1089 ATLANTIC BLVD FIRE COMMENTS Fire Plans Review Fire Prevention Division
214 N. Hogan Street, Room 281
Jacksonville, Florida 32202
June 30, 2015
Par Builders
Atlantic Self-Storage
1089 Atlantic Blvd
B15-CNEW-1297 Fire Review
Please correct or provide the following to obtain plans approval. When resubmitting corrected
sheets, please provide a written narrative letter responding to our comments, along with
clouded areas on revised sheets clearly showing areas where changes or corrections have
occurred.
Provide code summary to include applicable occupancy type as defined in NFPA 101 Chapter 6
with reference of all applicable Fire Codes currently adopted. Florida is currently using the 5th
Edition Florida Fire Prevention Code, Based on NFPA 1, Fire Prevention Code, 2012 edition &
NFPA 101, Life Safety Code, 2012 edition.
Provide plot plan of proposed structure to include the following details:
* Fire department access roads.
* Adjacent structures on property.
* Property lines.
Approved fire department access roads shall be provided for every facility, building, or portion
of a building here after constructed or relocated. A fire department access road shall extend to
within 50 ft. of at least one exterior door that can be opened from the outside and that
provides access to the interior of the building. Fire department access roads shall have an
unobstructed width of not less than 20 ft. with a vertical clearance of not less than 13 ft. 6 in.
Dead-end fire department access roads in excess of 150 ft. in length shall be provided with
approved provisions for the fire apparatus to turn around.
i
Please provide proof of meeting minimum required fire flow requirements for proposed
building per NFPA 118.4 and Table 18.4.5.1.2. This can be accomplished by contacting JEA and
obtain hydrant flow test information conducted within the last 12 months and providing
report with next submission. Flow data can also be obtained by private provider as long as it is
witnessed by our office. Hydrant must be within 500' of proposed building measured via
drivable fire department access road.
Provide Fire Alarm and Detection System design criteria per Florida Administrative Code
61G15-32.008 (A-O). Engineering documents shall be sealed by the designated engineer of
record. (Please copy and paste below link for requirements.)
https://www.flruies.org/gateway/ChapterHome.asp?Chapt r=61G15-32
Provide sprinkler system design criteria per Florida Administrative Code 61G15-32.004 (A-M)
http //www coi net/Departments/Planning-and-Development/Docs/Building-Inspection-
Division/firesprinklersystemdesigncriteria010708.aspx
NFPA 101 - 7.10 Provide identification of exit locations to include tactile exit signage.