1089 ATL BLDG DENIAL ,,cLyy City of Atlantic Beach APPLICATION NUMBER
Building Department (To be assigned by the Building Department.)
' 800 Seminole Road Jy
. 12.
Atlantic Beach, Florida 32233-5445 l
Phone(904) 247-5826 • Fax(904)247-5845
x VA �� E-mail: building-dept@coab.us Date routed: Z
City web-site: http://www.coab.us
APPLICATION REVIEW AND TRACKING FORM
Property Address: /00 / 4771n7C � VCI( Department review required Yes No
,eRuildin
Applicant: eRanning & o
Tree Administrator
Project:
/ ublic Uti i
;01,rr�� /� LOT — Public Safety
ire Se ices
S'0123
Review fee $ Dept Signature
Other Agency Review or Permit Required Review or Receipt Date
of Permit Verified By
Florida Dept. of Environmental Protection
Florida Dept. of Transportation
St. Johns River Water Management District
Army Corps of Engineers
Division of Hotels and Restaurants
Division of Alcoholic Beverages and Tobacco
Other:
APPLICATION STATUS
Reviewing Department First Review: ❑Approved. Denied.
(Circle one.) Comments: i
BUILDING
PLANNING&ZONING Reviewed by: Date:
TREE ADMIN. FlApp
Second Review: roved as revised. ❑Denied.
PUBLIC WORKS Comments:
PUBLIC UTILITIES
PUBLIC SAFETY Reviewed by: Date:
FIRE SERVICES Third Review: ❑Approved as revised. ❑Denied.
Comments:
Reviewed by: Date:
Revised 07/27/10
0 Cop
Ss1
CITY OF ATLANTIC BEACH
=' 800 SEMINOLE ROAD
ATLANTIC BEACH,FL 32233
(904)247-5800
"" 9r'
PLAN REVIEW 1089 Atlantic Blvd. 15-CNEW-1297 6/29/15
Gene ral Notes:
1. Oc upancy: Mixed; Business/Storage, S-1/Residential
2.Co struction Type IIB, Sprinklered(NFPA 13), Unprotected
3.Ris Category II
4.Nol in a flood zone (Zone X)
5.Wi d speed 129 mph, Vult; Exposure C
Permit Application is denied for the following:
1. En ineering pages must be original pages, signed/sealed/dated, per FAC 61G15-23.002 (facsimiles are not
acceptable). Please include all engineering details, including:
a) k1l wall construction details.
b) k1l roof construction details.
c) hear wall and wall deflection calculations. Please clarify all shearwall dimensions and locations and
speci ically how the north, south, and interior walls resist lateral loads imposed by the east and west walls.
lease include continuous uplift details and resistance to overturning of shearwalls.
d) 3age SD4 is referred to,but not found.
2. Engineering design criteria states"Minor Storage Facility, Iw= .87". This is a Risk Category II Building,
not Category I,per FBC, Table 1604.5.
3. Pl ase provide number, location, and details for accessible units, per FAC, Section 225.3.
4. Please submit all Florida Product Approval information.
5. PI ase provide minimum interior lighting, per FBC, Section 1205.3, with documentation.
6. Pl ase submit details for roof drainage.
7. Please submit fire sprinkler and alarm details.
8. Tis building is open to the public, with multiple tenants, and therefore qualifies as Mixed Business/S-1
Occuancy. Plumbing requirements for this size building includes three water closets and three lavatories, for
each ex; two Hi/Lo drinking fountains; and one mop sink,per FBC-P, Chapter 4.
9. N t a complete list.
Gene al Notes: Your re-submittal should include two complete sets of plans. Please insert the revised pages into
the plan sets, and pages removed from the stamped "Job copy" set, should be marked as 'old set" and should be
included in the re-submittal.
If of "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the
amo t of time necessary to review entire drawing again.
ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified
by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED -DEPENDING ON NEW
INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.
DanArlington 247-5813