Permit HVAC 1085 Atlantic Blvd 78 2012 CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 12-00001521 Date 10/16/12
Property Address . . . . . . 1085 ATLANTIC BLVD 78
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
1085 ATLANTIC LLC RUNNELS AIR CONDITIONING
5118 N 56TH ST 4222 CINDY RD
TAMPA FL 33610 LAKELAND FL 33810
(863) 581-4268
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 91 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 4/14/13
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 91 . 00 91 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 95 . 00 95 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION OV 7 fr--
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph(904) 247-5826 Fax (904)247-5845
JOB ADDRESS:
PR OJE C T VA L UE $ 7- 7 2- ARI# 7 C>00 Z-7
REQUIRED
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Pe�Unit Seer Ratin
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit -)- -
Heat: Unit Quantity BTU's Per Unit. 5 K LL) Seer Ratin2 15
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work,does not commence within a six month period orwork is suspended or abandoned for six months.I hereby certify that I have rea(
this application and know the same to be true and correct, All provisions of laws and ordinances governing this work-will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name X L/e"6-- M Phone Number
Mech ani c al C ompany A LL A n,&-(-S &�,jj i i can Aq Ckr-�*cle PhonZ63-561 YA e4-3-771?-?-/
Co. Address: -A, 02,1'k4ii 7RC=4 city LakgL*,j StateR Zip.�Mtn
License Holder(Print): t v—wrr 'RuarteLs State Certification/Registration#64-W 48 NC4
Notarized Signature of License Holder
Sworn and subscribed before me this day of 20
Signature of Notary Public
CERTIFIEDT
wwvv.a h rid i rectory.org
Certificate of Product Ratings
AHRI Certified Reference Number: 4765491 Date: 9/10/2012
Product: Split System:Air-Cooled Condensing Unit, Coil with Blower
Outdoor Unit Model Number: GSX130241C*
Indoor Unit Model Number: AR*FI82416C*
Manufacturer: GOODMAN MANUFACTURING CO., LP.
Trade/Brand name: GOODMAN,JANITROL,AMANA DISTINCTIONS, EVERREST, ONE HOUR AIR
CONDITIONING AND HEATING, ENERGI AIR
Manufacturer responsible for the rating of this system combination is GOODMAN MANUFACTURING CO., LP.
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 23000
EER Rating (Cooling): 11.00
SEER Rating (Cooling): 13.00
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed an this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s),or the
me rthorize listed on this Certificate.Certified ratings are valid only for models and configurations listed In the directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and Its contents are proprietary products ofAHRI.This Certificate shall only be used for individual,personal and confidential reference purposes.
The contents ofthis Certificate may not,In whole or In part be reproduced;copied;disseminated;entered Into a computer database;or otherwise utilized,In any
form or manner or by any means,except for the user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The Information forthe model cited on this certificate can be veffied atwww.ahridirectory.org, Air-Condifforting,Heating,
click on"Verify Certificate"link and enterthe AHRI Certified Reference Numberand the date on
was Issued,which Is listed above,and the Ceedficats No.,which Is listed below. and Refrigeration Institute
ut
@2012 Air-Conditioning,Heating,and Refrigeration Instit e CERTIFICATE NO.: 129917765623209026
DesignStar Load Calculation
Results are intended fbr usewith Rheem heating and cooling systems only
Tne New Dogtoo of OoWortlll
Customer Information
�77F�7-7-
-7,
L 6tlldn'-..
-ICT.
...........................
Street Address 1088 Atlantic blvd, DUVAL, FL 32233
.......... .......... .................... .........I-------.......... ..............
Latitude, Longitude 30,3375"t -81.76860 ,
................ ...............
...........
House Square Footage: 825 sq. ft.
.............
........... ............. ...........
Name: Terry Runnels
............
Phone: 863-581-4268
.................... ........................... .............. .................... ..........
Email: terunsr@aol.com
........... ............ .......------------ ............. .................. ............. ......
House Information
SHR .75
.......... .............. ........................................................... .................................. .............
Number of residents 4
............
Ceiling height 8
............ .......................... ...........................................*...................... .............. ..................
Wall U-value R-value 0,091 11
............................ ..................
Floor U-value I R-value 0.2 15
............ ......................... .................... ...........-------- .........
Ceiling U-value R-value, 0.05 19
.................. ...... ....................... .............. ...............
Window U-value
............. ..........
Window SHGF. 0.85
........................................ .......... .......... ..............
Moisture grains 0.85
------------- ........... ------
Duct loss O/o 10
........... ...........I................. ................. .......... ........................................- ....................
Duct gain % 10
............................ ............... ..............................
Cooling infiltraction, (ACH)
0.61
.................-1.1............. ............ ..............
Heating infiltration (ACH) 0.8
Wthterventil.atioh
0
11..................... .......... .......... ....................................
Summer ventilation 0
Design Conditions
Outdoor
............ ------------- ......................................Heating cooling
........... .............................
Dry bulb (OF) 32 93
..................... ............. .................................................. ....................... ................... .................................
Daily range M
...........-........ ------ ..................... ................................ .................-....... ............................ ............. ..................................... ............
Relative humidity
............ .......... ............... ....................... .............................................. ............. ...........-'-.............................
Moisture difference 53
.................... ................ ................. .......... ............................ .................. .............................. .................. ..........
Indoor Heating Cooling
................................................................................. ................- --------
Indoor temperature (OF) 70 75
.......... ............. ........... ...............................
Design temperature difference(OF) 38 18
................... ..........-...................................................... ................ ............. ........................... ...............111-................... ........... ........... ...............................
[�Heatinq Loads
Area Btuh % of load
....................................
Wall 1951 9.6
...............
Floor 6270 30.9
............ ..................................... .................
Ceiling 1662 &2
............. ......
Windows 25.4
....................... ............... ................... ............
Infiltration 3421 16.8
..........------ .......
System Efficiency Loss 1847 9,1
........................ ....... ..................... .......
Tota 1: 20318
........................... ........ ..................
Head ng Loads
20,318 BTU/hr
Ceiling
System Efficiency Loss
Floor
Wall
Infiltration
Windows
- -- ------- ----------------
C 0 S
olin
Area
Iftlih df load
............
924 4.3
..............
Ceilina 787 17
.......... .........
Wir
MCOWS 12789 59.7
..........
Sensible fn�iltration, 1215 5.7
LaLent Infiltration 2212 10.3
Syste ffid Ga 93 8.4
6-) E tenc tn,�,c
I n te r n a 1 926 4.3
Sensi'ble', Peo I p[e.1oad-
LatenL People Load 380 1,8
Totad: 21405
............ ---------.........................
Sensible load 18813
...................
Latent load 2592
SH R 0.88
..........
Capacity at .75 SHR 2.09 Tons
..........................................................
Cooling Loads
21,405 BTU/hr
Sensible PeopI Load
Latent People Load
Ceiling
Wail
Internal
Sensible Infiltratior
System Efficienc,
Windows
Latent Infiltration
Adequate Exposure Diversity-
AED Graph
20000
15000
10000
5000
0 8arn 9arn 10arn 11arn 12prn Ipm 2prn 3pm 4prn 5PM 6pm 7prn 8prn
Hourly Loads Average
'ACCA Manual S
System equipment selection will be made using the following Manual S derived values.
Summer Outdoor 930F
.......... ............. ................. ......
Summer Wet Bulb 770F
11................- ..............................................................-............ .......... ............. ...............................................--- -.......... ............
Summer Indoor 75"F
---l-.............-................... ----.................- ............. .............. ................ ..............................
Summer Design Grains 50%
..................... ......... ..........................................-................. ................ ................... ............. ...........................................
Winter Outdoor 32"F
................. ................. ...........--................. ........... .................... ..........----------------- ............
Winter Indoor 70OF
...................................- .......... .......... ............................ .......... ................
Sensible Cooling 18,813 Btuh
..................-- ....................... ................ .........................................--............................. .......... .................
LatentCoPling 2,592 Btuh
...................................-.-......................... .............. ............... .................. ................
Required Cooling Airflow 855 CFM
........... ........... ....... .......................---......................-..........7 ------
Sensible Heating 20,318 Btuh
...................
..................................................................... ......................................
Required Heaing Airflow 264 CFM
.................-...........
All calculations are based upon approved hvac industry standards and procedures,and comply with all local,
state and federal code requirements.All computed results are Estimates.Product provided by Energy Design
Systems and ldeaTree