Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
1021 ATLANTIC BLVD #977 - PET STORE LIGHTING
rli`1I 41 I S, CITY OF ATLANTIC BEACH 800 SEMINOLE ROAD \j r ATLANTIC BEACH,FL 32233 (904)247-5800 BUILDING DEPARTMENT REVIEW COMMENTS Date: 3/18/16 Permit#: 16-CINT-461 Applicant: TBD Site Address: 1021 Atlantic Blvd. #977 Address: Review: 1 Phone: RE#: Email: Correction Comments: Application is disapproved for the following issues: 1. Plans, as noted, are based on the 2010 Florida Building Code (FBC). Please note that the current code is the 2014 FBC, effective 6/31/15. 2. The Florida Accessibility Code (FAC), Section 202 requires updating restrooms to current Code. Please provide two restrooms (male and female) that comply with FAC, Sections 202,213, and Chapter 6, including a 60-inch clearance for at least one water closet in each restroom. 3. Please note that requirements in the FAC are slightly different than the national standard, including toilet compartments, grab rails and grab rail heights. 4. The existing walls between tenants are 1-hour fire-resistance rated walls. Please ensure that the fire-rating is maintained and that the walls are labeled above any ceilings. Dan Arlington, CBO 904-247-5813 darlington @coab.us 1 .01101101010.- 41001.11W *WNW& -Or40,0 41410 rsLut,-1J,., City of Atlantic Beach 6s ° ,, , Building Department APPLICATION NUMBER ' ';14, i J 800 Seminole Road (To be assigned by the Building Department.) /6 611//1/ s 14/ tl - „,- Atlantic Beach, Florida 32233-5445 Phone(904)247-5826 • Fax(904)247-5845 B1 ■ °moo„ig- E-mail: building-dept @coab.us City web site: http://www.coab.us Date routed: 2 �r APPLICATION REVIEW AND TRACKING FORM / 9� 1 Property Address: Z / A/7 74'G &id D- , _ - •. -nt review required d Yes No 4 Buil•ing Applicant: Planning &Zoning Tree Administrator Project: /f al Q AT per 4::7CT l Public Works Public Utilities Public Review fee $ Dept Signature Other Agency Review or Permit Required Review or Receipt of Permit Verified By Date Florida Dept. of Environmental Protection Florida Dept. of Transportation St.Johns River Water Management District Army Corps of Engineers Division of Hotels and Restaurants Division of Alcoholic Beverages and Tobacco Other: APPLICATION STATUS Reviewing Department First Review: I 'Approved. (Circle one.) Comments: Denied. BUILDING PLANNING &ZONING Reviewed by: Date: TREE ADMIN. Second Review: I 'Approved as revised. I (Denied. PUBLIC WORKS Comments: PUBLIC UTILITIES • PUBLIC SAFETY Reviewed by: Date: FIRE SERVICES Third Review: I 'Approved as revised. I 'Denied. Comments: Reviewed by: Date: wised 07/27/10 i ,-5LA ).4, City of Atlantic Beach �S , Building Department APPLICATION NUMBER "A g (To be assigned by the Building Department.) y,-.,' Il, 'I�� 800 Seminole Road y 9 p Atlantic Beach, Florida 32233-5445 611/477- /�• ,/11�// Phone(904)247-5826 • Fax(904)247-5845 �01119� E-mail: building-dept @coab.us City web-site: http://www.coab.us Date routed: 2 ill & APPLICATION REVIEW AND TRACKING FORM � 971 XProperty Address:/D21 ,417 7j'C �/VcJ I- nt review required red Y No 1 Buil. ng Applicant: / a _el � Pl anning &Zoning Tree Administrator Project: /ki d kT 4 7" c,C-7-D e Public Works Public Utilities Public -1711122)111111111111111 V Review fee $ Dept Signature Other Agency Review or Permit Required Review or Receipt of Permit Verified By Date Florida Dept. of Environmental Protection Florida Dept. of Transportation St.Johns River Water Management District Army Corps of Engineers Division of Hotels and Restaurants Division of Alcoholic Beverages and Tobacco Other: APPLICATION STATUS Reviewing Department First Review: I 'Approved. enied. (Circle one.) Comments: t 7cr--A- n►-r\Me..ATS BUILDING PLANNING &ZONING Reviewed by: —' Date: (1O `i TREE ADMIN. Second Review: pproved as revised. I 'Denied. PUBLIC WORKS Comments: PUBLIC UTILITIES ,-v_5 T k4 i,,_,,-,-,-c,k PUBLIC SAFETY Reviewed by: .J it/Date: 8 l� FIRE SERVICES Third Review: I 'Approved as revised. I (Denied. Comments: Reviewed by: Date: :vised 07/27/10 • i IPBUILDING PERMIT APPLICATION CITY OF ATLANTIC BEACH 800 Seminole Road, Atlantic Beach, FL 32233 Office (904)247-5826 Fax (904)247-5845 Job Address: I c-- 13idyl)• 9 77 Permit Number: Legal Description Parcel# Valuation of Work$ t( Floor Proposed Work he ted/cooled t non-heated/cooled Class of Work(circle one): New Addition Alteratio Repair Move P emolitio pool/spa window/door Use of existing/proposed structure(s)(circle one): Commercia 1 Re '•- tial If an existing structure,is a fire sprinkler system insta e i . - c e one): �' No N/A Florida Product Approval# For multiple products use product approval form Describe in detail the type of work to be performed:f l �'��C ,� � 1 Property Owner Information: Name: __`` ..U' i / 1*- Address: Ilia N i H IAM I l-Alz1)c115 IM City Sta e'd,Zi Phone_ 7 E-Mail or Fax#(Optional) ,1 t f' 1 4°et' i, n Contractor Information: CONTRACTOREMAIIVADDRESS: Company Name:'lD.9, Qualifying Agent: Address: City State Zip Office Phone Job Site/Contact Number Fax# State Certification/Registration# Architect Name&Phone# Engineer's Name&Phone# Fee Simple Title Holder Name and Address Bonding Company Name and Address Mortgage Lender Name and Address Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. This permit becomes null and void f work is not commenced within six(6)months, or if construction or work is suspended or abandoned for a period of six(6)months at any time after work is commenced. I understand that separate permits must be secured for Electrical !York,Plumbing,Signs, Wells,Pools, Furnaces,Boilers,Heaters, Tanks and Air Conditioners,etc. WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT. I hereby certify that I have read and examined this application and know the same to be true and correct. All provisions of laws and ordinances governing this type of work will be complied with whether spec r•d herein or not. The granting of a permit does not presume to give authority to violate or cancel the vrovisions of any other federal,state, or local law Latin construction or e performance of construction. 41111M,..---A it Alta Y Signature of 0 _ /,1II hi Signature of Contractor 'rint Name c 1 i 114g1 4II Print Name 3efore r P.R•1 A•4..5 , his .�•4T] b iz i(�■ :' y .,., Before me •e∎• ►'• this Day of ' Note wu•lic, a of Ohio ,20 -2 t' ....,1 /. `�.,- &.._ tat Ohi luta p °y . --. Notary Public tit- 3C.,.0 My Commission Expires rY . ;`.. .. October 1, 2017 -354... Revised 01.26.10 HERSCHMAN , 25001 Emery Road,ARCHITECTS Suite 400 INC. Cleveland.OH 44128 216.223.3200 216.223.3210 10 fax www.herschmanarchitects.com Transmittal Attn: Mike Jones Date: 02/18/16 City of Atlantic Beach Re: PET SUPPLIES PLUS Building Department ATLANTIC BEACH FL 800 Seminole Road Atlantic Beach FL 32233 (904) 247-5826 Fax (904) 247-5845 From: CRAIG WRIGHT We are sending you the following by 10AM Job#: 15179.00 Copies Date Description 3 2/18/2016 Permit Set(s) (24"x36") 1 2/18/2016 Permit Application 1 2/18/2016 Miscellaneous ComCheck (For complete drawing list, refer to Drawing Index) These items are transmitted as checked below: i1i For Your Use Approved For Bid For Approval Rejected ' For Permit For Review Comment Approved As Noted Reviewed As Requested Revise& Resubmit Remarks cc: 1 IIIIII IIIII IIIII IIIII IIIII IIIII IIIV IIIII VII III 05889901 COMcheck Software Version 4.0.2.7 Nfii(41 Interior Lighting Compliance Certificate Project Information Energy Code: 2014 Florida Building Code, Energy Conservation Project Title: Pet Supplies Plus Project Type: New Construction Construction Site: Owner/Agent: Designer/Contractor: Atlantic Village Shopping Center 977 Atlantic Blvd Atlantic Beach, FL 32233 Additional Efficiency Package Reduced interior lighting power.Requirements are implicitly enforced within interior lighting allowance calculations. Allowed Interior Lighting Power A B C D Area Category Floor Area Allowed Allowed Watts (ft2) Watts/ft2 (B X C) 1-Retail 11338 1 .30 14739 Total Allowed Watts= 14739 Proposed Interior Lighting Power A B C D E Fixture ID: Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D) Fixture Fixtures Watt. 1-Retail Linear Fluorescent 1:P1/P1E/P4/P4E/S1/S1E/S5/S5E:8'Fluoerescent Strip:48"T8 32W: 4 121 109 13189 Electronic: Linear Fluorescent 2:P2/P2E:8'Fluoerescent Strip:48"T8 32W:Electronic: 2 10 55 550 Linear Fluorescent 3:P3/S2/S2E/S3/S3E/S4:4'Fluorescent Strip:48"T8 32W:Electronic: 2 13 55 715 Linear Fluorescent 4:P5:4'Fluoerescent Strip:48"T8 32W:Electronic: 1 3 28 84 Total Proposed Watts= 14538 Interior Lighting PASSES: Design 1% better than code Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application.The proposed interior lighting systems have been designed to meet the 2014 Florida Building Code, Energy Conservation requirements in COMcheck Version 4.0.2.7 and to comply with the mandatory requirements listed in the Inspection Checklist. ��-1,-._ V .yc, i•o' 7....-16 -(6 Name-Title Signature Date )11111111' Project Title: Pet Supplies Plus Report date: 02/16/16 Data filename: J:\CLIENT\Engelke Construction\15179_Pet Supplies Plus_Atlantic Beach_FL\MEP\PSP-Atlantic Page 1 of 14 Beach.cck • COMcheck Software Version 4.0.2.7 Afii rit Mechanical Compliance Certificate Project Information Energy Code: 2014 Florida Building Code, Energy Conservation Project Title: Pet Supplies Plus Location: Atlantic Beach, Florida Climate Zone: 2a Project Type: New Construction Construction Site: Owner/Agent: Designer/Contractor: Atlantic Village Shopping Center 977 Atlantic Blvd Atlantic Beach, FL 32233 Additional Efficiency Package Reduced interior lighting power.Requirements are implicitly enforced within interior lighting allowance calculations. Mechanical Systems List Quantity System Type&Description 2 RTU-1,2(Single Zone): Heating: 1 each-Central Furnace,Gas,Capacity=350 kBtu/h Proposed Efficiency=80.00%Et,Required Efficiency=80.00%Et Cooling: 1 each-Single Package DX Unit,Capacity=194 kBtu/h,Air-Cooled Condenser,Air Economizer Proposed Efficiency=10.80 EER,Required Efficiency= 10.80 EER Fan System: 6000 cfm fan--Compliance(Motor nameplate HP method):Passes Fans: FAN 1 Supply,Constant Volume,6000 CFM,3.0 motor nameplate hp 2 RTU-3,4(Single Zone): Heating: 1 each-Central Furnace,Gas,Capacity=92 kBtu/h Proposed Efficiency=80.00%AFUE,Required Efficiency=80.00%AFUE Cooling: 1 each-Single Package DX Unit,Capacity=35 kBtu/h,Air-Cooled Condenser,Air Economizer Proposed Efficiency=13.00 SEER,Required Efficiency=13.00 SEER Fan System: 1200 cfm fan--Compliance(Motor nameplate HP method):Passes Fans: FAN 2 Supply,Constant Volume, 1200 CFM,0.5 motor nameplate hp Mechanical Compliance Statement Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application.The proposed mechanical systems have been designed to meet the 2014 Florida Building Code, Energy Conservation requirements in COMcheck Version 4.0.2.7 and to comply with the mandatory requirements listed in the Inspection Checklist. / / Co.e- �9-, /l c l/( � i • N. - Ttle Signature Date °Ostil 02 16 date:Repo Project Title: Pet Supplies Plus Re p / /16 Data filename: J:\CLIENT\Engelke Construction\15179_Pet Supplies Plus_Atlantic Beach_FL\MEP\PSP-Atlantic Page 3 of 14 Beach.cck Section Footing/ Foundation Inspection Complies? Comments/Assumptions & Req.ID C403.2.4. Freeze protection and snow/ice ❑Complies Requirement will be met. 5 melting system sensors for future ❑Does Not [FO9]3 connection to controls. ❑Not Observable ❑Not Applicable Additional Comments/Assumptions: Orik • ‘1114014 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Pet Supplies Plus Report date: 02/16/16 Data filename: J:\CLIENT\Engelke Construction\15179_Pet Supplies Plus_Atlantic Beach_FL\MEP\PSP-Atlantic Page 5 of 14 Beach.cck Section Mechanical Rough-In Inspection Complies? Comments/Assumptions & Req.ID C403.2.7. Ducts, air handlers,filter boxes, ❑Complies Requirement will be met. 3 building cavities, mechanical closets ❑Does Not [ME10]2 and enclosed support platforms that Not Observable form the primary air containment passageways for air distribution ❑Not Applicable systems are sealed in accordance with the applicable criteria of this section and Table C403.2.7.2. C403.2.7. Air distribution systems are sized and ❑Complies Requirement will be met. 5 designed in accordance with ❑Does Not [ME76]2 recognized engineering standards. Refer to section details. Not Observable ❑Not Applicable C403.2.7. Air-handling units not installed in ❑Complies Exception: Requirement does not apply. 6 attics of commercial buildings. ❑Does Not [ME77]2 [Not Observable ❑Not Applicable C403.2.7. Cavities in framed spaces are not EComplies Exception: Requirement does not apply. 4 used to deliver air from or return air to ❑Does Not [ME78]2 the conditioning system unless they contain an air duct insert which is Not Observable insulated in accordance with Section ❑Not Applicable C403.2.7.1 and constructed and sealed in accordance with the requirements of Section C403.2.7.2 appropriate for the duct materials used. C403.2.7. Ductwork operating >3 in.water EComplies Exception: Requirement does not apply. 1.3 column requires air leakage testing. ❑Does Not [ME11]3 ❑Not Observable ❑Not Applicable C403.2.7. Ductwork operating >3 in.water ❑Complies Exception: Requirement does not apply. 1.3 column requires air leakage testing. ❑Does Not [ME11]3 ❑Not Observable ❑Not Applicable C403.3.1, Air economizers provided where ❑Complies Requirement will be met. C403.3.1. required, meet the requirements for ❑Does Not 1 design capacity, control signal, [ME62]1 ventilation controls, high-limit shut-off, [Not Observable integrated economizer control,and ❑Not Applicable provide a means to relieve excess outside air during operation. C403.3.1, Air economizers provided where ❑Complies Requirement will be met. C403.3.1. required, meet the requirements for ❑Does Not 1 design capacity, control signal, [ME62]1 ventilation controls, high-limit shut-off, ❑Not Observable integrated economizer control,and ❑Not Applicable provide a means to relieve excess outside air during operation. C408.2.2. Air outlets and zone terminal devices EComplies Requirement will be met. 1 have means for air balancing. ❑Does Not [ME53]3 ❑Not Observable ❑Not Applicable . C403.4.2 VAV fan motors >=7.5 hp to be driven EComplies Exception: Requirement does .• ••• . [ME66]2 by variable speed drive, have a vane- ❑Does Not axial fan with variable pitch blades, or controls to limit fan motor ['Not Observable demand. ❑Not Applicable 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Pet Supplies Plus Report date: 02/16/16 Data filename: J:\CLIENT\Engelke Construction\15179_Pet Supplies Plus_Atlantic Beach_FL\MEP\PSP-Atlantic Page 7 of 14 Beach.cck Section Rough-In Electrical Inspection Complies? Comments/Assumptions & Req.ID C405.2.2. Automatic controls to shut off all EComplies Requirement will be met. 1 building lighting installed in all ❑Does Not [EL22]2 buildings. ❑Not Observable ❑Not Applicable C405.2.1. Independent lighting controls installed EComplies Requirement will be met. 1 per approved lighting plans and all EDoes Not [EL23]2 manual controls readily accessible and visible to occupants. [Not Observable ❑Not Applicable C405.2.1. Lighting controls installed to uniformly EComplies Requirement will be met. 2 reduce the lighting load by at least EDoes Not [EL15]1 50%. ❑Not Observable ❑Not Applicable C405.2.2. Daylight zones provided with EComplies Exception: Requirement does not apply. 3 individual controls that control the ❑Does Not [EL16]2 lights independent of general area lighting. ❑Not Observable ❑Not Applicable C405.2.3 Sleeping units have at least one EComplies Exception: Requirement does not apply. [EL17]3 master switch at the main entry door EDoes Not that controls wired luminaires and switched receptacles. ['Not Observable ❑Not Applicable C405.2.2. Occupancy sensors installed in EComplies Requirement will be met. 2 required spaces. ❑Does Not [EL18]1 ❑Not Observable ❑Not Applicable C405.2.2. Primary sidelighted areas are EComplies Exception: Requirement does not apply. 3 equipped with required lighting EDoes Not [EL20]1 controls. ❑Not Observable ❑Not Applicable C405.2.2. Enclosed spaces with daylight area ❑Complies Exception: Requirement does not apply. 3 under skylights and rooftop monitors ❑Does Not [EL21]1 are equipped with required lighting controls. ['Not Observable ❑Not Applicable C405.2.3 Separate lighting control devices for ❑Complies Requirement will be met. [EL4]1 specific uses installed per approved EDoes Not lighting plans. ❑Not Observable ❑Not Applicable C405.3 Fluorescent luminaires with odd EComplies Requirement will be met. [EL19]3 numbered lamp configurations that EDoes Not are within 10 feet center to center(if recess mounted) or are within 1 foot ❑Not Observable edge to edge (if pendant or surface ❑Not Applicable mounted) shall be tandem wired. C405.4 Exit signs do not exceed 5 watts per EComplies Requirement will be met. [EL6]1 face. EDoes Not ['Not Observable ❑Not Applicable C405.2.3 Additional interior lighting power EComplies Requirement will be met. (EL8I1 allowed for special functions per the EDoes Not approved lighting plans and is ❑Not Observable automatically controlled and separated from general lighting. ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Pet Supplies Plus Report date: 02/16/16 Data filename: J:\CLIENT\Engelke Construction\15179_Pet Supplies Plus_Atlantic Beach_FL\MEP\PSP-Atlantic Page 9 of 14 Beach.cck . Section Final Inspection Complies? Comments/Assumptions & Req.ID C403.2.4. Heating and cooling to each zone is EComplies Requirement will be met. 1 controlled by a thermostat control. ❑Does Not [FI47]3 ENot Observable E Not Applicable C403.2.4. Heating and cooling to each zone is EComplies Requirement will be met. 1 controlled by a thermostat control. ❑Does Not [F147]3 ENot Observable ❑Not Applicable C403.2.4. Minimum one humidity control device EComplies Requirement will be met. 3.4 per installed ❑Does Not [F151]3 humidification/dehumidification system. Controls prevent ENot Observable simultaneous operation of ENot Applicable humidification and dehumidification equipment. C403.2.4. Minimum one humidity control device EComplies Requirement will be met. 3.4 per installed ❑Does Not [FI51]3 humidification/dehumidification system. Controls prevent ENot Observable simultaneous operation of ENot Applicable humidification and dehumidification equipment. C403.2.4. Thermostatic controls have a 5 °F EComplies Requirement will be met. 2 deadband. ❑Does Not (F138]3 ENot Observable ❑Not Applicable C403.2.4. Temperature controls have setpoint EComplies Requirement will be met. 2 overlap restrictions. ❑Does Not [FI2013 ENot Observable E Not Applicable C403.2.4. Each zone equipped with setback EComplies Requirement will be met. 3 controls using automatic time clock or ❑Does Not [F139]3 programmable control system. ENot Observable ❑Not Applicable C403.2.4. Automatic Controls: Setback to 55°F EComplies Requirement will be met. 3 (heat) and 85°F (cool); 7-day clock, 2- ❑Does Not [F140]3 hour occupant override, 10-hour backup ENot Observable ❑Not Applicable C403.2.4. Systems include optimum start EComplies Requirement will be met. 3.3 controls. ❑Does Not [F141]3 ENot Observable E Not Applicable C403.2.4. Systems include optimum start EComplies Requirement will be met. 3.3 controls. ❑Does Not [F141]3 ENot Observable ❑Not Applicable C408.2.5. Furnished HVAC as-built drawings EComplies Requirement will be met. 1 submitted within 90 days of system ❑Does Not [FI7]3 acceptance. ENot Observable 0," ❑Not Applicable C303.3, Furnished O&M manuals for HVAC ❑Complies Requirement will be met. %Oki C408.2.5. systems within 90 days of system ❑Does Not 3 acceptance. [F18]3 ENot Observable ENot Applicable 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Pet Supplies Plus Report date: 02/16/16 Data filename: J:\CLIENT\Engelke Construction\15179_Pet Supplies Plus_Atlantic Beach_FL\MEP\PSP-Atlantic Page 11 of 14 Beach.cck Section Final Inspection Complies? Comments/Assumptions & Req.ID C408.2.3. HVAC equipment has been tested to DComplies Requirement will be met. 1 ensure proper operation. ❑Does Not [FI31]1 ❑Not Observable ❑Not Applicable C408.2.3. Economizers have been tested to ❑Complies Requirement will be met. 3 ensure proper operation. EDoes Not [F132]1 ❑Not Observable ❑Not Applicable C408.3 Lighting systems have been tested to ❑Complies Requirement will be met. [Fl33]1 ensure proper calibration, adjustment, ❑Does Not programming, and operation. ❑Not Observable ❑Not Applicable C406 Efficient HVAC performance, efficient ❑Complies Requirement will be met. [FI34]1 lighting system, or on-site supply of ❑Does Not renewable energy consistent with what is shown the approved plans. ENot Observable ❑Not Applicable Additional Comments/Assumptions: 001% #4 "ow 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Pet Supplies Plus Report date: 02/16/16 Data filename: J:\CLIENT\Engelke Construction\15179_Pet Supplies Plus_Atlantic Beach_FL\MEP\PSP-Atlantic Page 13 of 14 Beach.cck Graham, Shirley To: Groff, James Subject: RE: Plan review comments for pet store 1021 Atlantic Blvd. From: Groff, James [mailto:JGroff©coj.net] Sent: Wednesday, March 23, 2016 12:08 PM To: Graham, Shirley Subject: Plan review comments for pet store 1021 Atlantic Blvd. Shirley, Here are the plans review comments. I will have them dropped off to you tomorrow. Jim • Please correct or provide the following to obtain plans approval. When resubmitting corrected sheets, please provide a written narrative letter responding to our comments and directing the plans reviewer to where the changes have taken place. Revised sheets should be clouded clearly showing areas were changes or corrections have occurred and re-inserted with the original set of drawings with old sheets removed. If this is an electronic submission please make sure that written narrative is submitted under correspondence along with a "complete set" (not just the revised sheets) of electronic documents. Failure to provide response letter will result in a return for corrections plans review submission. • Please correct reference of applicable Fire Codes to those currently adopted. Florida is currently using the Florida Fire Prevention Code Fifth Edition based off NFPA 1 and NFPA 101 2012 Edition. • Provide life safety plan to include arrangement of means of egress to include all the following if applicable: *Dead end corridors measurements *Common path of travel measurements *Total travel distance to exits *Markings of means of egress to include tactile exit signage. *Emergency lighting *Fire extinguisher placement *All rated walls *Identify all area or rooms "uses" and provide occupant load which will be determined by floor use areas divided by the applicable occupant load factor per table 7.3.1.2 of NFPA 101. • Provide Exit Door Tactile signage (Raised Characters in Braille) per NFPA 101 7.10.1.3 • Alteration to existing sprinkler and fire alarm system to accommodate for changes to structure will require separate permit and plans review. ewpf, 7741m¢1 /F'Gf< CFPE Jacksonville Fire & Rescue Department Office of Fire Plans Review 214 N Hogan Street Jacksonville, FL 32202 (904)—255-8320 Office (904)- 718-7452 Cell 1 Section Mechanical Rough-In Inspection Complies? Comments/Assumptions & Req.ID C403.2.3 HVAC equipment efficiency verified. EComplies See the Mechanical Systems list for values. [ME55]2 ❑Does Not ❑Not Observable ENot Applicable C403.2.5. Demand control ventilation provided ❑Complies Requirement will be met. 1 for spaces >500 sq.ft. and >25 ❑Does Not [ME59]1 people/1000 sq.ft. occupant density and served by systems with air side ❑Not Observable economizer,auto modulating outside ENot Applicable air damper control, or design airflow >3,000 cfm. C403.2.7. HVAC ducts and plenums insulated ❑Complies Requirement will be met. 1 and sealed according to Florida EDoes Not [ME60]2 Section C403.2.7,Table C403.2.7.1, Table C403.2.7.2. Not Observable ❑Not Applicable C403.2.7. All ducts, air handlers,filter boxes, ❑Complies Requirement will be met. 2 building cavities, mechanical closets ❑Does Not [ME79]2 and enclosed support platforms that form the primary air containment Not Observable passageways for air distribution ❑Not Applicable systems are constructed and erected in accordance with Table C403.2.7.2 and with Chapter 6 of the Florida Building Code, Mechanical. Ducts are be constructed, braced, reinforced and installed to provide structural strength and durability.All transverse joints, longitudinal seams and fitting connections are securely fastened in accordance with the applicable standards of this section. C403.2.7. Duct insulation is protected from ❑Complies Exception: Requirement does not apply. 1.2 damage but not limited to the ❑Does Not [ME80]2 following: 1. Insulation exposed to weather is suitable for outdoor Not Observable service. Cellular foam insulation is ❑Not Applicable protected or painted with a coating that is water retardant and provides shielding from solar radiation. 2. Insulation covering cooling ducts located outside the conditioned space is vapor retardant located outside the insulation, all penetrations and joints of which shall be sealed. C403.2.7. Additional insulation with vapor ❑Complies Requirement will be met. 1.3 barrier is provided where the ❑Does Not [ME81]2 minimum duct insulation requirements Not Observable of Section C403.2.7.1.1 are determined to be insufficient to ENot Applicable prevent condensation. C403.2.8. Piping Insulation exposed to weather ❑Complies Requirement will be met. 1 is protected from damage(due to sun, ❑Does Not [ME7]3 moisture,wind, etc.). ❑Not Observable ENot Applicable C403.2.8 Thermally ineffective panel surfaces of❑Complies Exception: Requirement does not apply. [ME41]3 sensible heating panels have ❑Does Not insulation >= R-3.5. ['Not Observable ENot Applicable 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Pet Supplies Plus Report date: 02/16/16 Data filename: J:\CLIENT\Engelke Construction\15179_Pet Supplies Plus_Atlantic Beach_FL\MEP\PSP-Atlantic Page 6 of 14 Beach.cck COMcheck Software Version 4.0.2.7 Inspection Checklist IrriA Energy Code: 2014 Florida Building Code, Energy Conservation Requirements: 100.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section # Plan Review Complies? Comments/Assumptions & Req.ID C103.2 Plans, specifications, and/or ❑Complies Requirement will be met. [PR2]1 calculations provide all information EDoes Not with which compliance can be determined for the mechanical ENot Observable systems and equipment and ❑Not Applicable document where exceptions to the standard are claimed. Load calculations per acceptable engineering standards and handbooks. C405.7 Plans, specifications, and/or ❑Complies Requirement will be met. [PR17]1 calculations provide all information Does Not with which compliance can be determined for the electrical systems ENot Observable and equipment and document where ENot Applicable exceptions are claimed. Provisions are made for metering individual tenant units. Feeder connectors sized in accordance with approved plans with maximum drop of 2%and branch circuits sized for maximum drop of 3%. C103.2 Plans, specifications, and/or ❑Complies Requirement will be met. [PR4]1 calculations provide all information EDoes Not with which compliance can be determined for the interior lighting ENot Observable and electrical systems and equipment ENot Applicable and document where exceptions to the standard are claimed. Information provided should include interior lighting power calculations,wattage of bulbs and ballasts,transformers and control devices. C406 Plans, specifications, and/or ❑Complies Requirement will be met. [PR9]1 calculations provide all information EDoes Not with which compliance can be determined for the additional energy (=Not Observable efficiency package options. ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Pet Supplies Plus Report date: 02/16/16 Data filename: J:\CLIENT\Engelke Construction\15179_Pet Supplies Plus_Atlantic Beach_FL\MEP\PSP-Atlantic Page 4 of 14 Beach.cck COMcheck Software Version 4.0.2.7 frIA Exterior Lighting Compliance Certificate Project Information Energy Code: 2014 Florida Building Code, Energy Conservation Project Title: Pet Supplies Plus Project Type: New Construction Exterior Lighting Zone 0(Unspecified) Construction Site: Owner/Agent: Designer/Contractor: Atlantic Village Shopping Center 977 Atlantic Blvd Atlantic Beach, FL 32233 i Allowed Exterior Lighting Power A B C D E Area/Surface Category Quantity Allowed Tradable Allowed Watts Watts/Unit Wattage (B X C) Total Tradable Watts(a)= 0 Total Allowed Watts= 0 Total Allowed Supplemental Watts(b)= 500 (a)Wattage tradeoffs are only allowed between tradable areas/surfaces. (b)A supplemental allowance equal to 500 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces. Proposed Exterior Lighting Power Exterior Lighting TBD: Exterior lighting zone not specified (see project screen) Project Title: Pet Supplies Plus Report date: 02/16/16 Data filename: J:\CLIENT\Engelke Construction\15179_Pet Supplies Plus_Atlantic Beach_FL\MEP\PSP-Atlantic Page 2 of 14 Beach.cck • Section # Mechanical Rough-In Inspection Complies? Comments/Assumptions & Req.ID C403.4.2 VAV fan motors >=7.5 hp to be driven ❑Complies Exception: Requirement does not apply. [ME66]2 by variable speed drive, have a vane- ❑Does Not axial fan with variable pitch blades, or have controls to limit fan motor [Not Observable demand. El Not Applicable C403.2.6 Exhaust air energy recovery on ❑Complies [ME57]' systems meeting Table C403.2.6 ❑Does Not ❑Not Observable ❑Not Applicable C403.2.11 Unenclosed spaces that are heated ❑Complies Exception: Requirement does not apply. [ME71]2 use only radiant heat. El Does Not ❑Not Observable ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Pet Supplies Plus Report date: 02/16/16 Data filename: J:\CLIENT\Engelke Construction\15179_Pet Supplies Plus_Atlantic Beach_FL\MEP\PSP-Atlantic Page 8 of 14 Beach.cck Section Final Inspection Complies? Comments/Assumptions & Req.ID C408.2.5. An air and/or hydronic system EComplies Requirement will be met. 3 balancing report is provided for HVAC Does Not [F143]' systems. ❑Not Observable E Not Applicable C408.2.3. HVAC control systems have been ❑Complies Requirement will be met. 2 tested to ensure proper operation, ❑Does Not [FI10]1 calibration and adjustment of controls. ❑Not Observable El Not Applicable C408.2.2 An air and/or hydronic system EComplies Requirement will be met. [FI54]3 balancing report is provided for HVAC EDoes Not systems serving zones >5,000 ft2 of conditioned area. Refer to section for Not Observable full details. ❑Not Applicable C403.2.1 HVAC systems and equipment design EComplies Requirement will be met. [F15013 loads calculated in accordance with EDoes Not ANSI/ASHRAE/ACCA Standard 183 or 183 or ACCA Manual N and shall be ENot Observable attached to the code compliance form ENot Applicable submitted to the building department when the building is permitted or, in the event the mechanical permit is obtained at a later time,the sizing calculation shall be submitted with the application for the mechanical permit. • C403.2.2 HVAC systems and equipment ❑Complies Requirement will be met. [FI27]3 capacity does not exceed calculated ❑Does Not loads. ENot Observable ❑Not Applicable C408.2.5. Furnished as-built drawings for ❑Complies Requirement will be met. 1 electric power systems within 30 days EDoes Not [F116]3 of system acceptance. ENot Observable ❑Not Applicable C303.3, Furnished O&M instructions for ❑Complies Requirement will be met. C408.2.5. systems and equipment to the EDoes Not 2 building owner or designated [F11713 representative. ENot Observable ENot Applicable C405.5.2 Interior installed lamp and fixture EComplies See the Interior Lighting fixture schedule for values. [F11811 lighting power is consistent with what ❑Does Not is shown on the approved lighting plans, demonstrating proposed watts Not Observable are less than or equal to allowed ❑Not Applicable watts. C408.2.1 Commissioning plan developed by ❑Complies Requirement will be met. [F128]1 registered design professional or Does Not approved agency. ENot Observable ❑Not Applicable C408.2.4 Preliminary commissioning report ❑Complies Requirement will be met. [F129]1 completed and certified by registered EDoes Not design professional or approved agency. [Not Observable ENot Applicable C408.2.5. Final commissioning report due to EComplies Requirement will be met. 4 building owner within 90 days of EDoes Not [F130]1 receipt of certificate of occupancy. ENot Observable ❑Not Applicable 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) Project Title: Pet Supplies Plus Report date: 02/16/16 Data filename: J:\CLIENT\Engelke Construction\15179_Pet Supplies Plus_Atlantic Beach_FL\MEP\PSP-Atlantic Page 12 of 14 Beach.cck