Permit HVAC 1085 Atlantic Blvd 10 2012 CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 12-00001589 Date 10/29/12
Property Address . . . . . . 1085 ATLANTIC BLVD 10
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
1085 ATLANTIC LLC RUNNELS AIR CONDITIONING
5118 N 56TH ST 4222 CINDY RD
TAMPA FL 33610 LAKELAND FL 33810
(863) S81-4268
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 91 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 4/27/13
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 91 . 00 91 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 95 . 00 95 . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION �77Z'
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph (904) 247-5826 Fax (904) 247-5845
JOB ADDRESS: z2&. -AE A&a '
,j-d1-,e�"&W1u3Z�ERM1T#
PROJECTVALUE $ ------r- A RI# 14- 7 C>OeD 2-77
REQUIRED
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Ratin
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Rating_
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
#Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have rea
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name X L)8,�ja-- M es Phone Number
Mechanical CompanyALLA -C,46Picle Phon(e65-_5
If� _&YF St V4'.3-7 7-?.
Co. Address: 4ZZ7., 0--,;kL4Q :Rcaj City LaLkALgA State F
L - L Zip--7S'�
License Holder (Print): —1 ,-- rrL� &,*RuvirteLS State Certification/Registration #C*C0 4�1/60
1
Notarized Signature of License Holder
Sworn and subscribed before me this day of 20_
Signature of Notary Public
IM
CERTIFIED'
www.ahridirec ory.org
Certificate of Product Ratings
AHRI Certified Reference Number: 4765491 Date: 9/10/2012
Product: Split System:Air-Cooled Condensing Unit, Coll with Blower
Outdoor Unit Model Number: GSX130241C*
Indoor Unit Model Number: AR*F182416C*
Manufacturer: GOODMAN MANUFACTURING CO., LP.
Trade/Brand name: GOODMAN,JANITROL,AMANA DISTINCTIONS, EVERREST, ONE HOUR AIR
CONDITIONING AND HEATING, ENERGI AIR
Manufacturer responsible for the rating of this system combination is GOODMAN MANUFACTURING CO., LP.
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 23000
EER Rating (Cooling): 11.00
SEER Rating (Cooling): 13.00
Ratings followed by an asterisk(')indicate a voluntary rerate of previously published data.unless accompanied with a WAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not enclonse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assume*no responsibility for
the product(s)listed on this Certificate.AHRI expresally disclaims all liability for damages of any kind arising out of the use or performance of the product(s),or the
on of data listed on this Certificate.Certified ratings are valid only for models and configurations listed In the directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and ft contents are proprietary products ofAHRI.This Certificate shall only be used for Individual,personal and confidential reference purposes.
The contents ofthis Certificate may not In whole or in part,be reproduced;copied;disseminated;entered Into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the usoes Individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The information for the model cited on this certificate can be verified at www.ahridirectory.org,
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date on A "IMP' Air-Condifloning,Hoofing,
which the certificate was issued,which Is listed above,and the Certificate No,which Is listed below. hoU On ILI and Refrigeration institute
02012 Air-Conditioning,Heating,and Refrigeration Institute CERTIFICATE NO.: 129917765623209026
DesignStar Load Calculation
Results are intended for usewith Rheern heating and cooling systems only
Tno Now Ologioo o!Oomtrt"'
=701 goal R. 1,161
Location.-
.......... ......................
Street Address 1088 Atlantic blvd, DUVAL, FL 32233
..........
Latitude, Longitude 30.3375 0, -81.76860
.............. .......—........................................... ......................................... ........
House Square Footage: 825 sq. ft.
.......... ............. ............................ .......... ....................
Name: Terry Runnels
........... ----------............. ...................................................................... .......... ...........-............... ................
Phone: 863-531-4268
................................................................ ..........._................................. ...............................................
Email: terunsr@aol.com
................................ ......................... .................__................................. .................................... ................... ......- ......
Hou'se-Infotmatio
SHR .75
-.......................................1--_......-..................... ............. ........ .............................. ..............
Number of residents 4
............ .......... .................................................
Ceiling height 8
.-.................... ..................................................... .......................................1.11-11--11--...................................
Wall U-value I R-value 0.09111
I................................................................................ .............................. ... ..................
Floor U-value I R-value 0.2 15
............-......................... ............ ....... ...... .........
Ceiling U-value R-value 0.05 119
i
.............................. ................................ ............. .....................................-.............................................. .................
Window U-value 1
Window SHGF 0.$5
..1-1. -.1 11 1 1..........I... .......... .......... ..........
Moisture grains 0.85
....................... .......... -----------............................
Ductloss % 10
.......... -....................-
Duct gain % 10
............. ............... ............
Cooling infiltraction (ACH) 0.6
Heating infiltration (ACH) 0.8
..........
Winter ventilation 0
Summer ventilation 0
Outdoor Heating Cooling
Dry bulb (OF) 32 93
........................ ............................. ................. ............-.1......................................................--............. ........ ............ .........................................
Daily range M
............. ........................ ........ ...... -------------- -----------
Relative humidity 50%
..............................I................................................................................................. .................... ......-I...............11,...............
Moisture difference 53
..................... ..........-.-...........I....................... .......................... ........... -11-1.1...............................
Indoor Heating Cooling
................................ ....... ................. ........................ ..........
Indoor temperature (OF) 70 75
..........I -.....................................................- 1-1.�....................... ............. ..................... ............ ...............
Design temperature difference(OF) 38 is
...............I.............. ...........I................................... ............................. ................................ ..................................................................................
ITO I re Wre R 4
Area Btuh % of load
Wall 1951 9.6
.................... .........
Floor 6270 30.9
..........................
Ceiling 1662 8.2
-1-............... ........ ..................
Windows 5168 25.4
..........
Infiltration 3421 16.8
................................. ------------.-...........................
System Efficiency Loss 1847 9.1
............... .......................
Total: 20318
................. ........... -------- ............ ...........
Heating Loads
20,318 BTU/hr
Ceiling
System Efficiency Loss
Floor
Wall
Infiltration
Windo s J
Area Btuh % offoad
..........
Wall 924 4.3
..........
Ceiiing 787 3.7
VVindows 12789 59.7
Sensible Infiltration 1215 5,'17
LaLent Infiltration 2212 10.3
Sys-t-tafn Efficiency Gain 1793 8.4
ln�--rnal 926 4.3
Sensible Peo'pl-- Load 3 8'D 1.8
..........
Latent People Load 380 1.8
Tota 1 21405
..........-
Sensible load 18313
Latent load 2592
-------------
SHR 0,88
Capacity at .75 SHR 2.09 Tons
Cooling Loads
21,405 BTU/hr
Sens lble People Load
---�L�a!tent People Load
f Ceiling
Wall
Internal
Sensible Infiltration
System Efficienc,
Windows
Latent Infiltration
fire,U.-10 10,
AED Graph
20000
15000
V
10000
5000
0 8a m 9am loam llam 12pm 1pm 2pm 3pm 4pm 5pm 6pm 7pm spm
r---
Hourly Loads Average
System equipment selection will be made using the following Manual S derived values.
Summer Outdoor 930F
.............. .......... ............... ........................ ------------.- -................................... .......
Summer Wet Bulb 770F
............................ ................ ........................................ ..........
Summer Indoor 750F
..........------------ ...................................................................----.................................. .............................................................
Summer Design Grains 50%
............. ............... ..................... ................................................................ .......... .............................-,-........... ........................... ..................
Winter Outdoor 32"F
........... ............... ..........
Winter Indoor, 70"F
..............
Sensible Cooling 18,813 Btuh
........... .................................... ....................................
Latent Cooling 2,592 Btuh
...................-............... ................- ................. ......................... ............................. ................... .................... ............... .....................................
Required Cooling Airflow 855 CFM
..................... ................-.-..............----------
Sensible Heating 20,318 Btuh
-.1--..........----.........-11 -.-- .................................. ............. --------- ......
Required Heaing Airflow 264 CFM
.............1-1 --.111...... ........................-.................... ............... ..............
All calculations are based upon approved hvac: industry standards and procedures,and comply with all local,
state and federal code requirements.All computed results are Estimates.Product provided by Energy Design
Systems and Idea Tree