WORK, THE CONTRACTOR TO NOTIFY BUILDING OWNER REPRESENTATIVE THAT THE
PROJECT IS READY FOR INSPECTION. OWNER/REP WILL COMPILE A "PUNCH LIST" OF CORRECTIONS NEEDED OF
UNSATISFACTORY AND/OR INCOMPLETE WORK. FINAL PAYMENT WILL BE CONTINGENT UPON THE SUCCESSFUL
COMPLETION OF THE PUNCH LIST.
4. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK, USING THE CONTRACTORS BEST SKILL AND
ATTENTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS,
TECHNIQUES, SEQUENCES AND PROCEDURES, AND SHALL COORDINATE ALL PORTIONS OF THE WORK.
5. THE CONTRACTOR SHALL BE RESPONSIBLE TO THE OWNER FOR THE ACTS AND OMISSIONS OF THE
CONTRACTORS EMPLYEES, SUBCONTRACTORS AND THEIR AGENTS AND EMPLOYEES, AND ANY OTHER PERSONS
PERFORMING ANY OF THE WORK UNDER A CONTRACT WITH THE CONTRACTOR.
6. THE CONTRACTOR TO, AT ALL TIMES, KEEP THE PREMISES FREE OF ACCUMULATION OF WASTE MATERIALS OR
RUBBISH; PREMISES TO BE SWEPT CLEAN DAILY.
7. THE CONTRACTOR TO PROVIDE FINAL CLEANING OF ALL AREAS OF WORK INCLUDING THE CONSTRUCTION
ACCESS ROUTE. FINAL CLEANING TO INCLUDE WINDOWS AND CEILINGS.
LABOR, MATERIALS, AND WARRANTY:
1. UNLESS OTHERWISE PROVIDED IN THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL PROVIDE AND PAY
FOR ALL LABOR, MATERIALS, EQUIPMENT, TOOLS, CONSTRUCTION EQUIPMENT AND MACHINERY,
TRANSPORTATION, AND OTHER FACILITIES AND SERVICES NECESSARY FOR THE PROPER EXECUTION AND
COMPLETION OF THE WORK.
2. THE CONTRACTOR SHALL AT ALL TIMES ENFORCE STRICT DISCIPLINE AND GOOD ORDER AMONG THE
CONTRACTORS EMPLOYEES AND SHALL NOT EMPLY ON THE WORK ANY UNFIT PERSON OR ANYONE NOT
SKILLED IN THE TASK ASSIGNED THEM.
3. ALL WORK SHALL BE PERFORMED BY SKILLED AND QUALIFIED WORKMEN IN ACCORDANCE WITH THE BEST
PRACTICES OF THE TRADES INVOLVED AND IN COMPLIANCE WITH BUILDING REGULATIONS AND/OR
GOVERNMENT LAWS, STATUTES OR ORDINANCES CONCERNING THE USE OF UNION LABOR.
4. CONTRACTOR AND SUBCONTRACTORS TO FIELD VERIFY ALL DIMENSIONS AND CONDITONS SHOWN ON
DOCUMENTS AND MUST NOTIFY ARCHITECT OF ANY DISCREPANCIES, OMISSIONS AND/OR CONFLICTS PRIOR TO
PROCEEDING WITH THE WORK.
5. EACH TRADE WILL BE EXPECTED TO PROCEED IN A FASHION THAT WILL NOT DELAY OTHER TRADES.
6. THE CONTRACTOR IS RESPONSIBLE FOR THE DISTRIBUTION OF DRAWINGS TO ALL TRADES UNDER THEIR
JURISDICTION.
7. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN. LARGER SCALE DRAWINGS TO GOVERN OVER SMALLER
SCALE DRAWINGS.
8. DIMENSIONS ARE TO THE FINISHED FACE OF NEW CONSTRUCTION. DIMENSIONS ARE NOMINAL UNLESS
OTHERWISE INDICATED.
9. IF DIMENSIONS ARE IN QUESTION, THE CONTRACTOR IS RESPONSIBLE TO GET CLARIFICATION AND DIRECTION
FROM ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
10.THE CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING RECOQUIRED FOR HIS WORK UNLESS
OTHERWISE NOTED.
11.CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADEQUATE BLOCKING FOR WALL SUPPORTED ELEMENTS
INCLUDING MILLWORK, EQUIPMENT, FIXTURES AND FURNITURE. CONTRACTOR TO VERIFY EXTENT AND
COORDINATE WITH APPROPRIATE SUBCONTRACTORS.
12.ALL MATERIALS TO BE NEW UNUSED AND OF THE HIGHEST QUALITY IN EVERY RESPECT, UNLESS OTHERWISE
NOTED. MANUFACTURED MATERIALS AND EQUIPMENT TO BE STORED AND INSTALLED IN ACCORDANCE WITH
THE MANUFACTURERS WRITTEN RECOMMENDATIONS AND INSTRUCTIONS.
13.THERE WILL BE NO SUBSTITUTIONS OF MATERIALS WHERE A MANUFACTURER IS SPECIFIED. WHERE THE TERMS
"EQUAL TO" OR "APPROVED EQUAL" ARE USED, ARCHITECT TO DETERMINE EQUALITY BASED ON INFORMATION
SUBMITTED BY THE CONTRACTOR.
14.ALL FINISHES TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS AND
INSTRUCTIONS FOR THE TYPE OF MATERIAL AND INSTALLATION SPECEFIED.
15.PAINT TO BE APPLIED IN ACCORDANCE WITH THE MANUFACTURERS DIRECTIONS OVER PROPERLY PREPARED
SURFACES. WALLS TO BE STRIAGHT AND SMOOTH. PROVIDE MINIMUM ONE COAT PRIME AND ONE FINISH COAT.
FINISHED COAT TO COMPLETELY COVER WITH NO STREAKING OR BLEEDING OF UNDERCOATS.
16.MILLWORK TO CONFORM WITH AWI STANDARDS FOR PREMIUM GRADE MILLWORK. DRAWINGS INDICATE DESIGN
INTENT. FABRICATOR IS RESPONSIBLE FOR MILLWORK ENGINEERING.
17.DRYWALL CONTRACTORS TO CLOSELY COORDINATE HIS WORK WITH THAT OF OTHER TRADES. WHERE
DRYWALL IS IN CONFLICT WITH DUCTWORK, PLUMBING LINES, ETC. THIS CONTRACTOR TO PROVIDE ALL
NECESSARY BRIDGING AND BRACING REQUIRED TO SECURE DRYWALL AND TO MAINTAIN FIRE OR SOUND
RATING WHERE REQUIRED.
18.THE CONTRACTOR WARRANTS TO THE OWNER THAT ALL MATERIALS AND EQUIPMENT FURNISHED UNDER THIS
CONTRACT WILL BE NEW UNLESS OTHERWISE SPECIFIED, AND THAT ALL WORK WILL BE OF GOOD QUALITY,
FREE FROM FAULTS AND DEFECTS AND IN CONFORMANCE WITH THE CONTRACT DOCUMENTS FOR A PERIOD OF
NOT LESS THAN ONE YEAR FROM THE COMPLETION OF CONSTRUCTION. ALL WORK NOT CONFORMING TO THESE
REQUIREMENTS, INCLUDING SUBSTITUTIONS NOT PROPERLY APPROVED AND AUTHORIZED, MAY BE
CONSIDERED DEFECTIVE.
INSTALLATION NOTES:
1. ALL INSTALLED PLUMBING, MECHANICAL AND ELECTRICAL EQUIPMENT TO OPERATE QUIETLY AND BE FREE OF
VIBRATION.
2. UNLESS OTHERWISE NOTED IN MECHANICAL DRAWINGS OR SPECIFICATIONS, HOLD DUCTS AND MECHANICAL
EQUIPMENT TIGHT TO STRUCTURE ABOVE.
3. THE CONTRACTOR SHALL NOT LOCATE CEILING DIFFUSERS OR REGISTERS WHERE FULL HEIGHT SHELVING,
FILES OR STORAGE UNITS ARE INDICATED ON PLANS.
4. ALL CEILING DIFFUSERS AND REGISTERS TO BE THE SAME COLOR AS THE CEILING UNLESS NOTED OTHERWISE.
5. PATCH ALL AREAS WHERE THE FLOOR IS NOT LEVEL OR TRUE PRIOR TO INSTALLATION OF SPECIFIED FINISHES.
6. ALL SURFACES TO BE PROPERLY PRIMED OR PREPARED PRIOR TO INSTALLTION OF SPECIFIED FINISHES.
7. PROVIDE ALL NECESSARY CUT OUTS FOR THE INSTALLATION OF ELECTRICAL AND VOICE/DATA OUTLETS,
THERMOSTATS, SWITCHES AND OTHER DEVICES.
8. EXTEND ALL FIRE RATED PARTITIONS TO STRUCTURE, FILL ALL VOIDS WITH FIRE SAFING MATERIAL OR FIRE-
RATED CAULK, CONTINUOUS AS REQUIRED BY CODE.
9. ALL FIRE EXTINGUISHER CABINETS OR ELECTRICAL PANELS LOCATED IN RATED PARTITIONS TO BE BACKED
WITH GYPSUM BOARD AS REQUIRED TO MAINTAIN PARTITION RATING.
10.CONTRACTOR IS RESPONSIBLE FOR FIRESTOPPING ALL NEW AND EXISTING FIRE RATED PARTITIONS AND ALL
PENETRATION THROUGH AREAS INCLUDING SLABS. CONTRACTOR TO VERIFY IN FIELD.
11.WHERE PIPES, CONDUITS OR LOW TENSION WIRING PENETRATE A FIRE RATED ENCLOSURE, THE SPACE
AROUND SHALL NOT EXCEED 1/2" AND SHALL BE PACKED SOLID WITH BATT INSULATION AND FITTED WITH
ESCUTCHEON PLATES ON BOTH SIDES OR EQUIVALENT TREATMENT TO INSURE COMPLIANCE WITH FIRE RATING.
12.WHERE DUCT OR PART OF DUCT IS RUNNING PARALLEL OVER FIRE RATED PARTITION, EXTEND RATED
PARTITION AROUND DUCT TO EFFECT COMPLETE MAINTENANCE OF FIRE RATING.
A-INTENT & USE OF CONSTRUCTION DOCUMENTS
1. THE PURPOSE OF THESE DOCUMENTS IS TO CONVEY DESIGN INTENT ONLY. THE CONTRACTOR SHALL A) BE
SOLELY RESPONSIBLE FOR COMPLIANCE WITH ORDERS OF ANY PUBLIC AUTHORITY BEARING ON THE
PERFORMANCE OF THE WORK, B) PROMPTLY NOTIFY ARCHITECT IF THE DRAWINGS AND SPECIFICATIONS ARE AT
VARIANCE THEREWITH, AND C) OBTAIN ALL REQUISITE BUILDING AND OTHER PERMITS REQUIRED IN CONNECTION
WITH THE WORK.
2. THE CONTRACTOR WILL BE PRESUMED TO HAVE INSPECTED THE SITE AND TO HAVE READ AND TO BE
THOROUGHLY FAMILIAR WITH THE DRAWINGS AND SPECIFICATIONS. THE FAILURE OR OMISSION OF ANY
CONTRACTOR TO EXAMINE ANY FORM, INSTRUMENT OR DOCUMENT SHALL IN NO WAY RELIEVE THE CONTRACTOR
FROM ANY OBLIGATION IN RESPECT TO HIS WORK.
3. THE CONTRACTOR SHALL PERFORM NO PORTION OF THE WORK AT ANY TIME WITHOUT CONTRACT
DOCUMENTS, OR WHERE REQUIRED, APPROVED SHOP DRAWINGS, PRODUCT DATA OR SAMPLE FOR SUCH
PORTION OF THE WORK.
4. THESE DRAWINGS DO NOT NECESSARILY INDICATE OR DESCRIBE ALL WORK REQUIRED FOR FULL
PERFORMANCE AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. ON THE BASIS OF THE
GENERAL SCOPE INDICATED OR DESCRIBED, THE CONTRACTOR SHALL FURNISH ALL ITEMS REQUIRED FOR THE
PROPER EXECUTION AND COMPLETION OF THE WORK. DECISIONS OF ARCHITECT AS TO THE ITEMS OF WORK
INCLUDED WITHIN THE SCOPE OF THESE DOCUMENTS SHALL BE FINAL AND BINDING ON THE CONTRACTOR AND
THE OWNER.
5. THE ARCHITECT RESERVES THE RIGHT TO REJECT ITEMS INCORPORATED INTO THE WORK WHICH FAIL TO MEET
THE SPECIFIED MINIMUM REQUIREMENTS. THE ARCHITECT FURTHER RESERVES THE RIGHT, AND WITHOUT
PREJUDICE TO OTHER RECOURSE. ARCHITECT MAY OR MAY NOT ACCEPT NON-COMPLYING ITEMS SUBJECT TO ANY
ADJUSTMENT IN THE CONTRACT AMOUNT AS APPROVED BY THE ARCHITECT AND/OR THE OWNER.
B-PERMITS, FEES, TAXES, & NOTICES
1. THE CONTRACTOR SHALL PAY ALL SALES, CONSUMER, AND OTHER SIMILAR TAXES FOR THE WORK OR
PORTIONS THEREOF PROVIDED BY THE CONTRACTOR WHICH ARE LEGALLY ENACTED AT THE TIME OF
CONSTRUCTION.
2. UNLESS OTHERWISE PROVIDED IN THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL SECURE AND PAY
FOR THE BUILDING PERMIT AND FOR ALL OTHER PERMITS AND GOVERNMENTAL FEES, LICENSES AND INSPECTIONS
NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THE WORK.
3. THE CONTRACTOR SHALL GIVE ALL NOTICES AND COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS,
AND LAWFUL ORDERS OF ANY PUBLIC AUTHORITY BEARING ON THE PERFORMANCE OF THE WORK.
4. THE CONTRACTOR SHALL EXERCISE REASONABLE EFFORT TO MAKE CERTAIN THAT THE CONTRACT
DOCUMENTS ARE IN ACCORDANCE WITH APPLICABLE LAWS, STATUTES, BUILDING CODES AND REGULATIONS. IF
THE CONTRACTOR OBSERVES THAT ANY OF THE CONTRACT DOCUMENTS ARE AT VARIANCE THEREWITH IN ANY
RESPECT, HE SHALL PROMPTLY NOTIFY ARCHITECT IN WRITING, AND ANY NECESSARY CHANGES SHALL BE
ACCOMPLISHED BY APPROPRIATE MODIFICATION.
5. IF THE CONTRACTOR PERFORMS ANY WORK KNOWING IT TO BE CONTRARY TO SUCH LAWS, ORDINANCES,
RULES AND REGULATIONS, AND WITHOUT SUCH NOTICE TO DESIGNER, HE SHALL ASSUME FULL RESPONSIBILITY
THEREFORE AND SHALL BEAR ALL COSTS ATTRIBUTABLE THERETO.
C-COORDINATION & SUPERVISION
1. ALL WORK TO BE SCHEDULED DURING REGULAR BUSINESS HOURS UNLESS NOTED OTHERWISE.
2. CONTRACTOR TO PROVIDE ADVANCE NOTIFICATION TO TENANT'S REPRESENTATIVE WHEN TENANT OR THEIR
CONTRACTOR(S) ARE REQUIRED AT JOB SITE FOR COORDINATION MEETINGS OR INSTALLATIONS.
3. UPON COMPLETION OF THE WORK, THE CONTRACTOR TO NOTIFY BUILDING OWNER REPRESENTATIVE THAT THE
PROJECT IS READY FOR INSPECTION. OWNER/REP WILL COMPILE A "PUNCH LIST" OF CORRECTIONS NEEDED OF
UNSATISFACTORY AND/OR INCOMPLETE WORK. FINAL PAYMENT WILL BE CONTINGENT UPON THE SUCCESSFUL
COMPLETION OF THE PUNCH LIST.
4. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK, USING THE CONTRACTOR'S BEST SKILL AND
ATTENTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS,
TECHNIQUES, SEQUENCES AND PROCEDURES, AND SHALL COORDINATE ALL PORTIONS OF THE WORK.
5. THE CONTRACTOR SHALL BE RESPONSIBLE TO THE OWNER FOR THE ACTS AND OMISSIONS OF THE
CONTRACTOR'S EMPLOYEES, SUBCONTRACTORS AND THEIR AGENTS AND EMPLOYEES, AND ANY OTHER PERSONS
PERFORMING ANY OF THE WORK UNDER A CONTRACT WITH THE CONTRACTOR.
6. THE CONTRACTOR TO, AT ALL TIMES, KEEP THE PREMISES FREE OF ACCUMULATION OF WASTE MATERIALS OR
RUBBISH; PREMISES TO BE SWEPT CLEAN DAILY.
7. THE CONTRACTOR TO PROVIDE FINAL CLEANING OF ALL AREAS OF WORK INCLUDING THE CONSTRUCTION
ACCESS ROUTE. FINAL CLEANING TO INCLUDE WINDOWS AND CEILINGS.
D-LABOR, MATERIALS, & WARRANTY
1. UNLESS OTHERWISE PROVIDED IN THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL PROVIDE AND PAY
FOR ALL LABOR, MATERIALS, EQUIPMENT, TOOLS, CONSTRUCTION EQUIPMENT AND MACHINERY,
TRANSPORTATION, AND OTHER FACILITIES AND SERVICES NECESSARY FOR THE PROPER EXECUTION AND
COMPLETION OF THE WORK.
2. THE CONTRACTOR SHALL AT ALL TIMES ENFORCE STRICT DISCIPLINE AND GOOD ORDER AMONG THE
CONTRACTOR'S EMPLOYEES AND SHALL NOT EMPLOY ON THE WORK ANY UNFIT PERSON OR ANYONE NOT SKILLED
IN THE TASK ASSIGNED THEM.
3. ALL WORK SHALL BE PERFORMED BY SKILLED AND QUALIFIED WORKMEN IN ACCORDANCE WITH THE BEST
PRACTICES OF THE TRADES INVOLVED AND IN COMPLIANCE WITH BUILDING REGULATIONS AND/OR GOVERNMENT
LAWS, STATUTES OR ORDINANCES CONCERNING THE USE OF UNION LABOR.
4. CONTRACTOR AND SUB-CONTRACTORS TO FIELD VERIFY ALL DIMENSIONS AND CONDITIONS SHOWN ON
DOCUMENTS AND MUST NOTIFY ARCHITECT OF ANY DISCREPANCIES, OMISSIONS AND/OR CONFLICTS PRIOR TO
PROCEEDING WITH THE WORK.
5. EACH TRADE WILL BE EXPECTED TO PROCEED IN A FASHION THAT WILL NOT DELAY OTHER TRADES.
6. THE CONTRACTOR IS RESPONSIBLE FOR THE DISTRIBUTION OF DRAWINGS TO ALL TRADES UNDER THEIR
JURISDICTION.
7. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN. LARGER SCALE DRAWINGS TO GOVERN OVER SMALLER
SCALE DRAWINGS.
8. DIMENSIONS ARE TO THE FINISHED FACE OF NEW CONSTRUCTION. DIMENSIONS ARE NOMINAL UNLESS
OTHERWISE INDICATED.
9. IF DIMENSIONS ARE IN QUESTION, THE CONTRACTOR IS RESPONSIBLE TO GET CLARIFICATION AND DIRECTION
FROM ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
10. THE CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING REQUIRED FOR HIS WORK UNLESS
OTHERWISE NOTED.
11. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADEQUATE BLOCKING FOR WALL SUPPORTED ELEMENTS
INCLUDING MILLWORK, EQUIPMENT, FIXTURES AND FURNITURE. CONTRACTOR TO VERIFY EXTENT AND
COORDINATE WITH APPROPRIATE SUBCONTRACTORS.
12. ALL MATERIALS TO BE NEW, UNUSED AND OF THE HIGHEST QUALITY IN EVERY RESPECT, UNLESS OTHERWISE
NOTED. MANUFACTURED MATERIALS AND EQUIPMENT TO BE STORED AND INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S WRITTEN RECOMMENDATIONS AND INSTRUCTIONS.
11. THERE WILL BE NO SUBSTITUTIONS OF MATERIALS WHERE A MANUFACTURER IS SPECIFIED. WHERE THE
TERMS "EQUAL TO" OR "APPROVED EQUAL" ARE USED, ARCHITECT TO DETERMINE EQUALITY BASED ON
INFORMATION SUBMITTED BY THE CONTRACTOR.
12. ALL FINISHES TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND
INSTRUCTIONS FOR THE TYPE OF MATERIAL AND INSTALLATION SPECIFIED.
13. PAINT TO BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER'S DIRECTIONS OVER PROPERLY PREPARED
SURFACES. WALLS TO BE STRAIGHT AND SMOOTH. PROVIDE MINIMUM ONE COAT PRIME AND ONE FINISH COAT.
FINISHED COAT TO COMPLETELY COVER WITH NO STREAKING OR BLEEDING OF UNDERCOATS.
14. MILLWORK TO CONFORM WITH AWI STANDARDS FOR PREMIUM GRADE MILLWORK. DRAWINGS INDICATE
DESIGN INTENT. FABRICATOR IS RESPONSIBLE FOR MILLWORK ENGINEERING.
15. DRYWALL CONTRACTOR TO CLOSELY COORDINATE HIS WORK WITH THAT OF OTHER TRADES. WHERE
DRYWALL IS IN CONFLICT WITH DUCTWORK, PLUMBING LINES, ETC. THIS CONTRACTOR TO PROVIDE ALL
NECESSARY BRIDGING AND BRACING REQUIRED TO SECURE DRYWALL AND TO MAINTAIN FIRE OR SOUND RATING
WHERE REQUIRED.
16. THE CONTRACTOR WARRANTS TO THE OWNER THAT ALL MATERIALS AND EQUIPMENT FURNISHED UNDER THIS
CONTRACT WILL BE NEW UNLESS OTHERWISE SPECIFIED, AND THAT ALL WORK WILL BE OF GOOD QUALITY, FREE
FROM FAULTS AND DEFECTS AND IN CONFORMANCE WITH THE CONTRACT DOCUMENTS FOR A PERIOD OF NOT
LESS THAN ONE YEAR FROM THE COMPLETION OF CONSTRUCTION. ALL WORK NOT CONFORMING TO THESE
REQUIREMENTS, INCLUDING SUBSTITUTIONS NOT PROPERLY APPROVED AND AUTHORIZED, MAY BE CONSIDERED
DEFECTIVE.
E- INSTALLATION NOTES (MAY NOT APPLY)
1. ALL INSTALLED PLUMBING, MECHANICAL AND ELECTRICAL EQUIPMENT TO OPERATE QUIETLY AND BE FREE OF
VIBRATION.
2. UNLESS OTHERWISE NOTED IN MECHANICAL DRAWINGS OR SPECIFICATIONS, HOLD DUCTS AND MECHANICAL
EQUIPMENT TIGHT TO STRUCTURE ABOVE.
3. THE CONTRACTOR SHALL NOT LOCATE CEILING DIFFUSERS OR REGISTERS WHERE FULL HEIGHT SHELVING,
FILES OR STORAGE UNITS ARE INDICATED ON PLANS. (IF APPLICABLE)
4. ALL CEILING DIFFUSERS AND REGISTERS TO BE THE SAME COLOR AS THE CEILING UNLESS NOTED OTHERWISE.
5. ALL SURFACES TO BE PROPERLY PRIMED OR PREPARED PRIOR TO INSTALLATION OF SPECIFIED FINISHES.
5. PATCH ALL AREAS WHERE THE FLOOR IS NOT LEVEL OR TRUE PRIOR TO THE INSTALLATION OF SPECIFIED
FLOOR FINISH(-ES).
6. PROVIDE ALL NECESSARY CUT-OUTS FOR THE INSTALLATION OF ELECTRICAL AND VOICE/DATA OUTLETS,
THERMOSTATS, SWITCHES AND OTHER DEVICES.
7. EXTEND ALL FIRE RATED PARTITIONS TO STRUCTURE; FILL ALL VOIDS WITH FIRE SAFING MATERIAL OR FIRE-
RATED CAULK, CONTINUOUS AS REQUIRED BY CODE.
8. ALL FIRE EXTINGUISHER CABINETS OR ELECTRICAL PANELS LOCATED IN RATED PARTITIONS TO BE BACKED
WITH GYPSUM BOARD AS REQUIRED TO MAINTAIN PARTITION RATING.
9. CONTRACTOR IS RESPONSIBLE FOR FIRESTOPPING ALL NEW AND EXISTING FIRE RATED PARTITIONS AND ALL
PENETRATION THROUGH RATED AREAS INCLUDING SLABS. SEAL TO MAINTAIN PROPER RATING.
10. WHERE EXISTING FIREPROOFING HAS BEEN REMOVED AT COLUMNS OR BEAMS, NEW FIREPROOFING TO BE
INSTALLED TO COMPLY WITH THE REQUIRED FIRE RATING. CONTRACTOR TO VERIFY IN FIELD.
11. WHERE PIPES, CONDUITS OR LOW TENSION WIRING PENETRATE A FIRE RATED ENCLOSURE, THE SPACE
AROUND SHALL NOT EXCEED 1/2" AND SHALL BE PACKED SOLID WITH BATT INSULATION AND FITTED WITH
ESCUTCHEON PLATES ON BOTH SIDES OR EQUIVALENT TREATMENT TO INSURE COMPLIANCE WITH FIRE RATING.
12. WHERE DUCT OR PART OF DUCT IS RUNNING PARALLEL OVER FIRE RATED PARTITION, EXTEND RATED
PARTITION AROUND DUCT TO EFFECT COMPLETE MAINTENANCE OF FIRE-RATING.
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A001
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
GENERAL NOTES
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
NO. DESCRIPTION DATE
EXISTIN G SIN G LE STO R Y R ESID EN C ETO BE R EM O VED
LOT 24
EXISTING PROPERTY LINE
N44°15'40"W
118.97' (P)
N43°58'39"W
119.12' (M)EXISTING PROPERTY LINES10°51'23"E102.17' (M)S10°56'10"E102.17' (P)2 5 ' S E T B A C K7.5' SETBACK20' SETBACK7.5' SETBACK20' SETBACK
A M B E R J A C K L A N E
(6 0 ' R /W 2 3 ' C U R B E D A N D G U T T E R E D A S P H A L T )BACK OF CURB
EDGE OF PAVEMENT
EXISTING CONC.
DRIVEWAY EXISTING MOVABLEWOOD SHEDA/C
24" MANHOLE
WATER SUPPLE
TIE-IN
SEWER DRAIN
TIE-INL2L1L3
C 120'
-0"7'-6"20'-0"7 '-6 "25'-0"39'-0 3 /4"24'
-7 1/2"5'
-7 3/4"15'
-3"
2 3 '-6"4'-0 1 /4"1 0 '-6 1/2 "8'-7 1/2"15'-11"3 '-0 1 /4 "
1 3 '-8 "15'-8 3/4"30'
-1 1/4"30'-7 1/4"LOT 24
EXISTING PROPERTY LINE
N44°15'40"W
118.97' (P)
N43°58'39"W
119.12' (M)EXISTING PROPERTY LINES10°51'23"E102.17' (M)S10°56'10"E102.17' (P)2 5 ' S E T B A C K7.5' SETBACK20' SETBACK7.5' SETBACK20' SETBACK
A M B E R J A C K L A N E
(6 0 ' R /W 2 3 ' C U R B E D A N D G U T T E R E D A S P H A L T )BACK OF CURB
EDGE OF PAVEMENTL2L1L3
C 16'
-9 1/4"20'
-0"22'-1 3/4"7'-6"2'-3"20'-0"1 2 '-5 3 /4 "7 '-2 1 /2 "7 '-6 "
24" MANHOLE
WATER SUPPLE
TIE-IN
SEWER DRAIN
TIE-IN 16'-8 3/4"25'-0"5'-2"23'-5 1/2"6'-7"6'-10 1/4"7'-6"N E W (P R O P O S E D ) S IN G L E
S T O R Y R E S ID E N C E
PERVIOUS ROCKS
DRIVEWAY
NEW A/C
6'-0 1/4"46'-9 3/4"CURVE
C1(P)
C1(M)
RADIUS
120.00'
120.00'
DELTA
---
29°58'28"
ARC LENGTH
---
62.78'
CHORD BEARING
S62°25'18"W
S62°30'53"W
CHORD LENGTH
62.07'
62.06'
CURVE IDENTIFICATION TABLE
LINE
L1(P)(C)
L2(P)
BEARING
N23°42'20"E
N59°08'20"E
DISTANCE
10.00'
75.52'
LINE IDENTIFICATION TABLE
L3(P)S85°20'02"E 50.00'
L2(M)N59°12'35"E 65.18'
L3(M)S85°11'51"E 50.07'
DEMOLITION LEGEND:
DEMOLITION OF EXISTING BUILDING ELEMENTS
EXISTING BUILDING ELEMENTS TO REMAIN
DEMOLISH DOOR & FRAME
EXISTING DOOR & FRAME TO REMAIN
NEW BUIDLING ELEMENTS
GENERAL NOTES: DEMOLITION
1. CONTRACTOR TO COORDINATE SITE, LANDSCAPE AND UTILITY
DEMOLITION WITH OTHER DISCIPLINE DOCUMENTS.
2. CONTRACTOR TO LOCATE EXISTING UTILITIES AND PROTECT AND
MAINTAIN CRITICAL INFRASTRUCTURE THAT SERVES NEARBY BUILDINGS.
3. COORDINATE PROPOSED METHODS AND OPERATIONS OF DEMOLITION
WITH OWNER'S DESIGNATED REPRESENTATIVE PRIOR TO START OF
DEMOLITION WORK. INCLUDE IN SCHEDULE COORDINATION FOR SHUT-
OFF, CAPPING AND CONTINUATION OF UTILITY SERVICES AS REQUIRED.
4. INTERRUPTIONS IN DAILY OPERATIONS MUST BE COORDINATED IN
ADVANCED WITH OWNER'S DESIGNATED REPRESENTATIVE. THIS SHALL
INCLUDE SERVICE INTERRUPTIONS AND CONNECTIONS, RELOCATION OF
OCCUPANTS, REMOVAL OF EQUIPMENT, SHIFTS IN LOCATION OF WORK,
MECHANICAL AND ELECTRICAL DISRUPTION, ETC. ANY OF THE ABOVE
INTERRUPTIONS REQUIRE A MINIMUM OF THREE FULL WORKING DAYS
NOTICE TO THE OWNER. FRIDAY P.M. NOTICE FOR MONDAY A.M.
INTERRUPTIONS WILL NOT BE ACCEPTABLE.
5. CONDUCT DEMOLITION AND DEBRIS REMOVAL IN A SAFE MANNER TO
MINIMIZE INTERFERENCE WITH CORRIDORS, HALLS, STAIRS, AND OTHER
ADJACENT FACILITIES AND TO AVOID DAMAGE TO SAME. DO NOT CLOSE
OR OBSTRUCT TRAFFIC WAYS WITHOUT PERMISSION OF THE OWNER.
6. ERECT TEMPORARY ENCLOSURER(S) AROUND ALL EXTERIOR OPENINGS
CREATED IN THE BUILDING. THE BUILDING SHALL BE LEFT WEATHER TIGHT
AND SECURE AT THE END OF EACH WORKDAY.
7. PROVIDE TEMPORARY DUST ENCLOSURERS AROUND ALL AREAS OF WORK.
PREVENT DUST, DEBRIS, ETC. FROM REACHING ADJACENT AREAS OF
BUILDING.
8. REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS AND
SPECIFICATIONS FOR ADDITIONAL DEMOLITION REQUIREMENTS.
9. ALL SALVAGEABLE MATERIAL AND EQUIPMENT SHOWN OR SCHEDULED TO
REMAIN AS THE PROPERTY OF THE OWNER OR NOT DISCLAIMED BY THE
OWNER PRIOR TO THE BEGINNING OF DEMOLITION WORK SHALL BE
CAREFULLY REMOVED AND STORED WHERE DIRECTED BY THE OWNER.
THE CONTRACTOR SHALL VERIFY WITH THE OWNER ALL ITEMS TO BE
SALVAGED.
10.ALL SALVAGEABLE MATERIAL AND EQUIPMENT SCHEDULED TO BE
REMOVED AND NOT REUSED AND DISCLAIMED BY THE OWNER SHALL
BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE
TRANSPORTED FROM THE SITE AS THEY ARE REMOVED. STORAGE OR
SALE OF REMOVED ITEMS ON SITE WILL NOT BE PERMITTED.
11.VERIFY SAVING AND RE-USE OF ALL MISCELLANEOUS ITEMS AND
EQUIPMENT NOT SPECIFICALLY LISTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS WITH THE OWNER PRIOR TO DEMOLITION.
12.UNLESS OTHERWISE INDICATED ON THE DRAWINGS OR THE FINISH
SCHEDULE, ALL PORTIONS OF THE EXISTING BUILDING (INCLUDING
FINISHES) DISTURBED BY DEMOLITION OF EXISTING CONSTRUCTION
AND/OR INSTALLATION OF NEW CONSTRUCTION, INCLUDING MECHANICAL
AND ELECTRICAL WORK, SHALL BE REPAIRED AS REQUIRED AND
RETURNED TO ITS ORIGINAL UNDISTURBED CONDITION OR BETTER.
13.REMOVE ALL EXISTING WALL CONSTRUCTION, MILLWORK, EQUIPMENT,
ETC. SHOWN DASHED ON THIS DRAWING IN ITS ENTIRETY TO THE EXTENT
SHOWN ON THE DRAWINGS. PARTITIONS SHALL BE REMOVED FROM
FLOOR TO UNDERSIDE OF STRUCTURE ABOVE UNLESS OTHERWISE
NOTED. AT EXISTING INTERSECTING WALL WHERE ONE WALL HAS BEEN
DEMOLISHED, PREPARE NEWLY EXPOSED AREA OF WALL TO MATCH
EXISTING ADJACENT SURFACES.
14.EXISTING WALLS INDICATED TO REMAIN ARE FOR PURPOSES OF
EXONOMY ONLY. CONTRACTOR MAY ASSUME, IF MORE EXPEDIENT FOR
CONSTRUCTION OR LESS EXPENSIVE FOR THE OWNER, THAT EXISTING
CONSTRUCTION MAY BE REMOVED AND REPLACED WITH NEW
CONSTRUCTION ACCEPTABLE TO THE ARCHITECT AT NO ADDITIONAL
COST TO THE OWNER.
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A002
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
EXISTING AND NEW SITE /
PLOT PLANS, AND NOTES
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SITE CALCULATIONS:
TOTAL LAND AREA:0.25 ACRES = 10,844 SF
35% MAXIMUM LOT COVERAGE:3,795.4 SF
50% MAXIMUM IMPERVIOUS:5,422 SF
------------------------------NEW CONSTRUCTION:
NEW 1ST FLOOR:2,331 SF
TOTAL HEAT AND COOLING COVERAGE:2,331 SF
NEW 2 CAR GARAGE:442 SF
NEW FRONT PORCH COVERAGE:288 SF
NEW REAR PORCH COVERAGE:139 SF
NEW FRONT PORCH COVERAGE:29 SF
NEW SECONDARY COVERAGE:24 SF
(A/C CONCRETE PADS, STEPS)
TOTAL NEW AREA UNDER ROOF 2,941 SF
------------------------------LOT COVERAGE:
AREA UNDER ROOF:2,941 SF
SECONDARY COVERAGE:24 SF
ESTIMATED DRIVEWAY (TBD W/ BUILDER & CITY):646 SF
TOTAL LOT COVERAGE:3,611 SF
TOTAL PERVIOUS:7,233 SF / 66.70%
TOTAL IMPERVIOUS:3,611 SF / 33.30%
TRUE
NORTH
SCALE: 1" = 10'-0"2 EXISTING AND NEW SITE / PLOT PLAN
P L A N
N O R T H
NO. DESCRIPTION DATE
36"FRIDGE36"ELECTRICTOPDWDRYERWASHER
GENERAL NOTES:
1. DO NOT SCALE DRAWINGS.
2. ALL DIMENSIONS ARE TO FACE OF STUD/BAND
BOARD EXCEPT WHERE NOTED.
3. COORDINATE ALL WORK WITH ANY ENGINEERING
DRAWINGS, NOTES, OR REPORTS.
4. VERIFY ALL WORK WITH OWNER PRIOR TO
INITIALIZATION.
5. COORDINATE ALL DIMENSIONS WITH ACTUAL
EQUIPMENT, CABINETS, OR OTHER APPARATUS AS
SUPPLIED OR SELECTED BY OWNER.
6. SEE OTHER DRAWINGS THIS SET FOR ADDITIONAL
INSTRUCTIONS, NOTES, AND SPECIFICATIONS.
7. BRAND AND STYLE OF WINDOWS AND DOORS BY
BUILDER - COORDINATE WITH ENERGY CALCS.
8. ALL EXTERIOR WINDOWS AND DOORS TO HAVE
8'-0" HEAD A.F.F. UNLESS NOTED OTHERWISE.
9. ALL FINISHES TO BE DETERMINED BY BUILDER
AND OWNER.
10. DENOTES 5.0/5.7 SQFT. EGRESS REQUIRED
11. MINIMUM 11" TREADS - MAXIMUM 7 3/4" RISERS.
12. PROVIDE ELECTRICAL CONDUITS TO ISLAND AS
REQUIED PER PLANS.
13. VERIFY INTERIOR BEARING WALLS PER
STRUCTURAL ENGINEERING DRAWINGS.
14. PROVIDE ALL REQUIRED WOOD BLOCKING AT
WALLS FOR CABINETS AND TV'S AND ETC.
15. EXTERIOR DIMENSIONS ARE TO FACE OF
MASONRY AT EXTERIOR WALLS.
16. INTERIOR WALLS ARE WITH GYPSUM EACH SIDE
OR PVC WALL PANELLING OR VINYL WALL PANELS.
17. SQUARE FOOTAGES ARE CALCULATED FROM
EXTERIOR FACE OF WALLS.
18. CONTRACTOR TO COORDINATE ALL FURNISHES
INCLUDING BATHROOM TUB, VANITY AND
TOILET SIZES AND MANUFACTURERS WITH
OWNER.
19. ALL EXTERIOR STAIRS THAT ARE UTILIZING
PREFABRICATED OR WOOD STAIRS SHALL
INSTALL A STOOP TO MEET MINIMUM LATEST
EDITION OF THE FBC.
E
A202
1
A2012
A201
1
A202 2 43'-4"6'-6"3'-0"6'-6"5'-4"5'-4"5'-4"18'-0"3'-0"5'-0"8'-8"58'-0"2'-2"16'-0"2'-2"10'-4"4'-10"3'-0"4'-10"4'-8"3'-8"3'-0"3'-4"8'-8"11'-4"3'-0"1'-8"24"x22"ATTIC ACCESS24"x22"
ATTIC
ACCESS 23'-4"3'-0"31'-8"4020 FIXED OPAQUEHEAD AT 8'-0" A.F.F.3050 SH
HEAD AT 8'-0" A.F.F.30803050 SH
HEAD AT 8'-0" A.F.F.3050 SHHEAD AT 8'-0" A.F.F.SLOPE FLOOR
1/8" PER FOOT
18'-0" x 8'-0" O.H. GARAGE
DOOR
3050 SH
HEAD AT 8'-0" A.F.F.
3050 SH
HEAD AT 8'-0" A.F.F.308026802680268026802680
2680
GLASS
2480
2080
2680 2880LOUVERED2080
5080 DOUBLE
DOOR
5080 DOUBLE
DOOR 26805080 DOUBLE DOOR2680
26805080 DOUBLE
DOOR
30806"6"6"4"4"
TEMPERED GLASS
ENCLOSURE O/TILES
1/2 WALL 93" LAV.DOUBLE SINK*VENT E.F.TO EXT.*VENT E.F.TO EXT.36" LAV.
OWNERS BEDROOM
15'-0" x 18'-0"
C.H. AT 10'-3"
32" x 60"
TUB
BEDROOM
10'-8" x 12'-6"
C.H. AT 10'-3"
BEDROOM
10'-9" x 12'-6"
C.H. AT 10'-3"
HALLWAY
3'-4" x 7'-4 1/2"
C.H. AT 10'-3"3680 C.O.5880 C.O.DINING ROOM
8'-8" x 12'-0"
C.H. AT 10'-3"
KITCHEN
13'-3" x 21'-3"
C.H. AT 10'-3"36" DOUBLESINKVENT
HOOD
SEE CABINET MANUF.
SHOP DRAWINGS FOR
SIZE AND SPECS
ISLAND3'-8" x 9'-0"GREAT ROOM
15'-3" x 22'-3"
C.H. AT 10'-3"CLOSETCLOSET
PANTRY
COATSLINENSWH
LAUNDRY
SINKHALLWAY
3'-10" x 6'-0"
C.H. AT 10'-3"
STUDY ROOM
9'-2" x 10'-11"
C.H. AT 10'-3"
FOYER
4'-6" x 9'-6"
C.H. AT 10'-3"*VENT E.F.TO EXT.24" LAV.32" x 60"
TUB
AHU
HALLWAY
4'-8" x 13'-3 1/2"
C.H. AT 10'-3"
OWNERS BATH
9'-10" x 11'-05"
C.H. AT 10'-3"LINENSSHOWER
36" x 60"
WIC
9'-10" x 11'-11"
C.H. AT 10'-3"
BATH
5'-0" x 8'-8"
C.H. AT 10'-3"
BATH
5'-0" x 7'-6"
C.H. AT 10'-3"
BEDROOM
10'-9" x 11'-9"
C.H. AT 10'-3"FRONT PORCH
4'-8" x 5'-4"
C.H. AT 14'-3"
4'-8"1'-0"5'-4"REAR PORCH
8'-8" x 16'-0"
C.H. AT 10'-3"
A/C CONDENSER
UNIT 1
58'-0"52'-0"58'-0"
E
E
E
E
12" CEILING TRAY12" CEILING TRAY12" CEILING TRAY12" CEILING TRAY
EMERGENCY ESCAPE
AND RESCUE OPENING
EMERGENCY ESCAPE
AND RESCUE OPENING
EMERGENCY ESCAPE
AND RESCUE OPENING EMERGENCY ESCAPEAND RESCUE OPENING*VENT E.F.
TO EXT.
1
A301
(TYP)
1
A301
(TYP)
1
A301
(TYP)
2
A301
SIM
2
A301
SIM
1
A302
(TYP)
1
A302
(TYP)
MEDIA PANEL
CENTRAL
LOCATION
WASHER / DRYER FINAL
LOCATION TO BE DETERMINED
BY OWNER / BUILDER
LAUNDRY SINK FINAL
LOCATION TO BE DETERMINED
BY OWNER / BUILDER
WATER HEATER LOCATION
TO BE DETERMINED BY
OWNER / BUILDER
AIR HANDLER
LOCATION TO BE
DETERMINED BY
OWNER / BUILDER
R302.5.1 OPENING PROTECTION:
OPENINGS FROM A PRIVATE GARAGE
DIRECTLY INTO A ROOM USED FOR SLEEPING
PURPOSES SHALL NOT BE PERMITTED.
OTHER OPENINGS BETWEEN GARAGE AND
RESIDENCE SHALL BE EQUIPPED WITH SOLID
WOOD DOORS NOT LESS THAN 1 3/8"
(35 MM) INCHES THICKNESS, SOLID OR
HONEYCOMB CORE STEEL DOORS NOT LESS
THAN 1 3/8" (35 MM) THICK, OR 20-MINUTE
FIRE-RATED DOORS. NOTE: DOOR TO BE
SELF-CLOSING.
R302.6 DWELLING / GARAGE SEPARATION:
THE GARAGE SHALL BE SEPARATED AS
REQUIRED BY TABLE R302.6. OPENINGS IN
GARAGE WALLS SHALL COMPLY WITH
SECTION R302.5. THIS PROVISION DOES NOT
APPLY TO GARAGE WALLS THAT ARE
PERPENDICULAR TO THE ADJACENT
DWELLING
UNIT WALL.
SEE SHEET A001 FOR R302.5
AND R302.6 CODE
STEPS IN GARAGE TO BE MIN.
11" TREADS AND MAX. 7 3/4"
RISERS
PROVIDE WATER HEATER
PROTECTION PER FBC R 1307.3.1
AS REQUIRED
ALL AS-BUILT AND NEW CONSTRUCTION DIMENSIONS ARE SUBJECT TO VERIFICATION IN FIELD -BUILDER IS
RESPONSIBLE FOR VERIFICATION ONCE DEMOLITION HAS BEGUN AND PRIOR TO ORDERING
PRE-MANUFACTURED TRUSSES, STRUCTURAL MATERIALS, ARCHICTURAL MATERIALS, AND ALL
CONSTRUCTION ELEMENTS.
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A100
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
FLOOR PLAN
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 1/4" = 1'-0"1 FLOOR PLAN
NO. DESCRIPTION DATE
A202
1
A2012
A201
1
A202 2
RIDGE HIPHIPHIPHIPRIDGEHIPHIPRIDGEHIPHIPVALLEYHIPHIPHIPHIPVALLEYRIDGE5:12 SLOPE
5:12 SLOPE
5:12 SLOPE
5:12 SLOPE
5:12 SLOPE 5:12 SLOPE
5:12 SLOPE
5:12 SLOPE
5:12 SLOPE
5:12 SLOPE 5:12 SLOPE
5:12 SLOPE
O.H.
1'-6"58'-0"
O.H.
1'-6"O.H.1'-6"58'-0"O.H.1'-6"O.H.
1'-6"8'-10"
O.H.
1'-6"12'-8"
O.H.
1'-6"4'-2"
O.H.
1'-6"6'-0"
O.H.
1'-6"20'-4"
O.H.
1'-6"O.H.1'-6"13'-2"O.H.1'-6"O.H.1'-6"3'-4 1/2"O.H.1'-6"5'-3 1/2"O.H.1'-6"43'-4"O.H.1'-6"7'-2"O.H.1'-6"61'-0"61'-0"61'-0"55'-0"INDICATES PORCH BEAMS
AND COLUMNS PER STRUCTURAL,
TYPICAL
INDICATES PORCH BEAMS
AND COLUMNS PER STRUCTURAL,
TYPICAL
NEW ARCHITECTURAL SHINGLE
ROOF, TYPICAL WITH 30# FELT UNDERLAYMENT
AND PLYWOOD WOOD DECK OVER TWO (2)
LAYERS OF RIGID FOAM BOARD INSULATION
OVER ZIP SYSTEM ROOF SHEATHING AND
PRE-ENGINEERED TRUSSES
NEW ARCHITECTURAL SHINGLE
ROOF, TYPICAL WITH 30# FELT UNDERLAYMENT
AND PLYWOOD WOOD DECK OVER TWO (2)
LAYERS OF RIGID FOAM BOARD INSULATION
OVER ZIP SYSTEM ROOF SHEATHING AND
PRE-ENGINEERED TRUSSES
OVERHANG PER ROOF PLAN
(NON-VENTED, USE CEMENT
BOARD SOFFITS)
PLUMB CUT 1X6 P.T. SUB
FASCIA WITH 1X P.T. DRIP
EDGE FASCIA
DASHED LINES INDICATE
FACE OF WALL AT STRUCTURE
BELOW, TYPICAL10'-3" PLATE A.F.F.10'-3" PLATE A.F.F.
10'-3" PLATE A.F.F.
10'-3" PLATE A.F.F.10'-3" PLATE A.F.F.10'-3" PLATE A.F.F.10'-3" PLATE A.F.F.
12'-3" PLATE A.F.F.12'-3" PLATE A.F.F.10'-3" PLATE A.F.F.14'-3" PLATE A.F.F.
14'-3" PLATE A.F.F.
10'-3" PLATE A.F.F.
10'-3" PLATE A.F.F.
10'-3" PLATE A.F.F.
10'-3" PLATE A.F.F.10'-3" PLATE A.F.F.10'-3" PLATE A.F.F.10'-3" PLATE A.F.F.10'-3" PLATE A.F.F.CONTRACTOR NOTE:
"O.H." DENOTES OVERHANG.
GENERAL NOTES:
1. THE ROOFING PLAN IS GENERAL IN NATURE AND INDICATES APPROXIMATE CONDITIONS AT THE PROJECT
SITE AT THE TIME THE ROOFING IS READY TO BE INSTALLED. THE CONTRACTOR SHALL NOTIFY THE
ARCHITECT AND/OR OWNER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH THE WORK.
2. GENERAL CONTRACTOR TO COORDINATE WITH TRUSS MANUFACTURER AND MECHANICAL CONTRACTOR THE
PROVISION OF ALL A/C DUCT WORK OPENINGS THROUGH TRUSSES. SUBMIT SHOP DRAWINGS FOR APPROVAL.
3. GENERAL CONTRACTOR AND TRUSS MANUFACTURER TO COORDINATE ALIGNMENT OF TRUSSES. IF ANY
DISCREPANCIES CONTACT THE OWNER AND/OR ARCHITECT PRIOR TO FABRICATION OF TRUSSES.
4. FOR COMPLETE ROOFING PLAN DETAILS REFER TO STRUCTURAL DRAWINGS BY OTHERS.
5. ATTIC INSULATION TO BE AS INDICATED ON INDEX SHEET AND PER THE PLAN NOTATIONS.
6. OWNER OPTION: PROVIDE ALUMINUM GUTTERS AND DOWNSPOUTS - GC TO INSTALL/COORDINATE.
7. ROOFING MATERIAL COLOR TO BE SELECTED BY OWNER SELECTED MANUFACTURER.
8. METAL FLASHING TO BE 26 GA. G-90 GALVANIZED UNLESS NOTED OTHERWISE.
9. UNDERLAYMENT TO SELF ADHERING UNDERLAYMENT MEMBRANE (POLYGLASS TU PLUS OR EQUAL) OR
OTHER CODE COMPLIANT UNDERLAYMENT AS SELECTED BY OWNER.
10. PROVIDE PRESSURE-TREATED WOOD BATTENS AS/IF RECOMMENDED BY MANUFACTURER, AND FOR ALL
ROOFS WITH SLOPES GREATER THAN 7:12 WHEN BATTENS ARE USED, PROVIDE BATTENS 4'-0" LONG MAXIMUM
WITH 1/2" SPACE BETWEEN ENDS OF BATTENS, FOR WATER DRAINAGE.
11. ALL ROOFING TO BE ARCHITECTURAL SHINGLE UNLESS OTHERWISE NOTED.
ROOF VENT CALCULATIONS (1:300 RULE):
AREA CONDITIONED & PORCHES: 3,323 SF
NFA REQ'D 3,323 / 300 = 11.08 SF (1,595.04 IN
2) OF N.F.A.
REQUIRED SPLIT EVENLY BETWEEN SOFFITS
AND UPPER ROOF (797.52 IN2 EACH)
VENTS TO BE DISCUSSED BY BUILDER (T.B.D.)
NOTES:
1. SOFFIT VENT TYPE TO BE DETERMINED BY G.C.
2. THE CALCULATIONS AND VENT LOCATIONS INDICATED ON THESE PLANS ARE FOR REFERENCE
ONLY. RIDGE VENTS ARE CALCULATED AT 12.5 SQUARE INCHES PER FOOT OF N.F.A. ORV'S ARE
CALCULATED AT 60 SQUARE INCHES OF N.F.A. IT IS THE RESPONSIBILITY OF THE G.C. TO
COORDINATE VENTILATION TO BE INSTALLED WITH MANUFACTURER AND PROVIDE ALL
NECESSARY VENTILATION AT ROOF AS PER THE FLORIDA BUILDING CODE.
3. PROVIDE ROOF EXHAUST N.F.A. SHALL NOT EXCEED THE PROVIDED INTAKE SOFFIT N.F.A. NTAKE
SOFFIT SHALL BE EQUAL TO OR GREATER THAN EXHAUST N.F.A.
4. 18" FULLY VENTED VINYL SOFFIT PROVIDES APPROXIMATELY 9 SQ.IN. PER SQ. FT OF NET FREE
AREA.
5. 12" FULLY VENTED SCREEN SOFFIT PROVIDES APPROXIMATELY 6 SQ.IN. PER SQ. FT. OF NET FREE
AREA.
ABBREVIATIONS:
N.F.A. NET FREE AREA
R.V. RIDGE VENT
O.R.V. OFF RIDGE VENT
L.F.R. LINEAR FEET OR RIDGE
ROOF FRAMING NOTES:
1. THE ROOFING PLAN IS GENERAL IN NATURE AND INDICATES APPROXIMATE CONDITIONS AT THE PROJECT SITE
AT THE TIME THE ROOFING IS READY TO BE INSTALLED. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT
AND/OR OWNER OF ANY DISCREPENCIES PRIOR TO PROCEEDING WITH THE WORK.
2. GENERAL CONTRACTOR TO COORDINATE W/ TRUSS MANUFACTURER AND MECHANICAL CONTRACTOR THE
PROVISION OF ALL A/C DUCT WORK OPENINGS THROUGH TRUSSES. SUBMIT SHOP DRAWINGS FOR APPROVAL.
3. ROOF SLOPE SHALL BE5:12 UNLESS OTHERWISE NOTED.
4. ROOF OVERHANG SHALL BE 1'-5 1/2" FROM FACE OF FRAME TO TAIL OF TRUSS U.O.N. GABLE ENDS SHALL BE 12"
U.O.N. OVERHANGS SHALL BE SQUARE CUT.
5. NEW ROOFING SHALL BE ARCHITECTURAL SHINGLES UNLESS OTHERWISE NOTES - SELCTION BY BUILDER.
6. HEADER AND BEAM SIZES TO BE DETERMINED BY STRUCTURAL ENGINEER.
7. CONTRACTOR TO PROVIDE SOFFIT AND ROOF VENTING AS REQUIRED TO MEET MANUFACTURER
SPECIFICATIONS AND LOCAL CODE REQUIREMENTS.
8. 8" HEEL AT ALL RAFTER/TRUSSES U.O.N.
9. EXTERIOR DIMENSIONS TO SHEATHING OVER 2X6 STUDS (SHEATHING FLUSH W/ FOUNDATION). EXTERIOR
DIMENSION TO MASONRY FLUSH WITH FOUNDATION.
10. ATTIC INSULATION TO BE AS INDICATED PER SHEET SERIES A300's.
11. SEALED ATTICS, NO VENTILATION REQUIRED.
12. VENT CALCULATIONS ARE VOID IF BUILDER OPTS FOR THE USE OF OPEN CELLED "ICYNENE" SPRAY FOAM
INSULATION IN THE ATTIC SPACES. NO ROOF OR SOFFIT VENTS WILL BE REQUIRED AS THE ATTICS WILL BE
CONDITIONED. BUILDER TO PROVIDE REQUIRED PRODUCT APPROVALS AND ENERGY FORMS.
13. NEW ROOF SHALL BE CONVENTIONAL FRAMING AND/OR PRE-MANUFACTURERED TRUSSES, U.O.N.
14. FRAMING LUMBER SHALL BE #2 SP OR BETTER.
15. TRUSS ENGINEER TO ADD HEELS AS REQUIRED TO PLAN FASCIAS AT OPPOSING PITCHES.
16. INSTALL ROOF VENTS PER MANUFACTURER WRITTEN INSTRUCTIONS PER FBC SECTION R806.
17. INSTALL TWO (2) LAYERS OF FELT AT ALL ROOF SECTIONS WITH A 3:12 ROOF PITCH OR LESS, U.O.N.
RIGID FOAM INSULATION BOARD ATTIC NOTES:
1. VENT CALCULATIONS ARE VOID IF BUILDER
OPTS FOR THE USE OF RIGID FOAM
INSULATION BOARD IN THE - NO ROOF OR
SOFFIT VENTS WILL BE REQUIRED AS THE
ATTICS WILL BE CONDITIONED - BUILDER TO
PROVIDE REQUIRED PRODUCT APPROVAL
AND ENERGY FORMS.
2. OPT. DEHUMIDIFIER SYSTEM - SELECTION BY
BUILDER.
3. THE ROOF CALCULATIONS ARE BASED ON
THE SOFT. OF THE CONDITIONED SPACE AND
COVERED PORCH.
ROOF INSULATION NOTES:
1. TWO (2) LAYERS OF RIGID FOAM INSULATION
ALL JOINTS STAGGERED.
2. OUTERMOST LAYER SHALL BE 2" FOIL
FACED XPS RIGID FOAM INSULATION.
3. INNER LAYER SHALL BE 1 1/2" THICK XPS
RIGID FOAM INSULATION.
4. FLORIDA RESIDENTIAL BUILDING CODE AND
ENERGY CONSERVATION CODE, THE MINIMUM
CONTRIBUTION OF THE USE OF RIGID FOAM
INSULATION BOARDS SHALL BE AT LEAST 40%
OF TOTAL R-VALUE AT ROOF.
ALL AS-BUILT AND NEW CONSTRUCTION DIMENSIONS ARE SUBJECT TO VERIFICATION IN FIELD -BUILDER IS
RESPONSIBLE FOR VERIFICATION ONCE DEMOLITION HAS BEGUN AND PRIOR TO ORDERING
PRE-MANUFACTURED TRUSSES, STRUCTURAL MATERIALS, ARCHITECTURAL MATERIALS, AND ALL
CONSTRUCTION ELEMENTS.
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A140
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
ROOF PLAN
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 1/4" = 1'-0"1 ROOF PLAN
NO. DESCRIPTION DATE
ROOF FLASHING NOTES:
1.DRIP EDGE FLASHING:A DRIP EDGESHALL BE PROVIDED AT THE EAVES AND GABLE ENDS OF
TILED ROOFINGS AND SHALL OVERLAP A MINIMUM OF 3". EAVE DRIP EDGES SHALL EXTEND 1/2"
BELOW THE SHEATHING, AND EXTEND BACK ON THE ROOF FOR A MINIMUM OF 2".
THE DRIP EDGE SHALL BE FASTENED AMAXIMUM OF 6" ON CENTER. THE DRIP EDGE AT EAVES
SHALL BE INSTALLED OVER THE UNDERLAYMENT. THERE SHALL BE A MINIMUM OF 4" WIDTH OF
ROOF CEMENT INSTALLED OVER THE DRIP EDGE FLANGE.
WHERE THE BASIC WIND SPEED PER FIGURE R301.2(4) IS 110 MPH OR GREATER OR THE MEAN
ROOF HEIGHT EXCEEDS 33 FEET, DRIP EDGES SHALL FASTENED A MAXIMUM OF 4" ON CENTER.
INSTALL A MINIMUM 8" WIDE ANTI-PONDING METAL FLASHING TOENSURE POSITIVE DRAINAGE
OVER FASCIA/STARTER STRIP. NAIL TOP EDGE OF FLANGE ON TOP ROOF. THE UNDERLAYMENT
SHALL CONFORM WITH ASTM D 226, TYPE 1 OR TYPE 2, OR ASTM D4869 TYPE 1 OR TYPE 2.
THE UNDERLAYMENT SHALL BE INSTALLED IN WATER SHEDDING MEANS,STARTING WITH THE
EAVE EDGE AND ROLLED HORIZONTALLY. UNDERLAYMENT SHALL OVERLAP A MINIMUM OF 19'
AND BE FASTENED AT 36" ON CENTER MAXIMUM.
2.VALLEY FLASHING:ALL VALLEY FLASHING IS TO BE INSTALLED PER MANUFACTURER
INSTALLATION GUIDE OR SPECIFICATIONS PRIOR TO INSTALLING FINISHED ROOFING TILES.
(a)FOR CLOSED VALLEY INSTALLATION, INSTALL CLOSED VALLEY METAL, A MINIMUM WIDTH OF
16" - 24" WITH A MINIMUM 2 1/2" HIGH CENTER DIVERTER AND A MINIMUM 1" METAL EDGE RETURNS
OR A RIBBED DESIGN WITH 1" CENTER DIVERTER, A MINIMUM OF (4) 3/8" RIBS SPACED 3 1/2" WITH
(3) 3/4" FLANGE. LAP JOINTS A MIMUM OF 6" AND APPLY A COATING OR SEPARATOR SHEET.
(b) FOR OPEN VALLEYS INSTALLATION, INSTALL OPEN VALLEY WITH A MINIMUM OF 16" TO 24" WITH
A MINIMUM OF 1" HIGH TWIN CENTER DIVERTER AND A MINIMUM 1" METAL EDGE RETURNS. LAP
JOINTS A MINIMUM OF 6" AND APPLY A COATING OR SEPARATOR SHEET.
(c) OPTION OF UTILIZING VALLEY METAL WITH RETURNS, FIRSTLY, SECURE WITH CLIPS
FABRICATED FROM SIMILAR OR COMPATIBLE MATERIAL, CLIP 1" METAL EDGE RETURNS TO
BATTEN STRIP WITH ROOFING NAIL THROUGH METAL STRIP. SECONDLY, TRIM METAL AT ALL
VALLEY/RIDGE JUNCTIONS, ENSURING WATER SHEDDING CAPABILITIES INTO THE VALLEY. THIRD,
INSTALL LEAD SOAKER AT ALL VALLEY/RIDGE JUNCTIONS, TURN LEAD UP A MINIMUM OF 1" TO
CREATE A WATER DIVERTER, ENSURING WATER SHEDDING CAPABILITIES ONTO THE VALLEY.
LASTLY, THE OUTER EDGE OF THE VALLEY METAL SHALL OVERLAP DECK FLANGE OF DRIP EDGE
A MINIMUM OF 1" AND CENTER OF VALLEY FLASHING SHALL EXTEND A MINIMUM OF 2" BEYOND
DRIP EDGE.
3.RIDGE FLASHING:AT THE RIDGE LINE, APPLY THE FINAL LAYER OF UNDERLAYMENT BY FOLDING
THE UNDERLAYMENT OVER THE RIDGE AND FASTEN AT 36 INCHES ON CENTER MACIMUM AT THE
OPPOSITE SIDE OF THE ROOF. CONTINUE TO REPEAT THE PROCESS AT THE OPPOSITE SIDE OF
THE ROOF. UPON COMPLETION, THERE SHALL BE TWO LAYERS OF UNDERLAYMENT
OVERLAPPING THE RIDGE.
4.HIP FLASHING:AT THE HIP LINE, APPLY THE FINAL LAYER OF UNDERLAYMENT BY FOLDING THE
UNDERLAYMENT OVER THE HIP LINE AND FASTEN AT 36 INCHES ON CENTER MACIMUM AT THE
OPPOSITE SIDE OF THE ROOF. CONTINUE TO REPEAT THE PROCESS AT THE OPPOSITE SIDE OF
THE ROOF. UPON COMPLETION, THERE SHALL BE TWO LAYERS OF UNDERLAYMENT
OVERLAPPING THE HIP.
5.CRICKETS AND SADDLES FLASHING:A CRICKET OR SADDLE SHALL BE INSTALLED ON THE RIDGE
OF ANY CHIMNEY GREATER THAN (30) INCHES (762 mm) WIDE. CRICKET OR SADDLE COVERINGS
SHALL BE SHEET METAL OR OF THE SAME MATERIAL AS THE ROOF COVERING.
THE RIDGE AND VALLEY FLASHING OF CRICKETS OR SADDLES SHALL BE THE SAME AS THE RIDGE
AND VALLEY FLASHING ON THE MAIN ROOF.
6.BASE AND COUNTER FLASHING:BASE AND COUNTER FLASHING SHALL BE INSTALLED IN
ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS, OR A CONTINUOUS
METAL - MIN. 4 INCH BY 4 INCH "L" FLASHING SHALL BE SET IN APPROVED FLASHING CEMENT AND
SET FLUSH TO THE BASE OF THE WALL, AND OVER THE UNDERLAYMENT. BOTH HORIZONTAL AND
VERTICAL METAL FLANGES SHALL BE FASTENED 6 INCHES (152 mm) ON CENTER WITH APPROVED
FASTENERS.
ALL LAPS SHALL BE A MINIMUM OF 4 INCHES (102 mm), FLL SEALED IN APPROVED FLASHING
CEMENT. FLASHING SHALL START AT THE LOWER PORTION OF THE ROOF TO ENSURE WATER-
SHEDDING CAPABILITIES OF ALL METAL LAPS. THE ENTIRE EDGE OF THE HORIZONTAL FLANGE
SHALL BE SEALED, COVERING ALL NAIL PENETRATIONS WITH APPROVED FLASHING CEMENT AND
MEMBRANE. SHINGLES SHALL OVERLAP THE HORIZONTAL FLANGE, AND SHALL BE SET IN
APPROVED FLASHING CEMENT.
BASE FLASHING SHALL BE OF EITHER CORROSION-RESISTANT METAL PROVIDED IN SECTION
R905.2.8.1 OR MINERAL SURFACE ROLL ROOFING, WEIGHTING A MINIMUM OF (77) POUNDER PER (
100) SQUARE FEET (3.76 kg/m2).
COUNTER FLASHING SHALL BE CORROSION-RESISTANT METAL WITH A MINIMUM THICKNESS
PROVIDED IN TABLE 903.1 IN THE FLORIDA BUILDING CODE 2015 5TH EDITION.
NOTE:
REFER TO THE FLORIDA ROOFING, SHEET METAL AND AIR CONDITIONING CONTRACTORS (FRSA),
CONCRETE AND CLAY ROOF TILE INSTALLATION MANUAL FOR MORE INFORMATION.
1
1
2
4
3
5
6 CONTINUOUS CLEAT, FASTEND
6" O.C. MAXIMUM4" MIN.4" MIN.
1/4" HEM
KEMPEROL FIELD MEMBRANE -TURN
DOWN VERTICAL FACE OF WALL
FASTENERS 4" O.C. STAGGERED 1"
KEMPEROL MEMBRANE FLASHING -EXTEND
FULL WIDTH OF FLANGE AND 4" MINIMUM
ONTO KEMPEROL FIELD MEMBRANE
METAL DRIP EDGE -PRIME FLANGE
8" KEMPEROL MEMBRANE STRIP
OVER METAL JOINTS (OPTIONAL)
FACE OF SHEATHING
G.C. "Z" BAR FLASHING INSTALLED
PRIOR TO AND UNDER PAPER BACK
METAL LATH OR SIMILAR
CONT. P.T. 1X4
METAL FLASHING INSTALLED ON TOP
OF ROOF FELT OR PEEL AND STICK
MEMBRANE AND PRIOR TO TILES
ROOFING MATERIAL PER
ROOF PLAN TO BE
COORDINATED BY BUILDER,
EDGES AND PENETRATIONS
TO BE SEALED WITH ROOFING
CEMENT OVER 30# FELT OR
PEEL AND STICK MEMBRANE ON
STRUCTURAL FRAMING
NOTE:
ROOF SLOPES MEETS
WALL
FACE OF SHEATHING
G.C. "Z" BAR FLASHING INSTALLED
PRIOR TO AND UNDER PAPER BACK
METAL LATH OR SIMILAR
CONT. P.T. 1X4
8" WIDE CONTINUOUS ROLL FLASHING NAILED
TO SIDE OF 1X4 AND FACE OF ROOF SHEATHING
INSTALLED PRIOR TO ROOF FELT OR PEEL AND
STICK MEMBRANE AND SHINGLES
ROOFING MATERIAL PER
ROOF PLAN TO BE
COORDINATED BY BUILDER,
EDGES AND PENETRATIONS
TO BE SEALED WITH ROOFING
CEMENT OVER 30# FELT OR
PEEL AND STICK MEMBRANE ON
STRUCTURAL FRAMING
ROOFING MATERIAL PER
ROOF PLAN TO BE
COORDINATED BY BUILDER,
EDGES AND PENETRATIONS
TO BE SEALED WITH ROOFING
CEMENT OVER 30# FELT OR
PEEL AND STICK MEMBRANE ON
STRUCTURAL FRAMING
METAL VALLEY
FLASHING
ICE AND WATER
SHIELD STRIP
FLASHING
EXTERIOR FINISH
PER PLAN
OUTSIDE FACE OF
EXTERIOR WALL
2"
HOLD BACK FASCIA AND
DRIP EDGE 2" FROM
FACE OF WALL
FASCIA
ROOFING PER SPECIFICATIONS
KICK-OUT
SEE
ELEVATION
EXTERIOR STUDMETAL DRIP EDGE
FASCIA
ROOF SHEATHING
(WRB) OVERLAPS THE 5X5 FLASHING
5X5 FLASHING WITH KICK-OUT
TO SHED WATER AWAY FROM HOUSE
(WRB) WEATHER RESISTANT BARRIER
EXTERIOR WALL SHEATHING
OUTSIDE FACE OF
EXTERIOR WALL
2"
1 1 6
METAL DRIP EDGE
26 GUAGE GALVANIZED
N.T.S.
"Z" FLASHING
29 GUAGE GALVANIZED
N.T.S.
5X5 GALVANIZED FLASHING
26 GUAGE GALVANIZED
N.T.S.
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A150
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
FLASHING LOCATION
DIAGRAM, DETAILS, AND
NOTES
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 1/4" = 1'-0"1 ROOF FLASHING LOCATIONS DIAGRAM
SCALE: 12" = 1'-0"2 DRIP EDGE FLASHING DETAIL
SCALE: 3" = 1'-0"3 HEADWALL FLASHING DETAIL
SCALE: 3" = 1'-0"
4 SIDEWALL FLASHING DETAIL
SCALE: 3" = 1'-0"
5 VALLEY FLASHING DETAIL
SCALE: 1 1/2" = 1'-0"
6 KICK-OUT FLASHING DETAILS
NO. DESCRIPTION DATE
EXTERIOR ELEVATION NOTES:
1. ALL FINISHES, COLORS, ETC. TO BE
COORDINATED W/ OWNER PRIOR TO
PURCHASE AND/OR INSTALLATION.
2. OWNER APPROVAL SHALL BE OBTAINED
PRIOR TO ANY FIELD CHANGE,
SUBSTITUTION, OR ALTERATION FROM
APPROVED DESIGN.
3. ALL INTERIOR AND EXTERIOR
ARCHITECTURAL ACCENTS, FINISHES, ETC.
SHALL BE OF LIKE MATERIAL, COLOR, AND
FINISH UNLESS APPROVED BY OWNER FOR
DEVIATION FROM OWNER SELECTION.
4. U.N.O. ALL EXTERIOR TRIM SHALL BE AS
FOLLOWS...HARDIE TRIM.
A. HEADS: (5/4 SMOOTH) 1x6
B. SILL: (5/4 SMOOTH) 1x6
C. JAMBS: (5/4 SMOOTH) 1x4
D. SOFFIT BAND: (5/4 SMOOTH) 1x8
E. CORNER TRIM: (5/4 SMOOTH) 1x4
5. PROVIDE DOWNSPOUTS AS REQ. BY
OWNER. RUN TO UNDERGROUND
DRAINAGE PIPING AND RUN TO DAYLIGHT.
6. WHERE ABOVE GROUND UTILITIES OCCUR,
ROUTE INTO THE NEW STRUCTURE IN A
NEAT AND ORDERLY MANNER.
7. COORDINATE FINISH HEIGHTS WITH WALL
SECTIONS AND DETAILS CONTAINED IN
THE ENTIRE SET OF DRAWINGS. VERIFY ALL
DISCREPANCIES WITH OWNER AND
DESIGNER.
NEW ARCHITECTURAL SHINGLES AS REQUIRED
PER MANUFACTURER SPECIFICATIONSN
TYPICAL WITH 30# FELT UNDERLAYMENT
AND PLYWOOD WOOD DECK OVER TWO (2)
LAYERS OF RIGID FOAM BOARD INSULATION
OVER ZIP SYSTEM ROOF SHEATHING AND
PRE-ENGINEERED TRUSSES
TOP SLAB
EL. = 0'-0"
LEVEL 1 BEARING
EL. = 10'-3"
TOP OF ROOF
EL. = 20'-4"
5
12
5
12
APPROXIMATE LOCATION
A/C CONDENSER UNIT 1
5
12
5
12
5
12
TOP OF ROOF
EL. = 15'-6 1/2"
TOP OF ROOF
EL. = 18'-1 1/2"
TOP OF ROOF
EL. = 15'-11 1/4"
SQUARE CUT FASCIA
AND VINYL VENTED SOFFIT (VENTED)
OR CEMENT BOARD (NON-VENTED)
STEP DOWN TO PORCH
SEE PLAN
STYLE OF EXTERIOR DOORS AND
WINDOWS TO BE DISCUSSED BY
BUILDER, TYPICAL AT ALL
LOCATIONS
SIDING AND CORNER TRIM (INSTALL
PER MANUFACTURERS SPECS) -COLOR
TBD BY BUILDER
LEVEL 1 BEARING
EL. = 12'-3"
LEVEL 1 BEARING
EL. = 14'-3"2'-2"1'-4 3/4"
DECORATIVE BRACKET
TO BE DISCUSSED WITH
OWNER / CONTRACTOR
TYPICAL
1'-6"
STYLE OF SHUTTER TO
BE DISCUSSED BY BUILDER
TYPICAL AT ALL LOCATIONS
SIDING AND CORNER TRIM (INSTALL
PER MANUFACTUERS SPECS) -COLOR
TBD BY BUILDER
SQUARE CUT FASCIA
AND VINYL VENTED SOFFIT (VENTED)
OR CEMENT BOARD (NON-VENTED)
NEW ARCHITECTURAL SHINGLES AS REQUIRED
PER MANUFACTURER SPECIFICATIONSN
TYPICAL WITH 30# FELT UNDERLAYMENT
AND PLYWOOD WOOD DECK OVER TWO (2)
LAYERS OF RIGID FOAM BOARD INSULATION
OVER ZIP SYSTEM ROOF SHEATHING AND
PRE-ENGINEERED TRUSSES
5
12
TOP SLAB
EL. = 0'-0"
LEVEL 1 BEARING
EL. = 10'-3"
5
12
TOP OF ROOF
EL. = 20'-4"
5
12
STYLE OF EXTERIOR DOORS AND
WINDOWS TO BE DISCUSSED BY
BUILDER, TYPICAL AT ALL
LOCATIONS
TOP OF ROOF
EL. = 15'-6 1/2"6"TYPICAL
1'-6"
STYLE OF SHUTTERS TO
BE DISCUSSED BY BUILDER
APPROXIMATE LOCATION
A/C CONDENSER UNIT
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A201
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
EXTERIOR ELEVATIONS
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024SCALE: 1/4" = 1'-0"1 FRONT ELEVATION
SCALE: 1/4" = 1'-0"2 RIGHT ELEVATION
NO. DESCRIPTION DATE
EXTERIOR ELEVATION NOTES:
1. ALL FINISHES, COLORS, ETC. TO BE
COORDINATED W/ OWNER PRIOR TO
PURCHASE AND/OR INSTALLATION.
2. OWNER APPROVAL SHALL BE OBTAINED
PRIOR TO ANY FIELD CHANGE,
SUBSTITUTION, OR ALTERATION FROM
APPROVED DESIGN.
3. ALL INTERIOR AND EXTERIOR
ARCHITECTURAL ACCENTS, FINISHES, ETC.
SHALL BE OF LIKE MATERIAL, COLOR, AND
FINISH UNLESS APPROVED BY OWNER FOR
DEVIATION FROM OWNER SELECTION.
4. U.N.O. ALL EXTERIOR TRIM SHALL BE AS
FOLLOWS...HARDIE TRIM.
A. HEADS: (5/4 SMOOTH) 1x6
B. SILL: (5/4 SMOOTH) 1x6
C. JAMBS: (5/4 SMOOTH) 1x4
D. SOFFIT BAND: (5/4 SMOOTH) 1x8
E. CORNER TRIM: (5/4 SMOOTH) 1x4
5. PROVIDE DOWNSPOUTS AS REQ. BY
OWNER. RUN TO UNDERGROUND
DRAINAGE PIPING AND RUN TO DAYLIGHT.
6. WHERE ABOVE GROUND UTILITIES OCCUR,
ROUTE INTO THE NEW STRUCTURE IN A
NEAT AND ORDERLY MANNER.
7. COORDINATE FINISH HEIGHTS WITH WALL
SECTIONS AND DETAILS CONTAINED IN
THE ENTIRE SET OF DRAWINGS. VERIFY ALL
DISCREPANCIES WITH OWNER AND
DESIGNER.
SQUARE CUT FASCIA
AND VINYL VENTED SOFFIT (VENTED)
OR CEMENT BOARD (NON-VENTED)
TOP OF ROOF
EL. = 20'-4"
TOP SLAB
EL. = 0'-0"
LEVEL 1 BEARING
EL. = 10'-3"
5
12
5
12
NEW ARCHITECTURAL SHINGLES AS REQUIRED
PER MANUFACTURER SPECIFICATIONSN
TYPICAL WITH 30# FELT UNDERLAYMENT
AND PLYWOOD WOOD DECK OVER TWO (2)
LAYERS OF RIGID FOAM BOARD INSULATION
OVER ZIP SYSTEM ROOF SHEATHING AND
PRE-ENGINEERED TRUSSES
6X6 WRAPPED TO 8" WITH
12" BASE -10" CAPSTEP DOWN TO PORCH
SEE PLAN
STYLE OF EXTERIOR DOORS AND
WINDOWS TO BE DISCUSSED BY
BUILDER, TYPICAL AT ALL
LOCATIONS
SIDING AND CORNER TRIM (INSTALL
PER MANUFACTURERS SPECS) -COLOR
TBD BY BUILDER
STYLE OF SHUTTER TO
BE DISCUSSED BY BUILDER
TYPICAL AT ALL LOCATIONS
TYPICAL
1'-6"
5
12
5
12
SIDING AND CORNER TRIM (INSTALL
PER MANUFACTUERS SPECS) -COLOR
TBD BY BUILDER
TOP OF ROOF
EL. = 20'-4"
TOP OF ROOF
EL. = 18'-1 1/2"
5
12
TOP OF ROOF
EL. = 15'-11 1/4"
TOP OF ROOF
EL. = 15'-6 1/2"
STYLE OF EXTERIOR DOORS AND
WINDOWS TO BE DISCUSSED BY
BUILDER, TYPICAL AT ALL
LOCATIONS
SQUARE CUT FASCIA
AND VINYL VENTED SOFFIT (VENTED)
OR CEMENT BOARD (NON-VENTED)
TOP SLAB
EL. = 0'-0"
LEVEL 1 BEARING
EL. = 10'-3"
LEVEL 1 BEARING
EL. = 12'-3"6"DECORATIVE BRACKET
TO BE DISCUSSED WITH
OWNER / CONTRACTOR2'-2"1'-4 3/4"STYLE OF SHUTTER TO
BE DISCUSSED BY BUILDER
TYPICAL AT ALL LOCATIONS
NEW ARCHITECTURAL SHINGLES AS REQUIRED
PER MANUFACTURER SPECIFICATIONSN
TYPICAL WITH 30# FELT UNDERLAYMENT
AND PLYWOOD WOOD DECK OVER TWO (2)
LAYERS OF RIGID FOAM BOARD INSULATION
OVER ZIP SYSTEM ROOF SHEATHING AND
PRE-ENGINEERED TRUSSES
TYPICAL
1'-6"
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A202
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
EXTERIOR ELEVATIONS
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 1/4" = 1'-0"
1 REAR ELEVATION
SCALE: 1/4" = 1'-0"2 LEFT ELEVATION
NO. DESCRIPTION DATE
INSULATION NOTES:
1. PROVIDE R-38 BATT INSULATION AT ALL ROOFS.
2. PROVIDE R-19 BATT INSULATION AT ALL
EXTERIOR/GARAGE 2X6 WALLS.
3. PROVIDE R-7.5 MINIMUM RIGID INSULATION AT
ALL EXTERIOR CMU WALLS.
3. PROVIDE 24" WIDE 2" THICK RIGID INSULATION
AT ALL SLABS AT WALKOUT CONDITIONS.
4. FOAM SEAL ALL JOINTS AND OPENINGS.
TYPICAL WALL SECTION NOTES / AS REQUIRED:
1. PROVIDE WATERPROOFING MEMBRANE AT ALL ELEVATION
CHANGES. USE PERMA-CRETE INTERIOR/EXTERIOR ARCRLYIC
MASONRY SURFACE SEALER OR EQUIVALENT, TYPICAL.
2. IN THE EVENT THAT THE FOUNDATION IS LOCATED IN A FLOOD
ZONE, PROVIDE PROPER FLOOD VENTS AT STEM WALLS PER
STRUCTURAL DRAWINGS, FLORIDA BUILDING CODE AND
LOCAL MUNICIPALITIES.
3. BUILDER TO PROVIDE ALL PRODUCT APPROVAL SHEETS.
CONC. SLAB
G R A D E E L E V A T I O N
EXTERIOR
INTERIOR
PER
PLAN
12
NEW ARCHITECTURAL SHINGLES
TYPICAL WITH 30# FELT UNDERLAYMENT
AND PLYWOOD WOOD DECK OVER TWO (2)
LAYERS OF RIGID FOAM BOARD INSULATION
OVER 5/8" ZIP SYSTEM ROOF SHEATHING AND
PRE-ENGINEERED TRUSSES
1/2" OR 5/8" GYPSUM BOARD
AT CEILING JOIST, TYP.
1x FURRING STRIPS
AT 16" O.C.
GYPSUM BD. MIN.
OVER FURRING STRIPS
NOTES:
1.IN THE EVENT THAT THE FOUNDATION IS LOCATED
IN A FLOOD ZONE, PROVIDE PROPER FLOOD VENTS
OR BREAK AWAY FRAMING PER STRUCTURAL
DRAWINGS, FLORIDA BUILDING CODE AND LOCAL
MUNICIPALITIES.
2.PROVIDE WATERPROOFING MEMBRAINE AT ALL
ELEVATION CHANGES. USE PERMA-CRETE
INTERIOR/EXTERIOR ACRYLIC MASONRY SURFACE
SEALER OR EQUIVALENT, TYPICAL.
3.BUILDER TO PROVIDE ALL PRODUCT APPROVAL
NUMBERS BLOCKING8" HEEL8" HEEL BLOCKING
PLUMB CUT FASCIA WITH ALUMINUM DRIP
EDGE AND SOFFIT TO BE INSTALLED PER
MANUFACTURER SPECIFICATIONS OVER
1X DRIP FASCIA OVER P.T. 1X6 SUB FASCIA
EXISTING FOUNDATION
ATTIC SPACE
R-38 BATT INSULATION
G.C. TO COORDIANTE WITH
ENERGY CALCULATIONS
MASONRY WALL
LIQUID MEMBRANE
MOISTURE BARRIER (CLASS lll
VAPOR RETARDER)
APPLY PER MANUFACTURERS
INSTRUCTION
AIR AND WATER BARRIER
SEALANT
3/4" REFLECTIVE AIR SPACE
BETWEEN THE INSULATION
FOIL AND FURRING STRIPS
FIRESTOP
CONCRETE TIE BEAM,
SEE STRUCTURAL
CONTINUOUS BEAD OF
SEALANT
UNDERLAYMENT PER
LATEST FBC
OVERHANG PER ROOF PLAN (VENTED VINYL
SOFFIT IF VENTED. FOR NON VENTED, USE
CEMENT BOARD SOFFITS)
NO SEALANT BETWEEN
SIDING AND FLASHING
CONTINUOUS START STRIP
OVER FLASHING INSTALLED
PER MANUFACTURERS
INSTRUCTIONS
CLEARANCE1/4"1X6 TRIM WITH VENTED
CEMENT BOARD SOFFITS (NON-VENTED)
CONTINUOUS EAVE TRIM HEIGHT MAY VARY
VAPOR-PERMEABLE
WEATHER BARRIER
(HOUSE WRAP)
1x FURRING STRIPS
AT 16" O.C.
3/4" REFLECTIVE AIR SPACE
1 1/2" RIGID XPS INSULATION POLYISO
BOARD WITH A FOIL BACKING
(SEE OPTIONAL INTERIOR WALL SYSTEM)
BOARD AND BATTEN VINYL EXTERIOR SIDING
AND TRIM OVER APPROVED HOUSEWRAP
INSTALLED PER MANUFACTURERS WRITTEN
SPECIFICATIONS, TO BE SELECTEC BY OWNER /
BUILDER -U.O.N. ON ELEVATION
OPTIONAL INTERIOR WALL SYSTEM:
1.OWNER / BUILDER INTERIOR WALL SYSTEM OPTION; 4'-0" X 10'-0"
INSOFAST 2 1/2" EXTERIOR EXI FOAM PANELS R10.5 ON CMU WALLS.
2.PER NOTE 1) ABOVE, OWNER / BUILDER SHALL INSTALL PER
MANUFACTURERS WRITTEN SPECIFICATIONS.
3.OWNER / BUILDER SHALL MEET MINIMUM R-VALUE WALL
ASSEMBLY PER THE LATEST FLORIDA ENERGY EFFICIENCY CODE
FLOR BUILDING CONSTRUCTION.
G R A D E E L E V A T I O N
VINYL CEILING OVER TRUSS
TO BE DISCUSSED BY BUILDER
NOTE:
1.6" MINIMUM DIMENSION CLEARANCE BETWEEN
EXTERIOR WALL COVERINGS AND GRADE AND 4"
MINIMUM CLEARANCE TERMITE INSPECTION ZONE
ABOVE SLAB.
2.GENERAL CONTRACTOR TO PROVIDE FLORIDA
PRODUCT APPROVAL INFORMATION ON SHINGLES,
FLASHING AND VAPOR BARRIER. INSTALL PER
CODE AND MANUFACTURER SPECIFICATIONS.BLOCKING8" HEELINSTALL VAPOR
BARRIER IN
ACCORDANCE WITH
ASTM E 1643-98
FOUNDATION PER STRUCTURAL
TREATED AND DEBRIS
FREE SOIL FILL
ATTIC SPACE
R-38 BATT INSULATION
G.C. TO COORDIANTE WITH
ENERGY CALCULATIONS
INSTALL VAPOR
BARRIER IN
ACCORDANCE WITH
ASTM E 1643-98 VARIESHEEL BLOCKINGHEADER BEAM
SEE STRUCTURAL
6X6 WRAPPED TO 12", TYPICAL
10" BASE -16" CAP
(SEE STRUCTURAL)
1/8" PER FT.
CONC. SLAB
(SEE STRUCTURAL)SEE PLANINTERIOR CEILING HEIGHTCONC. SLAB
EXTERIOR
INTERIOR
1/2" OR 5/8" GYPSUM BOARD
AT CEILING JOIST, TYP.
1x FURRING STRIPS
AT 16" O.C.
GYPSUM BD. MIN.
OVER FURRING STRIPS
MASONRY WALL
LIQUID MEMBRANE
MOISTURE BARRIER (CLASS lll
VAPOR RETARDER)
APPLY PER MANUFACTURERS
INSTRUCTION
AIR AND WATER BARRIER
SEALANT
3/4" REFLECTIVE AIR SPACE
BETWEEN THE INSULATION
FOIL AND FURRING STRIPS
FIRESTOP
CONCRETE TIE BEAM,
SEE STRUCTURAL
CONTINUOUS BEAD OF
SEALANT
UNDERLAYMENT PER
LATEST FBC
NO SEALANT BETWEEN
SIDING AND FLASHING
CONTINUOUS START STRIP
OVER FLASHING INSTALLED
PER MANUFACTURERS
INSTRUCTIONS
VAPOR-PERMEABLE
WEATHER BARRIER
(HOUSE WRAP)
1x FURRING STRIPS
AT 16" O.C.
3/4" REFLECTIVE AIR SPACE
BETWEEN THE INSULATION
FOIL AND FURRING STRIPS
1 1/2" RIGID XPS INSULATION POLYISO
BOARD WITH A FOIL BACKING
(SEE OPTIONAL INTERIOR WALL SYSTEM)
CONTINUOUS EAVE TRIM HEIGHT MAY VARY
PER
PLAN
12
NEW ARCHITECTURAL SHINGLES
TYPICAL WITH 30# FELT UNDERLAYMENT
AND PLYWOOD WOOD DECK OVER TWO (2)
LAYERS OF RIGID FOAM BOARD INSULATION
OVER 5/8" ZIP SYSTEM ROOF SHEATHING AND
PRE-ENGINEERED TRUSSES
8" HEEL BLOCKING
PLUMB CUT FASCIA WITH ALUMINUM DRIP
EDGE AND SOFFIT TO BE INSTALLED PER
MANUFACTURER SPECIFICATIONS OVER
1X DRIP FASCIA OVER P.T. 1X6 SUB FASCIA
6"BOARD AND BATTEN VINYL EXTERIOR SIDING
AND TRIM OVER APPROVED HOUSEWRAP
INSTALLED PER MANUFACTURERS WRITTEN
SPECIFICATIONS, TO BE SELECTEC BY OWNER /
BUILDER -U.O.N. ON ELEVATION
OPTIONAL INTERIOR WALL SYSTEM:
1.OWNER / BUILDER INTERIOR WALL SYSTEM OPTION; 4'-0" X 10'-0"
INSOFAST 2 1/2" EXTERIOR EXI FOAM PANELS R10.5 ON CMU WALLS.
2.PER NOTE 1) ABOVE, OWNER / BUILDER SHALL INSTALL PER
MANUFACTURERS WRITTEN SPECIFICATIONS.
3.OWNER / BUILDER SHALL MEET MINIMUM R-VALUE WALL
ASSEMBLY PER THE LATEST FLORIDA ENERGY EFFICIENCY CODE
FLOR BUILDING CONSTRUCTION.
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A301
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
BUILDING SECTIONS
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 1" = 1'-0"1 SIDING - SECTION AT WALL
SCALE: 1" = 1'-0"2 SIDING - SECTION AT PORCH
WALL ASSEMBLY R-VALUE
1.BOARD AND BATTEN VINYL SIDING AND HOUSEWRAP = R-0.5
2.6" MASONRY WALL = R-1
3.1 1/2" RIGID XPS INSULATION = R-7.5
4.POLYISO BOARD WITH FOIL BACKING = R-9
5.3/4" REFLECTIVE AIR SPACE = R-2
6.GYPSUM WALLBOARD = R-0.5
TOTAL WALL R-VALUE = R-20.5
ROOF ASSEMBLY R-VALUE
1.ARCHITECTURAL SHINGLES AND UNDERLAYMENT = R-0.5
2.23/32" PLYWOOD SHEATHING = R-0.9
3.2" RIGID XPS INSULATION BOARD = R-10
4.1 1/2" RIGID XPS INSULATION BOARD = R-7.5
5.ZIP SYSTEM SHEATHING = R-0.6
6.12" BATT INSULATION = R-38
TOTAL ROOF R-VALUE = R-57
WALL ASSEMBLY R-VALUE
1.BOARD AND BATTEN VINYL SIDING AND HOUSEWRAP = R-0.5
2.6" MASONRY WALL = R-1
3.1 1/2" RIGID XPS INSULATION = R-7.5
4.POLYISO BOARD WITH FOIL BACKING = R-9
5.3/4" REFLECTIVE AIR SPACE = R-2
6.GYPSUM WALLBOARD = R-0.5
TOTAL WALL R-VALUE = R-20.5
ROOF ASSEMBLY R-VALUE
1.ARCHITECTURAL SHINGLES AND UNDERLAYMENT = R-0.5
2.23/32" PLYWOOD SHEATHING = R-0.9
3.2" RIGID XPS INSULATION BOARD = R-10
4.1 1/2" RIGID XPS INSULATION BOARD = R-7.5
5.ZIP SYSTEM SHEATHING = R-0.6
6.12" BATT INSULATION = R-38
TOTAL ROOF R-VALUE = R-57
NO. DESCRIPTION DATE
1/2" OR 5/8" GYPSUM BOARD
AT CEILING JOIST, TYP.
FIRESTOP
LAP SIDING WITH TRIM OR SIMILAR OVER
APPROVED HOUSEWRAP INSTALLED
PER MANUFACTURER WRITTEN
SPECIFICATIONS U.O.N. REFER TO
ELEVATIONS FOR LOCATION OF MATERIALS
(MATCH EXISTING IF REQUIED)
6 MIL MOISTURE BARRIER
WALL SHEATHING SUBSTRATE
OVER 2X STUDS OR TRUSS
(REFER TO STRUCTURAL)
NO SEALANT BETWEEN
SIDING AND FLASHING
CONTINUOUS START STRIP
OVER FLASHING INSTALLED
PER MANUFACTURERS
INSTRUCTIONS
SIDING (WOOD
OR VINYL)
NEW ARCHITECTURAL SHINGLES
TYPICAL WITH 30# FELT UNDERLAYMENT
AND PLYWOOD WOOD DECK OVER TWO (2)
LAYERS OF RIGID FOAM BOARD INSULATION
OVER 5/8" ZIP SYSTEM ROOF SHEATHING AND
PRE-ENGINEERED TRUSSES
ATTIC SPACE
R-38 BATT INSULATION
G.C. TO COORDIANTE WITH
ENERGY CALCULATIONS
PLUMB CUT FASCIA WITH ALUMINUM DRIP
EDGE AND SOFFIT TO BE INSTALLED PER
MANUFACTURER SPECIFICATIONS OVER
1X DRIP FASCIA OVER P.T. 1X6 SUB FASCIA
CONTINUOUS BEAD OF
SEALANT
ATTIC SPACE
R-38 BATT INSULATION
G.C. TO COORDIANTE WITH
ENERGY CALCULATIONS
PRE-ENGINEERED TRUSS
REFER TO STRUCTURAL
(SEE NOTE 4)
WALL SHEATHING SUBSTRATE
OVER 2X STUDS OR TRUSS
(REFER TO STRUCTURAL)
SIDING (WOOD
OR VINYL)
NEW ARCHITECTURAL SHINGLES
TYPICAL WITH 30# FELT UNDERLAYMENT
AND PLYWOOD WOOD DECK OVER TWO (2)
LAYERS OF RIGID FOAM BOARD INSULATION
OVER 5/8" ZIP SYSTEM ROOF SHEATHING AND
PRE-ENGINEERED TRUSSES
ATTIC SPACE
R-38 BATT INSULATION
G.C. TO COORDIANTE WITH
ENERGY CALCULATIONS
PLUMB CUT FASCIA WITH ALUMINUM DRIP
EDGE AND SOFFIT TO BE INSTALLED PER
MANUFACTURER SPECIFICATIONS OVER
1X DRIP FASCIA OVER P.T. 1X6 SUB FASCIA
PRE-ENGINEERED TRUSS
REFER TO STRUCTURAL
(SEE NOTE 4)
OVERHANG PER ROOF PLAN
(NON VENTED CEMENT BOARD
SOFFITS TO MATCH
EXISTING (F.V. & COORD.)
NEW MOLDING
OR TRIM
CONTINUE TRIM HEIGHT
MAY VARY
WALL SECTION WITH OVERHANG
CONTRACTORS OPTION
CONC. SLAB
G R A D E E L E V A T I O N
EXTERIOR
INTERIOR
1x FURRING STRIPS
AT 16" O.C.
GYPSUM BD. MIN.
OVER FURRING STRIPS
NOTES:
1.IN THE EVENT THAT THE FOUNDATION IS LOCATED
IN A FLOOD ZONE, PROVIDE PROPER FLOOD VENTS
OR BREAK AWAY FRAMING PER STRUCTURAL
DRAWINGS, FLORIDA BUILDING CODE AND LOCAL
MUNICIPALITIES.
2.PROVIDE WATERPROOFING MEMBRAINE AT ALL
ELEVATION CHANGES. USE PERMA-CRETE
INTERIOR/EXTERIOR ACRYLIC MASONRY SURFACE
SEALER OR EQUIVALENT, TYPICAL.
3.BUILDER TO PROVIDE ALL PRODUCT APPROVAL
NUMBERS.
4.REFER TO SHEET A301 IF TRUSSES ARE SPANNING
IN OPPOSITE DIRECTION.
EXISTING FOUNDATION
MASONRY WALL
LIQUID MEMBRANE
MOISTURE BARRIER (CLASS lll
VAPOR RETARDER)
APPLY PER MANUFACTURERS
INSTRUCTION
AIR AND WATER BARRIER
SEALANT
3/4" REFLECTIVE AIR SPACE
BETWEEN THE INSULATION
FOIL AND FURRING STRIPS
CONCRETE TIE BEAM,
SEE STRUCTURAL
UNDERLAYMENT PER
LATEST FBC
NO SEALANT BETWEEN
SIDING AND FLASHING
CONTINUOUS START STRIP
OVER FLASHING INSTALLED
PER MANUFACTURERS
INSTRUCTIONS
CLEARANCE1/4"CONTINUOUS EAVE TRIM HEIGHT MAY VARY
VAPOR-PERMEABLE
WEATHER BARRIER
(HOUSE WRAP)
1x FURRING STRIPS
AT 16" O.C.
3/4" REFLECTIVE AIR SPACE
BETWEEN THE INSULATION
FOIL AND FURRING STRIPS
1 1/2" RIGID XPS INSULATION POLYISO
BOARD WITH A FOIL BACKING
(SEE OPTIONAL INTERIOR WALL SYSTEM)
BOARD AND BATTEN VINYL EXTERIOR SIDING
AND TRIM OVER APPROVED HOUSEWRAP
INSTALLED PER MANUFACTURERS WRITTEN
SPECIFICATIONS, TO BE SELECTEC BY OWNER /
BUILDER -U.O.N. ON ELEVATION
SIDING ON TOP OF MASONRY WALL
OPTIONAL INTERIOR WALL SYSTEM:
1.OWNER / BUILDER INTERIOR WALL SYSTEM OPTION; 4'-0" X 10'-0"
INSOFAST 2 1/2" EXTERIOR EXI FOAM PANELS R10.5 ON CMU WALLS.
2.PER NOTE 1) ABOVE, OWNER / BUILDER SHALL INSTALL PER
MANUFACTURERS WRITTEN SPECIFICATIONS.
3.OWNER / BUILDER SHALL MEET MINIMUM R-VALUE WALL
ASSEMBLY PER THE LATEST FLORIDA ENERGY EFFICIENCY CODE
FLOR BUILDING CONSTRUCTION.
DOUBLE 2x PLATE @ TOP OF
WALL CONNECTION TO DECK/ROOF
ABOVE, IF EXISTING (F.V.)
BATT INSULATION
2x WALL STUDS AT 16" O.C.
2x BLOCKING AT 48" O.C. MAX.
BASE BOARDS PER
OWNER SELECTION
2x BASE PLATE
DESCRIPTION
• 2X4 OR 2X6 WOOD STUDS @ 16" O.C.
• ONE LAYER 5/8" GYP. BD. EA. SIDE
OR 5/8" PVC OR VINYL WALL PANELING
TOP OF SUBFLOOR/SLAB
INTERIOR INTERIOR
WALL BOARD SEE
DESCRIPTION
1/2" OR 5/8" GYPSUM BOARD
AT CEILING JOIST, TYPICAL
TYPICAL WALL SECTION NOTES / AS REQUIRED:
1. PROVIDE WATERPROOFING MEMBRANE AT ALL ELEVATION
CHANGES. USE PERMA-CRETE INTERIOR/EXTERIOR ARCRLYIC
MASONRY SURFACE SEALER OR EQUIVALENT, TYPICAL.
2. IN THE EVENT THAT THE FOUNDATION IS LOCATED IN A FLOOD
ZONE, PROVIDE PROPER FLOOD VENTS AT STEM WALLS PER
STRUCTURAL DRAWINGS, FLORIDA BUILDING CODE AND
LOCAL MUNICIPALITIES.
3. BUILDER TO PROVIDE ALL PRODUCT APPROVAL SHEETS.
BEARING AT FLOOR/CEILING/
ROOF ASSEMBLY
DOUBLE 2x PLATE @ TOP OF
WALL CONNECTION TO DECK/ROOF
ABOVE, IF EXISTING (F.V.)
INSULATION
6-MIL POLY VAPOR BARRIER-
OPTIONAL VERIFY WITH OWNER
WALL BOARD SEE
DESCRIPTION
2x WALL STUDS AT 16" O.C.
2x BLOCKING AT 48" O.C. MAX.
FELT OVERLAP WHERE
OCCURS AT HORIZONTAL
TRANSITIONS
FIRE RATED WALL BOARD
SEE DESCRIPTION
BASE BOARDS PER
OWNER SELECTION
2x BASE PLATE
3/16".
DESCRIPTION
• 2X6 WOOD STUDS AY 16" O.C.
• ONE LAYER 5/8" GYPSUM INTERIOR SIDE
OR 5/8" PVC OR VINYL WALL PANELING.
FIRE RATED
WALL SHEATHING REFER
TO STRUCTURAL
INTERIOR GARAGE
1/2" OR 5/8" GYPSUM BOARD
AT CEILING JOIST, TYPICAL
INSULATION NOTES:
1. PROVIDE R-38 BATT INSULATION AT ALL ROOFS.
2. PROVIDE R-19 BATT INSULATION AT ALL
EXTERIOR/GARAGE 2X6 WALLS.
3. PROVIDE R-7.5 MINIMUM RIGID INSULATION AT
ALL EXTERIOR CMU WALLS.
3. PROVIDE 24" WIDE 2" THICK RIGID INSULATION
AT ALL SLABS AT WALKOUT CONDITIONS.
4. FOAM SEAL ALL JOINTS AND OPENINGS.
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A302
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
BUILDING SECTIONS AND
WALL SECTIONS
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 1" = 1'-0"1 SIDING - SECTION AT WALL WITH ELEVATION > THAN 10'-3"
SCALE: 1 1/2" = 1'-0"2 WALL TYPICAL INTERIOR
SCALE: 1 1/2" = 1'-0"3 WALL TYPICAL AT GARAGE
WALL ASSEMBLY R-VALUE
1.BOARD AND BATTEN VINYL SIDING AND HOUSEWRAP = R-0.5
2.6" MASONRY WALL = R-1
3.1 1/2" RIGID XPS INSULATION = R-7.5
4.POLYISO BOARD WITH FOIL BACKING = R-9
5.3/4" REFLECTIVE AIR SPACE = R-2
6.GYPSUM WALLBOARD = R-0.5
TOTAL WALL R-VALUE = R-20.5
ROOF ASSEMBLY R-VALUE
1.ARCHITECTURAL SHINGLES AND UNDERLAYMENT = R-0.5
2.23/32" PLYWOOD SHEATHING = R-0.9
3.2" RIGID XPS INSULATION BOARD = R-10
4.1 1/2" RIGID XPS INSULATION BOARD = R-7.5
5.ZIP SYSTEM SHEATHING = R-0.6
6.12" BATT INSULATION = R-38
TOTAL ROOF R-VALUE = R-57
NO. DESCRIPTION DATE
1" MAX.DOOR UNDERCUT
FINISH FLOOR
MIN.
1' - 0"HEADERPER DOORMIN.6"LOUVERED OPENING
@ ALL OPENINGS
WITH UNDERCUT DOORS
NOTE:
ALL LOUVERED
OPENINGS
ABOVE DOOR SHALL
BE EQUAL AREA OF THE
INSUDE CONDITIONED
ROOMS
CEILING FRAMING MEMBER OR
BOTTOM CHORD OF ROOF TRUSS
WALL TOP
PLATE
WALL
FRAMING
MEMBER .,
UNDERLYING BOARD
7" FOR SINGLE NAILING.
8" TO 12" FOR DOUBLE NAILING
OR SCREWS
8" FOR SINGLE NAILING.
11" TO 12" FOR DOUBLE NAILING
OR SCREWS
GYPSUM BOARD ATTACHED
TO WALL FRAMING
VERTICAL SECTION, CEILING
FRAMING MEMBER
PERPENDICULAR TO WALL
BLOCKING AS REQUIRED
WALL TOP
PLATE
WALL
FRAMING
MEMBER .UNDERLYING BOARD
8" FOR SINGLE NAILING.
11" TO 12" FOR DOUBLE NAILING
OR SCREWS
GYPSUM BOARD ATTACHED
TO WALL FRAMING
VERTICAL SECTION, CEILING
FRAMING MEMBER
PERPENDICULAR TO WALL
FASTENERS @
CEILING
CEILING FRAMING MEMBER OR
BOTTOM CHORD OF ROOF TRUSS
5" EXPOSURE
NAILS
PREVAILING WIND DIRECTION MEMBRANE ROOF
VALLEY FLASHING
EACH STRIP TO EXTEND
AT LEAST 12" BEYOND
CENTER OF VALLEY
UNDERLAYMENT
CAUTION:
DO NOT LOCATE
NAILS CLOSER THAN
6" TO THE VALLEY
CENTERLINE
INSTALLED PER
MANUFACTURER'S
SPECIFICATIONS
CEMENT LOCATED
UNDER EACH TAB
FASTENERS
36".17".19".19".36".19".
.
WEATHER WATCH WATERPROOFING
UNDERLAYMENT SHOULD BE
INSTALLED
TO A POINT AT LEAST 24" BEYOND
INTERIOR WALL LINE
WALL LINE
WALL LINE
MEMBRANE FLASHING
DRIP EDGE
DRIP EDGE
DECK
UNDERLAYMENT OVERLAPPED
19" TO PROVIDE DOUBLE
COVERAGE ON ROOF DECK
8'-0"4'-0"4'-0"1/2"FLOOR
CEILING PANELS
WEATHERSTRIPPING
AT 1x STOP @ ALL
SIDES OF OPENING
1x STOP
24" x 30" PLYWOOD
ACCESS PANEL WITH
MANUAL ATTACHED
INSULATION
OSB INSULATION BULKHEAD
AT ACCESS OPENING ON ALL
SIDES - PROVIDING
BLOCKING TO SPAN
TRUSSES @ SIZE ON
BOTTOM CHORD MIN.8"GRAVITY HOOD
SEALANT
METAL COLLAR:
SEE SPECIFICATIONS FOR
MATERIAL AND MIN.
THICKNESS
MEMBRANE COLLAR
ASPHALT
SHINGLES
MIN. 30-POUND NON-SELF
ADHERING, NON-PERFORATED
ORGANIC ASPHALT SATURATED
ROOFING FELTROOF WOOD
MEMBER
UNDERLAYMENT
UPPER AND SIDE
SHINGLES OVERLAP
FLANGE AND ARE SET
IN ASPHALT ROOF
CEMENTPREFORMED FLANGE
PLACED OVER PIPE
AND SET IN ASPHALT
ROOF CEMENT
LOWER PART OF
FLANGE OVERLAPS
LOWER SHINGLES
SHINGLE CUT TO FIT
OVER PIPE AND SET
IN ASPHALT ROOF
CEMENT
1/2" GYPSUM BOARD
AT CEILING JOIST, TYP.
CONCRETE
TIE BEAMABOVE TRANSITIONEXTEND WRB MIN. 6"CONTINUOUS BEDDING
SEAL UNDER FLASHING
6 MIL WEATHER RESISTING
BARRIER (WRB)
WRAP WRB AROUND
CONCRETE TIE BEAM
OVER LIQUID MEMBRANEEXTEND WRB 6"SIDING (WOOD
OR VINYL)
MASONRY WALL
METAL FLASHING
NOTE:
1.NO SEALANT BETWEEN SIDING AND FLASHING.
2.REFER TO A301 FOR INFORMATION NOT
SHOWN.CLR.1/4"CONTINUOUS BEAD OF
SEALANT
SHIM UNDER SIDING
PRE-ENGINEERED TRUSS
REFER TO STRUCTURAL
PLUMB CUT FASCIA WITH ALUMINUM DRIP
EDGE AND SOFFIT TO BE INSTALLED PER
MANUFACTURER SPECIFICATIONS OVER
1X DRIP FASCIA OVER P.T. 1X6 SUB FASCIA
REFER TO A150 FOR
DRIP EDGE FLASHING
DETAIL
SEE SHEET SERIES A300
FOR ROOF INFORMATION
PRE-ENGINEERED TRUSS
REFER TO STRUCTURAL
CONTINUOUS
SEALANT TYPICALVARY, NAIL OFF UNDER DRIP-EDGEHEIGHT OF TOP TRIM PIECE MAYP.T. WOOD
1x FASCIA
BOTTOM TRIM PIECE
KEPT STRAIGHT, NAIL
OFF AT BOTTOM
(LAP AS REQUIRED),
TYPICAL
NOTE:
1.NO SEALANT BETWEEN SIDING AND FLASHING.
2.REFER TO A301 FOR INFORMATION NOT
SHOWN.
SIDING
(WOOD OR VINYL)
WALL SHEATHING SUBSTRATE
OVER 2X STUDS OR TRUSS
(REFER TO STRUCTURAL)
SIDING (WOOD
OR VINYL)
SEE SHEET SERIES A300
FOR ROOF INFORMATION
SEE SHEET SERIES A300
FOR INFORMATION ON
INSULATION
PLUMB CUT FASCIA WITH ALUMINUM DRIP
EDGE AND SOFFIT TO BE INSTALLED PER
MANUFACTURER SPECIFICATIONS OVER
1X DRIP FASCIA OVER P.T. 1X6 SUB FASCIA
PRE-ENGINEERED TRUSS
REFER TO STRUCTURAL
OVERHANG PER ROOF PLAN
(NON VENTED CEMENT BOARD
SOFFITS TO MATCH
EXISTING (F.V. & COORD.)
NEW MOLDING
OR TRIM
CONTINUE TRIM HEIGHT
MAY VARY
WALL SECTION WITH OVERHANG
CONTRACTORS OPTION
EXISTING
CONC. SLAB
UNDERLAYMENT PER
LATEST FBC
EPOXY SEALANT
SEALING TAPE
BASEBOARD DRAINAGE
CHANNEL
MASONRY WALL
EXISTING
FOUNDATION
FOUNDATION PER STRUCTURAL
STUCCO PARGE COAT
OVER FOUNDATION WALL
CONC. SLAB
AIR AND WATER BARRIER
SEALANT
UNDERLAYMENT PER
LATEST FBC
NO SEALANT BETWEEN
SIDING AND FLASHING
CONTINUOUS START STRIP
OVER FLASHING INSTALLED
PER MANUFACTURERS
INSTRUCTIONS
CLEARANCE1/4"2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A501
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
TYPICAL DETAILS
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 1/2" = 1'-0"1 DOOR UNDERCUT DETAIL
SCALE: 1 1/2" = 1'-0"2 DRYWALL FRAMING STANDARD DETAILS
SCALE: 1 1/2" = 1'-0"3 ROOF RIDGE SHINGLE DETAIL
SCALE: 3/8" = 1'-0"4 ROOF VALLEY DETAIL
SCALE: 3/4" = 1'-0"5 SHINGLE INSTALLATION DETAIL
SCALE: 1/4" = 1'-0"6 SHINGLE UNDERLAYMENT DETAIL SCALE: 1/2" = 1'-0"7 TYPICAL WALL PANEL & FASTENER LAYOUT
SCALE: 3/4" = 1'-0"8 CEILING ACCESS
SCALE: 1 1/2" = 1'-0"9 ROOF DETAIL - VENT THROUGH ROOF
SCALE: 1/2" = 1'-0"10 ROOF VENT DETAIL
SCALE: 1 1/2" = 1'-0"
11 TYPICAL MASONRY TO SIDING (WOOD OR VINYL) DETAIL
SCALE: 1 1/2" = 1'-0"
12 TYPICAL EAVELESS DETAIL
SCALE: 1 1/2" = 1'-0"13 TYPICAL BASEBOARD DETAIL
SCALE: 1 1/2" = 1'-0"
14 CMU - TYP. SIDING BASE OF WALL DETAIL
NO. DESCRIPTION DATE
SL
OPEFASCIA BOARD
FORMED DRIP-EDGE
NOTES:
IN COLD CLIMATES, WHERE SNOW AND ICE ARE COMMON, A SELF-ADHERINGICE & WATER MEMBRANE OR OTHER MEMBRANE, IS RECOMMENDED AS AN ICE-DAM PROTECTION MEMBRANE
AT ALL POTENTIAL ICE DAMMING LOCATIONS SUCH AS DOWNSLOPE EAVES, VALLEYS, CRICKETS, AROUND PENETRATIONS, AND RAKE EDGES. AT DOWNSLOPE ROOF PERIMETERS IT IS
RECOMMENDED TO EXTEND THE ICE DAM PROTECTION MEMBRANE 24" MIN. UPSLOPE FROM EXTERIOR WALL. CONSULT LOCAL BUILDING CODE REQUIREMENTS.
1. SEVERITY OF LOCALIZED CLIMATE CONDITIONS REGARDING RAINFALL, FREEZE-THAW CYCLING, AND ANTICIPATED SNOW AND ICING MAY DICTATE THE INSTALLATION OF PERIMETER
DRIP-EDGE METAL FLASHING. MOST LOCAL BUILDING CODES REQUIRE THE USE OF PERIMETER SHEET METAL FLASHINGS WITH WATER-SHEDDING ROOF SYSTEMS. REFER TO LOCAL
BUILDING CODE. PERIMETER DRIP EDGE METAL FLASHING IS SUGGESTED TO BE A MINIMUM OF 26-GAUGE PRE-FINISHED/PAINTED GALVANIZED STEEL, 16-OZ. COPPER, .032-INCH THICK
PRE-FINISHED ALUMINUM, OR AN EQUIVALENT LONGEVITY CORROSION-RESISTANT METAL.
2. THE PERIMETER OF THE ROOF DECK SHOULD PROVIDE A CONTINUOUS SOLID WOOD NAILING SURFACE OVER WHICH TO APPLY THE SHEET METAL DRIP-EDGE FLASHING.
3.THE VERTICAL-FACE FLANGE OF SHEET METAL DRIP-EDGE FLASHING SHOULD BE OF SUFFICIENT LENGTH TO PERMIT WATER TO DRIP OFF THE ROOF WITHOUT AFFECTING THE
UNDERLYING CONSTRUCTION DURING TIMES OF NO WIND.
4. THE HORIZONTAL FLANGE (I.E., ROOF SIDE) OF SHEET METAL DRIP-EDGE FLASHING SHOULD EXTEND APPROXIMATELY 2" TO 3" MINIMUM ONTO THE ROOF.
5. IN COLD CLIMATES, CONSIDER INSTALLATION OF AN ISOLATOR SHEET (E.G., A STRIP OF ASPHALT-SATURATED FELT) BETWEEN THE WOOD ROOF DECK AND SHEET METAL FLASHING
FLANGE(S) TO MINIMIZE POTENTIAL FOR CONDENSATION AND RESULTING DECAY.
6. DIMENSIONS SHOWN ARE RECOMMENDED MINIMUMS AND ARE INTENDED TO BE APPROXIMATE TO ALLOW FOR REASONABLE TOLERANCES DUE TO FIELD CONDITIONS.
7. THE PROFILE OF SPECIFIC COMPONENTS, THEIR CONFIGURATION OR SEQUENCING, CAN VARY WITH THE ROOF SYSTEM, WITH CLIMATIC DIFFERENCES, AND REGIONAL OR AREA
PRACTICES.
ASPHALT-SATURATED FELT,
OR OTHER APPROVED
UNDERLAYMENT
DOWNSLOPE PERIMETER EAVE
DRIP-EDGE FLASHING METAL
(Install underneath underlayment at
eave. Trim and bend in end at corner
to form closed.)
PERIMETER RAKE DRIP-EDGE
FLASHING METAL (Install over
underlayment at rake.)
ROOFING NAILS FASTENED AT
APPROXIMATELY 6" TO 10" ON
CENTER (O.C.)
CUTOUT (Keyway)TAB
EXPOSURE
5 5/8"HEADLAP
2"
OFFSET
6 1/2"
OVERLAP
7 5/8"
LENGTH 39 3/8"
WIDTH
13 1/4"
NOTES:
3-TAB STRIP SHINGLE: A SHINGLE ROOFING UNIT MANUFACTURED BY COATING A FIBERGLASS MAT WITH ASPHALT AND HAVING MINERAL
GRANULES, OR OTHER WEATHER-PROTECTIVE SURFACING, EMBEDDED INTO THE ASPHALT ON THE SIDE EXPOSED TO THE WEATHER.
CUTOUT: THE OPEN PORTIONS OF A STRIP SHINGLE BETWEEN THE TABS. SOMETIMES REFERRED TO AS A KEYWAY OR SLOT.
EXPOSURE: THE DIMENSION OF ROOFING THAT IS NOT COVERED OR OVERLAPPED BY THE UPSLOPE COURSE OR COMPONENT. THE EXPOSURE
OF MARATHON SHINGLES IS 5 5/8".
HEADLAP: THE DISTANCE OF OVERLAP MEASURED FROM THE UPPERMOST PLY OR COURSE TO THE POINT WHERE IT LAPS OVER THE
UNDERMOST PLY OR COURSE. THE HEADLAP FOR MARATHON SHINGLES IS 2".
OFFSET: THE DIMENSION THAT 'SETS-OFF' OR STAGGERS THE BUTT END OF ONE MARATHON SHINGLE FROM THE NEXT UPSLOPE OR
DOWNSLOPE COURSE. A TYPICAL OFFSET FOR MARATHON SHINGLES IS 6 1/2", ALTHOUGH OTHER OFFSETS ARE POSSIBLE. AT NO PLACE ON THE
ROOF SHOULD THE BUTT JOINTS WITHIN
ONE COURSE OF SHINGLES BE CLOSER THAN 4" TO THE BUTT JOINTS IN AN ADJACENT COURSE.
OVERLAP: THE DIMENSION THAT A SHINGLE IS COVERED, OR LAPPED, BY THE NEXT UPSLOPE COURSE.
TAB: THE EXPOSED PORTION OF STRIP SHINGLES THAT IS SEPARATED OR DEFINED BY CUTOUTS.
ALTERNATE: SEPARATE
SOFT METAL FLASHING
CAP, INTO PIPE
APPROX
1"
EXAMPLE:
PRE-FABRICATED
FLASHING COLLAR
EXAMPLE: METAL
FLASHING WITH STORM
COLLAR
STORM COLLAR
NOTES:
1. DETAIL DRAWN SHOWING MARATHON. ALSO APPLIES TO OTHER STYLES.
2. IN COLD CLIMATES, WHERE SNOW AND ICE ARE COMMON, AN ICE & WATER PROTECTOR MEMBRANE IS RECOMMENDED AS AN ICE-DAM PROTECTION MEMBRANE AT ALL POTENTIAL
ICE DAMMING LOCATIONS SUCH AS DOWNSLOPE EAVES, VALLEYS, CRICKETS, AROUND PENETRATIONS, AND RAKE EDGES. CONSULT LOCAL BUILDING CODE REQUIREMENTS.
3. SOIL PIPE STACKS SHOULD EXTEND A MINIMUM OF 8" ABOVE ROOF SURFACE.
4. IF EXPOSED FASTENERS ARE PLACED THROUGH VENT'S DOWNSLOPE FLANGE, THEY SHOULD BE WEATHERTIGHT, GASKETED FASTENERS (E.G., RING-SHANK NAILS OR SCREWS).
5. DIMENSIONS SHOWN ARE RECOMMENDED MINIMUMS AND ARE INTENDED TO BE APPROXIMATE TO ALLOW FOR REASONABLE TOLERANCES DUE TO FIELD CONDITIONS.
6. THE PROFILE OF SPECIFIC COMPONENTS, THEIR CONFIGURATION OR SEQUENCING, CAN VARY WITH THE ROOF SYSTEM, WITH CLIMATIC DIFFERENCES, AND REGIONAL OR AREA
PRACTICES.
7. IT MAY BE THAT THE LAYOUT OF THE SOIL PIPE PENETRATION OCCURS IN SUCH A WAY THAT AN ASPHALT SHINGLE BUTT-END JOINT, OR SHINGLE TAB CUTOUT, ALIGNS WITH THE
EDGE AND/OR BACK OF THE METAL FLASHING'S FLANGE. IN THIS CASE, IKO RECOMMENDS INSTALLING A PRESSURE-SENSITIVE SELF-ADHERED MODIFIED-ASPHALT MEMBRANE, OR
OTHER MEMBRANE, TO STRIP-IN THE SIDES AND BACK OF THE METAL FLASHING FLANGE TO EFFECTIVELY EXTEND THESE FLANGES.
METAL PIPE FLASHING
LEAD OR OTHER SOFT METAL PIPE
FLASHING (TURN DOWN INTO SOIL
STACK APPROXIMATELY 1".)
SOIL STACK PIPE (PLUMBING
VENT.)
FASTEN THROUGH UPSLOPE
FLANGE (i.e., blind-nail.) TO
SECURE VENT FLASHING
COMPATIBLE SEALANT
DRAWBAND
ALTERNATE: SEPERATE SOFT
METAL FLASHING CAP
AIRFLOW
A I R F L OW
VENTILATED RIDGE
-- SECTION VIEW
WIND BAFFLES
PRE-MANUFACTURED PLATE-STEELSEISMIC TIES AT RAFTERS PER LOCAL BUILDING CODE(S)
CONTINUOUS RIDGE VENT
INSECT SCREEN AND AIR
DRAFT
FILTER MEDIA
LAMINATED SHINGLES
INSULATION
PLYWOOD OR STRUCTURAL
WOOD
SHEATHING2" MINIMUM AIRSPACE
ASPHALT- SATURATED FELT,
OR
OTHER APPROVED
UNDERLAYMENT
(N) LOW- PROFILE SCREW (Install
for
secure attachement of ridge vent.)
IKO PRE-MANUFACTURED
RIDGE
SHINGLES
INSTALL RIDGE SHINGLES TO SEAL
WITH UNDERLYING RIDGE SHINGLE
(Optional: Hand tab to seal nails as may
be
appropriate.)
NOTES:
1. IN COLD CLIMATES, WHERE SNOW AND ICE ARE COMMON, AN ICE & WATER PROTECTOR MEMBRANE, IS RECOMMENDED AS AN ICE-DAM PROTECTION MEMBRANE AT ALL
POTENTIAL ICE DAMMING LOCATIONS SUCH AS DOWNSLOPE EAVES, VALLEYS, CRICKETS, AROUND PENETRATIONS, AND RAKE EDGES. CONSULT LOCAL BUILDING CODE
REQUIREMENTS.
2. TO DETERMINE AIRFLOW REQUIREMENTS AND/OR VENTILATION, INCLUDING VENT SIZES/NEEDS, REFER TO LOCAL BUILDING CODES.
3. SHEET METAL VENTILATORS ARE SUGGESTED TO BE A MINIMUM OF 26-GAUGE PRE-FINISHED/PAINTED GALVANIZED STEEL, 16 OZ. COPPER, .032-INCH THICK PRE-FINISHED
ALUMINUM, OR AN EQUIVALENT LONGEVITY NON-CORROSIVE METAL SUITABLE FOR WEATHERTIGHT JOINTING OR SOLDERED FABRICATION.
4. IF EXPOSED FASTENERS ARE PLACED THROUGH THE RIDGE VENTILATOR'S DOWNSLOPE FLANGE, THEY SHOULD BE WEATHERTIGHT, GASKETED FASTENERS (E.G. RING-SHANK
NAILS OR SCREWS).
5. NOTE THAT THE ABOVE ILLUSTRATION OF A RIDGE VENT DEPICTS ONE TYPE OR STYLE OF SHINGLE-OVER RIDGE VENTILATOR, BUT THERE ARE NUMEROUS DIFFERENT TYPES
AND PROFILES ON THE MARKET.
6. DIMENSIONS SHOWN ARE RECOMMENDED MINIMUMS AND ARE INTENDED TO BE APPROXIMATE TO ALLOW FOR REASONABLE TOLERANCES DUE TO FIELD CONDITIONS.
7. THE PROFILE OF SPECIFIC COMPONENTS, THEIR CONFIGURATION OR SEQUENCING, CAN VARY WITH THE ROOF SYSTEM, WITH CLIMATIC DIFFERENCES, AND REGIONAL OR AREA
PRACTICES.
8. ILLUSTRATION OF COMPONENTS (E.G. HEAVY-PLATE STEEL RIDGE TIES), FASTENERS, FASTENER NUMBER, SPACING, ETC. IS A GENERIC EXAMPLE OF ONE OPTION TO ALLOW
FOR RIDGE VENTILATION AND NOT INTENDED TO DEPICT ANY PARTICULAR PRODUCT, ARCHITECTURE, NOR ENGINEERING. SEE LOCAL BUILDING CODE AND STRUCTURAL
ENGINEER AS MAY BE REQUIRED.
P R E V A IL IN G W IN D
D IR E C T IO N
NOTES:
1. IN COLD CLIMATES, WHERE SNOW AND ICE ARE COMMON, AN ICE & WATER PROTECTOR MEMBRANE, IS RECOMMENDED AS AN ICE-DAM PROTECTION MEMBRANE AT ALL POTENTIAL
ICE DAMMING LOCATIONS SUCH AS DOWNSLOPE EAVES, VALLEYS, CRICKETS, AROUND PENETRATIONS, AND RAKE EDGES. CONSULT LOCAL BUILDING CODE REQUIREMENTS.
2. TO DETERMINE NEED FOR AIRFLOW AND/OR VENTILATION, INCLUDING VENT SIZES/NEEDS, REFER TO LOCAL BUILDING CODES.
3. CONSIDER SPECIFYING HIP AND RIDGE SHINGLES TO BE FIELD-CUT FROM FULL WIDTH 3-TAB SHINGLES, AS THEY MAY PROVIDE FOR MORE COVERAGE OR OVERLAP OF THE
UNDERLYING FIELD COURSE OF SHINGLES.
4. DIMENSIONS SHOWN ARE RECOMMENDED MINIMUMS AND ARE INTENDED TO BE APPROXIMATE TO ALLOW FOR REASONABLE TOLERANCES DUE TO FIELD CONDITIONS.
5. THE PROFILE OF SPECIFIC COMPONENTS, THEIR CONFIGURATION OR SEQUENCING, CAN VARY WITH THE ROOF SYSTEM, WITH CLIMATIC DIFFERENCES, AND REGIONAL OR AREA
PRACTICES.
INSTALL RIDGE SHINGLES TO SEAL
WITH UNDERLYING RIDGE SHINGLE
(Optional: Hand tab to seal nails as may be
appropriate.)
IKO PRE-MANUFACTURED RIDGE
SHINGLES
PLYWOOD OR STRUCTURAL WOOD
SHEATHING
ASPHALT-SATURATED FELT, OR OTHER
APPROVED UNDERLAYMENT
PLYWOOD OR STRUCTURAL WOOD
SHEATHING
ROOF UNDERLAYMENT (TURN UP WALLS, AND EXTEND
BEYOND VERTICAL FLANGE OF STEP FLASHING AS
INDICATED.)
SHEET METAL STEP FLASHING AT EACH COURSE (PLACE
JUST UPSLOPE FROM EXPOSED EDGE OF SHINGLE. EXTEND
MINIMUM 4" OVER UNDERLYING SHINGLE AND
APPROXIMATELY 4" UP VERTICAL WALL.)
OPTIONAL: ADDITIONAL EXTENSION OF ROOF
UNDERLAYMENT (See Note 4.)
EACH UPSLOPE FLASHING APPROXIMATELY 2" HEAD
LAP OVER LOWER STEP FLASHING
WALL CLADDING UNDERLAYMENT (BY OTHERS. SHOULD
EXTEND DOWN OVER VERTICAL FLANGE OF REGLET OR ONE
PIECE [E.G., 'Z'-BAR] COUNTERFLASHING.)
CLADDING (BY OTHERS. CEMENT PLASTER SHOWN.) WITH SHEET
METAL REGLET AND COUNTERFLASHING (LAP COUNTERFLASHING
MINIMUM 2" OVER STEP FLASHING AND MAINTAIN ABOVE THE ROOF
SURFACE.)
ROOFING NAILS (PLACE NAILS HIGH,
SO THEY ARE OVERLAPPED BY THE
NEXT UPSLOPE STEP FLASHING.)
NOTES:
1. DETAIL DRAWN SHOWING MARATHON. ALSO APPLIES TO OTHER STYLES.
2. IN COLD CLIMATES, WHERE SNOW AND ICE ARE COMMON AN ICE & WATER PROTECTOR MEMBRANE, IS RECOMMENDED AS AN ICE-DAM PROTECTION MEMBRANE AT ALL
POTENTIAL ICE DAMMING LOCATIONS SUCH AS DOWNSLOPE EAVES, VALLEYS, CRICKETS, AROUND PENETRATIONS, AND RAKE EDGES. CONSULT LOCAL BUILDING CODE
REQUIREMENTS.
3. SHEET METAL STEP FLASHING IS SUGGESTED TO BE A MINIMUM OF 26-GAUGE PRE-FINISHED/PAINTED GALVANIZED STEEL, 16 OZ. COPPER, .032-INCH THICK PRE-FINISHED
ALUMINUM, OR AN EQUIVALENT LONGEVITY NON-CORROSIVE METAL.
4. VERTICAL FLANGE OF STEP FLASHING SHOULD BE LAPPED A MINIMUM OF 2". SHEET METAL COUNTERFLASHING MAY BE OPTIONAL WHERE WALL CLADDING OR SIDING
OVERLAPS STEP FLASHING.
5. CONSIDER SPECIFYING THE EXTENSION OF ROOFING UNDERLAYMENT VERTICALLY UP THE WALL SO THAT IT IS OVERLAPPED BY THE WALL CLADDING UNDERLAYMENT.
6. DIMENSIONS SHOWN ARE RECOMMENDED MINIMUMS AND ARE INTENDED TO BE APPROXIMATE TO ALLOW FOR REASONABLE TOLERANCES DUE TO FIELD CONDITIONS.
7. THE PROFILE OF SPECIFIC COMPONENTS, THEIR CONFIGURATION OR SEQUENCING, CAN VARY WITH THE ROOF SYSTEM, WITH CLIMATIC DIFFERENCES, AND REGIONAL OR
AREA PRACTICES.
ASPHALT-SATURATED FELT, OR OTHER APPROVED
UNDERLAYMENT
OPTIONAL: BLOCKING (DEPENDING ON REGLET PROFILE.)
APRON FLASHING
OPTIONAL: HEMMED EDGES
OPTIONAL: SHOP FORM FLASHING
WITH SOLDERED CORNERS
METAL STEP FLASHING (See
Detail
S-9.)
APRON FLASHING SIDE FLANGE
(4" minimum extension past corner.)
STEP FLASHING (Extend bottom
piece past corner and bend in/wrap
the top corner. [Optional: Inject
sealant into corner.])
APRON FLASHING DOWNSLOPE
FLANGE (APPROXIMATELY 5".
[OPTIONAL: FABRICATE WITH
HEMMED EXPOSED/LEADING
EDGES.])
APRON FLASHING VERTICAL
FLANGES (APPROXIMATELY 4",
AND SAME UPSLOPE.)
CLADDING (WOOD OR FIBER-
CEMENT LAP CLADDING SHOWN.
LAP 2" MINIMUM OVER STEP
FLASHING AND MAINTAIN ABOVE
ROOF SURFACE. OPTIONAL:
SHEET METAL
COUNTERFLASHING, NOT
SHOWN.)
NOTES:
1. DETAIL DRAWN SHOWING LAMINATED SHINGLE. ALSO APPLIES TO OTHER STYLES.
2. IN COLD CLIMATES, WHERE SNOW AND ICE ARE COMMON, AN ICE & WATER PROTECTOR MEMBRANE, IS RECOMMENDED AS AN ICE-DAM PROTECTION MEMBRANE AT ALL POTENTIAL
ICE DAMMING LOCATIONS SUCH AS DOWNSLOPE EAVES, VALLEYS, CRICKETS, AROUND PENETRATIONS, AND RAKE EDGES. CONSULT LOCAL BUILDING CODE REQUIREMENTS.
3. SHEET METAL STEP AND APRON FLASHINGS ARE SUGGESTED TO BE A MINIMUM OF 26-GAUGE PRE-FINISHED/PAINTED GALVANIZED STEEL, 16 OZ. COPPER, .032-INCH THICK
PRE-FINISHED ALUMINUM, OR AN EQUIVALENT LONGEVITY NON-CORROSIVE METAL.
4. VERTICAL FLANGE OF STEP FLASHING SHOULD BE LAPPED A MINIMUM OF 2". SHEET METAL COUNTERFLASHING MAY BE OPTIONAL WHERE WALL CLADDING OR SIDING
OVERLAPS STEP FLASHING.
5. CONSIDER SPECIFYING THE EXTENSION OF ROOFING UNDERLAYMENT VERTICALLY UP THE WALL SO THAT IT IS OVERLAPPED BY THE WALL CLADDING UNDERLAYMENT.
6. DIMENSIONS SHOWN ARE RECOMMENDED MINIMUMS AND ARE INTENDED TO BE APPROXIMATE TO ALLOW FOR REASONABLE TOLERANCES DUE TO FIELD CONDITIONS.
7. THE PROFILE OF SPECIFIC COMPONENTS, THEIR CONFIGURATION OR SEQUENCING, CAN VARY WITH THE ROOF SYSTEM, WITH CLIMATIC DIFFERENCES, AND REGIONAL OR AREA
PRACTICES.
ASPHALT- SATURATED FELT, OR
OTHER APPROVED
UNDERLAYMENT (TURNED UP AT
WALL.)
WALL CLADDING UNDERLAYMENT
(BY OTHERS. LAP OVER STEP
FLASHING AND UP-TURNED ROOF
UNDERLAYMENT.)
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A502
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
TYPICAL ROOF DETAILS
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 1 1/2" = 1'-0"3 TYPICAL DRIP EDGE DETAIL
SCALE: 1 1/2" = 1'-0"1 TYPICAL STANDARD 3-TAB SHINGLE DETAIL
SCALE: 1 1/2" = 1'-0"5 TYPICAL VENT PIPE DETAIL
SCALE: 1 1/2" = 1'-0"2 VETED RIDGE DETAIL
SCALE: 1 1/2" = 1'-0"7 NON-VENTED RIDGE DETAIL
SCALE: 1 1/2" = 1'-0"6 STEP FLASHING DETAIL
SCALE: 1 1/2" = 1'-0"4 TYP. HEADWALL FLASHING DETAIL
NO. DESCRIPTION DATE
EXTERIOR INTERIOR
EQ.
MASONRY
MASONRY BOND BEAM
SEALANT & BACKER
ROD
GWB OVER WOOD
FURRING AT 16" O.C.
SHIM
SEALANT
WALL BEYOND
EQ.
METAL DRIP FLASHING
WITH HEMMED EDGE SENT IN
CONTINUOUS BED OF SEALANT
EXTEND 12" MAXIMUM SELF
ADHERING MEMBRANE FLASHING
OVER WINDOW/DOOR FLANGE
SET IN CONTINUOUS BED OF
SEALANT
LIQUID FLUID MEMBRANE
WINDOW / DOOR FRAME
TBD WITH OWNER
CONTINOUOS BEAD
OF SEALANT &
BACKER ROD
MASONRY
EXTERIOR INTERIOR
GWB OVER WOOD
FURRING AT 16" O.C.
EXTEND 12" MAXIMUM SELF
ADHERING MEMBRANE FLASHING
OVER WINDOW/DOOR FLANGE
SET IN CONTINUOUS BED OF
SEALANT
LIQUID FLUID MEMBRANE
WINDOW / DOOR FRAME
TBD WITH OWNER
WALL BEYOND
MASONRY BOND BEAM
MASONRY
GWB OVER WOOD
FURRING AT 16" O.C.
SEALANT
SEALANT & BACKER
ROD
SHIM
EXTERIOR INTERIOR
EQ.EQ.
SEE PLAN
VARIES
SILL PAN WIT REAR DAM
METAL DRIP FLASHING
SET IN CONTINUOUS
BED OF SEALANT
EXTEND 12" MAXIMUM SELF
ADHERING MEMBRANE FLASHING
OVER WINDOW/DOOR FLANGE
SET IN CONTINUOUS BED OF
SEALANT
LIQUID FLUID MEMBRANE
WALL BEYOND
MASONRY BOND BEAM
MASONRY
GWB OVER WOOD
FURRING AT 16" O.C.
CONTINUOUS SEALANT &
BACKER ROD EACH SIDE
SHIM
EXTERIOR INTERIOR
SILL PAN WIT REAR DAM
METAL Z-DRIP FLASHING
SET IN CONTINUOUS
BED OF SEALANT
EXTEND 12" MAXIMUM SELF
ADHERING MEMBRANE FLASHING
OVER WINDOW/DOOR FLANGE
SET IN CONTINUOUS BED OF
SEALANT
LIQUID FLUID MEMBRANE
MIN.
1 1/2"
BLOCKING
MASONRY SOLID TO
SUPPORT FLASHING
MASONRY SILL ( IF
LONGER THAN 48"
DOWEL AS REQUIRED)
EXTEND SELF ADHERING
MEMBRANE FLASHING BEHIND
AND UNDER MASONRY SILL SET
IN CONTINUOUS BED OF SEALANT
DETAIL WITHOUT WINDOW SILL DETAIL INCLUDING WINDOW SILL
DOVETAIL METAL
ANCHORWINDOW TBD
WITH OWNER
WINDOW TBD
WITH OWNER
DOOR AND FRAME
SEE PLAN
CMU BEYOND
THRESHOLD SET IN
SEALANT
CMU BEYOND
CONC FLOOR
SLAB
1/2" CONSTRUCTION JOINT
W/ COMPRESSIBLE FILLER
OR MONOLITHIC CONCRETE
SLAB, SEE STRUCTURAL
EXTERIOR PAVING
(LEVEL W/ T/ SLAB AT
THRESHOLDS)
MAXIMUM
4"
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
A601
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
WINDOW AND DOOR
TYPICAL DETAILS
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 3" = 1'-0"
1 TYPICAL WINDOW / DOOR HEAD DETAIL
SCALE: 3" = 1'-0"
3 TYPICAL WINDOW / DOOR JAMB DETAIL
SCALE: 3" = 1'-0"
2 TYPICAL WINDOW SILL DETAIL
SCALE: 3" = 1'-0"4 EXTERIOR - DOOR THRESHOLD DETAIL
SCALE: 3/4" = 1'-0"5 TYPICAL WOOD BUCK DETAIL
NO. DESCRIPTION DATE
36"FRIDGE36"ELECTRICTOPDWDRYERWASHER
REQUIRED RECEPTACLE OUTLETS
1. IN EVERY HABITAL ROOM NO POINT ALONG THE FLOOR LINE IN ANY WALL
SPACE SHALL BE MORE THAN 6 FEET FROM ANY OUTLET. WALL SPACE INCLUDES
ANY WALL 2 FEET OR WIDER, FIXED PANELS OF SLIDING OR FRENCH TYPE
PATIO DOORS, FIXED ROOM DIVIDERS SUCH AS FREE STANDING BAR TYPE
COUNTERS OR HAND RAILINGS.
2. ANY HALLWAY MORE THAN 10 FEET IN LENGTH SHALL HAVE AT LEAST ONE
RECEPTACLE OUTLET.
3. AT LEAST ONE WEATHERPROOF GFCI PROTECTED OUTLET SHALL BE INSTALLED
AT THE FRONT AND BACK OF THE DWELLING UNIT.
4. AT LEAST ONE GFCI PROTECTED OUTLET SHALL BE INSTALLED IN EACH
ATTACHED OR DETACHED GARAGE THAT HAS POWER.
5. AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED WITHIN 25 FEET FROM
ALL HVAC EQUIPMENT.
6. RECEPTACLE OUTLETS SHALL BE INSTALLED ON KITCHEN COUNTER TOPS SO
THAT NO PART OF THE COUNTER TOP IS MORE THAN 2 FEET FROM AN OUTLET.
7. AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED FOR EACH COUNTER
TOP SPACE ON PENINSULAR COUNTER TOPS THAT MEASURE MORE THAN 24
INCHES FROM THE LEADING EDGE OF THE COUNTER TOP.
8. AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED FOR EACH BATHROOM
COUNTER TOP WITHIN 36 INCHES OF EACH BASIN. RECEPTACLE OUTLETS SHALL
NOT BE INSTALLED IN TUB OR SHOWER SPACES.
9. AT LEAST ONE GFCI PROTECTED OUTLET SHALL BE INSTALLED IN CRAWL SPACES
THAT HAVE ELECTRICAL EQUIPMENT INSTALLED.
10.AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN ALCOVES THAT
ARE AT LEAST 2 FEET DEEP AND 3 FEET IN LENGTH INSTALLED IN HALLWAYS,
FOYERS, ENTRIES, AND LANDINGS.
11.RECEPTACLE OUTLETS INSTALLED IN WET LOCATIONS SHALL BE LISTED
WEATHER RESISTANT TYPE.
12.ALL 15 AND 20 AMP, 120 VOLT RECEPTACLE OUTLETS INSTALLED IN DWELLING
UNITS SHALL BE LISTED TAMPER RESISTANT TYPE.
13.BALCONIES, PORCHES, AND DECKS THAT ARE ACCESSIBLE FROM INSIDE THE
DWELLING UNIT THAT HAVE AN AREA OF MORE THAN 20 SQUARE FEET SHALL
HAVE AT LEAST ONE GFCI PROTECTED RECEPTACLE OUTLET.
SMOKE DETECTORS
1. SMOKE DETECTORS REQUIRED:
SMOKE DETECTORS SHALL BE INSTALLED IN EACH BEDROOM AND OUTSIDE EACH
BEDROOM AREA IN THE IMMEDIATE VICINITY OF THE BEDROOMS. DETECTORS
SHALL BE INSTALLED ON EACH STORY OF A DWELLING UNIT, INCLUDING
BASEMENTS AND CELLARS, BUT NOT CRAWL SPACES OR UNINHABITABLE ATTIC
SPACES. IN DWELLING UNITS WITH SPLIT LEVELS, DETECTORS NEED BE INSTALLED
ONLY ON THE UPPER LEVEL PROVIDED THE LOWER LEVEL IS LESS THAN ONE FULL
STORY BELOW THE UPPER LEVEL. IF THERE IS A DOOR BETWEEN LEVELS THEN A
DETECTOR SHALL BE INSTALLED ON EACH LEVEL.
2. ALL SMOKE DETECTORS SHALL BE INTERCONNECTED SO THAT ALL REQUIRED
DETECTORS IN THE DWELLING UNIT WILL BE ACTUATED WHEN ANY ONE DETECTOR
IS ACTUATED.
3. ALL DETECTORS SHALL BE APPROVED AN LISTED AND SHALL BE INSTALLED PER
THE MANUFACTURER'S LISTING. REQUIRED DETECTORS SHALL NOT BE INSTALLED
PER THE MANUFACTURER'S LISTING. REQUIRED DETECTORS SHALL NOT BE
INSTALLED IN KITCHENS OR GARAGES, OR IN AREAS WHERE THE TEMPERATURE
CAN FALL BELOW 40 DEGREES F.
4. IONIZATION DECTORS SHALL NOT BE INSTALLED CLOSER THAN 3 FEET HORIZONTALLY
FROM:
A. THE DOOR TO A KITCHEN.
B. THE DOOR TO A BATHROOM CONTAINING A TUB OR SHOWER.
C. THE SUPPLY REGISTERS OF A FORCED AIR HEATING OR COOLING SYSTEM.,
OUTSIDE OF THE AIR FLOW FROM THOSE REGISTERS.
GFCI PROTECTION FOR PERSONAL
THE FOLLOWING 120 VOLTS 15 AND 20 AMP RECEPTACLES SHALL BE GFCI PROTECTED:
A. ALL KITCHEN COUNTER TOP RECEPTACLES.
B. ALL BATHROOM RECEPTACLES.
C. ALL OUTSIDE RECEPTACLES.
D. ALL RECEPTACLES INSTALLED IN ACCESSORY STRUCTURES IN GRADE LEVEL
ROOMS NOT INTENDED AS HABITALE AND USED AS STORAGE OR WORKSPACE
.
E. ALL COUNTER TOP RECEPTACLES LOCATED WITHIN 6 FEET FROM THE EDGE OF
ANY SINK.
SPACING FOR RECEPTACLE OUTLETS AT KITCHEN COUNTERS
1. RECEPTACLES SHALL BE INSTALLED AT EACH WALL COUNTER SPACE 2 FEET
OR WIDE OR WIDER.
2. RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
IS MORE THAN 2 FEET MEASURED HORIZONTALLY FROM A RECEPTACLE. THESE
RECEPTACLES SHALL BE INSTALLED NO MORE THAN 18 INCHES ABOVE THE
COUNTER TOP SURFACE. RECEPTACLE OUTSIDE SHALL NOT BE INSTALLED
FACE UP IN THE COUNTER TOP.
3. AT LEAST 1 RECEPTACLE OUTLET SHALL BE INSTALLED IN EACH ISLAND
COUNTER SPACE WITH A LONG DIMENSION OF 24 INCHES OR GREATER AND A
SHORT DIMENSION OF 12 INCHES OR GREATER. A PENINSULAR COUNTERTOP IS
MEASURED FROM THE CONNECTING EDGE.
4. AT LEAST 1 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH PENINSULAR
COUNTER SPACE WITH A LONG DIMENSION OF 24 INCHES OR GREATER AND A
SHORT DISTANCE OF 12 INCHES OR GREATER.
5. COUNTER SPACE SEPERATED BY COUNTER MOUNTED COOKING UNITS OR
SINKS SHALL BE CONSIDERED SEPARATE COUNTER SPACES WHERE LESS THAN
12" OF COUNTER TOP IS BEHIND THE COUNTER MOUNTED COOKING UNIT OR
SINK.
PLACEMENT OF RECEPTACLE OUTLETS AT BATHROOM COUNTERS
1. AT LEAST 1 RECEPTACLE OUTLET SHALL BE INSTALLED IN BATHROOMS WITHIN
36 INCHES OF THE EDGE OF EACH BASIN. RECEPTACLE OUTLETS SHALL NOT BE
INSTALLED FACE UP IN THE BATHROOM COUNTER TOP.
2. RECEPTACLE OUTLETS SHALL NOT BE INSTALLED IN A TUB OR SHOWER SPACE.
3. DO NOT INSTALL RECEPTACLE OUTLETS SO THAT CORDS ON HAIR DRYERS,
RADIOS, CURLING IRONS, AND SUCH APPLIANCES WILL REACH TO FALL INTO A
BATHTUB.
ARC-FAULT CIRCUIT-INTERRUPTION PROTECTION
1. ALL BRANCH CIRCUITS THAT SUPPLY 125 VOLTS, 15 AND 20 AMP OUTLETS
INSTALLED IN DWELLING UNIT BEDROOMS SHALL BE PROTECTED BY AN ARC
FAULT CIRCUIT INTERRUPTED LISTED TO PROVIDE PROTECTION OF THE ENTIRE
CIRCUIT.
2. NOTE: "OUTLETS" INCLUDE RECEPTACLE OUTLETS, LIGHTING OUTLETS, AND
SWITCHING OUTLETS. EXCEPTIONS: OUTLETS INSTALLED FOR SMOKE DETECTORS.
S
TYPICAL ELECTRICAL SWITCH
S
TYPICAL ELECTRICAL SWITCH WITH
DIMMER
S
THREE WAY SWITCH
3
ELECTRICAL DUPLEX OUTLET
ELECTRICAL DUPLEX OUTLET
220 VOLTAGE OUTLET
OUTLET (APPLIANCE AS NOTED)GFCIOUTLET, GROUND FAULT INTERRUPTGFI
OUTLET, COUNTER HT. @ 4' A.F.F. GFICGFI
EXTERIOR OUTLET, GFIEGFI TH
THERMOSTAT (F.V. W/ HVAC & OWNER)
T
TELEPHONE
ELECTRICAL PANEL (G.C. TO F.V. LOAD)
SD SMOKE DETECTOR
LIGHT FIXTURE
LIGHT FIXTURE
EXIT LIGHT AS FOUND
CEILING FAN, LIGHT. OPTIONAL
(SEE OWNER FOR SELECTION)
EXTERIOR WALL SCONCE LIGHT
CATV
TV
ELECTRICAL SYMBOL LEGEND
EX.DESIGNATION OF ALL EXISTING ELEC. ITEM/
APPARATUS AS FOUND TO REMAIN, TO BE
RELOCATED, OR REMOVED.
MOISTURE PROOF LIGHT FIXTURE
MP
JUNCTION BOX SURGE PROTECTIVE KIT ETHERNET PORTJ
E-P
GDO GARAGE DOOR OPENER
FLOOD LIGHTS OPTIONAL
TYPICAL WHERE SHOWN
S
A/C COMP.
SS
SS
SS
MP
MP
MP
MP MP
AHU
MP
GDO
*VENT E.F. TO
EXTERIOR
(3) PENDANT
LIGHTS
*VENT E.F. TO
EXTERIOR
*VENT E.F. TO
EXTERIOR
*VENT E.F. TO
EXTERIOR
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SDSSSS S S SSSS3S3S3S 3S
SSSS S
S
SSSSSSSSSSSSS
GFI GFIGFITVTV
OPTIONAL CABLE TV
LOCATION
WP/GFI
WP/GFIWP/GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI24"x22"ATTIC ACCESS24"x22"
ATTIC
ACCESS
ELECTRICALPANELGFIGFIGFI
GFI
GFI
LAUNDRY
TUB
WP/GFI
WP/GFI
WP/GFI
WP/GFI
WP/GFI
WP/GFI
FLOOD LIGHTS OPTIONAL
TYPICAL WHERE SHOWN
FLOOD LIGHTS OPTIONAL
TYPICAL WHERE SHOWN
WH
J
S
TH
*VENT E.F.
TO EXT.
GFI
OWNER / BUILDER / CONTRACTOR NOTES:
1.AIR HANDLER FINAL LOCATION TO BE DETERMINED
BY OWNER / BUILDER / CONTRACTOR.
2.LAUNDRY SINK FINAL LOCATION TO BE DETERMINED
BY OWNER / BUILDER / CONTRACTOR.
3.WASHER / DRYER FINAL LOCATION TO BE DETERMINED
BY OWNER / BUILDER / CONTRACTOR.
4.WATER HEATER FINAL LOCATION TO BE DETERMINED
BY OWNER / BUILDER / CONTRACTOR.
SEE
NOTE 1 SEE
NOTE 4
SEE
NOTE 2 SEE
NOTE 3
GARAGE ELETRICAL VEHICLE WIRE AND
NEMA 14-50 RECEPTACLE POWER OUTLETE-PMEDIA PANEL
CENTRAL
LOCATION
E-P
E-PETHERNET PORT
TYPICAL AT BEDROOMS
SMOKE DETECTOR
HORN
DOOR BELL
CHIME
THERMOSTAT
SECURITY ALARM NOTE:
1.OWNER / BUILDER / CONTRACTOR TO PROVIDE
A SECURITY SYSTEM DEVICE INCLUDING SIREN
TO ALL WINDOWS AND DOORS.
2.SECURITY SYSTEM SHALL BE DESIGNED BY
OWNER / BUILDER / CONTRACTOR
ELECTRICAL NOTES:
1. METER LOCATION TO BE VERIFIED.
2. **ALL UTILITY SERVICES TO BE VERIFIED BY BUILDER**.
3. WATER HEATERS TO BE DETERMINED BY BUILDER.
4. PRE-WIRE AND TRIM FOR CAT5/TV PER PLANS AND OWNER.
5. CONFIRM WITH OWNER ON STRUCTURED WIRING.
6. ELECTRICAL PANELS TO BE VERIFIED BY BUILDER.
7. CONFIRM ALL ELECTRICAL WITH OWNER PRIOR TO WIRING ANYTHING.
8. ELECTRICAL LOAD CALCULATIONS PER 2020 NEC ART. 220
- PROVIDED ON SEPARATE DRAWINGS BY BUILDER / ELECTRICIAN.
9. CONDENSER LOCATION AND WIRING TO BE VERIFIED IN FIELD.
10. AIR HANDLER TO BE RELOCATED IN CLOSET WITH POWER AND LIGHTING
AS REQUIRED.
EFFICACY NOTE:
THE NEW FBC R FBC EC/R404.1 AND R202 BUILDING CODE REQUIRES ALL
PERMANENTLY INSTALLED, INTERIOR AND EXTERIOR LIGHT FIXTURES TO
HAVE 100% HIGH-EFFICACY CFL LAMPS OR LED'S
(THIS REQUIREMENT IS ONLY APPLICABLE TO NEW CONSTRUCTION)
PER FBC-R-E3902 AFCI PROTECTION REQUIRED:
ALL 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS
SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT FAMILY ROOMS, DINING
ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUN
ROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR ROOMS
OR AREAS SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT
INTERRUPTER, COMBINATION-TYPE.
PER FBC-R-E3901.7, NEC 210, E3901.7 AND E3902.3 GFCI PROTECTION
REQUIRED:
BATHROOMS, GARAGES, BOATHOUSES AND ACCESSORY STRUCTURES NOT
INTENDED AS HABITABLE ROOMS AND LIMITED TO STORAGE, WORK AND
SIMILAR USES. OUTDOORS, CRAWL SPACES, UNFINISHED BASEMENTS,
KITCHEN COUNTERTOPS. OUTLETS WITHIN 6 FEET OF LAUNDRY, UTILITY OR
WET SINKS. BALCONY, DECK OR PORCH GREATER THATN 20 SQUARE FOOT.
ONE AT THE FRONT AND BACK OF THE DWELLING AND AT THE CONDENSER
UNITS.
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
E101
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
ELECTRICAL FIRST FLOOR
PLAN AND NOTES
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 1/4" = 1'-0"1 ELECTRICAL FIRST FLOOR PLAN
NO. DESCRIPTION DATE
DESCRIPTION OF BUILDING ELEMENTS
TABLE 2304.10.1 FASTENING SCHEDULE
NUMBER AND TYPE OF FASTENER SPACING AND LOCATION
1. BLOCKING BETWEEN CEILING JOISTS, REAFTERS OR TRUSSES
TO TOP PLATE OR OTHER FRAMING BELOW
BLOCKING BETWEEN REAFTERS OR TRUSS NOT AT THE WALL
TOP PLATE, TO RAFTER OR TRUSS
FLAT BLOCKING TO TRUSS AND WEB FILLER
2. CEILING JOISTS TO TOP PLATE
3. CEILING JOIST NOT ATTACHED TO PARALLEL RAFTER, LAPS
OVER PARTITIONS (NO THRUST)
(SEE SECTION 2301.2)
4. CEILING JOIST ATTACHED TO PARALLEL RAFTER (HEEL JOINT) (SEE SECTION 2301.2)
5. COLLAR TIE TO RAFTER
6. RAFTER OR ROOF TRUSS TO TOP PLATE
(SEE SECTION 2301.2)
7. ROOF RAFTERS TO RIDGE VALLEY OR HIP RAFTERS; OR ROOF
RAFTER TO 2-INCH RIDGE BEAM
8. STUD TO STUD (NOT AT BRACED WALL PANELS)
9. STUD TO STUD AND ABUTTING STUDS AT INTERSECTING WALL
CORNERS (AT BRACED WALL PANELS)
10.BUILT-UP HEADER (2" TO 2" HEADER)
11.CONTINUOUS HEADER TO STUD
12.TOP PLATE TO TOP PLATE
13.TOP PLATE TO TOP PLATE, AT END JOINTS
14.BOTTOM PLATE TO JOIST, RIM JOIST, BRAND JOIST OR BLOCKING
(NOT AT BRACED WALL PANELS)
15.BOTTOM PLATE TO JOIST, RIM JOIST, BRAND JOIST OR BLOCKING AT BRACED WALL PANELS
16.STUD TO TOP OR BOTTOM PLATE
17.RESERVED
18.TOP PLATES, LAPS AT CORNERS AND INTERSECTIONS
19.1" BRACE TO EACH STUD AND PLATE
20.1" x 6" SHEATHING TO EACH BEARING
21.1" x 8" AND WIDER SHEATHING TO EACH BEARING
3-8d COMMON (2 1/2" x 0.131"); OR
3-10d BOX (3" x 0.128"); OR
3-3" x 0.131" NAILS; OR
3-3" 14 GAGE STAPLES, 7/16" CROWN
EACH END, TOENAIL
2-8d COMMON (2 1/2" x 0.131")
2-3" x 0.131" NAILS
2-3" 14 GAGE STAPLES
EACH END, TOENAIL
ROOF
2-16d COMMON (3 1/2" x 0.162")
3-3" x 0.131" NAILS
3-3" 14 GAGE STAPLES
EACH END
16d COMMON (3 1/2" x 0.162") @ 6" O.C.
3" x 0.131" NAILS @ 6" O.C.
3" x 14 GAGE STAPLES @ 6" O.C.
FACE NAIL
3-8d COMMON (2 1/2" x 0.131"); OR
3-10d BOX (3" x 0.128"); OR
3-3" x 0.131" NAILS; OR
3-3" 14 GAGE STAPLES, 7/16" CROWN
3-8d COMMON (2 1/2" x 0.131"); OR
3-10d BOX (3" x 0.128"); OR
3-3" x 0.131" NAILS; OR
3-3" 14 GAGE STAPLES, 7/16" CROWN
EACH JOIST, TOENAIL
FACE NAIL
PER SECTION 2301.2 FACE NAIL
3-10d COMMON (2 1/2" x 0.148"); OR
4-10d BOX (3" x 0.128"); OR
4-3" x 0.131" NAILS; OR
4-3" 14 GAGE STAPLES, 7/16" CROWN
FACE NAIL
3-10d COMMON (2 1/2" x 0.148"); OR
3-16d BOX (3" x 0.135"); OR
4-10d BOX (3" x 0.128"); OR
4-3" x 0.131" NAILS; OR
4-3" 14 GAGE STAPLES, 7/16" CROWN
TOENAIL
2-16d COMMON (3 1/2" x 0.148"); OR
4-16d BOX (3 1/2" x 0.135"); OR
4-10d BOX (3" x 0.128"); OR
4-3" x 0.131" NAILS; OR
4-3" 14 GAGE STAPLES, 7/16" CROWN
3-10d COMMON (3" x 0.148"); OR
4-16d BOX (3" x 0.135"); OR
4-10d BOX (3" x 0.128"); OR
4-3" x 0.131" NAILS; OR
4-3" 14 GAGE STAPLES, 7/16" CROWN
END NAIL
TOENAIL
WALL
16d COMMON (3 1/2" x 0.162");
10d BOX (3" x 0.128"); OR
3" x 0.131" NAILS; OR
3-3" x 14 GAGE STAPLES, 7/16"
24" O.C. FACE NAIL
16" O.C. FACE NAIL
16d COMMON (3 1/2" x 0.162");
16d BOX (3 1/2" x 0.135");
16" O.C. FACE NAIL
12" O.C. FACE NAIL
3" x 0.131" NAILS; OR
3-3" x 14 GAGE STAPLES, 7/16"12" O.C. FACE NAIL
16d COMMON (3 1/2" x 0.162"); OR
16d BOX (3 1/2" x 0.135");
16" O.C. EACH EDGE, FACE NAIL
12" O.C. EACH EDGE, FACE NAIL
4-8d COMMON (2 1/2" x 0.131"); OR
4-10d BOX (3" x 0.128")TOENAIL
16d COMMON (3 1/2" x 0.162");
10d BOX (3" x 0.128"); OR
3" x 0.131" NAILS; OR
3-3" x 14 GAGE STAPLES, 7/16" CROWN
16" O.C. FACE NAIL
12" O.C. FACE NAIL
8-16d COMMON (3 1/2" x 0.162"); OR
12-10d BOX (3" x 0.128"); OR
12-3" x 0.131" NAILS; OR
12-3" 14 GAGE STAPLES, 7/16" CROWN
EACH SIDE OF END JOINT, FACE NAIL
(MINIMUM 24" LAP SPLICE LENGTH
EACH SIDE OF END JOINT)
16d COMMON (3 1/2" x 0.162");
16d BOX (3" x 0.135"); OR
3" x 0.131" NAILS; OR
3" x 14 GAGE STAPLES, 7/16" CROWN
16" O.C. FACE NAIL
12" O.C. FACE NAIL
2-16d COMMON (3 1/2" x 0.162"); OR
3-16d BOX (3" x 0.135"); OR
4-3" x 0.131" NAILS; OR
4-3" 14 GAGE STAPLES, 7/16" CROWN
16" O.C. FACE NAIL
4-8d COMMON (2 1/2" x 0.131"); OR
4-10d BOX (3" x 0.128"); OR
4-3" x 0.131" NAILS; OR
4-3" 14 GAGE STAPLES, 7/16" CROWN; OR
2-16d COMMON (3 1/2" x 0.162"); OR
3-10d BOX (3" x 0.128"); OR
3-3" x 0.131" NAILS; OR
3-3" 14 GAGE STAPLES, 7/16" CROWN
TOENAIL
END NAIL
2-16d COMMON (3 1/2" x 0.162"); OR
3-10d BOX (3" x 0.128"); OR
3-3" x 0.131" NAILS; OR
3-3" 14 GAGE STAPLES, 7/16" CROWN
FACE NAIL
2-8d COMMON (2 1/2" x 0.131"); OR
2-10d BOX (3" x 0.128"); OR
2-3" x 0.131" NAILS; OR
2-3" 14 GAGE STAPLES, 7/16" CROWN
FACE NAIL
2-8d COMMON (2 1/2" x 0.131"); OR
2-10d BOX (3" x 0.128")
3-8d COMMON (2 1/2" x 0.131"); OR
3-10d BOX (3" x 0.128")
FACE NAIL
FACE NAIL
ULTIMATE COMPONENTS & CLADDING WIND
PRESSURES FOR WINDOWS AND WALLS (PSF)
GENERAL STRUCTURAL NOTES
DESIGN CRITERIA:
1. ALL WORK TO CONFORM TO THE FLORIDA BUILDING CODE 8th EDITION (2023).
2. WIND DESIGN DATA:
ULTIMATE DESIGN WIND SPEED, Vult (3-SECOND GUST) 129 MPH
NOMINAL DESIGN WIND SPEED, Vasd (3-SECOND GUST) 100 MPH
BUILDING RISK CATEGORY ll
WIND EXPOSURE D
INTERNAL PRESSURE COEFFICIENT +/- 0.18
STRUCTURE IS LOCATED WITHIN THE COASTAL WIND BORNE DEBRIS REGION.
WINDOW & WALLS SEE THIS SHEET
3. DESIGN LOADS:
ROOF LIVE
TOP CHORD = 20 PSF
BOT CHORD = 10 PSF
SUPERIMPOSED ROOF DEAD
TOP CHORD = 15 PSF
BOT CHORD = 5 PSF
EFFECTIVE WIND AREA (S.F.)
<10
ZONE
>50020010050
-49.0
-60.0
45.0
-44.0
-51.0
45.0
-42.0
-51.0
41.0
-40.0
-43.0
37.0
-38.0
-38.0
34.0
4
5
&4 5
EDGE ZONE = a = WITHIN 6 FEET OF OUTSIDE CORNERS
NOTES:
1. EDGE ZONE (a) IS DISTANCE FROM CORNERS OF BUILDINGS AND IS SHOWN BELOW
TABLE ABOVE.
2. POSITIVE AND NEGATIVE SIGNS SIGNIFY PRESSURES ACTING TOWARDS AND AWAY
FROM THE BUILDINGS SURFACES, RESPECTIVELY.
3. FOR EFFECTIVE AREAS BETWEEN VALUES GIVEN, INTERPOLATION MAY BE USED
OTHERWISE USE THE LOWER EFFECTIVE AREA.
EXISTING CONDITIONS:
1. THE EXISTING CONSTRUCTION SHOWN ON THE DRWAING WAS OBTAINED FROM LIMITED VISUAL OBSERVATIONS. THE
CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO PROCEEDING WITH WORK. CONSTRACTOR SHALL NOTIFY
ARCHITECT / ENGINEER OF ALL EXCEPTIONS TO ASSUMED CONDITIONS.
2. ALL REMOVAL, CUTTING, DRILLING ETC OF EXISTING CONSTRUCTION SHALL BE PERFORMED WITH GREAT CARE IN ORDER
TO NOT DAMGE THE EXISTING AND JEOPARDIZE THE INTERGRITY OF THE EXISTING BUILDING TO REMAIN.
ULTIMATE COMPONENTS & CLADDING WIND
PRESSURES FOR ROOF (PSF)
EFFECTIVE WIND AREA (S.F.)
<10
ZONE
>50020010050
-60.0
-83.0
34.0
-45.0
-57.0
23.0
-38.0
-45.0
19.0
1
3
ALL
-83.0 -57.0 -45.0
2
ULTIMATE COMPONENTS & CLADDING WIND
PRESSURES FOR ROOF OH (PSF)
EFFECTIVE WIND AREA (S.F.)
<10
ZONE
>50020010050
-66.0
-86.0 -69.0 -62.0
1
2
-63.0 -50.0 -41.0
-54.0
-62.0
-45.0
-118.0 -90.0 -76.0
3 -62.0 -45.0
-38.0
-45.0
19.0
-45.0
-38.0
-45.0
19.0
-45.0
FOUNDATION
FOUNDATION HAS BEEN DESIGNED FOR A MINIMUM SOIL BEARING CAPACITY OF 2000 PSF PER FBC. OWNER
SHALL ASSUME ALL RESPONIBILITY AND ASSOCIATED RISKS REGARDING OBTAINING A SOIL INVESTIGATION.
OWNER / CONTRACTOR SHALL OBTAIN A SOIL BEARING CAPACITY AND SUITABILITY OF SUBSURFACE
CONFIDTIONS REPORT FROM A REGISTERED GEOTECHNICAL ENGINEER. ALL REQUIREMENTS FOR SITE
PREPARATION AND SOIL COMPACTION SPECIFIED IN THE SOILS REPORTS, SOIL, COMPACTION SHALL MEET A
MINIMUM OF 95% COMPACTION.
WOOD SHEATHING
1. ALL WOOD SHALL CONFORM TO THE CURRENT EDITION OF THE NATIONAL DESIGN SPECIFICATION FOR
WOOD CONSTRUCTION (NDS) AND CHAPTER 23 OF THE FLORIDA BUILDING CODE.
2. BLOCKED DIAPHRAGM SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE.
THERE SHALL BE NO CONTINUOUS PANEL EDGES PARALLEL TO TRANSVERSE DIRECTION (STAGGER
SHEATHING SHEETS).
3. STRUCTURAL-USE PANEL STANDARDS: COMPLY WITH DOC PS 2, "PERFORMANCE STANDARD FOR WOOD-
BASED STRUCTURAL-USE PANELS, "UNLESS OTHERWISE INDICATED. PROVIDE PLYWOOD PANELS
COMPLYING WITH DOC PS 1, "U.S. PRODUCT STANDARD FOR CONSTRUCTION AND INDUSTRIAL PLYWOOD,
"WHERE P LYWOOD IS INDICATED.
4. TRADEMARK: FURNISH CONSTRUCTION PANELS THAT ARE EACH FACTORY-MARKED WITH CERTIFICATION
MARK EVIDENCING COMPLIANCE WITH GRADE REQUIREMENTS.
5. SHEATHING TO COMPLY WITH THE LATEST NDS AND FBC CODE PROVISIONS.
6. WALL SHEATHING: EXPOSURE 1 APA RATED, SHEATHING, OR APA STRUCTURAL 1. PLYWOOD OR ORIENTED
STRAND BOARD.
SPAN RATING: NOT LESS 32/16; THICKNESS: NOT LESS THAN 7/16 INCH
7. WOOD WALL SHEATHING PANELS SHALL BE NAILED TO ALL WOOD SUPPORTS AND BLOCKING WITH 8d NAILS
AT 6" O.C. ALONG ALL PANEL EDGES AND 6" ON CENTER AT ALL INTERMEDIATE SUPPORTS. REDUCE EDGE
NAILING AS INDICATED ON PLAN. INSTALL PANELS WITH L0NG DIMENSION PARALLEL TO STUDS WITH S
TAGGERED END JOINTS, BLOCK ALL HEDGES.
8. PAPER-SURFACED GYPSUM WALL SHEATHING: ASTM C 79/C 79M, WITH WATER-RESIS. MATERIAL
INCORPORATED INTO THE CORE AND WITH WATER-REPELLANT PAPER BONDED TO CORE'S FACE, BACK
AND LONG EDGES. TYPE AND THICKNESS: REGULAR, 1/2 INCH AND WHERE REQUIRED, TYPE X, 5/8" THICK.
EDGE AND END CONFIGURATION: V-SHAPED, TONGUE AND GROOVE LONG EDGES; SQUARE ENDS SIZE 48
BY 96 INCHES FOR VERTICAL INSTALLATION. FOR LOAD-BEARING INTERIOR WALLS, MINIMUM 1/2" GYPSUM
WALLBOARD EACH FACE W/ 1 1/2" WALLBOARD NAILS AT 6" O.C. EDGES AND 12" O.C. FIELD.
9. ROOF SHEATHING PANELS SHALL BE NAILED TO ALL WOOD SUPPORTS AND BLOCKING WITH 8d AT 6" O.C.
ALONG ALL PANEL EDGES AND 6" O.C. AT INTERMEDIATE SUPPORTS. REDUCE NAIL SPACING TO 4" O.C. AT
PANEL EDGES 4' FROM GABLE END WALLS.
10.SUBFLOORING AND UNDERLAYMENT: SUBFLOORING, EXPOSURE 1 TONGUE AND GROOVE, GLUED, APA
RATED SHEATHING OR STURDI-I-FLOOR. PLYWOOD OR ORIENTED STRAND BOARD. SPAN RATING NOT LESS
THAN 24" O.C. FOR STURDI-I-FLOOR OR 48/24 FOR APAP SHEATHING. THICKNESS, NOT LESS THAN 23/32".
11.FLOOR SHEATHING PANELS SHALL BE NAILED TO ALL WOOD SUPPORTS AND BLOCKING WITH 10d NAILS AT
6" O.C. ALONG ALL PANEL EDGES AND 6" O.C. AT INTERMEDIATE SUPPORTS.
GENERAL NOTES WOOD
WALL FRAMING
1. GENERAL: PROVIDE DIMENSIONAL LUMBER OF GRADES INDICATED ACCORDING TO THE AMERICAN LUMBER STANDARDS
COMMITTEE NATIONAL GRADING RULE PROVISIONS OF THE GRADING AGENCY INDICATED.
2. NON-LOAD BEARING INTERIOR PARTITIONS, EXTERIOR AND LOAD-BEARING WALLS: MIXED SOUTHER PINE (SP).
3. CEILING GOISTS (NON-LOAD BEARING) AND JOISTS RAFTERS AND OTHER FRAMING NOT LISTED ABOVE: NO. GRADE
SOUTHERN PINE.
4. LAMINATED VENEER LUMBER (LVL): LUMBER MANUFACTURED IN A CONTINUOUS PRESS USING AN EXTERIOR-TYPE
ADHESIVE COMPLYING WITH ASTM D 2559 TO PRODUCE MEMBERS WITH GRAIN OF VENEERS PARALLEL TO THEIR LENGTHS
AND COMPLYING WITH THE FOLLOWING REQUIREMENTS
EXTREME FIBER STRESS BENDING: 2,950 PSI
MODULUS OF ELASTICITY: 2,000,000 PSI
COMPRESSION PARALLEL TO GRAIN: 2,750 PSI
COMPRESSION PERPENDICULAR TO GRAIN: 750 PSI PERP. TO GRAIN AND PARALLEL TO GLUE LINE.
GLUE LINE. HORIZONTAL SHEAR: 285 PSI PERP. TO GLUE LINE.
5. PARALLAM (PSL): LUMBER MANUFACTURED IN A CONTINUOUS PRESS USING AN EXTERIOR-TYPE ADHESIVE COMPLYING
WITH ASTM D 2559 TO PRODUCE MEMBERS WITH GRAIN OF VENEERS PARALLEL TO THEIR LENGTHS AND COMPLYING WITH
THE FOLLOWING REQUIREMENTS
EXTREME FIBER STRESS BENDING: 2,950 PSI
MODULUS OF ELASTICITY: 2,000,000 PSI
COMPRESSION PARALLEL TO GRAIN: 2,900 PSI
COMPRESSION PERPENDICULAR TO GRAIN: 750 PSI PERP. TO GRAIN AND PARALLEL TO GLUE LINE.
GLUE LINE. HORIZONTAL SHEAR: 285 PSI PERP. TO GLUE LINE.
6. MINIMUM MATCH EACH GIRDER TRUSS PLY WITH A WALL STUD BELOW.
7. AT CHANGE IN PLATE HEIGHT BLOCK LOWER TOP PLATE INTO HIGH WALL A MINIMUM OF 32" AND NAIL SHEATHING TO
BLOCKING 3" ON CENTER.
8. LAP TOP PLATE OF CORNER WALL THAT HAS 1/2' ANCHOR AT END OF WALL ON TOP OF ADJACENT WALL.
9. BRACE TOP OF EXTERIOR WALLS THAT ARE NOT BRACED DIRECTLY BY TRUSS BEARING WITH 2X4 BLOCKING TO TRUSSES
AT 24" O.C.
10.EXTERIOR AND LOAD-- BEARING ALLS: SOUTHERN YELLOW PINE #2 (SYP).
11.FOR EXTERIOR AND INTERIOR LOAD BEARING WALLS PROVIDE NOMINAL WOOD STUDS OF MINIMUM GRADE SPECIFIED
BELOW SPACED 16' 0,C., U.N.O.,
2x4 SP #2 UP TO 8'.
2X4 SP #2 UP TO 10'
2X6 SP #2 UP TO 12'
2X8 SP #2 UP TO 18 '
12.TOP AND BOTTOM PLATES SHALL BE 2x SYP #2 MIN.
13.BLOCKING SHALL BE 2X SYP #2 MIN.
14.ATTACH FOUNDATION BASE PLATES 0R SILLS TO SLAB WITH SIMPSON 1/4"x4-1/2" TITEN SCREWS OR PDPXX .145" SHANK-3"
LENGTH SHOT PINS WITH 3" CONCRETE EDGE DISTANCE SPACED 32" ON CENTER. UP TO IO' HEIGHT BEARING WALLS AND
48" ON CENTER NON-- BEARING WALLS UP TO 14' HEIGHT; MINIMUM OF TWO CONNECTORS EACH PIECE WITH ONE NOT
MORE THAN 12" OR LESS THAN 4" OF EACH END OF EACH PIECE.
15.SET ROUGH CARPENTRY TO REQUIRED LEVELS AND LINES, WITH MEMBERS PLUMB, TRUE TO LINE, CUT, AND FITTED. FIT
ROUGH CARPENTRY TO OTHER CONSTRUCTION; SCRIBE AND COPE AS NEEDED FOR ACCURATE FIT. LOCATE FURRING,
NAILERS, BLOCKING, GROUNDS, AND SIMILAR SUPPORTS TO COMPLY WITH REQUIREMENTS FOR ATTACHING OTHER
CONSTRUCTION.
16.D0 NOT USE MATERIALS WITH DEFECTS THAT IMPAIR QUALITY OF ROUGH CARPENTRY OR PIECES THAT ARE TOO SMALL
TO USE WITH MINIMUM NUMBER OF JOINTS OR OPTIMUM JOINT ARRANGEMENT.
17.APPLY FIELD TREATMENT COMPLYING WITH AWPA M4 TO CUT SURFACES OF PRESERVATIVE-TREATED LUMBER AND
PLYWOOD.
18.SECURELY ATTACH ROUGH CARPENTRY WORK TO SUBSTRATE BY ANCHORING AND FASTENING AS INDICATED,
COMPLYING WITH THE FOLLOWING: PUBLISHED REQUIREMENTS OF METAL FRAMING ANCHOR MANUFACTURER. TABLE
2304.10.1, 'FASTENING SCHEDULE,' IN THE STANDARD BUILDING CODE.
19.USE COMMON WIRE NAILS OF STANDARD LENGTH PER LATEST NDS, U.N.0. MAKE TlGHT CONNECTIONS BETWEEN
MEMBERS. INSTALL FASTENERS WITHOUT SPLITTING WOOD, PRE-DRILL AS REQUIRED. SHOT PINS TO BE SET A MIN 3"
FROM EDGE OF CONCRETE.
20.BRACE PREFABRICATED TRUSSES PER TRUSS DESIGNER LEAVE CONSTRUCTION BRACING AS PERMENANT WHERE
POSSIBLE. ATTACH WEB CONTINUOUS LATERAL BRACING PER INDIVIDUAL TRUSS DRAWINGS TO TOP CHORD OF ROOF
TRUSS WITH A 2X4 V-BRACE 60 DEG. ANGLE AND (4) 12d NAILS EACH END, SPACED 10' APART MAX.
21.WHERE BUILT-UP BEAMS OR GIRDERS OF 2-INCH NOMINAL DIMENSTION LUMBER ON EDGE ARE REQUIRED, FASTEN
TOGETHER WITH 2 ROWS OF 20d NAILS SPACED NOT LESS THAN 16" O.C. LOCATE ONE ROW NEAR TOP EDGE AND OTHER
NEAR BOTTOM EDGE.
22.BUILT UP COLUMNS SHALL BE ATTACHED AS FOLLOWS: (2) MEMBERS 10d NAILS 6" O.C., (3) MEMBERS 30dX4 1/2" NAILS OR
SIMPSON SDS1/4X4.5" AT 12" O.C. STAGGERS SPACED, (4) MEMBERS SIMPSON SDS1/4X4.5" AT 8" O.C. STAGGERS SPACE.
CONSTRUCTION CORNERS AND INTERSECTIONS WITH THREE OR MORE STUDS. SHEATH OVERHANG AND CANTILEVER
EXTERIOR CEILINGS EXCEEDING 3'-0" OF ENCLOSED TYPE STRUCTURES WHERE WIND PATH LEADS TO ENCLOSED TYPE
ROOF MEMBERS.
23.FIRE BLOCK CONCEALED SPACES OF WOOD-FRAMED WALLS AND PARTITIONS AT EACH FLOOR LEVEL AND AT CEILING LINE
OF TOP STORY. WHERE FIRE BLOCKING IS NOT INHERENT IN FRAMING SYSTEM USED, PROVIDE CLOSELY FITTED WOOD
BLOCKS OF 2" NOMINAL THICK LUMBER OF SAME WIDTH AS FRAMING MEMBERS. FRAME OPENINGS WITH MULTIPLE STUDS
AND HEADERS. PROVIDE NAILED HEADER MEMBERS OF THICKNESS EQUAL TO WIDTH OF STUDS. SET HEADERS ON EDGE
AND SUPPORT ON JAMB STUDS.
24.ALL STRUCTURAL FRAMING MEMBERS SHALL BE SOUTHERN PINE GRADE NO. 2 UNLESS NOTED OTHERWISE ON PLANS
(MOISTURE 19% MAXIMUM).
25.NO STRUCTURAL MEMBERS SHALL BE CUT WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
26.ALL SILL PLATES RESTING ON CONCRETE OR MASONRY SHALL BE PRESERVATIVE-TREATED SOUTHERN PINE. ALL
FASTENERS FOR PRESERVATIVE TREATED WOOD (NAILS & ANCHORS) SHALL BE HOT-DIPPED ZINC COATED GALVANIZED
STEEL OR STAINLESS STEEL.
27.WHEN NAILING 2 OR MORE 2x MEMBERS TOGETHER, USE 10d NAILS AT 6" O.C. STAGGERED.
28.ALL WALL CORNERS SHALL HAVE TWO 2x WOOD STUDS BACK TO BACK EACH WAY.
29.FOR INTERIOR NON-BEARING WALLS AND PARTITIONS PROVIDE 2x STUD OR #2 GRADE WOOD STUDS SPACED 16" O.C.,
U.N.O.
30.TOP & BOTTOM PLATES SHALL BE 2x SP #2 MIN.
31.FOR NON-LOAD BEARING PARTITIONS, PROVIDE DOUBLE-JAMB STUDS WITH HEADERS NOT LESS THAN SINGLE 2x4 SET
FLAT FOR OPENINGS 32 INCHES AND LESS IN WIDTH, (2)~2X6 FOR OPENINGS 32 TO 48 INCHES IN WIDTH, (2) 2X8 FOR
OPENINGS UP TO 72 INCHES IN WIDTH, AND NOT LESS THAN (2)~2X10 FOR OPENINGS UP TO 96 INCHES IN WIDTH.
PRE-ENGINEERED WOOD TRUSSES
1. ALL WORK SHALL CONFORM TO THE "NATIONAL DESIGN STANDARD FOR METAL PLATE CONNECTED WOOD TRUSS
CONSTRUCION" (TPl 1 - 2007) BY THE TRUSS PLATE INSTITUTE.
2. PRE-ENGINEERED PRE-FABRICATED WOOD TRUSSES, TRUSS BRACING AND CONNECTIONS WITHIN THE TRUSS SYSTEM
SHALL BE DESIGNED FOR THE LOADS INDICATED ON THE DRAWINGS AND BE SIGNED AND SEALED BY A PROFESSIONAL
ENGINEER REGISTERED IN THE STATE OF FLORIDA WHO SHALL BE THE TRUSS SYSTEM ENGINEER.
3. SIGNED AND SEALED SHOP DRAWINGS SHOWING TRUSS CONFIGURATIONS WITH MEMBER SIZES AND CONNECTIONS,
TRUSS LAYOUT WITH PIECE MARKS, REQUIRED TRUSS TO TRUSS CONNECTIONS, DESIGN CRITERIA, DURATION FACTORS,
ERECTION DETAILS AND ALL BRACING FOR WIND AND ERECTION LOADS SHALL BE SUBMITTED FOR APPROVAL PRIOR TO
FABRICATION OF THE TRUSSES. AFTER RECEIVING APPROVAL FROM ARCHITECT/ENGINEER, SUBMIT APPROVED SHOP
DRAWINGS DIVISION FOR REVIEW AND APPROVAL PRIOR TO INSTALLING TRUSSES.
4. NO STRUCTURAL MEMBERS SHALL BE CUT, NOTCHED OR OTHERWISE REDUCED IN SIZE OR STRENGTH WITHOUT THE
WRITTEN PERMISSION OF THE REGISTERED DESIGN PROFESSIONAL.
5. EXISTING PRE-ENGINEERED WOOD TRUSS SHALL BE REINFORCED AND DESIGNED FOR THE NEW LOADS AND NEW
PRE-ENGINEERED TRUSSES INDICATED ON THE DRAWINGS AND BE SIGNED AND SEALED BY A PROFESSIONAL ENGINEER
REGISTERED IN THE STATE OF FLORIDA WHO SHALL BE THE TRUSS SYSTEM ENGINEER.
ROUGH CARPENTRY
PRODUCT MANUFACTURERS
1. WOOD PRODUCTS, GENERAL LUMBER: DOC PS 20 AND APPLICABLE RULES OF LUMBER GRADING AGENCIES
CERTIFIED BY THE AMERICAN LUMBER STANDARDS COMMITTEE BOARD OF REVIEW.
2. FACTORY MARK EACH PIECE OF LUMBER WITH GRADE STAMP OF GRADING AGENCY.
3. WHERE NOMINAL SIZES ARE INDICATED, PROVIDE ACTUAL SIZES REQUIRED BY DOC PS 20 FOR MOISTURE
CONTENT SPECIFIED. WHERE ACTUAL SIZES ARE INDICATED, THEY ARE MINIMUM DRESSED SIZES FOR DRY
LUMBER. PROVIDE DRESSED LUMBER, S4S, UNLESS OTHERWISE INDICATED. PROVIDE DRY LUMBER WITH 19
PERCENT MAXIMUM MOISTURE CONTENT AT TIME OF DRESSING FOR 2-INCH NOMINAL THICKNESS OR LESS,
UNLESS OTHERWISE INDICATED.
4. ENGINEERED WOOD PRODUCTS: PROVIDE ENGINEERED WOOD PRODUCTS ACCEPTABLE TO AUTHORITIES
HAVING JURISDICTION AND FOR WHICH CURRENT MODEL CODE RESEARCH OR EVALUATION REPORTS
EXIST THAT SHOW COMPLIANCE WITH BUILDING CODE IN EFFECT FOR PROJECT.
5. ALLOWABLE DESIGN STRESSES: PROVIDE ENGINEERED WOOD PRODUCTS WITH ALLOWABLE DESIGN
STRESSES, AS PUBLISHED BY MANUFACTURER, THAT MEET OR EXCEED THOSE INDICATED.
MANUFACTURER'S PUBLISHED VALUES SHALL BE DETERMINED FROM EMPIRICAL DATA OR BY RATIONAL
ENGINEERING ANALYSIS AND DEMONSTRATED BY COMPREHENSIVE TESTING PERFORMED BY QUALIFIED
INDEPENDENT TESTING AGENCY.
6. WOOD STRUCTURAL PANELS: PLYWOOD: DOC PS 1 OR DOC PS 2, ORIENTED STRAND BOARD: DOC PS 2
THICKNESS: AS NEEDED TO COMPLY WITH REQUIREMENTS SPECIFIED BY NOT LESS THAN THICKNESS
INDICATED ON DRAWINGS. COMPLY WITH "CODE PLUS" PROVISIONS IN APA FROM NO. E300. "APA
DESIGN/CONSTRUCTION CODE: RESIDENTIAL AND COMMERCIAL, " UNLESS SPECIFIED ON DRAWINGS.
FACTOR MARK PANELS ACCORDING TO INDICATED STANDARDS.
7. WOOD-PRESERVATIVE-TREATED MATERIALS: PRESERVATIVE TREATMENT BY PRESSURE PROCESS: AWPA
C2 (LUMBER) AND AWPA C9 (PLYWOOD). EXCEPT THAT LUMBER THAT IS NOT IN CONTACT WITH THE
GROUND AND IS CONTINUOUSLY PROTECTED FROM LIQUID WATER MAY BE TREATED ACCORDING TO AWPA
C31 WITH INORGANIC BORON (SBX).
8. PRESERVATIVE CHEMICALS: ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION AND ONE OF THE
FOLLOWING: CHROMATED COPPER ARSENATE (CCA-C), DOT SODIUM BORATE (SBX), ALKALINE COPPER
QUAT (ACQ-C AND ACQ-D (CARBONATE)), COPPER AZOLE (CBA-A AND CA-B), OTHER BORATE (NON DOT),
AMMONIACAL COPPER ZINC ARSENATE (ACZA).
9. KILN-DRY MATERIAL AFTER TREATMENT TO A MAXIMUM MOISTURE CONTENT OF 19% FOR LUMBER AND 15
PERCENT FOR PLYWOOD. DO NOT USE MATERIAL THAT IS WARPED OR DOES NOT COMPLY WITH
REQUIREMENTS FOR UNTREATED MATERIAL.
10.MARK EACH TREATED ITEM WITH THE TREATMENT QUALITY MARK OF AN INSPECTION AGENCY APPROVED
BY THE AMERICAN LUMBER STANDARDS COMMITTEE BOARD OF REVIEW.
11.APPLICATION: TREAT ITEMS INDICATED ON DRAWINGS, AND THE FOLLOWING: WOOD CANTS, NAILERS,
CURBS, EQUIPMENT SUPPORT BASES, BLOCKING, STRIPPING AND SIMILAR MEMBERS IN CONNECTION WITH
ROOFING, FLASHING, VAPOR BARRIERS, AND WATERPROOFING. WOOD SILLS, SLEEPERS, BLOCKING,
FURRING, STRIPPING, AND SIMILAR CONCEALED MEMBERS IN CONTACT WITH MASONRY OR CONCRETE.
WOOD FRAMING MEMBERS LESS THAN 18 INCHES ABOVE GRADE. WOOD FLOOR PLATES THAT ARE
INSTALLED OVER CVONCRETE SLABS DIRECTLY IN CONTACT WITH THE EARTH.
12.FLOOR JOIST FRAMING INSTALLATION: INSTALL FLOOR JOISTS PER MANUFACTURER'S INSTRUCTIONS TO
MEET MINIMUM BEARING CONDITIONS, SUPPORT ENDS, CROWN EDGE, AND ETC. WHERE SUPPORTED ON
WOOD MEMBERS, BY USING METAL FRAMING ANCHORS, WHERE FRAMED INTO WOOD SUPPORTING
MEMBERS, BY USING METAL JOIST HANGERS. FRAME OPENINGS WITH HEADERS AND TRIMMERS
SUPPORTED BY METAL JOIST HANGERS, DOBLE HEADERS AND TRIMMERS WHERE SPAN OF HEADER
EXCEEDS 48 INCHES. DO NOT NOTCH JOISTS, DO NOT BORE HOLES LARGER THAN 1" LOCATED NOT CLOSER
THAN INCHES FROM TOP OR BOTTOM CHORDS. PROVIDE SOLID BLOCKING OF 2 INCH NOMINAL THICKNESS
BY DEPTH OF JOIST AT ENDS OF JOIST UNLESS NAILED TO HEADER OR BAND. LAP MEMBERS FRAMING
FROM OPPOSITE SIDES OFBEAMS, GIRDERS, OR PARTITIONS NOT LESS THAN 4 INCHES OR SECURELY TIE
OPPOSING MEMBERS TOGETHER. PROVIDE SOLID BLOCKING OF 2 INCH NOMINAL THICKNESS BY DEPTH OF
JOIST OVER SUPPORTS. PROVIDE SOLID BLOCKING BETWEEN JOISTS UNDER JAMB STUDS FOR OPENINGS.
PROVIDE BRIDGING OF TYPE INDICATED BELOW, AT INTERVALS OF 96 INCHES O.C. BETWEEN JOISTS. STEEL
BRIDGING INSTALLED TO COMPLT\Y WITH BRIDGING MANUFACTURER'S WRITTEN INSTRUCTIONS. CEILING
JOIST AND RAFTER FRAMING INSTALLATION: CEILING JOISTS INSTALL CEILING JOISTS WITH CROWN EDGE
UP AND COMPLYING WITH REQUIREMENTS SPECIFIED ABOVE FOR FLOOR JOISTS. FACE NAIL TO ENDS OF
PARALLEL RAFTERS. WHERE CEILING JOISTS ARE AT RIGHT ANGLES TO RAFTERS, PROVIDE ADDITIONAL
SHORT JOISTS PARALLEL TO RAFTERS FROM WALL PLATE TO FIRST JOIST; NAIL TO ENDS OF RAFTERS AND
TO TOP PLATE AND NAIL TO FIRST JOISTS OR ANCHOR WITH FRAMING ANCHORS OR METAL STRAPS.
PROVIDE 1X8 OR 2X4 NOMINAL STRINGERS SPACED 48 INCHES O.C. CROSSWISE OVER MAIN CEILING
JOISTS. RAFTERS, NOTCH TO FIT EXTERIOR WALL PLATES AND USE METAL FRAMING ANCHORS, DOUBLE
RAFTERS TO FROM HEADERS AND TRIMMERS AT OPENINGS IN ROOF FRAMING, IF ANY, AND SUPPORT WITH
METAL HANGERS. WHERE RAFTERS ABUT AT RIDGE, PLACE DIRECTLY OPPOSITE EACH OTHER AND NAIL TO
RIDGE MEMBER OR USE METAL RIDGE HANGERS. AT HIPS AND VALLEYS, PROVIDE DOUBLE RAFTERS OF
SIZE INDICATED OR, IF NOT INDICATED, OF SAME THICKNESS AS REGULAR RAFTERS AND 2 IN. DEEPER.
BEVEL. ENDS OF JACK RAFTERS FOR FULL BEARING AGAINST VALLEY OR HIP RAFTERS.
GENERAL:
1. CONTRACTOR SHALL VERIFY ALL DIMENSIONS ON JOB SITE WITH COMPLETE SET OF LATEST
DRAWINGS. NOTES AND DIMENSIONS SHALL BE CHECKED AND VERIFIED WITH ARCHITECTURAL AND
STRUCTURAL DRAWINGS. ANY DISCREPENCIES IN NOTES OR DIMENSIONS SHALL BE BROUGHT TO
THE ATTENTION OF THE ARCHITECT BEFORE COMMENCING WORK SO THAT PROPER REMEDIAL
WORK CAN BE EXECUTED.
2. UNLESS SPECIFICALLY DETAILED ON THESE DRAWINGS, CONTRACTOR SHALL FURNISH AND
INSTALL ADEQUATE SHORING, BRACING, ETC. REQUIRED TO SAFELY EXECUTE ALL WORK AND
SHALL BE FULLY RESPONSIBLE FOR THE SAME.
3. DETAILS AND CONDITIONS NOT SPECIFICALLY SHOWN SHALL BE CONSTRUCTED IN ACCORDANCE
WITH DETAILS SHOWN FOR SIMILARS CONDITIONS AND MATERIALS.
4. ALL WORK SHALL CONFORM TO THE LATEST EDITION OF THE FLORIDA STATE BUILDING CODE,
THE NDS, AND ALL APPLICABLE ASTM STANDARDS. IN CASES OF CONFLICT, THE MOST STRINGENT
WITH APPROVED SHOP DRAWINGS.
5. CONTRACTOR SHALL COORDINATE AND VERIFY THE SIZE, LOCATION, TYPE, AND DIRECTION OF
ALL DEPRESSIONS, PADS, BOLTS, SLEEVES, ANCHORS, INSERTS, OPENINGS, ETC. TO BE SET OR
CAST IN CONCRETE PRIOR TO PLACEMENT. ALL SUCH ITEMS TO BE STRICT ACCORDANCE WITH
APPROVED SHOP DRAWINGS.
6. GENERAL CONTRACTOR SHALL DESIGN AND INSTALL ALL TEMPORARY SHORING REQUIRED TO
STABILIZE NEW AND EXISTING STRUCTURES AND FOUNDATIONS UNTIL CONSTRUCTION IS
COMPLETE.
SHOP DRAWINGS
1. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR REVIEW BY THE EOR AND THE PROJECT ARCHITECT. SHOP DRAWINGS
SHALL BE SUBMITTED FOR ALL STRUCTURAL COMPONENTS INCLUDING, BUT NOT LIMITED TO THE FOLLOWING:
- CONCRETE POST-INSTALLED ANCHORS
- PREFABRICATED FLOOR JOISTS, JOIST CONNECTIONS, JOIST TO FRAME CONNECTIONS, AND CALCULATIONS
(SIGNED AND SEALED BY PROFESSIONAL ENGINEER IN THE STATE THE PROJECT IS BEING COSTRUCTED).
- PREFABRICATED ROOF AND FLOOR TRUSSES, TRUSS CONNECTIONS, TRUSS TO FRAME CONNECTIONS, AND
CALCULATIONS (SIGNED AND SEALED BY PROFESSIONAL ENGINEER IN THE STATE THE PROJECT IS BEING
CONSTRUCTED).
- REINFORCED EXISTING ROOF TRUSSES, TRUSS CONNECTIONS, AND CALCULATIONS (SIGNED AND SEALED
BY PROFESSIONAL ENGINEER IN THE STATE THE PROJECT IS BEING CONSTRUCTED).
- ENGINEERED WOOD COMPONENTS (GLUED-LAMINATED WOOD, LVL MICROLAM, FRAMING, PSL, PLYWOOD
CHORD FLOOR TRUSSES, ETC.
- MASONRY REBARS, GROUT AND CONCRETE MIX DESIGN.
- CONCRETE REBARS AND CONCRETE MIX DESIGN.
2. SHOP DRAWINGS TO BE SUBMITTED SHALL PROVIDE COMPLETE INFORMATION FOR THE PRODUCTS OR COMPONENTS TO
BE SUPPLIED. SUBMITTAL INFORMATION SHALL INCLUDE, BUT NOT LIMITED TO: MEMBER SIZES AND DIMENSIONS. GRADES
OF MATERIAL FURNISHED; INFORMATION REGARDING CUTS, COPES, AND HOLES REQUIRED FOR OTHER TRADES; END
CONNECTIONS; CAMBER AND OTHER DEVIATION FROM LINE; SPECIAL ERECTION AND/OR INSTALLATION PROCEDURES,
INCLUDING REQUIREMENTS FOR TEMPORARY STABILIZATION.
3. CONTRACTOR SHALL SUBMIT ELECTRONIC COPIES OF SHOP DRAWINGS FOR REVIEW BY EOR. ELECTRONIC COPIES SHALL
BE SUBMITTED TO EOR IN PDF FILE FORMAT.
ABBREVIATIONS
ARCH. – ARCHITECT
O.C. – ON CENTER
TYP. – TYPICAL
CONT. – CONTINUOUS
P.T. - PRESSURE TREATED
U.N.O – ULESS NOETED OTHERWISE
DIA. – DIAMETER
SIM. – SIMILAR
W/ – WITH
SIMP. – SIMPSON STRONG TIE
W/O – WITH OUT
F.F.E – FINISH FLOOR ELEVATION
REQ'D – REQUIRED
T/ – TOP
B/ – BOTTOM
F.V. – FIELD VERIFY
FASTENERS
SCREW ANCHORS SHALL BE HILTI KWIK HUS-EZ, SIMPSON STRONG-TIE TITEN HD, POWERS WEDGE-BOLT OR APPROVED
EQUAL, UON. EMBEDMENT IN CONCRETE OR SOLID GROUTED MASONRY SHALL BE AT LEAST 9 TIMES THE BOLT DIAMETER,
UON. CLEAN HOLE AND INSTALL IN STRICT ACCORDANCE WITH MANUFACTURER'S PRINTED INSTRUCTIONS.
ADHESIVE ANCHORING (EPOXY)
• ADHESIVE ANCHORING FOR CONCRETE SHALL BE HILTI HIT-HY 200 CARTRIDGE SYSTEM, SIMPSON STRONG-TIE AT-XP,
POWERS PURE 110+ OR APPROVED EQUAL, UON. EMBEDMENT DEPTH SHALL BE AT LEAST 12 TIMES THE INSERT
DIAMETER, UON. HOLE DIAMETER SHALL BE NO GREATER THAN RECOMMENDED BY MANUFACTURER. THE HOLE SHALL BE
CLEANED PER MANUFACTURER'S RECOMMENDATIONS BY BRUSHING OUT WITH WIRE BOTTLE BRUSH AND BLOWN OUT
WITH AIR USING A COMPRESSOR WITH A FUNCTIONAL OIL TRAP (EXCEPT WHERE PERMITTED WHEN USING A HILTI SAFE
SET HIT Z ANCHOR ROD OR HILTI HOLLOW DRILL BIT w/ VACUUM).
• GENERAL - ANCHORS SHALL MEET THE REQUIREMENTS OF ACI 355.4. INSTALLATION SHALL BE IN STRICT ACCORDANCE
WITH MANUFACTURER'S PRINTED INSTRUCTIONS AND PERFORMED BY AN INSTALLER TRAINED BY THE MANUFACTURER.
INSTALLATION OF ADHESIVE ANCHORS HORIZONTALLY OR UPWARDLY, WHICH SUPPORT SUSTAINED TENSION LOADS
SHALL BE PERFORMED BY A CERTIFIED ADHESIVE ANCHOR INSTALLER IN ACCORDANCE WITH ACI318 AND CONTINUIOUSLY
INSPECTED PER ACI 318. PROOF OF CURRENT CERTIFICATION SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL.
• CAPACITIES - UON, DESIGN BOND STRENGTH OF ANCHORS HAVE BEEN BASED ON CRACKED CONCRETE, ACI 355.4
TEMPERATURE CATEGORY B, AND INSTALLATIONS INTO DRY HOLES DRILLED WITH A ROTARY IMPACT DRILL OR ROCK
DRILL INTO CONCRETE THAT HAS CURED AT LEAST 21 DAYS AND HAS A CONCRETE TEMPERATURE OF AT LEAST 50
DEGREES F AT TIME OF ANCHOR INSTALLATION.
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
S001
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
GENERAL NOTES
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
STRUCTURAL INDEX SHEET LIST
SHEET # SHEET DESCRIPTION
S001 GENERAL NOTES
S002 GENERAL NOTES AND COMPONENTS AND
CLADDING DIAGRAM
S003 SCHEDULES AND TABLES
S110 FOUNDATION AND SLAB PLAN
S111 SHEARWALL, WALL FRAMING, HEADERS,
AND HOLD-DOWN PLAN
S140 ROOF FRAMING PLAN
S501 TYPICAL CONCRETE DETAILS AND
SECTIONS
S502 TYPICAL MASONRY DETAILS AND SECTION
S601 TYPICAL WOOD FRAMING DETAILS
S602 WOOD FRAMING, BEARING AND
SHEARWALL SECTIONS AND DETAILS
NO. DESCRIPTION DATEANGEL ALICEA
E NCSIEL
S T A T E O F
No. 93531
REINFORCED CONCRETE NOTES
1. ALL CONCRETE WORK SHALL CONFORM TO ACI 318, "BUILDING CODE REQUIREMENTS FOR
REINFORCED CONCRETE".
2. ALL CONCRETE PLACED SHALL BE VIBRATED BY MECHANICAL VIBRATORS.
3. COMPLETE FABRICATION AND PLACING DRAWINGS FOR REINFORCING STEEL SHALL BE SUBMITTED
FOR APPROVAL. NO FABRICATION MAY BEGIN UNTIL SHOP DRAWINGS ARE COMPLETED AND APPROVED.
4. LAP SPLICES FOR REINFORCING STEEL SHALL BE IN ACCORDANCE WITH ACI 318. SPLICES SHALL BE
AS CALLED FOR IN THE LATEST EDITION OF THE CRSI "MANUAL OF STANDARD PRACTICE".
5. REINFORCING OF ALL CONCRETE MEMBERS SHALL HAVE THE FOLLOWING CLEAR CONCRETE COVER:
COVER (INCHES)
3
2
1 1/2
1 1/2
3/4
MEMBERS
CONCRETE CAST AGAINST AND
PERMANENTLY EXPOSED TO EARTH:
CONCRETE EXPOSED TO EARTH OR
WEATHER:
#6 BARS THROUGH #18 BARS
#5 BARS OR SMALLER
CONCRETE NOT EXPOSED TO WEATHER
OR IN CONTACT WITH EARTH:
SLAB AND WALLS:
#14 AND #18 BARS
#11 BARS AND SMALLER
6. THE CONTRACTOR SHALL PROVIDE ADEQUATE SUPPORT FOR REINFORCING TO ENSURE THE
REINFORCEMENT REMAINS IN ITS INTENDED POSITION WHEN CASTING CONCRETE. THE SUPPORT
SHALL BE CONSTRUCTED OF A TYPE THAT WILL NOT DAMAGE THE VAPOR BARRIER BELOW.
7. SPLICE WELDING OF REINFORCING STEEL SHALL BE DONE IN STRICT ACCORDANCE WITH THE
AMERICAN WELDING SOCIETY "REINFORCING STEEL WELDING CODE". PREHEATING OF THE
REINFORCING SHALL BE BASED ON THE CARBON EQUIVALENCY DETERMINED FROM REINFORCING
MILL REPORTS. GRADE 40 REINFORCING SHALL BE WELDED WITH E90XX LOW HYDROGEN
ELECTRODES.
8. MANUAL WELDING OF REINFORCING BARS FOR EMBEDS IS NOT ALLOWED.
9. SAWN JOINTS IN SLABS-ON-GRADE SHALL SHALL BE CUT AS SOON AS POSSIBLE AFTER THE CONCRETE
HARDENS. JOINTS CAN BE CUT WITH A POWER BLADE WITHIN 4 TO 12 HOURS AFTER THE SLAB HAS BEEN
CAST AND FINISHED. JOINTS MUST BE CUT AS SOON AS THE CONCRETE IS FIRM ENOUGH NOT TO BE
TORN OR DAMAGED BY THE BLADE. THE CONCRETE IS HARD ENOUGH WHEN THE BLADE DOES NOT
DISLODGE ANY AGGREGATE AND WHEN THE EDGES OF THE CUT DO NOT RAVEL.
10.CONTROL JOINTS IN ALL FOUNDATION AND RETAINING WALLS SHALL BE PLACED NOT MORE THAN 15'-0"
APART AND SHALL BE 3/4" V-CHAMFERED ON BOTH SIDES, UNLESS NOTED OTHERWISE. EXPANSION
JOINTS SHALL BE LOCATED AS NOTED ON THE PLANS. SEE TYP. DETAIL SHEET.
11.CHAMFER EXPOSED CONCRETE EDGES 3/4".
12.CONCRETE WALLS SHALL BE REINFORCED AROUND ALL OPENINGS WITH 2~#5 BARS ON ALL SIDES AND
EXTENDED 2'-0" BEYOND OPENING UNLESS NOTED OTHERWISE.
13.THE LONGITUDINAL REINFORCING STEEL IN BOND BEAMS, WALLS AND FOOTINGS SHALL BE CONTINUOUS
AROUND CORNERS. SEE TYP. DETAIL SHEET.
14. THE CONCRETE MIX DESIGNS ARE THE RESPONSIBILITY OF THE SUPPLIER. MIX DESIGNS SHALL BE
REVIEWED BY THE STRUCTURAL ENGINEER PRIOR TO CONCRETE PLACEMENT.
15. A MIX DESIGN SHALL BE PROVIDED FOR EACH TYPE OF CONCRETE. THE MIX DESIGNS SHALL CLEARLY
INDICATE ALL MATERIALS USED IN THE MIX, THE TYPE (USE) OF THE CONCRETE MIX, AND ALL MIX
BACK-UP, DATA, TO INCLUDE BUT NOT LIMITED TO, THE COMPRESSIVE STRENGTH BREAK DATA FOR
EACH MIX BEING SUBMITTED, FINE AND COARSE AGGREGATE GRADATIONS, AND ALL ADMIXTURES.
16. THE USE OF FLY ASH IS PROHIBITED IN ANY EXPOSED MEMBERS. FLY ASH SHALL BE ALLOWED IN
FOUNDATIONS AND SUB-SLABS UPON ENGINEER'S APPROVAL. CONCRETE MIX DESIGNS SHALL BE
SUBMITTED AND APPROVED PRIOR TO CASTING ANY CONCRETE.
17. CEMENT SHALL BE PORTLAND CEMENT CONFORMING TO ASTM C150, TYPE 1. MILL CERTIFICATE SHALL
SHOW TOTAL ALKALINE CONTENT NOT EXCEEDING 0.6%.
18. CONCRETE SHALL HAVE A MAXIMUM SLUMP = 4±1" UNLESS APPROVED BY ENGINEER.
19. THE MIX SHALL HAVE A MAXIMUM WATER/CEMENT RATIO OF 0.50. TROWEL FINISHED INTERIOR SLABS
SUBJECTED TO VEHICULAR TRAFFIC SHALL HAVE A MAXIMUM WATER/CEMENT RATIO OF 0.53.
20. ALL INTERIOR TROWEL FINISHED SLABS, SUBJECTED TO VEHICULAR TRAFFIC, SHALL HAVE A MAXIMUM
ENTRAPPED AIR CONTENT OF 3%.
21. WATER SHALL BE POTABLE, CLEAN AND FREE FROM OILS, ACIDS, SALTS AND OTHER DELETERIOUS
SUBSTANCES.
22.ALL EXPOSED EXTERIOR CONCRETE, SUBJECTED TO FREEZE/THAW CYCLES, SHALL ACHIEVE AN AIR
CONTENT OF 6% ± 1.5.
23. WATER REDUCING AGENTS SHALL CONFORM TO ASTM C494.1
24. AIR ENTRAINING AGENTS SHALL CONFORM TO ASTM C260.
25. AGGREGATE SHALL CONFORM TO ASTM C33. COARSE AGGREGATE SHALL BE CRUSHED ROCK OR
CRUSHED GRAVEL AND SHALL BE GRADED FROM 1 1/2" TO A NO. 4 SIEVE FOR WALLS AND SLABS. A
LARGER AGGREGATE, GRADED FROM 2" TO NO. 4 SIEVE FOR FOUNDATIONS IS ACCEPTABLE. COMBINED
AGGREGATE GRADATION SHALL BE 8% TO 18% RETAINED ON EACH SIEVE BELOW THE TOP SIZE AND
ABOVE THE NO. 100 SIEVE.
26. AGGREGATES SHALL BE TESTED FOR SOUNDNESS IN ACCORDANCE WITH ASTM C88 AND FOR POTENTIAL
REACTIVITY IN ACCORDANCE WITH ASTM C289. AGGREGATES USED FOR SLABS SHALL BE CONSIDERED
INNOCUOUS WHEN TESTED IN ACCORDANCE WITH ASTM C289.
27. ALL CONCRETE TESTING SHALL BE PERFORMED BY AN APPROVED TESTING AGENCY AND IN
ACCORDANCE WITH ALL APPLICABLE ASTM SPECIFICATIONS.
28. SAMPLE EACH TYPE/CLASS OF CONCRETE AT A RATE OF NOT LESS THAN ONE PER DAY NOR LESS THAN
ONE PER 100 CU. YD. NOR LESS THAN ONE FOR EACH 5,000 SQ. FT. OF SURFACE AREA FOR SLABS AND
WALLS (REF ACI 318, 5.6). IF TOTAL VOLUME OF CONCRETE IS SUCH THAT FREQUENCY OF TESTING
REQUIRED WOULD PROVIDE LESS THAN 5 STRENGTH TESTS FOR A GIVEN CLASS OF CONCRETE, TESTS
SHALL BE MADE FROM AT LEAST 5 RANDOMLY SELECTED BATCHES OR FROM EACH BATCH IF FEWER
THAN 5 BATCHES ARE USED.
29. EACH SAMPLE SHALL BE TESTED FOR, AS A MINIMUM, SLUMP, AIR CONTENT, TEMPERATURE, UNIT
WEIGHT, AND COMPRESSIVE STRENGTH.
30. COMPRESSIVE STRENGTH TESTS SHALL BE AS FOLLOWS: 1 CYLINDER SHALL BE TESTED @ 7 DAYS
AFTER POUR, 2 CYLINDERS SHALL BE TESTED @ 28 DAYS AFTER POUR AND 1 CYLINDER SHALL BE HELD
IN RESERVE.
31.VAPOR RETARDER SHALL BE STEGO WRAP 10 MIL CLASS A OR APPROVED EQUAL. RETARDER SHALL BE
INSTALLED, LAPPED 6" MIN. AND TAPED PER MFG. RECOMMENDATIONS.
32. ALL ANCHOR RODS AND EMBEDDED ITEMS SHALL BE ACCURATELY LOCATED AND SECURELY SUPPORTED PRIOR
TO CONCRETE POUR. WET SETTING OF ANCHOR RODS AND EMBEDDED ITEMS IS PROBHIBITED.
a = 6 FT.
5
4
5 5
4
5
a
a
CONCRETE (28 DAYS)
FOOTINGS
PIERS
WEAR SLAB/SLAB-ON-GRADE
ELEVATED SLABS
SUB-SLAB
PRECAST/PRESTRESSED CONCRETE
TILT-UP
ALL OTHER CONCRETE
REINFORCING STEEL
HEADED STUDS
WELDED WIRE FABRIC
COMPOSITE STUDS
DEFORMED BAR ANCHORS (DBA)
STRAND
ADHESIVE ANCHORING
3000 PSI
3000 PSI
4000 PSI
3000 PSI
3000 PSI
5000 PSI (MIN.)
4000 PSI (3000 PSI @ 7 DAYS)
3000 PSI
A615 GRADE 60
A108
A185
SIZE AS NOTED ON DRAWINGS MEETING AWSD1.1
A1064
UNCOATED, ASTM-416 GRADE 270
HILTI HIT-RE 500 V3 ADHESIVE ANCHOR SYSTEM (ICC ESR-3814)
HILTI HIT-RE 500-SD ADHESIVE ANCHOR SYSTEM (ICC ESR-2322)
HILTI HIT-HY 200 ADHESIVE ANCHOR SYSTEM (ICC ESR-3187)
a = 6 FT.
3
2
1
1
1
1
1
1
1
1
1
2 2 2
2
2
22
2
2
2
22
3
3
3
3
33
3
3
3
3
3
3"a""a""a""a"REINFORCED MASONRY NOTES
1. ALL MASONRY CONSTRUCTION SHALL COMPLY WITH ACI 530/ASCE 5/ TMS 402 "BUILDING CODE
REQUIREMENTS FOR MASONRY STRUCTURES".
2. WALLS SHALL BE ADEQUATELY BRACED DURING CONSTRUCTION.
3. GROUT ALL CELLS CONTAINING VERTICAL REINFORCEMENT IN 4'-0" LIFTS MAXIMUM. DO NOT BEGIN
PLACEMENT OF GROUT UNTIL ALIGNMENT OF CELLS ARE INSPECTED AND APPROVED.
4. FILL ALL CELLS BELOW FINISHED FLOOR.
5. ALL ANCHORS INSERTED INTO WALL SHALL BE PLACED IN FULLY GROUTED CELLS.
6. GROUTING SHALL BE STOPPED 1 1/2" BELOW THE TOP OF A COARSE SO AS TO FORM A KEY AT THE POUR
JOINT/UPPER POUR.
7. WHEN THE GROUTING IS STOPPED FOR ONE HOUR OR LONGER, HORIZONTAL CONSTRUCTION JOINTS
SHALL BE FORMED BY STOPPING THE POUR OF GROUT NOT LESS THAN 1/2" BELOW THE TOP OF THE
UPPERMOST UNIT GROUTED.
8. WHERE LINTELS BEAR ON MASONRY WALLS, THEY SHALL BEAR ON EITHER A BOND BEAM COURSE OR
CORES GROUTED SOLID. ALL LINTELS SHALL HAVE AT LEAST 8" OF BEARING AT EACH END UNLESS NOTED
OTHERWISE.
9. VERTICAL CELLS TO BE FILLED WITH GROUT SHALL HAVE VERTICAL ALIGNMENT SUFFICIENT TO MAINTAIN A CLEAR,
UNOBSTRUCTED, CONTINUOUS, VERTICAL CELL MEASURING NOT LESS THAN 3" AND HAVING A CLEAR
AREA OF 10 SQUARE INCHES.
10.ALL REINFORCED HOLLOW UNIT MASONRY SHALL BE BUILT TO PRESERVE THE UNOBSTRUCTED VERTICAL
CONTINUITY OF THE CELLS TO BE FILLED. WITH GROUT WALLS AND CROSS WEBS FORMING SUCH CELLS TO
BE FILLED SHALL BE FULL-BEDDED IN MORTAR TO PREVENT LEAKAGE OF GROUT. ALL HEAD (OR END) JOINTS
SHALL BE FILLED SOLID WITH MORTAR FOR A DISTANCE IN FROM THE FACE OF THE WALL OR UNIT NOT LESS
THAN THE THICKNESS OF THE LONGITUDINAL FACE SHELLS. BOND SHALL BE PROVIDED BY LAPPING UNITS
IN SUCCESSIVE VERTICAL COURSES OR BY EQUIVALENT MECHANICAL ANCHORAGE.
11.TYPICAL JOINT REINFORCEMENT: PROVIDE #9 GALV. HORIZONTAL JOINT REINFORCEMENT IN WALLS AT 16"
O.C. VERTICALLY UNLESS NOTED OTHERWISE. LAP JOINT REINFORCEMENT 12" MINIMUM.
12.JOINT REINFORCEMENT AT CONTROL JOINTS: PROVIDE HORIZONTAL JOINT REINFORCEMENT AT 32" O.C.
ACROSS VERTICAL CONTROL JOINTS IN WALLS. PROVIDE HORIZONTAL JOINT REINFORCEMENT AT 16" O.C.
ACROSS VERTICAL CONTROL JOINTS IN BOND BEAMS.
13.TOP AND BOTTOM REINFORCEMENT IN BOND BEAMS SHALL BE CONTINUOUS ACROSS CONTROL JOINTS.
14.LAP VERTICAL BARS 48 DIAMETERS WITH WIRE TIES AND SECURE IN POSITION WITH SPACERS
BEFORE GROUTING.
15.PROVIDE 1-#5 BAR VERTICAL MINIMUM AT ALL CORNERS, INTERSECTIONS AND EACH SIDE OF CONTROL
JOINTS.
16.PROVIDE 2-#5 BARS VERTICAL AT 8" O.C. AT WALL ENDS.
17.PROVIDE 1-#5 BAR VERTICAL MINIMUM EACH SIDE OF OPENING 4'-0" WIDE OR LESS. PROVIDE 2~#5 BARS
VERTICAL MINIMUM 8" O.C. ON EACH SIDE OF OPENING GREATER THAN 4'-0".
18.VERTICAL REINFORCING BARS SHALL TERMINATE WITH HOOKS IN THE TIE BEAM OR BEAM ABOVE.
19.REINFORCING BARS SHALL BE SECURED IN POSITION PRIOR TO GROUTING CELLS.
20.VERTICAL REINFORCING BARS SHALL HAVE A MINIMUM OF 3/4" CLEARANCE FROM FACE OF MASONRY.
21.WHERE OPENINGS IN WALL REQUIRE CUTTING OF BLOCK, THE CONTRACTOR SHALL ALLOW FOR CUTTING
OF THE BLOCK SUCH THAT 1~#5 VERTICAL CAN BE INSTALLED AND GROUTED.
22.PROVIDE VERTICAL CONTROL JOINTS AT 24'-0" O.C. MAXIMUM. LOCATE BOND BEAM CONTROL JOINTS AT
CENTERLINE OF COLUMNS AS APPROPRIATE. SEE DRAWING S002 FOR ADDITIONAL INFORMATION.
23.VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION AT TOP AND BOTTOM AND AT INTERVALS NOT
EXCEEDING 10 FEET.
24.GROUT MIX DESIGN IS THE RESPONSIBILITY OF THE SUPPLIER. MIX DESIGN SHALL BE APPROVED BY
STRUCTURAL ENGINEER PRIOR TO PLACEMENT. GROUT SHALL HAVE A MAXIMUM SLUMP = 9±1" AND A 28
DAY COMPRESSIVE STRENGTH OF 2,000 PSI MIN.
25.AGGREGATE FOR GROUT SHALL CONFORM TO ASTM C404.
26. AGGREGATE FOR MORTAR SHALL CONFORM TO ASTM C144.
27.WATER SHALL BE POTABLE, CLEAN AND FREE FROM OILS, ACIDS, SALTS AND OTHER DELETERIOUS
SUBSTANCES.
28.REINFORCING SHALL CONFORM TO ASTM A615, GRADE 60.
29.REINFORCEMENT PLACEMENT DRAWINGS FOR ALL MASONRY WALLS SHALL BE SUBMITTED AND
REVIEWED PRIOR TO CONSTRUCTION.
30.MATERIAL CERTIFICATES AND TEST REPORTS SHALL BE PROVIDED FOR EACH TYPE OF MASONRY UNIT.
MASONRY
CONCRETE MASONRY UNIT (CMU)
NET AREA ASSUMED; An
MORTAR
GROUT
JOINT REINFORCEMENT
SCREW ANCHOR
ADHESIVE ANCHORING
C90, f’m = 2000 PSI
FACE SHELL BEDDING NCMA-TEK 141A
C270 TYPE M OR S BELOW GRADE, TYPE N OR S ABOVE GRADE
C476 2000 PSI
W1.7 OR 0.148” DIA.
SIMPSON STRONG-TIE TITEN HD SCREW ANCHOR (ICC ESR-1056)
HILTI HIT-HY 270 ADHESIVE ANCHOR SYSTEM (ICC ESR-4143)
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
S002
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
GENERAL NOTES AND
COMPONENTS AND
CLADDING DIAGRAM
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
COMPONENTS AND CLADDING DIAGRAM - WALL
ROOF COMPONENTS & CLADDING DIAGRAM
NO. DESCRIPTION DATEANGEL ALICEA
E NCSIEL
S T A T E O F
No. 93531
SHEAR WALL SCHEDULE
MARK TYPE SHEATHING WOOD SHEATHING NAILING
(NAIL SIZE - EDGE SPACING - FIELD SPACING)
EXTERIOR/INTERIOR SHEAR
WALL SOLE PLATE ANCHORS
SHEAR WALL NOTES:
1.SEE TYPICAL SHEAR WALL CONSTRUCTION DETAILS FOR VARIOUS WALL TYPES.
2.ALL CONNECTORS SHALL BE MANUFACTURED BY THE SIMPSON STRONG-TIE COMPANY.
3.BLOCK ALL EDGES OF SHEAR WALL SHEATHING WHERE INDICATED AS (BLOCKED) IN
SHEAR WALL SCHEDULE.
4.ATTACH SHEAR WALL SHEATHING DIRECTLY TO THE WALL FRAMING (STUDS).
5.SHEATHING INDICATED IN SCHEDULES IS THE SHEATHING REQUIRED TO RESIST CODE
REQUIRED LATERAL LOADS. SEE ARCHITECTURAL DOCUMENTS FOR ALL OTHER
SHEATHING REQUIREMENTS.
6.USE COMMON NAILS, FOR WOOD SHEATHING NAILING AND COOLER NAILS FOR GYPSUM
WALLBOARD NAILING, U.N.O.
7.(*) DENOTES 5/8" GYPSUM WALLBOARD OR 5/8" PVC OR VINYL WALLBOARD.
GYPSUM WALLBOARD NAILING
(NAIL SIZE - EDGE SPACING - FIELD SPACING)
1SW1
GYPSUM WALLBOARD
PER SCHEDULE
(SEE NOTE 7)WOOD SHEATHING
PER SCHEDULE
WOOD STUD
INTERIORGARAGE
TYPE 1
10d -2" -2"
GARAGE: 15/32" WOOD SHEATHING
INTERIOR: (*) 5/8" GYPSUM
WALLBOARD
SP15d -4" -4"
2SW2 ----
GARAGE: (*) 5/8" GYPSUM
WALLBOARD
INTERIOR: (*) 5/8" GYPSUM
WALLBOARD
SP26d -4" -4"
GYPSUM WALLBOARD
PER SCHEDULE
(SEE NOTE 7)
WOOD STUD
INTERIORGARAGE
TYPE 2
GYPSUM WALLBOARD
PER SCHEDULE
(SEE NOTE 7)
16d COMMON
NAILS AT 16" OC
16d COMMON
NAILS AT 16" OC
EACH FACE
1/2" PLYWOOD SPACER
2X6 CONT
BETWEEN
BEARING STUDS
H2/S003H1/S003
J1/S003
10d COMMON NAILS
STAGGERED AT 12" OC
1/2" PLYWOOD SPACER
16d COMMON
NAILS AT 16" OC
2X6 CONT
BETWEEN
BEARING STUDS
FULL HEIGHT STUD
SEE SCHEDULE
10d COMMON NAILS
STAGGERED AT 8" OC
BEARING STUD
SEE SCHEDULE
J2/S003
FULL HEIGHT STUD
SEE SCHEDULE
10d COMMON NAILS
STAGGERED AT 8" OC
BEARING STUD
SEE SCHEDULE
J3/S003
FULL HEIGHT STUD
SEE SCHEDULE
10d COMMON NAILS
STAGGERED AT 8" OC
BEARING STUD
SEE SCHEDULE
J4/S003
FULL HEIGHT STUD
SEE SCHEDULE
10d COMMON NAILS
STAGGERED AT 8" OC
BEARING STUD
SEE SCHEDULE
WOOD HEADER JAMB AND SILL SCHEDULE
H1
HEADER JAMB SILL
H2
MARK SIZE MAX. OPENING DETAIL SIZE
FULL
HEIGHT
STUDS
BEARING
STUDS DETAIL
REMARKS
(2) 2x6
(2) 2x8
H1/S003
H1/S003
(2) 2x4
(2) 2x4
(1) 2x4
(2) 2x4
J1/S003
J2/S003
(1) 2x4
(1) 2x6
SP #2
NOTE:
1.SEE TYPICAL WOOD FRAMING ELEVATION FOR WALL CONFIGURATIONS.
H7 (3) 1 3/4" x7 1/4" -------H2/S003 (3) 2x6 (6) 2x6 J4/S003 -----
SP #2
LVL MICROLAM
H4 (3) 2x8 H2/S003 (3) 2x6 J2/S003 (2) 2x6
SP #2
H5 (3) 2x10 H2/S003 (4) 2x6 J2/S003 (2) 2x6 SP #2
H3 (3) 2x6 H2/S003 (2) 2x6 (2) 2x6 J2/S003 (2) 2x6
SP #2
-------
-------
-------
-------
-------
H6 (3) 2x12 H2/S003 (5) 2x6 J2/S003 (2) 2x6 SP #2-------
H8 (3) 1 3/4" x9 1/4" -------H2/S003 (3) 2x6 (3) 2x6 J4/S003 -----LVL MICROLAM
H9 (3) 1 3/4" x11 1/4" -------H2/S003 (3) 2x6 (3) 2x6 J4/S003 -----LVL MICROLAM
H10 (3) 1 3/4" x11 7/8" -------H2/S003 (4) 2x6 (3) 2x6 J4/S003 -----LVL MICROLAM
H11 (3) 1 3/4" x14" -------H2/S003 (5) 2x6 (3) 2x6 J4/S003 -----LVL MICROLAM
(2) 2x6
(2) 2x6
(2) 2x6
EXTERIOR/INTERIOR SHEAR WALL SOLE PLATE CONNECTION SCHEDULE
1/2" DIA. HILTI TITEN HD
WITH MINIMUM EMBED = 6"
MARK TYPE SPACING
(ON CENTER)COMMENTS
SP1 1'-2"-----
SHEAR WALL SOLE PLATE CONNECTION NOTES:
1.EACH SOLE PLATE WALL SEGMENT REQUIRES (3) ANCHORS MINIMUM.
2.WHERE NOT INDICATED ON PLAN, ANCHOR WALL SOLE PLATES W/ "SP1" FIRST FLOOR AND "SP5" SECOND FLOOR.
1/2" DIA. HILTI TITEN HD
WITH MINIMUM EMBED = 4"SP2 2'-0"-----
CONCRETE TENSION LAP SPLICE SCHEDULE
#3 28"
BAR
SIZE
#4 37"
#5 47"
#6 56"
#7 81"
#8 93"
#9 118"
19"
31"
37"
54"
62"
70"
25"
22"
29"
36"
43"
63"
72"
81"
24"
32"
40"
48"
70"
80"
91"
TOP BARS OTHER BARS
4000 PSI
OTHER BARSTOP BARS
3000 PSI
NOTES:
1.TABULATED VALUES ARE BASED ON THE FOLLOWING: NORMAL
WEIGHT CONCRETE. UNCOATED GRADE 60 REINFORCING BARS.
CLEAR COVER NOT LESS THAN 1.0 x BAR DIAMETER. CLEAR
SPACING NOT LESS THAN 2.0 BAR DIAMETER. LAP CLASS B.
2.TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12 INCHES
OF CONCRETE CAST BELOW THE BARS.
HOLD-DOWN SCHEDULE
MARK TYPE FASTENERS TO
VERTICAL STUD
THRU FLOOR
ANCHOR/CONCRETE
SLAB
COMMENTS
HOLD-DOWN NOTES:
1.HOLD-DOWNS MANUFACTURED BY SIMPSON STRONG-TIE.
2.USE COMMON NAILS, U.N.O.
3.IF SCHEDULED POST DIFFERS FROM POST ON PLAN PROVIDE LARGER OF TWO POSTS.
4.HOLD-DOWN MAY BE LOCATED WITHIN 8" OF SHEAR WALL SEGMENT END TO AVOID
CONFLICTS, BUT HOLD-DOWNS MUST ALIGN VERTICALLY.
5.NUMBER OF FASTENERS INDICATED IN HOLD-DOWN SCHEDULE INDICATES TOTAL
NUMBER OF FASTENERS REQUIRED FOR EACH INDIVIDUAL HOLD-DOWN.
6.AT LOCATIONS WHERE HOLD-DOWNS ARE ATTACHED TO MULTIPLE VERTICAL STUDS,
NAIL SHEAR WALL SHEATHING TO EACH VERTICAL STUD WITH FASTENERS SPECIFIED
IN SHEAR WALL SCHEDULE AT 6" O.C.; STAGGER FASTENERS IN ADJOINING STUDS.
7.SEE "TYPICAL EXPANSION ANCHOR HOLD-DOWN DETAIL".
POST
DTT2ZHD1 (2) 2x68-SDS 1/4"x1 1/2"
1/2" DIA.
THREADDED ROD
(4" EMBEDMENT)
SEE NOTES
HDU11-SDS2.5HD2 (4) 2x630-SDS 1/4"x1 1/2"
1" DIA.
THREADDED ROD
(6" EMBEDMENT)
SEE NOTES
TRUSS BLOCKING DESIGN CRITERIA
(2) BLOCKING PANEL
BETWEEN EVERY TRUSSSHEAR WALL 1
LOCATION MAXIMUM SPACING SERVICE UNIT SHEAR
1,750 LBS/FT
(1) BLOCKING PANEL
BETWEEN EVERY
OTHER TRUSS
OTHERWISE 350 LBS/FT
(1) BLOCKING PANEL
BETWEEN EVERY TRUSSSHEAR WALL 2 750 LBS/FT
TRUSS / RAFTER UPLIFT CONNECTION TO TOP PLATE SCHEDULE
CONNECTOR
FASTENERS
TO TRUSS TO PLATES UPLIFT LATERAL
OR JOIST OR HEADER
OR WALL
REMARKSQTY.MARK
H10A (9) 10d x 1 1/2" 2,280 LBS.
EXTERIOR LOAD BEARING
CMU WALL2
ALLOWABLE ALLOWABLE
TRUSS / RAFTER CONNECTOR NOTES:
1.ALL ANCHORS TO BE SIMPSON (WWW.STRONGTIE.COM) OTHER CONNECTORS MAY BE USED BUT MUST
BE PROVEN EQUAL TO THE UPLIFT VALUES GIVEN IN THE TABLE.
2.THE CONTRACTOR SHALL SELECT AN UPLIFT CONNECTOR(S) FOR EACH TRUSS/RAFTER THAT MEETS OR EXCEEDS
THE UPLIFT/LATERAL REACTIONS ON THE SCHEDULE PROVIDED ABOVE.
3.WOOD TOP PLATES SHALL BE #2 SOUTHERN PINE. WOOD TOP PLATES IN CONTACT WITH CONCRETE SHALL BE
PRESSURE TREATED.
4.HURRICANE TIES IN CONTACT WITH PRESSURE TREATED WOOD SHALL HAVE A MINIMUM ZMAX FINISH.
5.THE CONTRACTOR MAY USE ALTERNATE CONNECTORS WITH EQUIVALENT CAPACITIES. ALTERNATE CONNECTORS
SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS SPECIFICATIONS.
6.WHERE (2) CONNECTORS ARE USED, INSTALL SO THAT FASTENERS ARE STAGGERED WHERE FASTENERS ARE
NOT STAGGERED SISTER TRUSS/RAFTERS WITH ADDED 2x ATTACHED WITH 10d NAILS TO MATCH NUMBER OF
FASTENERS IN CONNECTOR.
7.PROVIDE VGTR/L CONNECTOR AT ALL GIRDER TRUSS/RAFTER LOCATIONS. GIRDER TRUSS/RAFTER IS DEFINED AS
GIRDER CARRYING OTHER TRUSS/RAFTER OR MULIPLE PLY TRUSS/RAFTERS WITH SPECIAL LOADING.
1,180 LBS.(9) 10d x 1 1/2"
VGT (32) SDS 1/4" x 3" 7,185 LBS.
GIRDER / HIP TRUSSES AT
EXTERIOR LOAD BEARING
CMU WALL
2 ----2-5/8"
1,200 LBS.INTERIOR LOAD BEARING
WOOD WALLS2H2.5A (5) 8d (5) 8d 220 LBS.
MARK
MH1
MH2
MH3
DEPTH
8"
16"
24"
1-#5 BOTTOM
1-#5 BOTTOM
REINFORCEMENT
6" WALL 8" WALL
NOTES:
1. PROVIDE 8" MIN. BEARING EACH END.
2. ALL LINTELS SHALL BE GROUTED SOLID.
3. REFER TO ARCH. & MECH. DWGS. FOR EXACT
SIZE AND LOCATION OF MASONRY OPENINGS.
4. ALL PRECAST LINTELS SHALL BE HIGH
STRENGTH PRECAST/PRESTRESSED.
5. ALL LINTELS SHALL HAVE A MINIMUM 3"x4"
OPENING/NOTCH AT THE END OVER
SUPPORTS TO ACCOMMODATE VERTICAL
REINFORCEMENT AND GROUT.
6. PRECAST LINTEL SUPPLIER SHALL SUBMIT
CAPACITY/LOAD RATING TABLES SIGNED AND
SEALED BY A PROFESSIONAL ENGINEER
REGISTERED IN THE PROJECT STATE.DEPTHDEPTHCONCRETE BEAM
BOND BEAM
REINFORCEMENT
REINFORCEMENT
#4 STIRRUP @ 8" O.C.
(@ 12'-0" TO 16'-8")
#4 STIRRUP @ 12" O.C.
(@ ALL OTHERS)
* USE CONCRETE BEAM ONLY
2-#5 BOTTOM WITH #3
TIES AT 16" O.C.
CONC MASONRY WALL
SEE SCHEDULEDEPTHMASONRY BOND BEAM
LINTEL, SEE SCHEDULE
FOR SIZE & REINF0'-2 1/2"2" CLRTOP BARS
PER SCHEDULE
STIRRUPS
PER SCHEDULE
GROUT LINTEL SOLID
BTM BARS
PER SCHEDULE
WOOD POST SCHEDULE
MARK MEMBER
6X6 P.T. POSTWP1
COMMENTS
WP2
ATTACH BASE W
SIMPSON AB66Z
COLUMN BASE
12X12 P.T. POST
ATTACH BASE W
SIMPSON AB1212Z
COLUMN BASE
MASONRY LAP
SPLICE SCHEDULE
#3 2'-3"
BAR
SIZE
#4
#5
#6
LAP
SPLICE
3'-0"
3'-9"
4'-6"
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
S003
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
SCHEDULES AND TABLES
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SHEAR WALL SCHEDULE
WOOD HEADER JAMB AND SILL SCHEDULE
EXTERIOR SHEAR WALL SOLE PLATE CONNECTION SCHEDULE
HOLD-DOWN SCHEDULE
TRUSS BLOCK DESIGN CRITERIA
TRUSS/RAFTER UPLIFT CONNECTION TO TOP PLATE SCHEDULE
CONCRETE MASONRY LINTEL SCHEDULE
WOOD POST SCHEDULE
NO. DESCRIPTION DATEANGEL ALICEA
E NCSIEL
S T A T E O F
No. 93531
SE1.8
ON GRANULAR BASE (PER NOTES)
ON COMPACTED FILL.
6X6 - W1.4xW1.4 WWF
ON 6 MIL VAPOR RETARDER
T/SLAB ELEV. 0'-0" (F.V.)
4" CONCRETE SLAB W/6"25'-8"4'-0"13'-8"8'-8"6'-6"3'-0"6'-6"5'-4"5'-4"5'-4"18'-0"3'-0"5'-0"
10'-4"4'-10"3'-0"4'-10"4'-8"3'-8"3'-0"3'-4"2'-2"16'-0"2'-2"6"6"SE1.8SE2.0
SE1.8
SE2.0
SE2.0
SE1.8
SE1.8
SE1.8
SE1.8
SE1.0SE2.0SE2.0SE1.8SE1.8SE1.8SE2.0SE2.0SE1.8SE1.8SE1.8WP1 WP1
WP2
ON GRANULAR BASE (PER NOTES)
ON COMPACTED FILL.
6X6 - W1.4xW1.4 WWF
ON 6 MIL VAPOR RETARDER
T/SLAB ELEV. -0'-4" (F.V.)
4" CONCRETE SLAB W/
ON GRANULAR BASE (PER NOTES)
ON COMPACTED FILL.
6X6 - W1.4xW1.4 WWF
ON 6 MIL VAPOR RETARDER
T/SLAB ELEV. -0'-4" (F.V.)
4" CONCRETE SLAB W/
MW1
MW1
MW1
MW1
MW1
CMU6
MW1
MW1
MW1
MW1
MW1
MW1
MW2
MW1
MW2
MW1
MP2
MP2
MP2
MP2
MP1 MP1
MP1 MP1
MP2
MP2 MP1 MP1 MP2
MP1
MP1
MP2
MP3
MP2
MP3
MP2
MP1MP2
MP1
MP1
MP2MP1
MP1
MP2
MP2
MP1
MP1
16'-0"16'-0"26'-0"
58'-0"8'-8"52'-0"10'-4"12'-8"4'-8"10'-0"20'-4"31'-8"3'-0"23'-4"58'-0"10'-8"58'-0"
5 1/2"8"F3.0 F3.0
F2.06"2'-10"12
S501
10
S501
10
S501
12
S501
1
S502
1
S502
MP3
MP4
MP2
MP3
FOUNDATION/SLAB NOTES:
1.DATUM TOP OF SLAB ELEVATION 0'-0". OTHER TOP OF SLAB ELEVATIONS ARE
REFERENCED AS (+) OR (-) FROM DATUM.
2.TYPICAL CONCRETE SLAB ON GRADE SHALL BE 4" THICK 4,000 PSI W/ FIBERMESH
CONCRETE OR 6x6x 1.4/1.4 WWF CENTERED IN SLAB OVER 6 MIL. VAPOR BARRIER
OVER CLEAN, WELL COMPACTED TERMITE TREATED FILL. INTERIOR SLABS
CEMENTITIOUS MATERIALS RATIO IS 0.45 AND EXTERIOR IS 0.4.
3.EXTERIOR LOAD BEARING / SHEAR WALLS REFER TO ELEVATIONS AND SHALL HAVE
(4) STUDS MINIMUM EACH END.
4.COORDINATE WITH OTHER DISCIPLINES AND TRADES FOR LOCATIONS AND DIMENSIONS
OF OPENINGS, RECESSES, SLEEVES AND PIPING.
5.REFER TO GENERAL NOTES FOR INFORMATIONS NOT INDICATED ON PLAN.
6.ALL EXTERIOR WOOD AND WOOD BEARING ON CONCRETE SHALL BE PRESSURE TREATED.
7.CONTRACTOR TO COORDINATE ALL OPENING HEADERS AND SILL WITH THE LATEST
EDITION OF THE FLORIDA BUILDING CODE. ATTACH PER FBC.
8.ALL EXTERIOR STEEL OR METALS SHALL BE GALVANIZED.
9.UNLESS NOTED OTHERWISE, MINIMUM FASTENING OF WOOD OF WOOD MEMBERS SHALL
CONFORM TO TABLE OF THE LATEST EDITION OF THE FLORIDA BUILDING CODE.
10.REFER TO S501 FOR TYPICAL CONCRETE DETAILS.
INDICATES MASONRY WALLS
INDICATES NEW CONCRETE SLAB-ON-GRADE
INDICATES NEW 2X WALL
CONCRETE MASONRY WALL SCHEDULE
5 5/8"
MARK WIDTH
#5 BARS AT 24" O.C.
VERTICAL REINFORCING DOWELS TO FOUNDATION
MW1
NOTES
FULLY GROUT WALL
W1.7 JOINT REINFORCEMENT AT 32" O.C.#5 BARS AT 24" O.C.
5 5/8" #5 BARS AT 32" O.C.
MW2 FULLY GROUT WALL
W1.7 JOINT REINFORCEMENT AT 8" O.C.#5 BARS AT 32" O.C.
CONCRETE MASONRY PIER SCHEDULE
5 5/8"
MARK WIDTH
#5 BAR AT 8" O.C.
VERTICAL REINFORCING DOWELS TO FOUNDATION
MP1
NOTES
GROUT PIER SOLID#5 BAR AT 8" O.C.
LENGTH
0'-8"
HORIZONTAL REINFORCEMENT
W1.7 JOINT REINF. AT 48" O.C. ---
DETAIL
5 5/8"MP2 GROUT PIER SOLID1'-4"
5 5/8"MP3 GROUT PIER SOLID2'-2"
#5 BAR AT 8" O.C.
(4) #5 BARS
#5 BAR AT 8" O.C. W1.7 JOINT REINF. AT 48" O.C.
#3 TIES AT 8" O.C.
---
---(4) #5 BARS
5 5/8"MP4 GROUT PIER SOLID3'-0"(6) #5 BARS #3 TIES AT 8" O.C. ---(6) #5 BARS
CONTINUOUS SLAB EDGE FOUNDATION SCHEDULE
MARK DEPTH LONGITUDINAL REINFORCING TRANSVERSE REINFORCING NOTESWIDTH
1'-4" (2) #5 BARSSE1.8 ----#5 BAR AT 18" O.C.1'-8"
1'-4" (3) #5 BARSSE2.0 ----#5 BAR AT 18" O.C.2'-0"
FOOTING SCHEDULE
1'-2"
MARK DEPTH
(3) #5 BARS BOTOM
LONGITUDINAL REINFORCING TRANSVERSE REINFORCING
F2.0
NOTES
----
WIDTH
2'-0"(3) #5 BARS BOTOM
1'-2" (4) #5 BARS BOTOMF3.0 3'-0"(4) #5 BARS BOTOM
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
S110
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
FOUNDATION AND SLAB
PLAN
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 1/4" = 1'-0"1 FOUNDATION / SLAB PLAN
NO. DESCRIPTION DATEANGEL ALICEA
E NCSIEL
S T A T E O F
No. 93531
(SW1)
LOAD BEARING WALL
2X6 STUDS AT 16" O.C.
NOTES:
1.EXTERIOR LOAD BEARING / SHEAR WALLS REFER TO ELEVATIONS AND SHALL HAVE
(4) STUDS MINIMUM EACH END.
2.COORDINATE WITH OTHER DISCIPLINES AND TRADES FOR LOCATIONS AND DIMENSIONS
OF OPENINGS, RECESSES, SLEEVES AND PIPING.
3.REFER TO GENERAL NOTES FOR INFORMATIONS NOT INDICATED ON PLAN.
4.SWX INDICATES BEARING / SHEARWALL..
5.REFER TO S501 FOR TYPICAL CONCRETE DETAILS.
6.REFER TO S502 FOR TYPICAL MASONRY DETAILS.
7."XXX LBS/FT." DENOTES TRUSS BLOCK LOAD (ULTIMATE) 1.0WL. REFER TO S003 FOR
TRUSS BLOCK DESIGN CRITERIA.350 LBS/FT350 LBS/FT
HD2 HD2
(SW2)
LOAD BEARING WALL
2X6 STUDS AT 16" O.C.
(SW2)
LOAD BEARING WALL
2X6 STUDS AT 16" O.C.
INDICATES 1/2" EPOXY SET THREADED ROD LOCATIONS SHIFT A MAXIMUM OF 4" WHERE
REQUIRED. MAXIMUM SPACING AT 6'-0" O.C.
INDICATES HOLD-DOWN LOCATIONS PER SCHEDULE PER SHEET S111.
4'-4 1/2"16'-4"14'-8"7'-0"6'-0"2'-0"3'-3 3/4"6"5'-4"LOAD BEARING WALL
2X12 STUDS AT 16" O.C.
HD1
HD1
MH3
MH2
MH3
MH2MH1MH2
MH2
MH1 MH2
MH1350 LBS/FT1,750 LBS/FT350 LBS/FT750 LBS/FT
350 LBS/FT
350 LBS/FT
750 LBS/FT
350 LBS/FT
350 LBS/FT
750 LBS/FT750 LBS/FT350 LBS/FTH3H5
REFER TO TRUSS BLOCKING
DESIGN CRITERIA ON SHEET
S003, TYPICAL
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
S111
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
SHEARWALL, WALL
FRAMING, HEADERS, AND
HOLD-DOWN PLAN
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 1/4" = 1'-0"1 SHEARWALL AND WALL FRAMING PLAN
NO. DESCRIPTION DATEANGEL ALICEA
E NCSIEL
S T A T E O F
No. 93531
9
S602
9
S602
9
S602
11
S602
(TYP)
PLYWOOD DIAPHRAGM (ROOF SHEATHING)
23/32" APA RATED SHEATHING STRUCTURAL 1
EXPOSURE 1 OVER PRE-ENGINEERED
TRUSS FRAMING SPACED AT 2'-0" O.C. MAX.
SEE NOTE 3 FOR DIAPHRAGM ATTACHMENT
PATTERNS (TYP.)
TRUSS BEARING
EL. = 10'-3"
TRUSS BEARING
EL. = 10'-3"
PLYWOOD DIAPHRAGM (ROOF SHEATHING)
23/32" APA RATED SHEATHING STRUCTURAL 1
EXPOSURE 1 OVER PRE-ENGINEERED
TRUSS FRAMING SPACED AT 2'-0" O.C. MAX.
SEE NOTE 3 FOR DIAPHRAGM ATTACHMENT
PATTERNS (TYP. AS REQUIRED)
RIDGE HIPHIP HIPHIPRIDGEHIP HIPRIDGEHIP HIP VALLEYHIPHIPHIPHIPVALLEYRIDGE5:12 SLOPE 5:12 SLOPE
5:12 SLOPE
5:12 SLOPE 5:12 SLOPE
5:12 SLOPE
5:12 SLOPE 5:12 SLOPE
5:12 SLOPE 5:12 SLOPE
5:12 SLOPE2-PLY GIRDER TRUSS2-PLY GIRDER TRUSS2-PLY GIRDER TRUSS2-PLY GIRDER TRUSS
GIRDER TRUSS
TRUSS BEARING
EL. = 10'-3"
TRUSS BEARING
EL. = 12'-3"
TRUSS BEARING
EL. = 12'-3"
TRUSS BEARING
EL. = 14'-3"
TRUSS BEARING
EL. = 10'-3"
TRUSS BEARING
EL. = 10'-3"
PLYWOOD DIAPHRAGM (ROOF SHEATHING)
23/32" APA RATED SHEATHING STRUCTURAL 1
EXPOSURE 1 OVER PRE-ENGINEERED
TRUSS FRAMING SPACED AT 2'-0" O.C. MAX.
SEE NOTE 3 FOR DIAPHRAGM ATTACHMENT
PATTERNS (TYP.)
1'-6"16'-0"5'-4"5'-4"5'-4"26'-0"1'-6"1'-6"58'-0"1'-6"1'-6"8'-10"1'-6"12'-8"1'-6"3'-7 1/2"1'-11 1/2"6'-1"1'-6"20'-4"1'-6"1'-6"7'-2"1'-6"43'-4"1'-6"61'-0"61'-0"8'-8"46'-4"10'-4"15'-8"5'-7"6'-1"23'-4"
H9 H9 H9
H5
SIMPSON STRONG TIE
HGUM5.50-SDS
SIMPSON STRONG TIE
HGUM5.50-SDS
SIMPSON STRONG TIE
LGUM26-3-SDS
SIMPSON STRONG TIE
HGUS28-3
SIMPSON STRONG TIE
HGUS5.50/12
PRE-ENGINEERED TRUSS MANUFACTURER
TO PROVIDE BRIDGING AS REQUIRED
TRUSS MANUFACTURER IS RESPONSIBLE
FOR THE TRUSS DESIGN, TRUSS CONNECTIONS,
AND HURRICANE/UPLIFT CONNECTIONS
PRE-ENGINEERED TRUSS MANUFACTURER
TO PROVIDE BRIDGING AS REQUIRED
5:12 SLOPE
GIRDER TRUSS
REFER TO SHEET S003
FOR UPLIFT SCHEDULE
TYPICAL
ROOF FRAMING NOTES:
1.T/WALL ELEVATION = SEE PLAN.
2.VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
3.PLYWOOD ROOF DIAPHRAGM SHEATHING OR OSB SHALL BE CONSTRUCTION IN ACCORDANCE WITH THE FLORIDA
BUILDING CODE. THERE SHALL BE NO CONTINUOUS PANEL EDGES PARALLEL TO TRANSVERSE DIRECTION
(STAGGER PLYWOOD SHEETS). NAIL BLOCKED DIAPHRAGM WITH 10d NAILS AT 4" O.C. AT DIAPHRAGM PERIMETER
AND ALL PANEL EDGES AND 4" AT INTERMEDIATE SUPPORTS. NAIL SPACING SHALL BE 4" O.C. AT ENDS IN ALL CASES.
PROVIDE BLOCKING AT ALL EDGES OF ROOF SHEATHING.
4.REFER TO GENERAL NOTES FOR INFORMATIONS NOT INDICATED ON PLAN.
5.CONTRACTOR TO COORDINATE ALL OPENING HEADERS AND SILL WITH THE LATEST EDITION OF THE FLORIDA
BUILDING CODE. ATTACH PER LATEST EDITION OF THE FBC.
6.UNLESS NOTED OTHERWISE, MINIMUM FASTENING OF WOOD MEMBERS SHALL CONFORM TO TABLE OF THE LATEST
EDITION OF THE FLORIDA BUILDING CODE.
7.CONTRACTOR TO VERIFY THAT EXISTING TRUSS IS ALIGNED WITH EXISTING POSTS. IF NOT ALIGN, PROVIDE 2x4
HORIZONTAL BLOCKING AND ATTACH TO EACH ADJACENT EXISTING BOTTOM CHORD TRUSS WITH SIMPSON A34
FRAMING ANGLES.
8.REFER TO S601 AND S602 FOR TYPICAL WOOD FRAMING DETAILS.
9.REFER TO S603 FOR BEARING / SHEARWALL DETAILS.
10. REFER TO S003 FOR UPLIFT SCHEDULES
INDICATES NEW ROOF
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
S140
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
ROOF FRAMING PLAN
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 1/4" = 1'-0"1 ROOF FRAMING PLAN
NO. DESCRIPTION DATEANGEL ALICEA
E NCSIEL
S T A T E O F
No. 93531
BOT/BASE PLATE
TOP/FOOTING
TOP/PIER 1 1/2" MIN.OR 4xANCHOR ROD DIA.5 1/2" THD. MIN.EMBEDMENTCOVERIF COVER < 3"3" HAUNCHLEVELING NUT
(NOT REQ'D. IN FREEZER)
ANCHOR ROD
HEX NUT
BASE PLATE ANCHOR ROD HOLE
ANCHOR ROD DIA.
3/4" TO 1"
1 1/4" TO 2"
HOLE DIA.
5/16" OVERSIZE
1/2" OVERSIZE
ANCHOR ROD PLATE WASHERS
DIAMETER
7/8"
1 1/4"
DIAMETER
1 9/16"
2 1/16"
ANCHOR ROD MAX. HOLE
W/ 1 1/16" DIA. HOLE
2 1/2" x 5/16"
3" x 1/2"
PLATE WASHER SIZE
NOTES:
1. HOLES IN INSULATION BLOCKS SHALL BE 1/8" LARGER THAN THE
DIAMETER OF THE ANCHOR BOLT.
2. IF ANCHOR ROD HOLE DIAMETER IS SPECIFIED LARGER THAN
SHOWN IN SCHEDULE, ANCHOR ROD PLATE WASHERS SHALL
BE USED. (SEE BELOW)
NOTE:
IF MAX. HOLE DIA. OPTION IS CHOSEN, PLATE WASHERS MUST
BE WELDED TO BASE PLATE WITH 3/16" FILLET WELD FULL
LENGTH OF PLATE WASHER ON TWO OPPOSING SIDES WHEN
LOCATED AT A BRACED COLUMN.
ANCHOR ROD DETAIL
SET ANCHORS TO ENSURE PROPER EMBEDMENT
FROM TOP OF PIER OR FOOTING
1" 1 13/16" 3" x 3/8"
3/16
1 1/2" 2 5/16" 3 1/2" x 1/2"
3/4" 1 5/16" 2" x 1/4"
NOTE:
SLAB SHALL BE POURED
MONOLITHICALLY WITH
TURN DOWN
REFER TO SCHEDUEL FOR
BASE CONNECTION DETAIL
1
1
CONT. P.T.
2x PLATE
WELDED WIRE
MESH, SEE SLAB
PAN
2'-0" LAP
#4 DOWEL AT 18" O.C.
SEE PLAN FOR REINFORCEMENT
1'-4" MINIMUMT/ SLAB
SEE PLAN
CONCRETE SLAB
SEE PLAN
SEE PLAN FOR
REINFORCEMENT
TYPICAL INTERIOR THICKENED SLAB DETAIL
TYPICAL MONILITHIC POUR STEP DOWN DETAIL
TYPICAL FOUNDATION SLAB EDGEMINIMUM1'-0"T/ SLAB
SEE PLAN
T/ SLAB
SEE PLAN
CONCRETE SLAB
SEE PLAN
PLANSEE#4 DOWEL AT 18" O.C.
SEE PLAN
COORDINATE FOOTING
DEPTH WITH FINISHED GRADE
CONCRETE SLAB
SEE PLAN
#4xCONT. NOSING
BAR
TURN WELDED WIRE FABRIC
OVER NOSING BAR AND
EXTEND
6"SEE PLAN FOR REINFORCEMENT
FINISHED
GRADE
ACI LAP
PROVIDE MIN.ACI LAPPROVIDE MIN.ACI LAPPROVIDE MIN.CORNER AND JUNCTION BARS TO BE
SAME SIZE AS CONTINUOUS
HORIZONTAL REINFORCING
CONTINUOUS HORIZONTAL WALL OR
FOOTING REINFORCING
CORNER DETAIL JUNCTION DETAIL
1/8" CUT
"T/4"1" TYP."T""T/3"1" MIN."T""T/4"1/8" CUTJOINT SEALANT, FINISH
FLUSH WITH SURFACE
CUT W.W.F.BREAK BONT
W/ CURING
COMPOUNT
CRACK CONTROL JOINTS -(C.C.J.)CONSTRUCTION JOINT -(C.J.)
SLAB ON GRADE JOINT NOTES:
1. C.C.J. SHALL BE PREFORMED OR SAWED. IF SAWED, SAWING MUST
TAKE PLACE WITHIN 12 HRS. OF SLAB PLACEMENT.
2. * USE INSTEAD OF CRACK CONTROL JOINT WHEREVER CONSTRUCTION
IS STOPPED OR WHERE CALLED FOR ON PLAN.
COMPACTED FILL
VAPOR RETARDER
SLAB ON GRADE
SLAB REINFORCEMENT
WWF, SEE PLAN
1-#4 CONT
8"PLANSEEGRADE,
SEE CIVIL
COORD w/
GEOTECH MIN12".CONTINUOUS CONCRETE
FOOTING
FOUNDATION WALL
PIPE SLEEVE PER SECTION
PIPE OR CONDUIT
ENCASE PIPE SLEEVE
IN 3000 PSI CONCRETE
FILL PRIOR TO PLACING
CONTINUOUS WALL FTG.1'-6" MIN.8" MIN.1'-0"1'-0"
8" MIN.
1" VOID BETWEEN SLEEVE
AND PIPE SHALL BE FREE OF
SOIL AND CONCRETE AND
FILLED WITH COMPRESSIBLE
MATERIAL
CAST IRON OR STEEL PIPE
SLEEVE WITH INSIDE DIAMETER
2" GREATER THAN PIPE OR
CONDUIT DIAMETER. MINIMUM
1/4" SLEEVE WALL THICKNESS
MIN. (OR EQ. TO VERT. STEP)
1' - 0"MAX. (U.N.O.)2' - 0"COORD. STEP LOCATION
W/ WALL, UTILITIES, GRADE
CONDITIONS, ETC.
EL. SLAB
= SEE PLAN
36"
36"
MATCH CONT.
FTG. REINF.
NOTE:
SEE FND. PLAN AND FTG. SCHED.
FOR FTG. SIZE AND REINF.
T/ SLAB
= SEE PLAN
1
1
2~#3x2'-0"
(2" BELOW T/SLAB)SLAB/WALL JOINT3"2"FIN. FLR.
COMPACTED FILL
LAP
2'-0"SEE PLAN SLAB REINF.
SEE PLAN
#4 HOOK BAR AT 16" O.C.
#4xCONT. NOSING
BAR
#4 BAR AT 12" O.C.
EACH WAY 4"SEE PLAN4"8"4"
SEE PLAN & COORDINATE
WITH EQUIP FURNISHED
(EQUIP SIZE + 1'-0" MIN)
EXISTING CONCRETE SLAB
OR PAVEMENT
PROVIDE ANCHOR BOLTS,
LEVELING CHANNELS, ETC
AS REQUIRED BY EQUIPMENT
FURNISHED
0'-4 1/128"0'-2 1/256"CLREXPANSION JOINT
MATERIAL
#4 AT 12" OC
EACH WAY
TOP AND BOTTOM
0'-2 1/256"CLR0'-8 1/64"WITH EQUIP FURNISHED
(EQUIP SIZE + 1'-0" MIN)0'-2 1/256"CLRPROVIDE ANCHOR BOLTS,
LEVELING CHANNELS, ETC
AS REQUIRED BY EQUIPMENT
FURNISHED
#4 AT 12" OC
EACH WAY
TOP AND BOTTOM
CONCRETE SLAB
#4 + HOOK ON A 18" OC
GRID DRILLED AND ADHESIVE
ANCHORED TO SLAB WITH
4" EMBED
SEE PLAN & COORDINATE
0'-4 1/128"1
1
2'-0" LAP
MINIMUM1'-0"(2)-#5 DOWEL THROUGH
SIMPSON CB7 BASE CONNECTION
WITH STD. ACI HOOK AT BOTTOM END
SLAB EDGE CONTINUE
REINFORCEMENT THROUGH
FOOTING, REFER TO 3/S501
FOR SLAB EDGE DETAIL
SLAB EDGE BEYOND
POST PER PLAN
REFER TO PLAN FOR FOOTING
AND REINFORCEMENT DETAIL
FINISHED
GRADE
#4 DOWELS AT AT 12" O.C.
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
S501
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
TYPICAL CONCRETE
DETAILS AND SECTIONS
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
SCALE: 1 1/2" = 1'-0"1 Anchor Rod Detail
SCALE: 3/4" = 1'-0"10 TYPICAL SLAB EDGE DETAIL
SCALE: 1/2" = 1'-0"6 TYPICAL WALL / FOOTING / SLAB EDGE DETAILS
SCALE: 3/4" = 1'-0"2 C.C.J. DETAIL
SCALE: 3/4" = 1'-0"5 TYPICAL SLAB-ON-GRADE DETAIL
SCALE: 3/4" = 1'-0"4 TYPICAL PORCH SLAB TURNDOWN
SCALE: 3/4" = 1'-0"9 TYPICAL SLEEVED PIPE CROSSING BELOW SLAB EDGE
SCALE: 1/2" = 1'-0"3 TYPICAL STEP FOUNDATION DETAIL
SCALE: 3/4" = 1'-0"8 TYPICAL RE-ENTRANT CORNER BAR DETAIL
SCALE: 3/4" = 1'-0"7 TYPICAL RECESSED SLAB DETAIL
SCALE: 3/4" = 1'-0"
11 TYPICAL EQUIPMENT PAD DETAIL
SCALE: 3/4" = 1'-0"
12 SECTION AT PATIO/PORCH FOOTING
NO. DESCRIPTION DATEANGEL ALICEA
E NCSIEL
S T A T E O F
No. 93531
#5 DOWEL (MATCH CMU WALL SPACING)
STANDARD ACI HOOK AT TOP
T/ SLAB
SEE PLAN
NOTES:
1. 8" MINIMUM CMU STEM WALL SOLID GROUTED PER SECTION R404.1.4.1.
2. ALL EXTERIOR FOOTING WIDTHS SHALL FOLLOW PLAN SLAB EDGE (SE) NOTES.
3. ALL EXTERIOR FOOTINGS AT LOAD BEARINGS AND/OR SHEARWALLS SHALL BE
1'-6" IN WIDTH MINIMUM.
4.REFER TO MASONRY NOTES ON THIS SHEET.
FINISHED GRADE
#4 VERT. BAR AT 32" O.C.
WITH STANDARD ACI
HOOK AT BOTTOM
FULLY GROUT ALL
CELLS
MINIMUM1'-2"SEE PLAN12" MINIMUM DEPTH#4x CONTINUOUS BAR
SLAB SEE PLAN
SEE PLAN FOR FOOTING REINFORCING
DOWELS TO MATCH VERTICAL BARS
SIZE AND SPACING WITH
STANDARD ACI HOOK AT BOTTOM
T/ SLAB
SEE PLAN
NOTES:
1. 8" MINIMUM CMU STEM WALL SOLID GROUTED PER SECTION R404.1.4.1.
2. ALL EXTERIOR FOOTING WIDTHS SHALL FOLLOW PLAN SLAB EDGE (SE) NOTES.
3. ALL EXTERIOR FOOTINGS AT LOAD BEARINGS AND/OR SHEARWALLS SHALL BE
1'-6" IN WIDTH MINIMUM.
4.REFER TO MASONRY NOTES ON THIS SHEET.
VERTICAL REINFORCEMENT
SEE PLAN
SLAB SEE PLAN
SEE PLAN FOR FOOTING REINFORCINGMINIMUM1'-0"PER SECTIONS R404.1.6 AND R317.1MINIMUM CLEARANCEFINISHED GRADE
SEE PLANLAP SPLICEVERTICAL REINFORCEMENT
SEE PLAN WITH ACI STANDARD
HOOK AT BOTTOM
NOTE 1
VERTICAL
REINFORCEMENT
WCENTERED REINF
NOTE1
VERTICAL
REINFORCEMENT
EACH FACE REINF
NOTES:
1. VERTICAL BAR POSITIONERS LOCATE AT TOP OF FIRST COURSE, ONE COURSE
BELOW TOP OF WALL, AND AT 192 BAR DIAMETERS WHEN USING HIGH LIFT
GROUTING.
2: WHERE REINFORCEMENT IN MASONRY WALL SCHEDULE IS DESIGNATED AS
INSIDE FACE OR OUTSIDE FACE, INSIDE FACE SHALL REPRESENT BUILDING
INTERIOR FACE OF WALL AND OUTSIDE FACE SHALL REPRESENT BUILDING
EXTERIOR OR RETAINED SOIL FACE OF WALL. W/2W/2SEALANT
HORIZ JOINT REINF
DISCONTINUED AT
CONTROL JOINT
PREMOLDED RUBBER OR
PVC CONTROL JOINT
RAKE JOINT 3/4" DEEP
#2 Z-BAR
TONGUE & GROOVE
BLOCK UNITS
NOTES:
1. REINFORCEMENT PER PLAN & SCHEDULE
PROVIDE MIN (1) #5 BAR AT END CELL
OF WALL. GROUT CELL SOLID.
2. SUBMIT CONTROL JOINT PLAN
TO ARCH FOR REVIEW.
SEALANT
HORIZ JOINT REINF
DISCONTINUED AT
CONTROL JOINT
4
6
4
OPTION #1
OPTION #2
NOTE 1
NOTE 1
NOTES:
1. FOR WALLS WITH #6 REBAR, PROVIDE 2#6 IN LIEU OF 2#5 UNO.
SEE ARCH DOCS FOR
LOCATIONS & DIMENSIONS
PROVIDE 1#5 VERT MIN
OR AS NOTED ON PLAN EACH
SIDE OF OPENING. BARS TO
EXTEND FULL HEIGHT OF
STORY IN WHICH OPENING
OCCURS. GROUT CELL SOLID
PLAN VIEW
MASONRY OPNG
HORIZ BOND BEAM REINF
(2) #5 CORNER BARS
BOND BEAM
TENSION LAP SPLICE
ACI CLASS A TENSION LAP SPLICEACI CLASS A24
24
TENSION LAP SPLICEACI CLASS "A"HORIZ BOND BEAM REINF
(2) #5 CORNER BARS
BOND BEAM
24
24 LAP MIN48 BAR DIAMETERINTERSECTING MASONRY WALL
JAMB REINFORCING FOR
OPENING IN MASONRY WALL MASONRY CONTROL OR
EXPANSION JOINT
CONCRETE TIE BEAM OR
MASONRY BOND BEAM
VERTICAL REINFORCING
LINTEL
#5 BAR SILL REINFORCING
DOWELS TO MATCH VERTICAL
REINFORCING WITH STD 90 DEG
HOOK
TOP OF FOOTING
FINISH FLOOR
TOP OF WALL
OPENING
OPENING
NOTES:
1. SEE PLAN AND SCHEDULE FOR REINFORCING REQUIREMENTS.
2. SEE ASSOCIATED TYPICAL MASONRY DETAILS.
3. PROVIDE MASONRY JOINT REINF AT 16" OC (NOT SHOWN FOR CLARITY)0'-4"2'-0"
GROUT INSPECTION HOLES
FILL ALL CELLS BELOW FINISH
FLOOR SOLID WITH GROUT
CONC MASONRY
FOUNDATION WALL
CONT CONC WALL FTG
EL T/FTG
GC COORD W/
REQUIRED CONDUIT
SLOPES & MIN
CONDUIT COVER
REQUIREMENTS 2"MAX1' - 0"MOCONDUIT
MAX DIA = 12"2"MIN8"PROVIDE COMP FILLER
AROUND CONDUIT
TOOTH MASONRY
TOGETHER AT EVERY
OTHER COURSE
REINF W/ (2) #5 GROUT
CELL SOLID INTERSECTING
CONC MASONRY WALL
STRAP ANCHOR 1/4"X1-1/2"X2'-6" W/ 3"
RIGHT ANGLE BENDS AT EACH END AT
48" OC VERT MAX EMBED BENDS IN
CORES FILLED W/ GROUT OR CONC
NOTES:
1. TYP AT ENDS & INTERSECTIONS OF WALLS.
2. GROUT ONLY THOSE CELL CONTAINING VERT REINF UNO.
3. PROVIDE 2'-0" MIN LAP FOR ALL
VERT BARS TYP AT ALL FLOORS.
4. FOR MASONRY WALLS NOT SHOWN ON PLAN NO REINF OR
GROUTING IS REQUIRED
EXCEPT AS SHOWN ON TYP DETAILS.
5. USE OPTION #1 AT WALL CORNERS.
CONTROL JOINT RAKE OUT &
CAULK
REINF W/ (2) #5
GROUT CELL SOLID
CONT CONC
MASONRY WALL
STRAP
ANCHOR
TOOTHED MASONRY
NOT REQUIRED
OPTION #1 OPTION #2
INTERSECTING
CONC MASONRY WALL
3"
3"
2 '-6 "
1 1/2"
1/4"
SEE PLAN1'-4" MIN.PLANSEE3" CLRCONC MASONRY
PARTITION WALL.
SEE ARCH DOCS
FOR THICKNESS.
(2) #5 CONT
1
1
EQ EQ
"D"3" CLR"A"
3" CLR
CONC MASONRY
WALL
TRANSVERSE
REINFORCING
LONGITUDINAL
REINFORCING
T/ FTG
DOWEL
NOTE:
SEE PLAN/SCHED
FOR ALL INFO NOT
SHOWN
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
S502
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
TYPICAL MASONRY
DETAILS AND SECTION
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
SCALE: 1 1/2" = 1'-0"1 TYPICAL EXTERIOR WALL FOUNDATION DETAIL Copy 1
SCALE: 3/4" = 1'-0"10 TYPICAL CONCRETE MASONRY WALL REINFORCEMENT DETAIL
SCALE: 3/4" = 1'-0"7 TYPICAL MASONRY VERTICAL CONTROL JOINT DETAIL
SCALE: 3/4" = 1'-0"11
TYPICAL JAMB REINFORCING
FOR OPENING IN LOAD
BEARING MASONRY WALL
DETAIL
SCALE: 3/4" = 1'-0"8 TYPICAL BOND BEAM CORNER DETAIL
SCALE: 3/4" = 1'-0"9 TYPICAL BOND BEAM INTERSECTION DETAIL
SCALE: 1/2" = 1'-0"5 TYPICAL MASONRY WALL REINFORCING ELEVATION
SCALE: 3/4" = 1'-0"4 TYPICAL MEP CONDUIT PENETRATION THRU MASONRY FOUNDATION WALL DETAIL
SCALE: 3/4" = 1'-0"6 TYPICAL INTERSECTING MASONRY WALL DETAILS
SCALE: 3/4" = 1'-0"2
TYPICAL THICKENED SLAB
DETAIL AT CONCRETE
MASONRY PARTITION WALL
SCALE: 3/4" = 1'-0"3 TYPICAL CONTINUOUS MASONRY WALL FOOTING DETAIL
NO. DESCRIPTION DATEANGEL ALICEA
E NCSIEL
S T A T E O F
No. 93531
DOUBLE 2x TRIPLE 2x
16d AT 12" O.C.
EA. EDGE
STAGGERED
2'-0"
1'-0"1'-0"
1/2" DIAMETER BOLT
AT 24" O.C. EA. EDGE
STAGGERED
8" 8"
2-2x
STUDS
3-2x
STUDS
12d AT 16" O.C.
STAGGERED EA.
SIDE AND EA. PLY
12d AT 16" O.C.
STAGGERED EA.
SIDE 8"8"8"8"1'-4"1 1/2"1 1/2"
(3) 16d NAILS
KING STUD TO
HEADER
JACK STUD
KING STUDS
HEADER
OPENING.PROVIDE ADEQUATE CLEARANCE
FOR TRUSS DEFLECTION
INTERIOR PARTITION
SIMPSON STC TRUSS CLIPS
AT 24" O.C. STAGGER CLIPS
PREFABRICATED TRUSS /JOIST
2x4 BLOCKING
AT 24" O.C.
PLYWOOD SHEATHING
WALL PARALLEL TO TRUSS / JOIST
WALL PERPENDICULAR TO TRUSS / JOIST.PROVIDE ADEQUATE CLEARANCE
FOR TRUSS DEFLECTION
INTERIOR PARTITION
SIMPSON STC TRUSS CLIPS
AT 24" O.C. STAGGER CLIPS
PLYWOOD SHEATHINGPREFABRICATED TRUSS/JOIST
TYPICAL INTERIOR WOOD STUD
PARTITION AT WOOD TRUSS/JOIST DETAIL
ATTACH PLYWOOD
SHEATHING TO BLOCKING
AT 4" O.C. W/ 8d NAILS; 3" O.C.
OVER SHEAR WALL
NOTE 1
NOTE 2
NOTES:
1.BLOCKING SHALL BE PROVIDED AT EVERY OTHER ROOF
TRUSS BAY. BLOCKING MAY BE ATTACHED TO TOP PLATE
W/ SIMPSON LS50 (8)-0.148 x 3 (2 MINIMUM PER BLOCKING PLACING.
PROVIDE CONTINUOUS BLOCKING AT SHEAR WALL ATTACHED
PER SHEAR WALL ELEVATION.
2.PROVIDE A SIMPSON TYPE A44 AT EACH ROOF
FRAMING MEMBER.
3.TRUSS / RAFTER CONNECTIONS NOT SHOWN FOR CLARITY.
4.PROVIDE TRUSS BLOCKING WHERE HEEL HEIGHT EXCEEDS
2x LUMBER DEPTH.
H8
(H2.5A,
H5 SIMILAR)(2) H2.5A TSP
MTS12
(LTS,
HTS SIMILAR)H10A
(H1,
H14 SIMILAR)
NOTE:
REFER TO SCHEDULE FOR HURRICANE CLIPS
ON SHEET S003.
FRONT VIEW
2X6 BOTTOM VIEW
2"
SPLICE (UPPER OR LOWER TOP
PLATE), STAGGER TOP / BOTTOM
PLATE SPLICES 4'-0" MIN.
8" MAX.
FLAT-WISE FULL LENGTH 2x
BLOCK EACH SIDE OF SPLICE
SAME MATERIAL AS TOP PLATES
1/4" DIA x 4 1/2"
SDS SCREWS
1'-4" STUD SPACING 1'-4" STUD SPACING
1/4" DIA x 4 1/2" STRONG DRIVE
SDS SCREW (16 TOTAL)2 1/2" TYP.1 1/2" TYP.
2"
CONTINUOUS WEB BRACING AS REQUIED BY TRUSS
MANUFACTURER. REFER TO TRUSS SHOP DRAWINGS. LAP
BRACING SPLICES ONE TRUS BAY (MIN.)
TEMPORARILY BRACE TOP CHORD AS
REQUIRED PRIOR TO SHEATHING
PLYWOOD OR O.S.B. ROOF SHEATHING
DIAGONAL BRACING OF
TRUSS COMPRESSION
WEBS - SEE SECTION BELOW
CONTINUOUS LATERAL BOTTOM CHORD BRACING AT
10'-0" O.C. SEE BELOW. SEE TRUSS SHOP DRAWINGS
FOR LOCATIONS
CONTRACTOR NOTES:
1. NAIL BRACES TO EACH TRUSS WITH (2) 16d NAILS (MIN.)
2. REFER TO "BCSI 2006 BUILDING COMPONENT INFORMATION
GUIDE TO GOOD PRACTICE FOR HANDLING, INSTALLING,
RESTRAINING, & BRACING OF METAL PLATE CONNECTED
WOOD TRUSSES" ERECTION BRACING REQUIREMENTS.
TRUSS ELEVATION
THE FOLLOWING DIAGRAMS ILLUSTRATE SOME OF
THE REQUIRED BRACING FOR ROOF TRUSSES. THE
DIAGRAMS ARE NOT REPRESENTATIVE OF THE
PARTICULAR DETAILS OF THIS PROJECT. SUCH AS
ROOF SLOPE, WEB LOCATIONS, OVERHANGS, ETC.
REFER TO ROOF FRAMING DRAWINGS AND THE TRUSS
MANUFACTURER'S SHOP DRAWINGS FOR SPECIFIC
LOCATIONS OF OTHER REQUIRED BRACING.
SECTION THROUGH TRUSSES
2X4 DIAGONAL BRACING LOCATED AT TRUSS
COMPRESSION WEBS. INSTALL AT GABLE ENDS
GABLE END TRUSS
CONTINUOUS 2X4 LATERAL BRACING OF BOTTOM
CHORD - SEE BELOW
WEB BRACING AS REQUIRED BY TRUSS
MANUFACTURER-SEE TRUSS SHOP DRAWINGS
ROOF SHEATHING
TRUSS WEBS
GABLE END TRUSS
TRUSSES
10 FT. MAXIMUM10 FT. MAXIMUM20 FT. MAXIMUM
BEARING WALL / BEAM
BEARING WALL / BEAM
2X4 DIAGONAL BRACING NAILED TO
BOTTOM CHORDS
CONTINUOUS 2X4 LATERAL BRACING ON TOP OF
BOTTOM CHORDS SPACED AT 10 FEET O.C.
(MAXIMUM). LOCATED BRACES NEXT TO WEB / BOTTOM
CHORD JOINT
CONTRACTOR NOTES:
1. CONTRACTOR SHALL BE FAMILIAR WITH AND
STRICTLY ADHERE TO PUBLICATION "BCSI 2006"
WHICH IS TYPICALLY DELIVERED WITH TRUSS
PACKAGE.
2. PLEASE NOTE THAT COMPRESSION WEB BRACING
REQUIREMENTS ARE SHOWN ONLY ON THE TRUSS
"SHOP" DRAWINGS WHICH ARE ALSO DELIVERED
WITH TRUSSES.
BOTTOM CHORD BRACING PLAN
GIRDER RAFTER
WOOD DOUBLE TOP PLATE
SHEATHING SEE
GENERAL NOTES
SHEATHING SEE
GENERAL NOTES
3" MAX
PLYWOOD SHEATHINGBLOCKING SEE
TYPICAL DETAIL
WOOD HEADER
SEE SCHEDULE
HURRICANE TIE
SEE SCHEDULE
WOOD STUD
SEE SCHEDULE
(8) 10d
TOE NAILS(1) 2x BELOW
HEADER TYPICAL
SIMPSON A 35 AT
OPENINGS
GREATER THAN 6'-0"
(4) 10d TOE
NAILS TO JAMB
WOOD SILL
SEE SCHEDULE
FULL HEIGHT STUD
SEE SCHEDULE
WOOD BEARING STUD
SEE SCHEDULE
PT SILL PLATE1/2" DIA. GALV. ADHESIVE
ANCHOR W/ 8" EMBED
ALIGNED W/ THREADED ROD
NUT AND 1/2" x 3"
GALV. SQUARE
PLATE WASHER
50 LB FELT BARRIER
TYPICAL AT SHEAR
WALL HOLDOWN
TIMPSON HDU4-SDS2.5 W/
5/8" DIA. THREADED ROD
SET IN ADHESIVE W/ MIN.
8" EMBEDMENT
COUPLER
(1) ROW MID
HEIGHT BRIDGING
1/2" DIA. THREADED ROD
ADJACENT TO EACH
SIDE OF OPENING
1/2" DIA. THREADED
ROD AT 48" O.C. MAX.
BUILT-UP STUD TO
MATCH NUMBER
OF TRUSS PLYS
GIRDER TIE DOWN
SEE SCHEDULE
SIMPSON SP1 AT 32" O.C.
INSTALLED ON SAME
SIDE AT HURRICANE TIES
NUT AND 1/4" x 3"
SQUARE PLATE WASHER
SIMPSON SP2 EACH END OF
CRIPPLE STUD, TYPICAL
NOTES:
1.SEE SHEAR WALL ELEVATION FOR ADDITIONAL REQUIREMENTS AT SHEAR WALLS.
2.SEE RAFTER UPLIFT REQUIREMENTS TO TOP PLATE DETAIL THIS SHEET FOR
HURRICANE TIE REQUIREMENTS.
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
S601
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
TYPICAL WOOD FRAMING
DETAILS
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
SCALE: 3/4" = 1'-0"3 TYPICAL BUILT-UP BEAMS DETAIL
SCALE: 3/4" = 1'-0"4 TYPICAL BUILT-UP COLUMNS/STUDS DETAIL
SCALE: 3/4" = 1'-0"
6
TYPICAL HEADER TO KING
STUD CONNECTION DETAIL
SCALE: 3/4" = 1'-0"5 TYPICAL NON-LOAD BEARING WALL DETAILS
SCALE: 3/4" = 1'-0"8 TYPICAL RAFTER BLOCKING
SCALE: 3/4" = 1'-0"
7 TYPICAL ROOF FRAMING AT BEARING DETAIL
SCALE: 3/4" = 1'-0"9 TYPICAL TOP PLATE DETAIL
SCALE: 1/2" = 1'-0"1 TYPICAL TRUSS BRACING DIAGRAMS
SCALE: 3/4" = 1'-0"2 TYPICAL WOOD FRAMING ELEVATION
NO. DESCRIPTION DATEANGEL ALICEA
E NCSIEL
S T A T E O F
No. 93531
PROVIDE BLOCKING SYSTEM
PARALLEL TO TOP PLATE
CAPABLE OF TRANSFERRING
UNIT SHEAR NOTED IN TRUSS
BLOCKING CRITERIA TABLE
ATTACH BLOCKING TO TOP
PLATE W/(1) SIMPSON LS50 WITH (8)
0.148" x 3" FASTENERS EACH END
BETWEEN EACH TRUSS
(2) 2x TOP PLATE
PRE-ENGINEERED
ROOF TRUSS
ROOF SHEATHING
ATTACH BLOCKING TO
ROOF SHEATHING AT
4" O.C. W/ 8d NAILS;
3" O.C. OVER SHEAR WALL
SEE ARCHHEEL HEIGHTSHEAR WALLS;
SEE SHEAR WALL
SCHEDULE FOR ADDITIONAL
INFORMATION
16d AT 8" O.C.
STAGGERED
PANEL EDGE NAILING
PER SHEAR WALL SCHEDULE
16d AT 8" O.C.
ADDITIONAL STUDS AT HOLD
DOWN PER SHEAR
WALL SCHEDULE
PANEL EDGE NAILING
PER SHEAR WALL
SCHEDULE
SHEAR WALLS;
SEE SHEAR WALL
SCHEDULE FOR ADDITONAL
INFORMATION
(4)STUDS AT WALL END
REFER TO BUILT-UP STUD
TYPICAL DETAIL
EXTERIOR
WALL
SEE WALL SCHEDULE
FOR WALL SHEATHING
AND FASTENING
NOTE:
CONTRACTOR TO COORDINATE
W/ HOLD-DOWN MANUFACTURER NUMBER OF
STUDS REQUIRED FOR END CONNECTION.
WOOD TRUSS / RAFTERWOOD SHEATHING
HOLDOWNS
SEE ELEVATIONS
BLOCKING AT ALL PANEL
EDGES W/ BROAD FACE
AGAINST THE SHEATHING
EDGE NAILING
PER SCHEDULE
WOOD SHEATHING
SEE SCHEDULE
WOOD SHEAR WALL ELEVATION NOTES:
1.FOUNDATION ANCHORS BOLTS SHALL HAVE 1/4"x3"x3" PLATE WASHERS, TYP.
2.PLYWOOD SHEATHING SHALL BE INSTALLED IN 4FT x 8FT SHEETS W/ THE LONG
DIRECTION PARALLEL OR PERPENDICULAR TO THE STUDS AND ENDS
STAGGERED 1/2 PANEL LENGTH SO THAT PANEL ENDS DO NOT ALIGN.
3.SEE GENERAL NOTES FOR SHEATHING REQUIREMENTS.
(2) SIMPSON LS50 WITH (8)
0.148" x 3" FASTENERS BETWEEN
EACH TRUSS AT SHEAR WALL
BLOCKING PER TYPICAL DETAIL
BETWEEN EACH RAFTER
SEE ELEVATION FOR EXTENTS
EDGE OF
SHEARWALL
OR DECKING
GYPSUM BOARD OR
PLYWOOD PANEL
NAIL SPACING @
SUPPORTED EDGES,
SEE NOTES OR
SCHEDULE
PANEL EDGE
BLOCKING
PROVIDED
STUDS, OR
ROOF TRUSSES,
NAILING TO
INTERMEDIATE
SUPPORT IS
SEE S001
NOTES:
1) ROOF SHEATHING SHALL BE STAGGERED AS SHOWN
WITH LONG DIRECTION OF PLYWOOD TRANSVERSE TO
TRUSSES OR JOISTS.
2) UNSUPPORTED (UNBLOCKED) PANEL EDGE. PROVIDE
BLOCKING IF REQ'D BY NOTES OR SCHEDULE.
SPLICE
SPLICE BOT.
PLATE OVER
STUD
TYP STUDS
2-16d AT 4" OC
(24-16d MIN EA SIDE
OF EA SPLICE)
4'-0" MINIMUM LAP
(2) P.T. 2x WALL PL.
ROOF RAFTERS
& CEILING JOISTS AS
SPECIFIED
SIMPSON HURRICANE
UPLIFT CONNECTIONS REFER TO
SCHEDULE ON S003
ATTACH W/ 10d NAILS AS
SPECIFIED BY STRAP MANUF.
SIMPSON SPH4
AT 16" O.C. TO HEADER
HEADER PER SCHEDULE1/2" DIA. A36 STEEL
THREADED ROD PER PLAN
SEE PLAN FOR HOLDOWNS
EACH STUD
RULL-LENGTH STUDS. ATTACH TO
ADJACENT STUD WITH 10d NAILS
STAGGER SPACED 4" O.C. EACH PLY
HEADER STUDS. TWO MIN. FASTENED
WITH 10d NAILS STAGGERED SPACED 6"
ON CENTER.
ATTACH SIMPSON STHD14
W/ MIN. 6" EMBEDMENT INTO
CONCRETE
2x P.T. BASE PLATE
SPLICE
TYP STUDS
NEW 2x6 BOTTOM PLATE & ATTACH W/ 1/4"x4 1/2"
TITEN SCREWS OR PDPXX 0.145" SHANK x 3" LENGTH
SHOT PINS W/ 3" CONCRETE EDGE DISTANCE SPACED
AT 30" O.C. UP TO 10' HEIGHT BEARING WALLS AND 48"
O.C. FOR NON-BEARING WALLS UP TO 14' HEIGHT.
SPLICE
PROVIDE 12" LONG STRAPS
@ EA. SPLICE (E.O.R TO APPROVE
STRAPS), TYPICAL
5
12SEE PLAN FOR
SHEATHING
5 5/8" x 19" CONCRETE TIE BEAM
WITH (3) #5 x CONTINUOUS BARS
TOP AND BOTTOM (CENTERED)
PRE-ENGINEERED TRUSS
AT 24" O.C. SEE PLAN
UPLIFT CONNECT, SEE
SCHEDULE ON S003
2X6 P.T. SP NO.2 DOUBLE TOP
PLATE. FASTEN TO CONCRETE TIE BEAM
WITH 1/2" Ø F1554 ANCHOR BOLT AT 24" O.C.
PROVIDE 12" EMBED WITH DOUBLE NUT AND
PLATE WASHER
CMU WALL, SEE PLAN
SEE PLAN
2x HEEL BLOCING
TRUSS BEARING
EL. SEE PLAN
ATTACH BLOCKING TOP TOP PLATE
W/ (1) SIMPSON LS50 CLIP EACH END
(REFER TO DETAIL 8/S601)
SIMPSON A34 AT TRUSS
5 5/8" x 19" CONCRETE TIE BEAM
WITH (3) #5 x CONTINUOUS BARS
TOP AND BOTTOM (CENTERED)
UPLIFT CONNECT, SEE
SCHEDULE ON S003
2X6 P.T. SP NO.2 DOUBLE TOP
PLATE. FASTEN TO CONCRETE TIE BEAM
WITH 1/2" Ø F1554 ANCHOR BOLT AT 24" O.C.
PROVIDE 12" EMBED WITH DOUBLE NUT AND
PLATE WASHER
CMU WALL, SEE PLAN
TRUSS BEARING
EL. SEE PLAN
ATTACH BLOCKING TOP TOP PLATE
W/ (1) SIMPSON LS50 WITH (8)
0.148" x 3" FASTENERS EACH END
THEN 2'-0" O.C.
SEE PLAN
SEE PLAN FOR
SHEATHING
PRE-ENGINEERED TRUSS
AT 24" O.C. SEE PLAN
15/32" WOOD SHEATHING WITH
10d NAILS SPACED AT 4" O.C. AT EDGE
AND 4" O.C. FIELD SPACING
NOTE:
1.REFER TO 10/S602 FOR OUTRIGGER, X-BRACE
AND BLOCKING INFORMATION NOT SHOWN ON
THIS DETAIL FOR CLARITY.
2.IF TRUSSES ARE SPANNING IN OPPOSITE
DIRECTION, REFER TO SECTION 9/S6002.
4-16d
4-16d NAILS
4-16d NAILS
HURRICANE CLIP @
EACH OUTRIGGER
TOP CHORD OR GABLE
END TRUSS/RAFTER DROP 3 1/2"
4-16d NAILS SIMPSON CS20
STRAP W/14-10d @ EA. X-BRACE
BOTTOM CHORD OF GABLE
END TRUSS/RAFTER
12d TOE NAILS @ 8" O.C. FROM TRUSS/RAFTER
BOTTOM CHORD TO DOUBLE TOP PLATE
DOUBLE TOP PLATE
BLOCKING
2x OUTRIGGERS PER PLAN. ALIGN
ONE OUTRIGGER W/ EACH
X-BRACE OR PROVIDE 2x4
BLOCKING
4-12d TOE NAILS (2-EA.
SIDE)
2X4 X-BRACE (2
EA. SIDE)
2X4 BLOCK @ X-BRACE
ROOF SHEATHING
SEE PLAN
4-12d (2 ES) TOE NAILS EA. END,
FROM BLOCK TO TRUSS/RAFTER
TOP CHORD
3-12d NAILS TYPICAL @
VERTICALS
2x4 SC AB @ 48" O.C. IF VERT.
WEB IS NOT PRESENT @
X-BRACE
CONT. 2x4x8' SYP LATERAL BRACE @ 48"
O.C. W/ 3-16d INTO EACH TRUSS/RAFTER
BOTTOM CHORD
2x4 BLOCKING @ 48" O.C. BETWEEN GABLE
AND FIRST TRUSS/RAFTER
12d @ 4" O.C. FROM LATERAL BRACE
TO BLOCK BELOW
NOTE:
SLOPE ROOF AS REQUIRED PER PLAN
2
A
B
D
E
21
PROJECT INFORMATION
SHEET ID
SHEET TITLE
REVISIONS
DATE ISSUED:
REVIEWED BY:
A/EOR:
DESIGNED BY:
PROJECT NUMBER:
1 3
3
4
4
6
65
5
C
SEAL
Professional certification. I hereby certify that these documents
were prepared or approved by me, and that I am a duly licensed
professional architect/engineer under the laws of the state of ____
CONSULTANT
AA & Associates of Florida, LLC.
All rights reserved. No part of this work may be used ,
reproduced, distributed, displayed, or otherwise
communicated in any form or by any means without the
prior written consent of AA & Associates of Florida,
LLC.
3956 HEIDI ROAD WEST
JACKSONVILLE, FLORIDA 32277
THIS DOCUMENT HAS BEEN ELECTRONICALLY SIGNED AND
SEALED BY ANGEL L. ALICEA, PE ON ________________ USING A
DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE
NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURES
MUST BE VERIFIED ON ANY ELECTRONIC COPLIES.
CONSTRUCTION DRAWINGS
S602
NEW CONSTRUCTION -
LUNDGREN RESIDENCE
WOOD FRAMING,
BEARING AND
SHEARWALL SECTIONS
AND DETAILS
EOR
ALA
12/31/2024
ALA
324-035
893 AMBERJACK LANE
ATLANTIC BEACH, FL 32233
FL.
12/31/2024
FL
SCALE: 3/4" = 1'-0"3 TYPICAL EXTENDED BLOCKING DETAIL
SCALE: 3/4" = 1'-0"4 TYPICAL SHEAR WALL INTERSECTION AT CORNERS DETAIL
SCALE: 3/4" = 1'-0"1 TYPICAL WOOD SHEAR WALL ELEVATION
SCALE: 1/2" = 1'-0"2 NAILING REQUIREMENTS FOR FLOOR, ROOF AND SHEARWALL
SCALE: 3/4" = 1'-0"6 TYPICAL TOP PLATE SPLICE DETAIL
SCALE: 12" = 1'-0"8 ROOF TRUSS/RAFTERS AND CEIL. JOIST BEARING
SCALE: 3/4" = 1'-0"5 TYPICAL HEADER DETAIL
SCALE: 3/4" = 1'-0"7 TYPICAL BOTTOM PLATE SPLICE REPAIR DETAIL
SCALE: 1" = 1'-0"9 SECTION AT CMU WALL
SCALE: 1" = 1'-0"11 SECTION AT CMU WALL > THAN 10'-3"
SCALE: 3/4" = 1'-0"10 SECTION AT OUTRIGGER WITH WALL > THAN 10'-3"
NO. DESCRIPTION DATEANGEL ALICEA
E NCSIEL
S T A T E O F
No. 93531