1175 ATLANTIC BLVD REVISED G.H. found dwgsDESIGN CRITERIA AND LOADS Building Code 2014 5th Edition Florida Building Code Code for Design Loads ASCE / SEI 7-10 Construction Type NEW WIND LOADING PER FBC 1603.1.4 (Cd = 1.60) ASCE 7-10, 3 SEC. GUST ULTIMATE DESIGN WIND. SPEED, Vult 120 mph NOMINAL DESIGN WIND SPEED,Vasd 93 mph EXPOSURE CATEGORY D RISK CATEGORY I ENCLOSURE CLASSIFICATION ENCLOSED INTERNAL PRESSURE COE:FF 0.18 MEAN ROOF HEIGHT 20 FT. RISE—TO—SPAN RATIO, r 0.5 (ARCHED ROOF) FEMA FLOOD INFORMATION PER FBC 1603.1.7 FIRM MAP ITEM ID 12031 CO408H EFFECTIVE DATE JUNE 3, 2013 FLOOD ZONE X — UNSHADED (OTHER AREAS) SLAB ON GRADE SEE PLAN DETAIL SCALE: NTS (1) #5 CONT CONCRETE AND FOUNDATION NOTES 1 1. CONCRETE COMPRESSIVE STRENGTH FOR F OTINGS= 3,000 PSI AT 28 PATTERN DAYS (UNO). SEALANT 2. CONCRETE COMPRESSIVE STRENGTH FOR SAB =� 3,000 PSI AT 28 DAYS Qm- (UNO). 3. ALL REINFORCING STEEL SHALL BE ASTM A615 GRADE 60 (UNO). 4. ANCHOR BOLTS SHALL A307 OR A36 THRE DED RODS 5. WELDED WIRE FABRIC SHALL BE ASTM A18 z 6. EARTH AND EARTH FILL SUPPORTING SLAB ON 'GRADE IS ASSUMED TO HAVE A MINIMUM BEARING CAPACITY OF 2, 00 psf IN ACCORDANCE WITH FRC 2004 TABLE R401.4.1, AND SHALL BE FREE OF ORGANIC MATERIAL AND COHESIVE SOILS. COMPACT THE FILL IN 12" LIFTS TO AT LEAST 95% OF MODIFIED PROCTOR MAXIMUM DRY DENSITY. IT IS THE OWNER'S OR CONTRACTOR'S RESPONSIBILITY TO CONFIRM THESE ASSUMPTIONS. 7. CONCRETE FLOOR SLABS ON GRADE SHALL BE INSTALLED OVER A MINIMUM 6 MIL POLYETHYLENE VAPOR RETARDER. WITH JOINTS LAPPED 6" AND SEALED OVER CLEAN, COMPACTED EAF TH OR FILL WITH APPROVED CHEMICAL SOIL TREATMENT FOR PREVENTIO OF SUBTERRANEAN TERMITES. 8. TO CONTROL CRACKING, CUT 1'2 SAWCUTS IN THE SLAB AS SHOWN WITHIN 12 HOURS OF CONCRETE PLACEMENT. CONTACT EOR FOR ALTERNATIVE METHODS. 9. DO NOT SCALE FOOTING DIMENSIONS AND LOCATIONS FROM THE FOUNDATION PLAN. STEEL COLUMN BY OTHERS 1/8 It WIDE x 1 it DEEP SAWCUT IN 16'-0" x 16'-0"± GRID PATTERN w/ELASTOMERIC SEALANT STEEL COLUMN BY OTHERS AND EPDXY ANCHOR BOLTS PER RBI PLAN. 1/2 it EXP. JOINT_ FILLER, SEE PLAN c' "g ON GRADE.- PLAN d-............................. x :..,�y................. :........... .. - ............... ----------- :.....:...........•••••. s» (2) #5 TOP & BOT. w/#3 TIES CONTINUOUS GRADE BEAM REINFORCING. SPACE #3 TIES @ 24" O.C. DETAIL SCALE: NTS � coy. & FTG SL� FOUNDATION KEYNOTES: A 5'-0" x 5-0" x V-6" DEEP FOOTING W/(6) #5 EACH WAY, BOTTOM 3'-0" x 3'-0" x V-6" DEEP FOOTING B W/(4) #5 EACH WAY, BOTTOM CALCULATIONS: THIS FOUNDATION DESIGN WAS BASED UPON "STRUCTURAL CALCULATIONS FOR ATLANTIC BEACH URBAN FARMS, LLC" SIGNED BY MICHAEL SPURRIER, P.E., OF ROUGH BROTHERS, INC. (RBI), AND DATED OCTOBER 31, 2014.. COL. & FTG V NON—SHRINK GROUT BELOW � STEEL BASE PLATE WITH � LEVELING NUTS AND' j CHAMFERED EDGES SL� ....-------------- FOOTING SIZE & v 3" CLR, REINFORCING, SEE TYP COL. SCHEDULE ac r i INCREASE OOTING THICKNESS AS' REQUIRED BENEATH BOLTS TOMAINTAIN MINIMUM 3" CLEARCONCRETE COVER. TYPICAL INTERIOR FOOTING DETAIL SCALE: NTS GRADE BEAM LONGITUDINAL BARST\ 36" LAP I I r1l CORNER SPLICE BARS SAMESIZE & QUANTITY ASLONGITUDINAL REINF. I BARS I I I REF. ER TO SECTIONS & DETAILS FOR REBAR SIZE & QUANTITY �� I PLAN: REINFORCING IN CONCRETE RFonn !`(1RNIFRC DETAIL CALE: NTS STEEL COLUMN BY OTHERS AND EPDXY ANCHOR BOLTS PER RBI PLAN VARIES: SEE PLAN SLAB ON GRADE. SEE PLAN (2) #5 TOP &BOT. w/#3 TIES CONTINUOUS GRADE BEAM REINFORCING. SPACE #3 TIES @ 24" O.C. DETAIL SCALE: NTS STEEL COLUMN NOT SHOWN. TRENCH DRAIN BY OTHERS SLAB ON GRADE. SEE PLAN (2) #5 BOT. --" w/#3 TIES @ 24" O.C. MIN (2) #5 TOP &BOT. w/#3 TIES CONTINUOUS GRADE BEAM REINFORCING. SPACE #3 TIES @ 24" O.C. DETA11L SCALE: NTS REVISION BP# ! S' Fo'��— DATE Z'� ! SIGNEO `fit b L GRADE BEAM REINFORCMENT NOT SHOWN. I \ SLAB ON GRADE.—N,,,,,,VARIES. SEE PLAN \ SEE PLAN FOR FOOTING SIZE AND REINFORCEMENT. DETAIL SCALE: NTS (� coy. Rr F-Tf` STEEL COLUMN � Q m= J V U' n �LQF J z Qm- �I Q �Q: z �Q� Jo 1 1 of -8#1 EL. 9.75 FT. EL. 9.75 FT. 4" THICK CONCRETE SLAB FOR BREEZEWAY 5'-0" 12'-0" 2 12'-0" EL. 9.75 FT. L 3 STEEL COLUMN, BASE PLATE AND ANCHOT BOLTS BY OTHERS. TYP L --J L --J SIDEWALK: 4" CONC. SLAB ON GRADE W/6x6—W1.4xW1.4 WWF OVER 6 MIL VAPOR BARRIER, ALL OVER TERMITE TREATED, COMPACTED CLEAN FILL. SEE 1/S-1 FOR CRACK CONTROL JOINT DETAIL. .......... s. 12'-0" EL. 9.75 FT. SJEEL COLUMN, BASE PTE AND ANCHOT BVS BY OTHERS. 4� 85'-4'0 12'-0" to 12f — 0 Efu 7 8 2 zi 0 1- 8 • 12'-0" 11 12'-0" 5 7 .......... L J L J L -J SLP EARTH FILL SLOPES TO TRENCH DRAIN, SEE ARCH TYP, 6 SLP 9 7 5 S-1 EL. 9.75 FT. oo\�� FOUND ATION PLAN 0:: j > –J SJEEL COLUMN, BASE PTE AND ANCHOT BVS BY OTHERS. 4� 85'-4'0 12'-0" to 12f — 0 Efu 7 8 2 zi 0 1- 8 • 12'-0" 11 12'-0" 5 7 .......... L J L J L -J SLP EARTH FILL SLOPES TO TRENCH DRAIN, SEE ARCH TYP, 6 SLP 9 7 5 S-1 EL. 9.75 FT. oo\�� FOUND ATION PLAN L TRENCH DRAIN BY OTHERS. EL. 8.95 FT. rh 6 14.7 Q j > L TRENCH DRAIN BY OTHERS. EL. 8.95 FT. rh 6 14.7 Q F 9.75 FT. REVISIO f3p# DAT9 SIGNED_...._.— 0 0 In C U� > L LJ i - F 9.75 FT. REVISIO f3p# DAT9 SIGNED_...._.— 0 0 In C SHEET NO.: Structural Plans JOB NO.: 15 52 SUBDIVISION: LOT NO.: FLOOR PLAN: DESIGNED: AFL REVIEWED: AFL REVISIONS DATE DETAIL 3 9/6/15 A NEW R4WA 9/6/15 SON . 5 r. X. ANDRES F.LOPERA PE # 70791 09/08/2015 U� > I I I v) Q � 0 zW LLJ < ry CDN m N > LL - D I m C) F- < LLJ U Z QUO M:D < 0 1-- -U < < < M C) > < U 0 z SHEET NO.: Structural Plans JOB NO.: 15 52 SUBDIVISION: LOT NO.: FLOOR PLAN: DESIGNED: AFL REVIEWED: AFL REVISIONS DATE DETAIL 3 9/6/15 A NEW R4WA 9/6/15 SON . 5 r. X. ANDRES F.LOPERA PE # 70791 09/08/2015