No preview available
 /
     
535 Atlantic Boulevard Gate Station Fire Review comments i1 p7� r City of Atlantic Beach APPLICATION NUMBER n Building Department - - (To be assigned by the Building Depanment.) n 800 Seminole Road / Atlantic Beach, Florida 32233-5445 Phone(904)247-5826 Fax(904)247-5845 -rif ur' E-mail: building-deptCwab.us Date routed: City web-site: http://www.Mab.us APPLICATION REVIEW AND TRACKING FORM Property Address: FATL.p r;017 ment review required Yes No Applicant: ! IaTC PETRQ r=r &Zoning (� mi ra or Project: �l�Y(; \ = 20L.CVorks tilitiesafety Review fee $ _ Dept Signature Other Agency Review or Permit Required Review or Receipt Date of Permit Verified B Florida Dept.of Environmental Protection Florida Dept.of Transportation St.Johns River Water Management District Army Corps of Engineers Division of Hotels and Restaurants Division of Alcoholic Beverages and Tobacco Other. APPLICATION STATUS Reviewing Department First Review: ❑Approved. Denied. (Circle one.) Comments: - BUILDING AFF AJ�'a�av PLANNING &ZONING Reviewed by: / Alac Date: 814/ TREE ADMIN. Second Review: ❑Approved as revised. Denied. PUBLIC WORKS Comments: PUBLIC UTILITIES PUBLIC SAFETY Reviewed by: Date: FIRE SERVICES Third Review: ❑Approved as revised. ❑Denied. Comments: Reviewed by: Date: tevised 05H4/09 Fire Plans Review Fire Prevention Division 214 N. Hogan Street, Room 281 Jacksonville, Florida 32202 August 30, 2016 Gate Petroleum 535 Atlantic Blvd 16-CNEW-1781 Fire Review Please correct or provide the following to obtain plans approval. When resubmitting corrected sheets, please provide a written narrative letter responding to our comments and directing the plans reviewer to where the changes have taken place. Revised sheets should be clouded clearly showing areas were changes or corrections have occurred and re-inserted with the original set of drawings with old sheets removed. If this is an electronic submission please make sure that written narrative is submitted under correspondence along with a "complete set' (not just the revised sheets) of electronic documents. Failure to provide response letter will result in a return for corrections plans review submission. 1. Exit tactile signs required at all exits marked with an exit sign 2. Please Provide Fire Flow Calculations Performed Within The Last Year For the Nearest Fire Hydrant Located Within 500' Of The Most Remote Point Of The Proposed Building In Accordance With NFPA 1, Chapter 18 "Fire Flow Requirements For Buildings" (2012 5th Edition) NFPA 1, 18.4.1.1• The procedure determining fire flow requirements for buildings hereafter constructed shall be in accordance with Section 18.4.NFPA 1, 18.4.5.2 Buildings Other Than One- and Two-Family Dwellings.The minimum fire flow and flow duration for buildings other than one- and two-family dwellings shall be as specified in Table 18.4.5.1.2. Publicly Owned Fire Hydrant Flow Calculations May Be Obtained by Contacting Scott Stevens (stevgs@jea.com). Private Hydrant Calculations May Be Obtained Through The Services Of A Fire Protection Contractor Witnessed By The Local AHJ. 1 3.Please indicate on drawing the location of Fire Hydrant within 500' of the most remote point of the proposed building 4.Motor Fuel Dispensing NFPA 30A: Provide classification of liquids to be dispensed per NFPA 30A Provide storage, piping, dispensing, electrical, vapor processing, recovery details per NFPA 30A Provide Life safety plan to include the following: • Provide Fire Code Summary and analysis to include all the following information if applicable: Reference 2014 Florida fire Prevention Code 5th Edition, NFPA 30 2012, & NFPA 30A 2012. • Emergency Electrical Disconnect locations. Must be at least 20' and no further than 30' from the fuel dispensing devices. • Fire Extinguisher locations per NFPA 10. Extinguishers shall be provided according to the Extra (High) hazard requirements for class B hazards, except that maximum travel distance to an 80B: C extinguisher shall be permitted to be (100ft). • Warning signage details and locations incorporating the flowing or equivalent wording: WARNING: It is unlawful and dangerous to dispense gasoline into unapproved containers. No smoking. Stop motor. No filling of portable containers in or on a motor vehicle. Place container on ground before filling. Discharge your static electricity before fueling by touching a Metal surface away from nozzle. Do not re-enter your vehicle while gasoline is pumping. If a fire starts, do not remove nozzle—back away immediately. Do not allow individuals under licensed age to use the pump. 2 • Operating signage details and locations for unattended self-service motor fuel dispensing Facilities details and locations incorporating the flowing or equivalent wording: Emergency Instructions: In case of fire or spill: (1) Use emergency stop button. (2) Report accident by calling (specify local fire number). Report location. 3