1021 Atlantic Blvd #1001 - HVAC 1'1(1
' \s„ CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
INSPECTION PHONE LINE 247-5814
MECHANICAL HVAC PERMIT
MUST CALL BY 4PM FOR NEXT DAY INSPECTION: 247-5814
JOB INFORMATION:
Job ID: 16-MECH-560
Job Type: MECHANICAL HVAC ONLY
Description: HVAC - 1 AC, 1 AHU, 4 TON -UNIT 1001
Estimated Value: $4,400.00
Issue Date: 3/8/2016
Expiration Date: 9/4/2016
PROPERTY ADDRESS:
Address: 1021 ATLANTIC BLVD =
RE Number: 177602-0040
PROPERTY OWNER:
Name: EQUITY ONE ATLANTIC VILLAGE,
Address: 16 NE MIAMI GARDENS DR ATTN: TREASURY DEPT
GENERAL CONTRACTOR INFORMATION:
Name: COOL CHANGE HEATING & AIR
Address: 4596 HARBOUR CT QA MANSON L. MCCLAIN, JR
Phone: - -
PERMIT INFORMATION: Sticker for overcurrent protection must be on A/C equipment prior to
inspection. Failure to comply will result in a failed inspection and reinspect fees. No
exceptions.
FEES:
Furnaces and Heating $24.00
AC and Refrigeration $32.00
State Mech DBPR Surcharge $2.00
State Mech DCA Surcharge $2.00
Trade Permit Base Fee $55.00
Total Payments: $115.00
PERMIT IS APPROVED ONLY IN ACCORDANCE WITH ALI. Cr1'Y OF ATLANTIC BEACH ORDINANCES AND THE FLORIDA
BUILDING CODES.
MECHANICAL PERMIT APPLICATION
f 0 ZCITY OF ATLANTIC BEACH
800 Seminole Rd Atlantic Beach, FL 32233
CT' Ph (904) 247-5826 Fax (904) 247-5845
JOB ADDRESS: 1001ATLANTIC BLVD, ATLANTIC BEACH, FL 32233 PERMIT#
PROJECT VALUE $ 4400 ARI# 3015811 REQUIRED
Air Handling Equipment Only X Air Handling Unit & Condenser Condenser Only
NEW AIR CONDITIONING & HEATING SYSTEM INSTALLATION
Air Conditioning: Unit Quantity I Tons Per Unit
Heat: Unit Quantity 1 BTU's Per Unit Seer Rating
Duct Systems: Total CFM REQUIRED
REPLACEMENT AIR CONDITIONING & HEATI u TEM INSTALLATION
Air Conditioning: Unit Quantity 1 Tons Per Un t 4
Heat: Unit Quantity BTU's Per • Seer Rating 13
Duct Systems: Total CFM REQUIRED
FIRE PREVENTION
Fire Sprinkler System Quantity (Requires 3 sets of plans)
Fire Standpipe Quantity (Requires 3 sets of plans)
Underground Fire Main Value (Requires 3 sets of plans)
Fire Hose Cabinets Quantity (Requires 3 sets of plans)
Commercial Hoods Quantity (Requires 3 sets of plans)
Fire Suppression Systems Quantity (Requires 3 sets of plans)
FIRE PLACES MISCELLANEOUS:
Prefabricated Fireplace Qty — Automobile Lifts
Gas Piping Outlets Boilers BTU's
Elevators/Escalators
ALL OTHER GAS PIPING Heat Exchanger
Quantity of Outlets Pumps
# Vented Wall Furnaces Refrigerator Condenser BTU's
#Water Heaters Solar Collection Systems
Tanks (gallons)
Wells
OTHER:
Permit becomes void if work does not commence within a six month period or work is suspended or abandoned for six months.I hereby certify that I have read
this application and know the same to be true and correct. All provisions of laws and ordinances governing this work will be complied with whether specified or
not. The permit does not give authority to violate the provisions of any other state or local law regulation construction or the performance of construction.
Property Owners Name Equity One Atlantic Village Inc. Phone Number
Mechanical Company Cool Change Heating& Air LLC Office Phone 904-571-1944 Fax 904-928-9261
Co. Address: 4596 Harbour North Ct City Jacksonville State FL Zip 32225
License Holder (Print): Manson L McClain State Certification/Registration # CAC 1816300
Notarized Signature of License Holder � —
Before me this day of /)%a 20
,� LEON WILLIAMS /
s. '. Commission#FF 078092 )
R° Expires January 29,20187roy
Signature of Notary Public _
"•' �'e p Fn'n Insurance 800.385.7019 .�
Right-Suite®Universal 2015 Load Summary Job: Sally Beauty Supply
-41- wrightsoft Building DDate: Mr 07,2016
Project Information
For: Sally Beauty Supply
1001 Atlantic Blvd, Atlantic Beach, FL 32233
Zone: Building COOLING LOAD
1. DESIGN CONDITIONS at Jul 1700 LDT Peak load at Jul 1700 LDT
Inside: 75 °F Outside: 93 °F TD: 18 °F
RH: 50 % MoistDift. 52.3 gr/Ib Mult: 1.0 Ins.wb 63 °F
Sensible Latent
2. SOLAR RADIATION THROUGH GLASS 1821 -
3. TRANSMISSION GAINS Sensible 10141 -
Walls: 5206 - -
Glass: 953 - -
Doors: 109 - -
Partitions: 0 - -
Floors: 0 - -
Ceilings: 3873 - -
4. INTERNAL HEAT GAIN Sensible Latent 16954 4000
Occupants: 5000 4000 - -
Lights: 8610 - - -
Motors: 0 - - -
Appliances: 3344 0 - -
5. INFILTRATION: Outside air cfm: 10 196 355
6. SUBTOTAL: Space load Sensible Latent 29111 4355
Envelope 29111 4355 - -
Less external 0 - - -
Redistribution 0 0 - -
7. SUPPLY DUCT 1456 -
8. SUBTOTAL: Space load +supply duct 30567 -
Actual cfm: 1600 at supply TD: 20 - -
9. VENTILATION: Make-up air cfm: 184 3599 6536
10. RETURN AIR LOAD: Lighting + plenum(net) 0 -
11. RETURN DUCT 873 -
12. TOTAL LOADS ON EQUIPMENT 35039 10892
HEATING LOAD
13. DESIGN CONDITIONS Mutt: 1.0
Inside: 70 °F Outside: 32 °F TD: 38 °F
14. TRANSMISSION LOSSES 15077
Walls: 6503 -
Glass: 2326 -
Doors: 265 -
Partitions: 0 -
Floors: 4126 -
Ceilings: 1857 -
15. INFILTRATION: Outside air cfm: 90 3778
16. SUBTOTAL: Space load 18855
Envelope 18855 -
Less external 0 -
Less transfer 0 -
Redistribution 0 -
17. SUPPLY DUCT: 943
18. VENTILATION: Make-up air cfm: 184 7723
19. HUMIDIFICATION 4889
Piping 0
20. RETURN DUCT 566
21. TOTAL HEATING LOAD ON EQUIPMENT 32976
4 wrightsoft Rig ht-Su rte®Universal 2015 15.0.25 RSU11033 2016-Mar-071P0
age1
9
...\DocumentstCool ChangetSallys Beauty Supply.rup Calc=CLTD Front Door faces: E
I
,aj%LDjjI1 �
yA,`1
'-). 1P. 'sf NOTICE
OF
� _....
,±;< ADDITIONS or CORRECTIONS
�FA< < f,E4C DO NOT REMOVE
JOB ADDRESS DATE
(0LI krt._,,.► c c SrI OOI 31tct► G
THIS JOB HAS NOT BEEN COMPLETED
The following additions or corrections shall be made
before the job will be accepted.
k-k V& L CA 1,4..-.r.ov
E,c, 5-rc.4 (.,-- E cQ.)%r► 4...1.L-r-- i s
D1/4_3 C..-r-ti--o 4.-Ii- t-e.- tjN.-r \.-C.-T--4
60-(e.--TZ$cD D.J r' .
4 ..........e ` 04 4 rtt C.....hTr C7 o4 ?A J S T-
- Ai'c--( \/ri fbC j 5-rdel›.-riv4
��COM 4E-.WD ?. -C.2'►.t % CX2.4.
\-1.-ink 6 5 kl>AV _ l F) ....5--r--
14
...3-r-t-&e r `-e.e..-0.-.)ev....<'O
. (.As-rt.L.t_. —t L- b i Sol. .."
- C'r.( (ZR.5 S%.J P?cY 735
- Z4 ,I. kgv("EL Pc)oF Sv'ZtFike-C--
/
- ,r�-g- D`s C---r" `--615
t 5 �..(c•c1> loDE- -- 3O 7.,-f-
.
Sc
241 - -5- 13
x$55.00 REINSPECT FEE LI NO CHARGE
Its is unlawful for any Carpenter, Contractor, Builer or other
persons, to cover to cause to be covered, any part of the
work with flooring, lath, earth or other material, until the
proper inspector has had ample time to approve the
installation.
After additions or corrections have f BLDG
been made contact the Building Dept. ELEC
at 247-5814 for an inspection. Office MECH (-----
hours
hours are Monday through Friday PLMG
8:00 a.m.to 5:00 p.m.