1021 Atlantic Blvd COMM18-0010 CITY OF ATLANTIC BEACH
800 Seminole Road
Atlantic Beach,Florida 32233
REVISION REQUEST/CORRECTIONS TO PLAN REVIEW COMMENTS
Date Z( Ing Revision to Issued Permit V-�Currections to Comments_ Permit
Project Address 102—
Contractor/
02—Contractor/Contact Na tte c A ` �"j
Phon C4 4-- b�-3 Email ?Q Me y%- � Cow
Description of Proposed Revision/Coometions: Permit Fee Due$
&C— Dr 2 !9 ` eW AA A
Additional Increase in Building Value$ L��C.220 Additional S.F. 8
y si g below, he Revision is inclusive of the proposed changes.
(printed verve)
o Co to. ent(Comtracto if increase m valuation) Date'
(Office Use Only)
Approved Denied—X— Not Applicable to Department
Revision/Plan Review Comments
De artment Review Required: �y[A
Pl11
anni f' Iy"viewed By
Planning &Zoning !/
Tree Administrator
Public Works
Public Utilities Date
P0*65fiaty,
ire Services
Dipierri Miguel
08/24/2018 review not approved
Returned for Corrections:
The plans submitted for review have been returned for corrections. Please correct or provide the proceeding requested
information to obtain plans approval.When resubmitting corrected sheets, please provide a written narrative letter
responding to our comments and directing the plans reviewer to the sheets the changes have taken place. Failure to
provide response letter'W ILL" result in an immediate return for corrections plans review submission. Revised sheets
should be clouded clearly showing areas were changes or corrections have occurred and re-inserted with the original set
of drawings with old sheets removed. Unbound plans will not be reviewed. If this is an electronic submission please make
sure that written narrative is submitted under correspondence along with a"complete set" (not just the revised sheets) of
electronic documents.
Life Safety Plan:
The City of Jacksonville's Fire Marshal's Office requires the submittal of a life safety plan for building permits for all new
construction and existing building alterations in order to ascertain ii occupancy is currently code compliant and to assist
fire inspector in performing Life Safety Inspections. Please provide a Life Safety Plan to include all the following
information on one page. If Life Safety Plan was submitted and you are receiving this comment, it means that all of the
required info listed below was not included in your original submittal. It is understood that all listed items may not apply in
your situation.
Provide required Fire Code specific code summary: (Florida is currently using the"2015 Florida Fire Prevention Code
Sixth Edition" effective Dec 31 , 2017 based off NFPA 1 and NFPA 101 2015 Edition.)
•Occupancy type sub-classification (per NFPA 101 6.1)
•Building construction type (per NFPA 101 8.2.1)
•Gross square footage
•Number of stories
•Building height
•Interior wall and ceiling finish requirements(per NFPA 101 10.2
•Allowable dead end limits
•Allowable Common path of travel limits
•Allowable travel distance limits
•Any fire protection systems (sprinkler,fire alarm, etc.)
•Statement from architect or engineers that their design to the best of their knowledge complies with the 5'" Edition
Florida Fire Prevention Code(FFPC).
Required measurements: (Worst case only need be shown.)
•Dead end corridors measurements.
•Common path of travel measurements.
•Total travel distance to exits.
Required separation:
•All rated walls/adjacent tenant occupancy type, required occupancy separation
Required Lock Latch details:
•Lock/Latch details: Panic Hardware,Thumb tum lock, Key Lock with indicator and required
Signage.
Required Occupant Load Calculation:
•Calculated occupant load using table 7.3.1.2 of NFPA 101 2012 edition.
1
Required Egress Inches:
•Egress inches for means of egress components(doors, stairs, etc.)
Required Number of Exits:
•All required exits shall terminate at a"public way'. Access to the public way shall be via a stable,firm, and slip resistant
conveyance such as a concrete sidewalk with a min. 5k6landing and 44"walkway.
Required Exit Separation Distance:
Separation of exits using the one half (non-sprinkled) or one third (sprinkled)the diagonal distance rule.
Required Electrical StoplDisconnect Details:
•Any required Emergency stops or Shunt trips.
•Main Electrical disconnects access/location.
Required markings of means of egress:
•Exit signs to include tactile exits signage.
Required Emergency lighting:
•Show emergency illumination.
MIGUEL Di PIERRI
Fire Safety Inspector/CDN Reviewer
JFRD PREVENTION OFFICE
515 N.Julia St.,Jacksonville,Florida 32202
Oflice: 904-255-8561 cell: 904-237-7212—Email: DIPIERRIC&COJ.NET
2