Permit HVAC 1085 Atlantic Blvd 24 2012 Nt) CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
Application Number . . . . . 12-00001837 Date 12/19/12
Property Address . . . . . . 1085 ATLANTIC BLVD 24
Application type description MECHANICAL HVAC ONLY
Property Zoning . . . . . . . TO BE UPDATED
Application valuation . . . . 0
----------------------------------------------------------------------------
Application desc
1 cu 1 ahu
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
1085 ATLANTIC LLC RUNNELS AIR CONDITIONING
5118 N 56TH ST 4222 CINDY RD
TAMPA FL 33610 LAKELAND FL 33810
(863) 581-4268
----------------------------------------------------------------------------
Permit . . . . . . MECHANICAL HVAC PERMIT
Additional desc . .
Permit Fee . . . . 91 . 00 Plan Check Fee . 00
Issue Date . . . . Valuation . . . . 0
Expiration Date . . 6/17/13
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE MECH DCA SURCHARGE 2 . 00
STATE MECH DBPR SURCHARGE 2 . 00
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 91 . 00 91 . 00 . 00 . 00
Plan Check Total . 00 . 00 . 00 . 00
Other Fee Total 4 . 00 4 . 00 . 00 . 00
Grand Total 95 . 00 9S . 00 . 00 . 00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALL CITY OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
lqr-7��?q
MECHANICAL PERMIT APPLICATION
CITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
Ph (904)247-5826 Fax (904) 247-5845
JOBADDRESS: A�Lq-vittt, -atvd . kZa2dL- �WebZZ-:;6rERMIT#
PROJECTVALUE $ 7,i2� 7Z , q! A RI# t4, 7 00 0 2--7
REQUIRED
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit
Heat: Unit Quantity BTU's Per Unit Seer Ratin
Duct Systems: Total CFM REQ UIR
REPLACEMENT AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity Tons Per Unit ;—)
Heat: Unit Quantity BTU's Per Unit 5 K Seer Rating_
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity — (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity — (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty_ Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
Vented Wall Furnaces Refrigerator Condenser BTU's
Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have rea
this application and know the same to be true and correct. All provisions of la%N,s and ordinances governing this work will be complied with whether specified
or not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name X up-,6, M-es Phone Number A-J4
CC" _YF Zax
J�Okj(4!4 ce 5LL
Mechanical Company-RLL ri ng-(S if�961pic Phonc&;3- T4M-771?-22
Co. Address: 4ZZ7-� 0-,1'k4Q city &-L"d— State F/ Zip3g&C
LicenseHolder (Print): �rr Lj -Rann-P—LS ation/Registration #CkZ 4�//60
.7 State CegifR
Notarized Signature of License Holde
Sw:�and scribed before me this day of 20
Signature of Notary Public
Mill
-rm i
anal CERTIFIED"
www.ahridirectory.org
Ceftificate of Product Ratings
AHRI Certified Reference Number: 4765491 Date: 9/10/2012
Product: Split System:Air-Cooled Condensing Unit, Coll with Blower
Outdoor Unit Model Number: GSX130241C*
Indoor Unit Model Number: AR*F182416C*
Manufacturer: GOODMAN MANUFACTURING CO., LP.
Trade/Brand name: GOODMAN,JANITROL,AMANA DISTINCTIONS, EVERREST, ONE HOUR AIR
CONDITIONING AND HEATING, ENERGI AIR
Manufacturer responsible for the rating of this system combination Is GOODMAN MANUFACTURING CO., LP.
Rated as follows in accordance with AHRI Standard 210/240-2008 for Unitary Air-Conditioning and Air-Source
Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent,third
party testing:
Cooling Capacity(Btuh): 23000
EER Rating (Cooling): 11.00
SEER Rating (Cooling): 13.00
Ratings followed by an asterisk()indicate a voluntary rerate of previously published data,unless accompanied with a VAS,which indicates an involuntary rerate.
DISCLAIMER
AHRI does not endorse the product(s)listed on this Certificate and makes no representations,warranties or guarantees as to,and assumes no responsibility for,
the product(s)listed on this Certificate.AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the prodUCt(3),or the
unauthorized alteradon of data listed on this Certificate.Certified ratings are valid onty for models and configuraltions listed In the directory at www.ahridirectory.org.
TERMS AND CONDITIONS
This Certificate and its contents are proprietary products of AHRI.This Cer0ficats shalt only be used for individual,personal and confidential reference purposes.
The contents of this Cartiflicato may not In whole or In part,be reproduced;copied;disseminated;entered Into a computer database;or otherwise utilized,in any
form or manner or by any means,except for the user's Individual,personal and confidential reference.
CERTIFICATE VERIFICATION
The Information forthe,model cited on this certificate can be verified at www.ahridirectory.org, Air-Conditioning,Heating,
click on"Verify Certificate"link and enter the AHRI Certified Reference Number and the date on
which the certificate was Issued,which Is listed above,and the Ceftffkate No,which Is listed below. and Refrigeration Institute
09026
02012 Air-Conditioning,Heating,and Refrigeration Institute CERTIFICATE NO.: 1299177656232:J
DesignStar Load Calculation
Results are intended for usewith Rheern heating and cooling systems only
'No Now Ocgi o*of Comortl
C 0 S t 0'rll� r'.111, I h f b r m a t i n
Location:
................ ........................... ............ .....................
Street Address 1088 Atlantic blvd, DUVAL, FL 32233
Latitude, Longitude 30.3375 0, -81.76860
...........-............ ......................................... ................... .................... ..........
House Square Footage: 825 sq. ft.
........................ .............. .................. ...................... ............. ............................... ..........
Name: Terry Runnels
................... .................................. .......... .................... ............. ...........
Phone: 863-581-4268
...................................... .......... ............................................... ...................................................
Email: terunsr@aol.com
.................. ............. .................................. .................... ..................... .................... ...........
HOUSPInformation' - ' ,�
SHR .75
........................................--...... ................. ----------.......... ............................................................... .............. ............
Number of residents 4
.................... ...................-.......... .............. ................................ .................
Ceiling height 8
............. ..............................--------- ....... .........................- ...................
Wall U-value I R-value 0.09111
........... ...................... .............................. ....................................... ..................-..........
Floor U-value R-value 0.2 15
'--.............---............ --l......... .......... ................. ......
Ceiling U-value R-value 0.05 119
i
................................ ....... ................... .............----...................................................- ...............
Window U-value 1
................. ...........
Window SHGF 0.85
..................... ..................... ............. ............. ............. ........ ............. ........... .................
Moisture grains 0.85
---............---- I------- ...............-
Ductloss % 10
Duct gain % 10
..........-1.... ........ ................ ....................................................
Cooling infiltraction (ACH) 0.6
........... ........... ..........
Heating infiltration (ACH) 0.8
—---------------------
Wi nter venti I ati on 0
............
Summer ventilation 0
is mmume emernme i
m
Outdoor Heating Cooling
........................... ...................
Dry bulb (OF) 32
93
........................ ................ ......................... ................ ....................
Daily range M
................ -----------................... --------
Relative humidity 50%
I.......... ...................... ...... ..............................-........... .................. .....................
Moisture difference 53
........... ............................. .......................... ............ ..........11.............. .............---.......... ....................
Indoor Heating Cooling
.......... ............I........ .................. .............. ........... ............ ----------.-...................
Indoor temperature (OF) 70 75
I................. .............-...............-1--.............. ........................................ ..........-.-....................................................................
Design temperature difference(OF) 38 18
....................11 -.............I-- I I -- r I................ r............................................. ...................................I............ ............. ............
ism M- .
Area Btuh % of load
................... ....................... -----------------
Wall 1951 9.6
........... .....................................
Floor 6270 30.9
................I., .......... .......... ...............................
Ceiling 1662 8.2
................
Windows 5168 25.4
..........-............. ................ ..........I ........I.......
Infiltration 3421 16.8
.1.1-1..........-- I..........--.-................ ........ --------..- --------..........................
System Efficiency Loss 1847 9,1
.......... ............ ............. .................--............
Total: 20318
.......... ....... ........... .................................
Heating Loads
20,318 BTU/hr
Ceiling
System Efficiency Loss
Floor
Wall
Infiltration
Windows
NO
Area Btuh % of load
... ..........
Wall 924 4.3
.............
Ceiling 787 3.7
Wi n d ovis 12789 59.7
Siensible� infiltration 1215 5.7
Latent Infiltration 2212 10.3
System Efficiency Gain 11793 8,4
Inte
--unal 926 4.3
............
5 ensit ble People Load, 330 1.8
Latent People Load 318 0 1.8
Total: 21405
........... ---------
Sensible load 18813
Latent load 2592
SHR 0.83
Capacity at .75 SHR 2.09 'Fons
........... ...............................
Cooling Loads
2 1A 0 S 0 FU/hr
Sensible People Load
La�nt People Load
Ceiling
Wall
Internal
Sensible Infittratior
System Efficienc,
Windows
Latent Infiltration
M470 MIN-3111on- MR
AED Graph
20000
15000
10000
3
5000
0 Sam 9am loam llarn 12pm 1pm 2pm 3pm 4pm 5pm 6pm 7pm Spm
(—L:ftullly�11 I Z111ge---'
ACCAM-anual,-S - ''
System equipment selection will be made using the following Manual S derived values.
Surnmer Outdoor 930F
...................-............... .......... ............................................. ........................ ....................... ............ .................
Summer Wet Bulb 770F
................... -............ .................................................................................... ................. .............................................. ............
Summer Indoor 750F
............................- --........... ..........--...................................................................... ...................... ......................................
Summer Design Grains 50% �
-1-...........................1 11 -....................................--......................-............... ............................................ ................. ...............
Winter Outdoor 320F
---............... .................... ....... ....................... ................... ...............--...................... ..................-
Winter Indoor 70OF
1.1-............................................... ........................... ...............-.......... ................ ...........
Sensible Cooling 18,813 Btuh
....................-.............-------- .................... .....................-.................. ............................---....... ...... .......
Latent Cooling 2,592 Btuh
111.1..................................... --................. ................................................................. ............ ............................................. ........ ............... .................
Required Cooling Airflow 855 CFIVI
.................. ............. ............. ........------------..........
i
Sensible Heating 20,318�113tuh
-11---...............-.1.1-.1.......... ........................ ......... .............1---.1 - .................................
Required Heaing Airflow 264 CFIVI
-..................... ............................ ..........-................... ........-...............
All calculations are based upon approved hvac industry standards and procedures,and comply with all local,
state and federal code requirements.All computed results are Estimates.Product provided by Energy Design
Systems and Idea Tree