Permit HVAC 1085 Atlantic Blvd 2 2012 CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 12-00001580 Date 10/29/12
Property Address . . . . . . 1085 ATLANTIC BLVD 2
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
1085 ATLANTIC LLC RUNNELS AIR CONDITIONING
5118 N 56TH ST 4222 �CINDY RD
TAMPA FL 33610 LAKELAND FL 33810
(863) 581-4268
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 91 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 4/27/13
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 91 . 00 91 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 95 . 00 95 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph (904) 247-5826 Fax (904) 247-5845
JOBADDRESS: 10?,L5 A4�0-�-Iee- -5( Vd . &4Z1dL1&Wk-3Z�ERMrF#
PROJECT VALUE $ Z' i 2- 7Z ARI# N 7 000 2--7
REQUIRED
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit Z
Heat: Unit Quantity BTU's Per Unit 5 K Seer Rating 15
Duct Systems: Total CFM REQ
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name 9 Liet6Le mes t-k-c Phone Number
Mechanical Company- if �14pkll A
R Lt-ti K Y-0 CS Cja" ' ' rAo&4W6 icle PhonZ63-5&yFEZW3-77'?-'?-,
Co. Address: 4ZZA., 0-,1'k4(4 �Rc=ck City Lalegj"j _ StateELZip3M
License Holder (Print): �rr W &-Runrt-P—LS State:Certification/Registration #d*Lp 4P/60
Notarized Signature of License Holder
Sworn and subscribed before me this day of 20_
Signature of Notary Public
CERTIFIEDTM
www.ahridirectory.org
Cleftificate of Product Ratings
AHRI Certified Reference Number: 4765491 Date: 9/10/2012
Product: Split System: Air-Cooled Condensing Unit, Coil with Blower
Outdoor Unit Model Number: GSX130241C*
Indoor Unit Model Number: AR*FI82416C*
Manufacturer: GOODMAN MANUFACTURING CO., LP.
Trade/Brand name: GOODMAN,JANITROL,AMANA DISTINCTIONS, EV ERREST, ONE HOUR AIR
CONDITIONING AND HEATING, ENERGI AIR
Manufacturer responsible for the rating of this system combination is GOODMAN MANUFACTURING CO., LP.
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by,AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 23000
EER Rating (Cooling): 11.00
SEER Rating (Cooling): 13.00
Ratings followed by an asterisk(*)indicate a voluntary rerate of previously published data,unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(*)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind orlaing out of the use or performance of the product(s),or the
unauthorized alteration of data listed on this Certificate.Certified ratings are valid only for models and configurations listed In the directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and ft contents are proprietary products ofAHRL This Certificate shall only be used for Individual,personal and confidential reference purposes.
The contents ofthis Certificate may not,In whoW or In part,be reproduced;copied;disseminated;entered Into a computer database;or otherwise utilized,In any
form or manner or by any means,except for the user's Individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The Information for the model cited on this certificate can be verified at www.ahridirectory.org, Air-Conditioning,Hoofing,
click on"Verhly Certificate"link and enter the AHRI Certified Reference Number and the date on
which ffm cerfificats was Issued,which Is listed above,and the Certificate No,which Is listed below. an ILI and Refrigeration Institute
02012 Air-Conditioning,Heating,and Refrigeration Institute CERTIFICATE NO.: 129917765623209026
DesignStar Load Calculation
Results are intended for use with Rheern heating and cooling systems only
Tne NI%nv Oogm of Om!ort"4
Cus' tbmer'-�]'nf Orr*iati'
Location:
................. ........... ...... ....................... ------
Street Address 1088 Atlantic blvd, DUVAL, rL 32233
................ ............ ........... ---------.........
Latitude, Longitude 30.3375", -81.76860
.................... ............ ........... ------- -------
House Square Footage: 825 sq. ft.
.......... .................... ............ ...................
Name: Terry Runnels
.............. ....................................................... .......... ........................ .......
Phone: 863-581-4268
............................... .......... ...........I--................ .............. .................... ------ ...........
Email: terunsr@aol.com
..........-------- ........... ............ ........ .............................
',Hou;se lnformatipn-,.��-
SHR .75
...........--.............................-........ .................... --------------............
Number of residents 4
-.1................................. ............. ...... ...........
Ceiling height 8
.......... ....... .............................. ............................. ...........................................
Wall U-value I R-value 0.09111
................-..........I..........-.1.................... ......................... ................ ............. ..........
Floor U-value I R-value 0.2 15
............-1................I.-........... .............-
Ceiling U-value R-value 0.05 119
.................. ............... ............... .................................... ...........................................................................
Window LI-value
Window SHGF 0.85
............ ........
Moisture grains 0.85
............... .......... -------..................... ............ ............. ..........
Ductloss % 10!
.............
Duct gain % 10
-............... ....................................... ...................................................111.1- ---------
Cooling infiltraction (ACH) 0.6
...................
Heating infiltration (ACH) 0.8
.................... ........... ...........
Winter ventilation 0
-1-1—I........... ........
Summer ventilation 0
Outdoor Heating Cooling
.............. ......................-.-.............
Dry bulb (OF) 32 1 93
....................................... .................................. ............................................................I.I....-I....... ........................................
Daily range M
........... .................
Relative humidity 50%
.........................................................................................................- ....................-............... ................................... ..............I--...........
Moisture difference 53
........... .......................... ..................... .......................--................ .......... ...................... ..........
Indoor Heating Cooling
.......... ........... ........................................................ ....... --------....................... ................................
Indoor temperature (OF) 70 75
...............I -.-..........-.1.1-1 ........... ..................... ............I.- 1-.1-.-1.1.1....-.........................................
Design temperature difference(OF) 38 18
................................................................... ............................................. ..............-..-..................... ..........I........... ............................
Area Btuh % ofload
............... ......
Wall 1951 9.6
................................... -------
Floor 6270 30.9
...............
Ceiling 1662 8.2
.............- ..........
Windows 5168 25.4
................. .................................-.-........... ...........-
Infiltration 3421 16.8
............................. --............1 1.-.-.-.- --
System Efficiency Loss 1847 9.1
.......... ..........— ................................. ..........
Tota 1: 20318
............... ........... -----------
Heating Loads
20,318 BTU/hr
Ceiling
System Efficiency Loss
Floor
Wall
'AA
Infiltration
Windows
Men$ 1110101
Area Btuh % of load
Wall 924 4.3
Ceiling 787 3.7
.......... ............
Wi n d ows
12-189 59.7
S,ensible Infiltration 121 15 5. 1
Latent Infiltration 2212 10.3
System Efficiency Gam 1793 8.4
Internal 926 4.3
-----------------
Se4sibl.e People Load 380, 1.8
.....................
Laterit People Load 380 1.8
Total, 21405
..................................
Sensible load 18813
................... .................
Latent I oad 2592
SHR 0.88
........................
Capacity at .75 SHR 2.09 Tons
...........
Cooling Loads
21,405 BTU/hr
Sens ible People Load
Latent People Load
Ceiling
Wall
'14 Internal
--,—Sensible Infiltration
System Efficienc,
Windows
Latent Infiltration
AED Graph
20000
15000
V
M 10000
9
5000
0 Bam 9am 10am 11am 12pm Ipm 2pm 3pm 4pm 5pm 6prn 7pm sprn
Hourly Loads Average
ACCANanua[--S ,�
System equipment selection will be made using the following Manual S derived values.
Summer Outdoor 930F
-1--.1.1.........................._-_.___-_1.......... ........ ............................... ..........
Summer Wet Bulb 770F
-..................................................... ........................ ......................................................................................... .................... ......................
Summer Indoor 75'F
...........__------1.___._,_--.-.,_.............. ................................................................................................ ........
Surnmer Design Grains 50%
................................................................................. ..................................................... .............. ....................................... .................................................................... ............
Winter Outdoor 320F
.............. ............ .......... ............
Winter Indoor 70"F
................................................. ..................... ..........- .................... ........................... ....................................... .......................
Sensible Cooling 18,813 Btuh
---.1---------.......... ------- ..........--------1-11....................1....__._.__.._-_....1........................
Latent Cool i ng 2,592 Btuh
i
.......................... ............................ .......... .......... ................... ...................... . .......*..........
Required Cooling Airflow 855 CFM
Sensible Heating 20,318,Btuh
........... ----------- ----- ................................ .....................
Required Heaing Airflow 264 CFM
............ ........................ .......... ------......- .......... ...... ..........
All calculations are based upon approved hvac industry standards and procedures,a nd comply with all local,
state and federal code requirements.All computed results are Estimates.Product provided by Energy Design
Systems and Idea Tree