645 Atlantic Blvd COMM24-0049 Plumbing Plans signedPROJECT DEMOLITION NOTES1. REMOVE EXISTING PLUMBING FIXTURES, EQUIPMENT, AND EQUIPMENT PADS TOTHE EXTENT INDICATED ON THE PLUMBING AND ARCHITECTURAL DEMOLITIONDRAWINGS.2. REMOVE EXISTING WATER PIPING TO THE EXTENT INDICATED ON THE DRAWINGS.POINTS OF DISCONNECTION/RECONNECTION ON DRAWINGS ARE BASED BESTAVAILABLE INFORMATION AND SHALL BE FIELD LOCATED AND ADJUSTEDACCORDINGLY. UNLESS OTHERWISE INDICATED, INACCESSIBLE EXISTINGUNDER-SLAB PIPING NOT INTERFERING WITH NEW CONSTRUCTION MAY BEABANDONED IN PLACE AFTER COMPLETELY DISCONNECTING FROM NEW SYSTEM,DRAINING, CUTTING AND CAPPING BELOW GRADE.3. REMOVE EXISTING SANITARY, WASTE, & VENT PIPING SYSTEMS TO THE EXTENTINDICATED ON THE DRAWINGS. POINTS OF DISCONNECTION/RECONNECTION ONPLANS ARE BASED BEST AVAILABLE INFORMATION AND SHALL BE FIELD LOCATEDAND ADJUSTED ACCORDINGLY. INACCESSIBLE EXISTING UNDER-SLAB PIPING NOTINTERFERING WITH NEW CONSTRUCTION MAY BE ABANDONED IN PLACE AFTERCOMPLETELY DISCONNECTING FROM NEW SYSTEM, DRAINING, CUTTING ANDCAPPING BELOW GRADE. EXISTING VTR'S OF REQUIRED SIZE AND ACCEPTABLECONDITION MAY BE RE-USED.4. EXISTING PIPING TO BE RE-USED IS SHOWN FADED.5. RECOVER ALL REFRIGERANT IN ACCORDANCE WITH ALL FEDERAL, STATE ANDLOCAL REQUIREMENTS.6. PROPERLY DISPOSE OF ALL REMOVED MATERIAL OFFSITE.7. ALL EQUIPMENT BEING REUSED SHALL BE INSPECTED FOR PROPER OPERATIONAND REASONABLE CONDITION AND SHALL BE PRESSURE TESTED WITH THE NEWSYSTEM. ALL PIPING BEING REUSED SHALL BE VISUALLY INSPECTED FORREASONABLE CONDITION, SLOPE AND INVERT, AS APPLICABLE; AND SHALL BEFLUSHED AND PRESSURE TESTED.8. EXISTING PLUMBING SYSTEM, WHERE INDICATED, ARE BASED ON BEST AVAILABLEINFORMATION. CONTRACTOR SHALL VISIT SITE PRIOR TO BIDDING AND FIELDCONFIRM EXTENT OF DEMOLITION, EXISTING INVERTS, ETC. CONTRACTOR SHALLCONFIRM ALL EXISTING CONDITIONS AS DEMOLITION OCCURS. REFER TO ORIGINALCONSTRUCTION DRAWINGS WHERE AVAILABLE FOR ADDITIONAL INFORMATION OFEXISTING CONDITIONS.1. SANITARY, WASTE AND VENT PIPE AND FITTINGS SHALL BE SOLID CORE DWV SCH 40 PVC, WITH A SOLID CELLULAR CORE, OR COMPOSITEWALL MATERIAL AS SPECIFIED, UNLESS STATED OTHERWISE BY LOCAL CODES AND REGULATIONS; ASTM D2665; ASTM F891; ASTM F1488; CSAB181.2. PROVIDE APPROVED FIRE RATED JACKET WHERE PIPE PASSES THROUGH RETURN AIR PLENUM.2. OFFSET VENT THRU ROOF'S (VTR'S) AS REQUIRED TO PENETRATE ROOF AT LOCATION AT LEAST 10' FROM AIR CONDITIONING UNIT INTAKESAND TERMINATE A MINIMUM OF 12" (INCHES) AWAY FROM ANY VERTICAL SURFACE. COORDINATE EXACT LOCATION OF AIR CONDITIONINGUNITS WITH MECHANICAL CONTRACTOR AND ADJUST AS NECESSARY. EXISTING VTR'S MAY BE RE-USED WHERE SUITABLE.3. REFER TO RISERS FOR PIPE SIZES NOT SHOWN ON PLAN. REFER TO SCHEDULE FOR SANITARY DRAIN, DOMESTIC WATER AND INDIVIDUALVENT CONNECTION SIZES.4. REFER TO ARCHITECTURAL PLANS TO CONFIRM LOCATION OF FIRE RATED WALLS, SMOKE BARRIERS, AND SMOKE PARTITIONS. ALLPENETRATIONS OF RATED WALLS SHALL BE MADE WITH FIRE STOPPING MATERIALS IN ACCORDANCE WITH THE 2023 FLORIDA BUILDING CODEREQUIREMENTS. PENETRATIONS OF ALL FIRE RATED ASSEMBLIES SHALL BE MADE IN ACCORDANCE WITH THE FIRE RATED ASSEMBLY'S ULLISTING, AS APPROVED BY THE AUTHORITY HAVING JURISDICTION.5. SLEEVE ALL FLOOR/WALL PENETRATIONS THAT ARE NOT CORE BORED.6. POTABLE WATER PIPING AND FITTINGS SHALL BE CPVC WITH COMPATIBLE CPVC FITTINGS AND SOLVENT CEMENT, MATERIAL AS SPECIFIED.OR POTABLE WATER PIPING AND FITTINGS SHALL BE TYPE K COPPER BELOW GRADE AND TYPE L COPPER ABOVE GRADE AS SPECIFIED.PROVIDE APPROVED FIRE RATED JACKET WHERE PIPE PASSES THROUGH RETURN AIR PLENUM.7. INSULATE ALL HOT WATER PIPING, AND COLD WATER PIPING IN EXPOSED LOCATIONS, AS SPECIFIED.8. REFER TO WATER HEATER DETAIL FOR EMERGENCY DISCHARGE, DRAIN PAN, AND OTHER PIPING REQUIREMENTS.9. ISOLATION AND SHUTOFF VALVES AND STOP VALVES SHALL BE GATE VALVES, BALL VALVES OR ANGLE STOPS, RATED FOR 150 PSI AT 180°F.REFER TO SPECIFICATIONS.10. PROVIDE WATER HAMMER ARRESTORS FOR ALL FIXTURES IN ACCORDANCE WITH PDI 201 GUIDELINES.11. PROVIDE TRAP PRIMERS FOR ALL FLOOR DRAINS AND/OR FLOOR SINKS. PROVIDE ADA COVERING OVER TRAP PRIMERS INSTALLED UNDERADA LAVATORIES AND SINKS.12. ALL WATER PIPE SHALL BE RUN CONCEALED IN CHASE, WALL, OR ABOVE CEILING EXCEPT IN MECHANICAL ROOMS OR AS OTHERWISENOTED.13. PRIOR TO ORDERING FIXTURES, CONFIRM DIMENSIONAL FIT-UP REQUIREMENTS FOR DWV PIPING LAYOUTS, FRAMING/MILLWORK, FAUCETTRIM HOLES, ETC. AND COORDINATE ANY REQUIRED ADJUSTMENTS FOR PROPER FIT FORM AND FUNCTION OF EACH FIXTURE.14. PROVIDE ALL REQUIRED FITTINGS FOR COMPLETE INSTALLATION OF EACH FIXTURE INCLUDING, BUT NOT LIMITED TO, 3/8" FLEXIBLESUPPLIES, ESCUTCHEON PLATES, STOP VALVES, DRAINS, TRAPS, MOUNTING HARDWARE, ETC. ALL EXPOSED HARDWARE SHALL BE POLISHEDBRASS OR CHROME FINISH.15. INSTALL ALL FIXTURES IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, PLUMB AND LEVEL, PROPERLY SECURED ANDSEALED TO WALL OR FLOOR.16. ALL PLUMBING FIXTURES AND MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2023 FLORIDA PLUMBING CODE AND ENERGYCONSERVATION CODE, LATEST EDITION ADOPTED BY AUTHORITY HAVING JURISDICTION.17. ALL PLUMBING FIXTURES AND MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH 2023 FLORIDA ACCESSIBILITY CODE. ENSURESANITARY ROUGH-INS ARE LOCATED TO MAINTAIN ADA CLEARANCES AFTER FIXTURES ARE INSTALLED. REFER TO ARCHITECTURAL DRAWINGSFOR EXACT DIMENSIONS.18. REVIEW PLANS TO CONFIRM ADEQUATE CHASE AND/OR WALL CAVITY CLEARANCE EXISTS PRIOR TO INITIATION OF WORK.19. ALL PIPING, MATERIALS AND EQUIPMENT ARE NEW UNLESS OTHERWISE NOTED.20. REVIEW BUY AMERICA(N) REQUIREMENTS WITH GENERAL CONTRACTOR. IF RELEVANT TO THIS CONTRACT, CONFIRM ALL EQUIPMENTPROVIDED MEETS THESE REQUIREMENTS, REGARDLESS OF MAKE/MODEL INDICATED ON BASIS OF DESIGN EQUIPMENT SCHEDULES.21. ALL WORK AND MATERIAL SHALL BE PERFORMED AND INSTALLED IN COMPLIANCE WITH THE 2023 FLORIDA BUILDING CODE AND ALLCURRENT AMENDMENTS. NOTHING IN THESE DRAWINGS IS TO BE CONSTRUED TO PERMIT WORK NOT CONFORMING TO THESE CODES.22. ALL PLUMBING WORK SHALL BE INSTALLED TO AVOID INTERFERENCES WITH ELECTRICAL, MECHANICAL AND STRUCTURAL FRAMING.23. EXACT LOCATIONS AND MOUNTING HEIGHTS OF PLUMBING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL DRAWINGS.24. BEFORE COMMENCEMENT OF WORK, CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS, ELEVATIONS, AND CHARACTERISTICS OF ALLUTILITIES AND PIPING. IMMEDIATELY NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES.25. ALL WASTE AND VENT PIPING SHALL SLOPE AT 1/8" PER FOOT OR 1/4" PER FOOT UNLESS INDICATED OTHERWISE.26. REMOVE ALL FACTORY MARKINGS ON EXPOSED PVC PIPING. USE ACETONE, XYLENE, MEK OR ANOTHER APPROPRIATE SOLVENT.27. ALL FLOOR DRAINS; CLEANOUTS; FLOOR SINKS AND TROUGHS SHALL BE INSTALLED FLUSH TO FINISHED FLOOR, NO DISHING PERMITTED.28. ALL VENT PIPING SHALL BE FULL LINE SIZE IF A WALL CLEAN-OUT IS SHOWN OR AS INDICATED.29. FLOOR DRAIN LINE SIZE AND VENTING IN ACCORDANCE WITH THE 2023 FLORIDA PLUMBING CODE INCLUDING LATEST REVISIONS,COMBINATION WASTE AND VENT SYSTEM.30. ALL VENT PIPING SHALL BE LOCATED WITHIN MASONRY WALLS AND OTHER WALL CONSTRUCTION THAT MAY BE USED TO ENCLOSE THEVENT PIPING. PIPING SHOWN ON DRAWINGS MAY NOT REFLECT THIS INSTALLATION METHOD BECAUSE OF THE DEGREE OF DETAILINCONSISTENT WITH 1/8" PLANS. IF PIPING CANNOT BE INSTALLED WITHIN THESE STRUCTURES, APPROVAL OF THE ENGINEER OF ANOTHERINSTALLATION METHOD IS REQUIRED. ALL EXPOSED VENT PIPING SHALL BE ATTACHED TO WALL NO FURTHER THAN 3" AWAY.31. PLUMBING FIXTURE DESCRIPTION SHALL TAKE PRECEDENCE WHEN EXISTS A CONFLICT WITH THE DESCRIPTION AND MODEL NUMBER.32. PLUMBING CONTRACTOR SHALL PROVIDE A PRESSURE REDUCING VALVE (PRV) WHERE WATER MAIN ENTERS BUILDING IF PRESSUREEXCEEDS 80 PSI. SET PRESSURE REDUCING VALVE TO 75 PSI.33. WHILE EVERY ATTEMPT HAS BEEN MADE IN THE PREPARATION TO THESE PLANS TO AVOID MISTAKES, THE DESIGNER AND COMPANYCANNOT GUARANTEE AGAINST ERROR OR UNFORESEEN FIELD CONDITIONS. THE CONTRACTOR OR BUILDER MUST CHECK ALL DIMENSIONSAND DETAILS AND REPORT ANY DISCREPANCIES.34. CONTRACTOR MUST CHECK EQUIPMENT NOT IN CONTRACT SO THAT THE SERVICE REQUIREMENTS ARE CORRECTLY TYPED, ADEQUATELYSIZED, AND ROUGHED-IN PROPERLY SO AS TO MINIMIZE THE AMOUNT OF MATERIALS AND FITTINGS NEEDED FOR FINAL HOOK-UP, RESULTINGIN A NEAT AND ORDERLY LOOKING INSTALLATION.35. COORDINATE WITH GENERAL CONTRACTOR AND ALL OTHER DISCIPLINES FOR CONNECTION REQUIREMENTS AND RUN LOCATIONS TOPREVENT CONFLICTS.36. LANDLORD TO APPROVE ALL ROOF PENETRATIONS. ALL ROOF WORK MUST BE BY LANDLORD'S APPROVED ROOFER.PLUMBING LEGENDPROJECT GENERAL NOTESABBREVIATIONSPIPINGNOTE:NO PLUMBING, GAS, MECHANICAL OR ELECTRICAL CONNECTIONS OR INSTALLATIONSSHALL BE MADE UNTIL THE GENERAL CONTRACTOR, SUB-CONTRACTOR ANDOWNER/TENANT HAVE FIELD VERIFIED ALL EQUIPMENT REQUIREMENTS WITHEQUIPMENT SUPPLIER.ABBREVIATIONSPOINT OF CONNECTION TOEXISTINGPOINT OF DISCONNECTIONFROM EXISTINGELBOW (PLAN, UP, DOWN)SHUT-OFF VALVES (GATE/BALL VALVES)BRANCH CONNECTIONS (TOP, BOTTOM, SIDE)TEE (PLAN, UP, DOWN)TRAP, PLAN VIEWHOT WATERSANITARYVENTCOLD WATERSTRAINERGASGASNATURAL GAS/PROPANEEXISTING SANITARY (FADED)EXISTING COLD WATER (FADED)EXISTING HOT WATER (FADED)EXISTING HOT WATER RETURN (FADED)CAP FOR FUTURE CONNECTIONGAS BALL OR PLUG VALVEDIRECTION OF FLOWCIRCUIT BALANCING VALVE WITH MEMORY STOPPRESSURE REDUCING VALVEUNIONCLEANOUT IN FLOORCLEANOUT ON END OF PIPEHOSE BIBBFLOOR DRAIN, FLOOR SINKGLOBE VALVEEXISTING VENT (FADED)AACOMPRESSED AIRTEMPERED WATER MIXING VALVEDEMOLITIONREDUCED PRESSURE BACKFLOW PREVENTERHOT WATER RECIRCULATION PUMPCHECK VALVEWATER METERMCONTINUATIONASME PRESSURE/TEMP RELIEF VALVEHOT WATER RETURNGREASE WASTEFILTERED COLD WATERWATER HEATER RELIEFBUTTERFLY VALVENOTE:CONTRACTORS SHALL VISIT THE JOB SITE TOFAMILIARIZE WITH BUILDING CONDITIONS PRIORTO SUBMITTING BID.DOMESTIC TEMPERED HOT WATERNOTE:ALL PIPING LAYOUTS, DUCT LAYOUTS, AND WIRING LAYOUTS ARE SCHEMATIC. EXACTLOCATIONS SHALL BE DETERMINED BY THE CONSTRUCTION AND STRUCTURE OF THEBUILDING AND SHALL BE VERIFIED AND COORDINATED IN THE FIELD. EACH TRADECONTRACTOR SHALL VERIFY WITH THE GENERAL CONTRACTOR THAT HE HASTHOROUGHLY REVIEWED AND COORDINATED ALL LOCATIONS AND ROUTINGS WITHALL OTHER TRADES PRIOR TO FABRICATION OF PIPING, DUCTS, OR CONDUITS, ANDSTART OF INSTALLATION OF SAME (INCLUDING SPRINKLER PIPING WHEN PRESENT ONJOB). ANY INSTALLATION OR CONSTRUCTION CONFLICTS WHICH OCCUR IN THE FIELDSHALL BE RESOLVED BY THE TRADE CONTRACTOR TO THE SATISFACTION OF THEOWNER AND ARCHITECT AND AT NO EXPENSE TO THE OWNER, ARCHITECT AND/ORGENERAL CONTRACTOR.NOTE:BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES ANDORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLEDIN STRICT ACCORDANCE WITH GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOTWITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT, ENGINEER OR OWNER OFANY APPARENT DISCREPANCIES BETWEEN GOVERNING CODES AND DESIGN INTENT.NOTE:THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER PRIOR TO BIDDINGFOR INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN AND INCLUDE IN HIS BID ALLCOSTS TO MEET THE DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OROWNER AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT CONTRACTORS COST.GAS PRESSURE REGULATING VALVEGAS SHUT-OFF VALVEROOF DRAINSOLENOID CONTROL VALVEBALANCING VALVETHREE-WAY CONTROL VALVETWO-WAY CONTROL VALVENTSNOT TO SCALEWCOVTRTYP.WHAHWCLEAN-OUT ON GRADEWALL CLEAN-OUTCLEAN-OUTFLOOR CLEAN-OUTVENT THRU ROOFELECTRIC WATER COOLERTYPICALWATER HAMMER ARRESTORDOMESTIC COLD WATER LINEHOT WATER LINEHOSE BIBBFLOOR DRAINFLOOR SINKABOVE FINISHED FLOORHWPHOT WATER RECIRCULATION PUMPCONDENSATE DRAINSANSANITARY LINEVVENT LINEAVERAGEWMWATER METERCUBIC FEET PER HOURMBHTHOUSAND BTU'S PER HOURPSIPOUNDS PER SQUARE INCHWCWATER COLUMNTHERMAL EXPANSION TANKBRITISH THERMAL UNIT PER HOURAUTHORITIES HAVING JURISDICTIONTMVTEMPERATURE MIXING VALVEGREASE INTERCEPTORLINT INTERCEPTORLIGALLONS PER FLUSHGALLONS PER MINUTETPVTRAP PRIMER VALVEWSVWASTE STACK VENTCOMPRESSED AIRVSVENT STACKWSWASTE STACKABOVEBARRIER TYPE SEAL-TRAP PRIMERELECTRIC WATER HEATERGAS REGULATORGAS WATER HEATERHUB DRAININSTANTANEOUS WATER HEATERIWHICE MAKER VALVE BOXIVBPRVPRESSURE REDUCING VALVERVBREFRIGERATOR VALVE BOXRDROOF DRAINSDSHOWER DRAINSPSUMP PUMPTDTRENCH DRAINWVBCLOTHES WASHER VALVE BOXWALL HYDRANTHYYHYARD HYDRANTFORCE MAINRLRAIN LEADERAIR ADMITTANCE VALVEHOT WATER RETURN LINEHWRGREASE WASTE LINEBELOW FINISHED GRADEBELOW FINISHED FLOOREXTERIOR CLEAN-OUTGAS LINECENTER LINEDOWNEACHGENERAL CONTRACTORHAIR INTERCEPTORNICNOT IN CONTRACTOWOIL WASTE SANITARY LINEOWSOIL WASTE SEPARATORTWTEMPERED WATER LINEVBVACUUM BREAKERFILTERED WATER LINEFCOCOEWCHBCWFDFSAFFCNDAVGCFHETBTU/HAHJGIGPFGPMCAABVBTSEWHGRGWHHDFMAAVGWBFGBFFECOGASCLDNEAGCHIFWCOOGAIR COMPRESSORACAMERICANS DISABILITIES ACTADAADJUSTABLEADJABOVE FINISHED GRADEAFGBUILDING AUTOMATION SYSTEMBASBELOWBELBRAKE HORSEPOWERBHPBACKFLOW PREVENTERBFPCUBIC FEET PER HOURCFHCUBIC FEET PER MINUTECFMCAST-IRONCICEILINGCLGCONTINUATIONCONTDEGREES FARENHEITDEG FDIAMETERDIADRAWINGDWGEXISTINGEXFLUSH VALVEFVHORSEPOWERHPINVERT ELEVATIONIEINCHESINLAVATORYLAVLIQUID PROPANE GASLPMAXMAXIMUMMINMINIMUMMISCMISCELLANEOUSCHLORINATED POLYVINYL CHLORIDECPVCAMER. SOCIETY OF MECH. ENGINEERSASMEAMER. SOCIETY OF PLBG. ENGINEERSASPEAMER. SOCIETY OF SAN. ENGINEERSASSEAMER. SOCIETY OF TEST. & MATERIALSASTMFLOOR TROUGHFTPDIPLUMBING DRAINAGE INSTITUTEPVCPOLYVINYL CHLORIDE PIPENFPANATIONAL FIRE PROTECTION ASSOC.NSFNATIONAL SANITATION FOUNDATIONPRVPRESSURE REDUCING VALVESFSQUARE FEETREQDREQUIREDUNOUNLESS NOTED OTHERWISEFUNNEL FLOOR DRAINFNDGREASE VENT LINEGVPROJECT PIPING NOTES1. PROVIDE TRAPEZE PIPE HANGERS FOR PIPES 3 OR MORE. DOUBLE NUT U-BOLTS EVERY THIRD HANGER. U-BOLT SHALL BE LOOSELYFASTENED. INTENT IS NOT TO BIND OR HOLD PIPE, BUT ONLY TO PROVIDE LATERAL SEPARATION.2. PROVIDE 1" X 1" X 1/8" ANGLE WELDED TO BOTH SIDES OF PIPE OF BAR JOIST IF PIPE HANGAR IS MORE THAN 6" AWAY FROM PANEL POINTS.3. PROVIDE WATER HAMMER ARRESTORS FOR ALL GANG TOILET AREAS OR ANY OTHER SINGLE OR MULTIPLE WATER USING DEVICE.4. FASTEN ALL INSULATION PIPE SHIELDS TO PIPE INSULATION WITH ADHESIVE.5. ALL PIPE SUPPORT SYSTEMS SHALL NOT CRUSH THE INSULATION WHEN RESTING UPON THE SUPPORT. THE USE OF METAL SADDLES ISNECESSARY WHEN THE WEIGHT OF PIPE EXCEEDS THE WEIGHT SUPPORT LIMIT OF THE INSULATION.6. PIPE SIZES MAY BE SHOWN FOR THE SAME PIPING ON MORE THAN ONE PLAN. IN CASE OF PIPE SIZE DISCREPANCY, THE LARGER PIPE SIZESHALL BE CONSIDERED CORRECT DURING THE BIDDING AND DURING CONSTRUCTION UNLESS SPECIFICALLY APPROVED BY THEARCHITECT/ENGINEER OTHERWISE.7. PROVIDE SHUT-OFF VALVES FOR BOTH HOT AND COLD DOMESTIC WATER AT ALL RESTROOM LOCATIONS AND HEAT TRAPS FOR WATERHEATERS.8. PROVIDE 1" INSULATION ON HOT WATER PIPING. REFER TO TABLE C403.2.10 OF THE 2023 FLORIDA ENERGY CONSERVATION CODE.9. PIPE PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS SHALL BE INSULATED AND HAVE SPACE SEALED WITH FIRE STOP MATERIAL.10. PROVIDE A POSI-SET SYSTEM GAS CONNECTION SYSTEM FOR ALL GAS APPLIANCES.PLUMBING LEGEND AND PROJECT NOTES P-1SHEET TITLE:SHEETDATE:DRAWN BY:CHECKED BY:11-07-24370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 12/02/24 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.12-02-24NO.REVISIONDATE SOUTHERN STEER CMDTENANT BUILD-OUT 645 ATLANTIC BOULEVARD ATLANTIC BEACH, FLORIDA 32233MJS PLUMBING SCHEDULES P-2SHEET TITLE:SHEETDATE:DRAWN BY:CHECKED BY:11-07-24370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 12/02/24 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.12-02-24NO.REVISIONDATE SOUTHERN STEER CMDTENANT BUILD-OUT 645 ATLANTIC BOULEVARD ATLANTIC BEACH, FLORIDA 32233MJS EXISTING COVERED PORCHEXISTINGRESTROOM102EXISTING ADARESTROOM103PREPDISHWASHINGAREA105WALK-INCOOLER108EXISTINGSTORAGE 1106EXISTINGSTORAGE 2107COUNTER101RETAIL100HALL104AHU-2EXISTINGRESTROOM1XXEXISTINGRESTROOM1XXPREPDISHWASHINGAREA1XXWALK-INCOOLER1XXEXISTINGSTORAGE 11XX EXISTINGSTORAGE 21XXCOUNTER1XXRETAIL1XXSANITARY WASTE PLAN AND GREASE WASTE RISER P-3SCALE: 1/4" = 1'-0"02'4'8'SCALE:1/4"=1'-0"SANITARY WASTE PLANSHEET TITLE:SHEETDATE:DRAWN BY:CHECKED BY:11-07-24370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 12/02/24 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.12-02-24NO.REVISIONDATE SOUTHERN STEER CMDTENANT BUILD-OUT 645 ATLANTIC BOULEVARD ATLANTIC BEACH, FLORIDA 32233MJSSCALE:N.T.S.GREASE INTERCEPTOR INSTALLATION DETAILSSCALE:N.T.S.GREASE WASTE RISER DIAGRAM EXISTING COVERED PORCHEXISTINGRESTROOM102EXISTING ADARESTROOM103PREPDISHWASHINGAREA105WALK-INCOOLER108EXISTINGSTORAGE 1106EXISTINGSTORAGE 2107COUNTER101RETAIL100HALL104AHU-2 EXISTINGRESTROOM1XXEXISTINGRESTROOM1XXPREPDISHWASHINGAREA1XXWALK-INCOOLER1XXEXISTINGSTORAGE 11XXEXISTINGSTORAGE 21XXCOUNTER1XXRETAIL1XXCH M CHMDOMESTIC WATER PLAN P-4SCALE: 1/4" = 1'-0"02'4'8'SCALE:1/4"=1'-0"DOMESTIC WATER PLANSHEET TITLE:SHEETDATE:DRAWN BY:CHECKED BY:11-07-24370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 12/02/24 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.12-02-24NO.REVISIONDATE SOUTHERN STEER CMDTENANT BUILD-OUT 645 ATLANTIC BOULEVARD ATLANTIC BEACH, FLORIDA 32233MJS P-5SCALE:N.T.S.FLOOR DRAIN DETAIL (FD)SCALE:N.T.S.FLOOR SINK DETAIL (FS)PLUMBING DETAILSSHEET TITLE:SHEETDATE:DRAWN BY:CHECKED BY:11-07-24370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 12/02/24 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.12-02-24NO.REVISIONDATE SOUTHERN STEER CMDTENANT BUILD-OUT 645 ATLANTIC BOULEVARD ATLANTIC BEACH, FLORIDA 32233MJSSCALE:N.T.S.TYPICAL PIPE SLEEVE THRU WALL DETAILSCALE:N.T.S. EXTERIOR CLEANOUT ON GRADE DETAIL (COOG)SCALE:N.T.S.WATER HAMMER ARRESTOR DETAILSCALE:N.T.S.3-COMPARTMENT SINK PIPING DETAILSCALE:N.T.S.ANTI-SCALD DEVICE DETAIL (TMV-P)