Permit HVAC 1085 Atlantic Blvd 73 2012 CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
.......... INSPECTION PHONE LINE 247-5814
Application Number . . . . . 12-00001516 Date 10/16/12
Property Address . . . . . . 1085 ATLANTIC BLVD 73
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
1085 ATLANTIC LLC RUNNELS AIR CONDITIONING
5118 N 56TH ST 4222 CINDY RD
TAMPA FL 33610 LAKELAND FL 33810
(863) 581-4268
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 91 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 4/14/13
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 91 . 00 91 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 95 . 00 95 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION dV,-,P7-7j
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph (904)247-5826 Fax (904)247-5845
JOB ADDRESS: - — - 2!Y-
A�Laaitt',_, AAa&L-&W4_0Za2PERMlT#
PROJECT VA L UE$ 7- 7,2, - - ARI# -7po
_C 2_--7
REQUIRED
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity I TonsPerUnit .2- -
Heat: Unit Quantity BTU's Per Unit 5 R Lj--- Seer Rating--L--b
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipc Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commcrcial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Piping Outlets Boilers BTU*s
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or-work-is suspended or abandoned for six months.I beret)),certify-that I have rea(
m
this application and know the same to be true and correct, All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name L/ "mes Phone Number
4�
Mechanical Company_?)�V_A_v1-e_(S 77
Co. Address: c=4 City LaLlf 4_01"J, ---- State R zip3m(,!�)
License Holder(Print)- -T;a-r-r L/ a,rl.tt fels State Certification/Registration#CACZ 4-1/60
I
Notarized Signature ofLicense Holder
Sworn and subscribed before me this day of 20
Signature of Notary Public
Utertificate of Product Rabn2s
AHRI Certified Reference Number: 4765491 Date: 9/10/2012
Product: Split System:Air-Cooled Condensing Unit, Coil with Blower
Outdoor Unit Model Number: GSX130241C*
Indoor Unit Model Number: AR*FI82416C*
Manufacturer: GOODMAN MANUFACTURING CO., LP.
Trade/Brand name: GOODMAN,JANITROL,AMANA DISTINCTIONS, EVERREST, ONE HOUR AIR
CONDITIONING AND HEATING, ENERGI AIR
Manufacturer responsible for the rating of this system combination is GOODMAN MANUFACTURING CO., LP.
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 23000
EER Rating(Cooling): 11.00
SEER Rating(Cooling): 13.00
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)Rated on this Certificate and makes no representations,warrantles or guarantees as to,and assume&no responsibility for,
the product(s)listed on this Certiftate.AHRI expressly disclaims all lability for damages of any kind arising out of the use or pefformance,of the product(s),*rthe
iteration of data Usted on this Cartificats.Certified ratings are valid only for modeft and configurations listed In the directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This certificate and its contents are proprietary products of AHRI.This CoMficate shall only be used for Individual,personal and confidential reference purposes.
The contents of this Certifleste may not,In whole or in part,be reproduced;copied;disseminated;entered Into a computer database;or otherwise utilized,In any
form or manner or by any means,except for the user's individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificift can be verified at www.ahridirectory.org, A "Imp,
click on"Verify Certificate"link and enter the AHRi Certified Reference Number and the date on 2 Air-Conditioning,Heating,
whirli thartifiroft was Issued,which is Rated above,and the Cordficate No.,which is listed below. APW INS IkE and Refrigeration Institute
02012 Air-Conditioning,Heating,and Refrigeration Institute CERTIFICATE NO.: 129917765623209026
1 - ------ :J
esignStar Load Calculation
ults are intended fbr use with Rheem heating and cooling systems only
Tne Now 0091,00 of comfort",
'Customer Informati
on
..........
d DUVAL, Fl- 82238
..........
'itu
fatitude, ba
-81.V;6
............ ............ ............ ...........
House Square Foota e: 750 sq. ft.
9
Name: Terry Runnels
................... .............. ........... ...................... ......
Phone: 868-581-42:68
................... ...............
Email: terunsr@aol.com
.................... ................................. ...................... ............................ .............
Pouse Information
SHR .75
.............. ............. ............ ...........-
Number of.residents.-. 4
Ceiling height 8
................. .......-
Wall U-value R-value
.......... ..................... .................................... .............. ........... ................ .................. .........................
Floor U-value R-value 0.2 5
................ ......... ......-----------
,Ceiling P,-value R-Value
................ ............... ...................... .......... .......... ...........
Window U-value 1
...................------
Window SHGF
........... .......... ................ ............. .............................
Moisture grains 0.85
................- ....................... ......
Ouctlossl%
.............. ............................................................................... .................. ............ .............. ...........- ...............................
Duct gain % 10
................ ........ .............
Cooling infiltraction (ACH) 0.6
D
Res
................. .................. ............................. ......................
Heating infiltration (ACH) 0.8
........... ........... .......... ........... ......
Wi-nt&Ventilation 0
................ ............
Summer ventilation 0
�Design Conditions
Outdoor Heating Cooling
........................... -------------
Dry bolb 32 93
.............. ........... ........... ............. .......... ............. .......... ...........
Daily range M
.................................. ------ -.7...............
Relative humidity
50%�
............................ .......... .......... ............. .............. ............. ...................... .............. .......... ............
Moisture difference 53
...........--.-.......... .................... ............... .................... ............... .......... .......................................................
Indoor Heating Cooling
...........1.................. ............................ ................. ------------- ...................... ........................
l.ndoor,tempera,ture ('F) 70 75:
........................ ........... ............... ............
Design temperature differenceff) 38 18
..........---................. .............................................. ...................- ....................................... ............ .........................-....................... .............
'Heating Loads
Area Btuh % ofload
............. ......
Wall 1860 9.7
............
Floor 5700 29.9
.......... .................
Ceiling 7.9-
Windows 5168 27.1
.................. ........... ............ ................
Infiltration h10 16.3
...........
System Efficiency Loss 1735 9.1
.........................
Total.- : 19083
..........
Heating Loads
19,083 BTU/hr
Cei ing
System Efficiency Loss
Floor 2�011;1
.........
Wall
Infiltration
j-
Windows
za
........ ---------I
-7
�'Coo I i nq Loads
A,
Windows 127891161.5
-Q`
.................... ........................ ........
Late
rit load 2356
SH'R ,
Capacity zit,75SHR'�' 2.05 Tons .:
...........
............
Cooling Loads
20,783 BTU/hr
SensibleP plel-oad
L='it People Load
ceiling
Internal
Wall
Sensible Infiltratioril
System Efficiencl,
Windows
Latent Infiltrat'
ion
Adequate Exposure DiversitV 77
AED Graph
20000
15000
10000
5000
0 8am 9am loam llam 12pm 1pm 2pm 3pm 4pm 5pm 6pm 7pm 8Pm
Hourly Loads —Average
ACCA Manual S
System equipment selection will be made using the following Manual S derived values.
Summer Outdoor 930F
............ ..................
Summer Wet Bulb, 7T-F
...................................... .............
Summer Indoor 750F
.................................................. ..............
Summer Design Grains 50%
............. ........... .........................I ........... ..........
Winter Outdoor 320F
........... ................................... .......... ...... ................
'Winter Indoor 70OF
F-1.114-1 --m-.- ........................................... ..........
Sensible Cooling 18,427 Btuh
................ ...............
Latent Cool i'ng. 2,356 BtUh
................ ............. .......
.................... ............................
Required Cooling Airflow 838 CFM
.............. .......... ............... ..........- ........... ....... .....................
Sensi,ble Heatin-9, 1.9.083 Btuh
............ .................... ...... ......... .......... .......... .......... ----------- ................ ............
Required Heaing Airflow 248 CFM
............. .............. ..........
All calculations are based upon approved hvac industry standards and procedures,and.comply with alf.local
state, and federal code requirements,All compul3ed results are Estimates,Product provided by Energy Design
Systems and Idea Tree