323 AHERN ST RES17-0276 ENERGY EFF CODE 4 3Z3 RF - --
Ras - OZ7
FORM R405-2017
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: 1931 Left ! A7 Builder Name:
Street: Permit Office:
City,State,Zip: Atlantic Beach,FL, Permit Number:
Owner: Jurisdiction:
Design Location: FL,Jacksonville County:: Duval(Florida Climate Zone 2)
1. New construction or existing New(From Plans) 9. Wall Types(2962.3 sqft.) Insulation Area
a. Frame-Wood,Exterior R=19.0 2710.30 ft2
2. Single family or multiple family Single-family b.Frame-Wood,Adjacent R=19.0 252.00 ft2
3. Number of units,if multiple family 1 c.N/A R= ft2
4. Number of Bedrooms 3 d. N/A R= ft2
10.Ceiling Types (946.0 sqft.) Insulation Area
5. Is this a worst case? No a.Under Attic(Vented) R=19.0 946.00 ft2
6. Conditioned floor area above grade(ft2) 1931 b. N/A R= ft2
c. N/A R= ft2
Conditioned floor area below grade(ft2) 0 11.Ducts R ft2
7. Windows(267.5 sqft.) Description Area a.Sup:Attic, Ret:Attic,AH:Main 6 296
a. U-Factor: Dbl,U=0.36 267.51 ft2
SHGC: SHGC=0.31 12.Cooling systems kBtu/hr Efficiency
b. U-Factor: N/A ft2 a.Central Unit 47.5 SEER:15.00
SHGC:
c. U-Factor: N/A ft2
SHGC: 13. Heating systems kBtu/hr Efficiency
d. U-Factor: N/A ft2 a. Electric Heat Pump 47.5 HSPF:8.50
SHGC:
Area Weighted Average Overhang Depth: 3.185 ft. 14.Hot water systems
Area Weighted Average SHGC: 0.310 Cap: gallons 55
a. Electric
8. Floor Types (966.0 sqft.) Insulation Area EF:0.950
a.Floor over Garage R=19.0 596.00 ft2 b. Conservation features
b.Slab-On-Grade Edge Insulation R=0.0 266.00 ft2 None
c.other(see details) R= 104.00 ft2 15.Credits Pstat
Total Proposed Modified Loads: 57.56
Glass/Floor Area: 0.139 PASS
Total Baseline Loads: 65.72
I hereby certify that the plans and specifications covered by Review of the plans and ..-.'"4,tp[E sTar,'"•:
this calculation are in compliance with the Florida Energy specifications covered by this „�1�'' ,, ;_ ;:.•4�,
Code. calculation indicates compliance l+4'1,,,,�O'`' • _ .., .rt+�-
PREPARED BY:
with the Florida Energy Code.
Before construction is completed :neo, ' - e,
P_- --- - ---- -- -e. _ Ve--- -- -- ' ��
DATE: --___ 3-28-2018 this building will be inspected for : cd:.c., Loc, , r 2•
compliance with Section 553.908 * • p .1i *
I hereby certify that this buildi• Florida Statutes.
as gned, is . ompli ce C •........ - ".A.:
with the Florida Energy C• oD ws '
OWNER/AGENT: _ , BUILDING OFFICIAL: -
DATE: V/4/ DATE: 640 f -
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.3.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402. 1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 7.00 ACH50(R402.4.1.2). I(%/
^
eo
3/28/2018 2:39 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Aja e 1 of 5
l
FORM R405-2017
PROJECT
Title: 1931 Left Bedrooms: 3 Address Type: Lot Information
Building Type: User Conditioned Area: 1931 Lot# 1A
Owner Name: Total Stories: 3 Block/Subdivision: Ahem Townhomes
#of Units: 1 Worst Case: No PlatBook:
Builder Name: Rotate Angle: 0 Street:
Permit Office: Cross Ventilation: No County: Duval
Jurisdiction: Whole House Fan: No City,State,Zip: Atlantic Beach,
Family Type: Single-family FL,
New/Existing: New(From Plans)
Comment:
CLIMATE
/ Design Temp Int Design Temp Heating Design Daily Temp
V Design Location TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,Jacksonville FL_JACKSONVILLE_INT 32 93 70 75 1281 49 Medium
BLOCKS
Number Name Area Volume
1 Blockl 1931 17379
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated
1 Main 1931 17379 Yes 4 3 1 Yes Yes Yes
FLOORS
V # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
1 Floor over Garage Main ____ ____ 596 ft19 0 0 1
2 Slab-On-Grade Edge lnsulatio Main 74 ft 0 266 ft2 ____ 0 0 1
3 Raised Floor Main ____ ____ 104 ft2 19 0 0 1
ROOF
Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
1 Flat Gravel 949 ft2 40 ft' Medium 0.65 N 0.9 No 0 4.8
/ ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 No attic Vented 300 946 ft2 N N
3/28/2018 2:39 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 2 of 5
I .
FORM R405-2017
CEILING
V # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type -_
1 Under Attic(Vented) Main 19 Blown 946 ft2 0.1 Wood
WALLS
__#__-Omt -moo- Wall��pe_
AdCavity Width Height Sheathing Framing Solar Below
Space RNalue------Ft-In--Ft In ---Area--- R-Value--Fraction_ _Absor.-Grade
1
_ -- --
_ 1 E Exterior Frame-Wood Main 19 39 11 10 0 399.2 ft2 0 0.25 0.5 0
_ 2 E Exterior Frame-Wood Main 19 52 1 9 0 469.0 ft2 0 0.25 0.5 0
_ 3 S Exterior Frame-Wood Main 19 12 1 10 0 120.8 ft2 0 0.25 0.5 0
_ 4 S Exterior Frame-Wood Main 19 94 9 9 0 853.0 ft2 0 0.25 0.5 0
_ 5 W Exterior Frame-Wood Main 19 19 10 10 0 198.3 ft2 0 0.25 0.5 0
_ 6 W Exterior Frame-Wood Main 19 74 5 9 0 670.0 ft2 0 0.25 0.5 0
7 - Garage Frame-Wood Main 19 28 0 9 0 252.0 ft2 0 0.25 0.01 0
DOORS
V # Ornt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 E Insulated Main None .39 3 8 24 ft2
2 - Insulated Main None .39 2 10 6 10 19.4 ft2
WINDOWS
Orientation shown is the entered,Proposed orientation.
Wall Overhang
# Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening
1 e 1 Vinyl Low-E Double Yes 0.36 0.31 N 16.5 ft2 4 ft 0 in 2 ft 0 in Drapes/blinds None
2 e 1 Vinyl Low-E Double Yes 0.36 0.31 N 4.0 ft2 0 ft 0 in 0 ft 0 in Drapes/blinds None
3 e 1 Vinyl Low-E Double Yes 0.36 0.31 N 54.0 ft2 2 ft 0 in 2 ft 0 in Drapes/blinds None
4 e 2 Vinyl Low-E Double Yes 0.36 0.31 N 7.0 ft2 4 ft 0 in 2 ft 0 in Drapes/blinds None
5 e 2 Vinyl Low-E Double Yes 0.36 0.31 N 4.0 ft2 4 ft 0 in 2 ft 0 in Drapes/blinds None
-
6 e 2 Vinyl Low-E Double Yes 0.36 0.31 N 10.0 ft2 0 ft 0 in 0 ft 0 in Drapes/blinds None
7 s 3 Vinyl Low-E Double Yes 0.36 0.31 N 6.0 ft2 0 ft 0 in 0 ft 0 in Drapes/blinds None
8 s 4 Vinyl Low-E Double Yes 0.36 0.31 N 12.0 ft2 0 ft 0 in 0 ft 0 in Drapes/blinds None
9 s 4 Vinyl Low-E Double Yes 0.36 0.31 N 30.0 ft2 0 ft 0 in 0 ft 0 in Drapes/blinds None
10 s 4 Vinyl Low-E Double Yes 0.36 0.31 N 12.0 ft2 0 ft 0 in 0 ft 0 in Drapes/blinds None
-
11 w 5 Vinyl Low-E Double Yes 0.36 0.31 N 30.0 fr 2 ft 0 in 2 ft 0 in Drapes/blinds None
-
12 W 6 Vinyl Low-E Double Yes 0.36 0.31 N 82.0 ft2 7 ft 0 in 2 ft 0 in Drapes/blinds None
-
GARAGE
V _ # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation ---
1 596 ft2 596 ft2 72 ft 9 ft 1
3/28/2018 2:39 PM EnergyGauge8 USA-FlaRes2017 Section R405.4.1 Compliant Software Page 3 of 5
FORM R405-2017
INFILTRATION
# Scope Method SLA CFM 50 ELA EqLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .0004 2027.6 111.31 209.33 .4286 7
HEATING SYSTEM
V # System Type _ Subtype- _ ___ Efficiency Capacity Block Ducts
1 Electric Heat Pump/ Split HSPF:8.5 47.5 kBtu/hr 1 sys#1
COOLING SYSTEM
# System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit/ Split SEER: 15 47.5 kBtu/hr cfm 0.7 1 sys#1
HOT WATER SYSTEM
V # System Type SubType Location EF Cap Use SetPnt Conservation
1 Electric None Garage 0.95 55 gal 60.9 gal 120 deg None
SOLAR HOT WATER SYSTEM
VFSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ft2
DUCTS
—Supply ---- --Return
Air CFM 25 CFM25 HVAC#
V # Location R-Value Area Location Area Leakage Type Handler TOT OUT ON RLF Heat Cool
1 Attic 6 296 ft2 Attic 90 ft2 Default Leakage Main (Default) (Default) 1 1
TEMPERATURES
Programable Thermostat:Y Ceiling Fans:
Cooling Jan H Feb Mar l A r Ma X Jun X Jul X Au X Se Oct Nov Dec
Heatingg X�Jan Feb X Mar ]Arl Mal Junl Jull Aul Set ONov XDecVentin Jan Feb X Mar X Apr [ May [ Jun [ Jul [ Aug [ SepX Oct [X Nov [ Dec
3/28/2018 2:39 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 4 of 5
ti
FORM R405-2017
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78
78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
3/28/2018 2:39 PM EnergyGauge®USA-FlaRes2017 Section R405.4.1 Compliant Software Page 5 of 5
FORM R405-2017
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 88
The lower the EnergyPerformance Index, the more efficient the home.
, Atlantic Beach, FL,
1. New construction or existing New(From Plans) 9. Wall Types Insulation Area
2. Single family or multiple family Single-family a. Frame-Wood,Exterior R=19.0 2710.30 ft'
3. Number of units,if multiple family 1 b. Frame-Wood,Adjacent R=19.0 252.00 ft2
c.N/A R= ft2
4. Number of Bedrooms 3 d.N/A R= ft2
5. Is this a worst case? No 10.Ceiling Types Insulation Area
a. Under Attic(Vented) R=19.0 946.00 ft'
6. Conditioned floor area(ft') 1931 b.N/A R= ft2
7. Windows** Description Area c.N/A R= ft2
a. U-Factor: Dbl,U=0.36 267.51 ft' 11. Ducts R ft'
SHGC: SHGC=0.31 a.Sup:Attic,Ret:Attic,AH:Main 6 296
b. U-Factor: N/A ft2
SHGC: 12.Cooling systems kBtu/hr Efficiency
c. U-Factor: N/A ft' a.Central Unit 47.5 SEER:15.00
SHGC:
d. U-Factor: N/A ft'
SHGC: 13.Heating systems kBtu/hr Efficiency
Area Weighted Average Overhang Depth: 3.185 ft. a. Electric Heat Pump 47.5 HSPF:8.50
Area Weighted Average SHGC: 0.310
8. Floor Types Insulation Area 14. Hot water systems
a.Floor over Garage R=19.0 596.00 ft2 a. Electric Cap:55 gallons
b.Slab-On-Grade Edge Insulation R=0.0 266.00 ft2 EF:0.95
c.other(see details) R= 104.00 ft' b. Conservation features
None
15.Credits Pstat
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded) O �gt:sf Tho
in this home before final in :-, ion. Otherwise, a new EPL Display Card will be completed :''„.7 ' Ifse of.
based on installed Code o ••liant features. - '" % --'=�.°
Builder Signature: Date: 5-1---/-! � � � :y
Address of New Home: T.Z3 ,,e/y,02, fT ' City/FL Z ,X(9,/iL�r-L04,7U ••. r*' N.c,.S .
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage(EEM) incentives if you obtain a Florida EnergyGauge Rating. Email EnergyGauge tech support at
techsupport@energygauge.com or see the EnergyGauge web site at energygauge.com for information and a list of
certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building
Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
3/28/2018 2:39 PM EnergyGauge®USA-FlaRes2017 -Section R405.4.1 Compliant Software Page 1 of 1
A
2017-AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: 1931 Left Builder Name:
Street: Permit Office:
City,State,Zip: Atlantic Beach, FL, Permit Number:
Owner: Jurisdiction:
Design Location: FL,Jacksonville
COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA
General A continuous air barrier shall be installed in the building envelope. Air-permeable insulation shall
The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material.
requirements Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit
Ceiling/attic the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings,drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be shalt be insulated by completely filling the cavity with
sealed. a material having a thermal resistance of R-3 per inch
Knee walls shall be sealed. minimum.
Exterior thermal envelope insulation for framed walls
shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows,skylights The space between window/door jambs and framing,and
and doors skylights and framing shall be sealed.
Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated.
Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to
(including insulation. maintain permanent contact with the underside of
above-garage subfloor decking,or floor framing cavity insulation
and cantilevered shall be permitted to be in contact with the top side
floors) of sheathing,or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation,insulation
a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls.
Shafts,penetrations Duct shafts,utility penetrations,and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit,or narrow
Narrow cavities cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spaces.
Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building
shall be sealed to the drywall. thermal envelope shall be air tight and IC rated.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls,or insulation that on
installation readily conforms to available space shall
extend behind oOpg and wiring.
Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall
on exterior wall tubs shall separate them from the showers and tubs. be insulated.
Electrical/phone box or The air barrier shall be installed behind electrical or communication
exterior walls boxes or air-sealed boxes shall be installed.
HVAC register boots HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub-floor or drywall.
Concealed When required to be sealed,concealed fire sprinklers shall only be
sprinklers sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cover plates and walls or ceilings
a.In addition,inspection of log walls shall be in accordance with the provisions of ICC-400.
3/28/2018 2:39 PM EnergyGauge®USA-FlaRes2017 FBC 6th Edition(2017)Compliant Software Page 1 of 1
FORM R405-2017 Envelope Leakage Test Report Performance
FLORIDA ENERGY EFFICIENCY CODE
FOR BUILDING CONSTRUCTION
Envelope Leakage Test Report
Performance Method
Project Name: 1931 Left Builder Name:
Street: Permit Office:
City,State,Zip: Atlantic Beach, FL, Permit Number:
Design Location: FL,Jacksonville Jurisdiction:
Cond.Floor Area:: 1931 sq.ft. Cond.Volume: 17379 cu ft.
Envelope Leakage Test Results Leakage Characteristics
Regression Data:
C: n: R:
Single or Multi Point Test Data Required ACH(50)from
HOUSE PRESSURE FLOW: FORM R405-2017 :
1 Pa cfm
2 Pa cfm Tested ACH(50) * :
3 Pa cfm
*Tested leakage must be less than or equal to the
4 Pa cfm required ACH(50)shown on Form R405-2017 for
5 Pa cfm this building. If the tested ACH(50)is less than 3
the building must have a mechanical ventilation
6 Pa cfm system.
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes per hour
in Climate Zones 1 and 2...Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Testing shall be conducted by
either individuals as defined in Section 553.993(5)or(7),Florida Statutes or individuals licensed as set forth in Section 489.105(3)(f),(g),or(i)or an
approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing
shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other
infiltration control measures;
2.Dampers including exhaust,intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration
control measures;
3. Interior doors,if installed at the time of the test,shall be open;
4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed;
5.Heating and cooling systems,if installed at the time of the test,shall be turned off;and
6.Supply and return registers,if installed at the time of the test,shall be fully open.
I hereby certify that the above envelope leakage Testing shall be conducted by either ;:•OtVIE srgj•;••.
- O
performance results demonstrate compliance individuals as defined in Section
I 553.993(5)or(7), Florida Statutes or • 7. i.,, ;',;,`
with Florida Energy Code requirements in � � -s-r s.
individuals licensed as set forth in ti:41,4_4%
accordance with Section R402.4.1.2. _
Section 489.105(3)(f), (g), or(i)or an • °—'
,q, •
approved third party.A written report of `: .• I, -
the results of the test shall be signed : *'t <t
SIGNATURE: _ by the third party conducting the test
•
and provided to the code official.
. Cpp�'Lqi •,.
PRINTED NAME:
—
BUILDING OFFICIAL:
DATE:
DATE:
3/28/2018 2:39 PM EnergyGauge®USA-FlaRes2017 -Section R405.4.1 Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 6th Edition (2017)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: Permit Number:
Atlantic Beach , FL,
MANDATORY REQUIREMENTS See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level(EPL)display card(Mandatory).The building official shall require that an energy performance level(EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy.Florida law
(Section 553.9085,Florida Statutes)requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings.The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit.The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building.A copy of the EPL display card can be found in Appendix RD.
R402.4 Air leakage(Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2.The sealing
methods between dissimilar materials shall allow for differential expansion and contraction.
R402.4.1.1 InstallationThe components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1,as applicable to the method of construction.Where required
by the code official,an approved third party shall inspect all components and verify compliance.
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2,and three air changes per hour in Climate Zones 3 through 8.Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g.(50 pascals).Testing shall be conducted by either
individuals as defined in Section 553.993(5)or(7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(0,(g)or(i)or
an approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions,alterations,renovations,or repairs,of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended
weatherstripping or other infiltration control measures.
2. Dampers including exhaust, intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond
intended infiltration control measures.
3. Interior doors,if installed at the time of the test,shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems,if installed at the time of the test,shall be turned off.
6. Supply and return registers,if installed at the time of the test,shall be fully open.
R402.4.2 Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers or doors,and outdoor combustion air.Where
using tight-fitting doors on factory-built fireplaces listed and labeled in accordance with UL 127,the doors shall be tested and listed for the
fireplace.Where using tight-fitting doors on masonry fireplaces,the doors shall be listed and labeled in accordance with UL 907.
R402.4.3 Fenestration air IeakageNindows,skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per
square foot(1.5 L/s/m2),and swinging doors no more than 0.5 cfm per square foot(2.6 L/s/m2),when tested according to NFRC 400 or
AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited,independent laboratory and listed and labeled by the manufacturer.
Exception: Site-built windows,skylights and doors.
3/28/2018 2:39 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 1 of 5
MANDATORY REQUIREMENTS - (Continued)
R402.4.4 Rooms containing fuel-burning appliances. In Climate Zones 3 through 8,where open combustion air ducts provide combustion air to
open combustion fuel burning appliances,the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room,isolated from inside the thermal envelope.Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2,where the walls,floors and ceilings shall meet not less than the basement wall R-value requirement.The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403.The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code,Residential.
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not
more than 2.0 cfm(0.944 Us)when tested in accordance with ASTM E283 at a 1.57 psf(75 Pa)pressure differential.All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
R403.1 Controls. SECTION R403 SYSTEMS
R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls
that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load.
R403.3.2 Sealing(Mandatory) All ducts,air handlers,filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers,shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5)or
(7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i),Florida Statutes,to be"substantially leak free"in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
R403.3.3 Duct testing(Mandatory).Ducts shall be pressure tested to determine air leakage by one of the following methods:
1, Rough-in test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the system,including the
manufacturer's air handler enclosure if installed at the time of the test.All registers shall be taped or otherwise sealed during the test.
2. Postconstruction test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the
entire system,including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the
test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
R403.3.5 Building cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums.
R403.4 Mechanical system piping insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C)
or below 55°F(13°C)shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight,moisture,equipment maintenance and wind,and shall provide shielding from solar radiation that can cause
degradation of the material.Adhesive tape shall not be permitted.
R403.5.1 Heated water circulation and temperature maintenance systems(Mandatory)Heated water circulation systems shall be in
accordance with Section R403.5.1.1.Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls,temperature sensors and pumps shall be accessible.Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return
pipe shall be a dedicated return pipe or a cold water supply pipe.Gravity and thermosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the
occupancy.The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
R403.5.1.2 Heat trace systems.Electric heat trace systems shall comply with IEEE 515.1 or UL 515.Controls for such systems
shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water is used in the occupancy.
3/28/2018 2:39 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017)Complian Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.5.5 Heat traps(Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets.External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 Y2 inches(89 mm)in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies(Mandatory).
R403.5.6.1.1 Automatic controls. Service water-heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use.The minimum temperature
setting range shall be from 100°F to 140°F(38°C to 60°C).
R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off.A separate valve shall be provided to permit the energy supplied to the main burner(s)of
combustion types of service water-heating systems to be turned off.
R403.5.6.2 Water-heating equipment Water-heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code,Energy Conservation,Commercial Provisions,for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water-heating category.Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water-heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system.The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems.Solar collectors shall be tested in accordance with ISO Standard 9806,Test Methods for Solar Collectors,
and SRCC Standard TM-1,Solar Domestic Hot Water System and Component Test Protocol.Collectors in installed solar
water-heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal:and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation(Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code,Residential,or Florida Building Code,Mechanical,as applicable,or with other approved means of ventilation
including:Natural, Infiltration or Mechanical means.Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.6.1 Whole-house mechanical ventilation system fan efficacy.When installed to function as a whole-house mechanical
ventilation system,fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where whole-house mechanical ventilation fans are integral to tested and listed HVAC equipment,they shall be
powered by an electronically commutated motor.
R403.6.2 Ventilation air. When installed to function as a whole-house mechanical
ventilation system,fans shall meet the efficacy requirements of Table R403.6.1.
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2,Ventilation for Acceptable
Indoor Air Quality,shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces,attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s),then the walls of the space(s)from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19,space permitting,or R-10
otherwise.
R403.7 Heating and cooling equipment(Mandatory).
R403.7.1 Equipment sizing. Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies,
based on building loads for the directional orientation of the building.The manufacturer and model number of the outdoor and
indoor units(if split system)shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1.This Code does not allow designer safety factors,provisions for future expansion or other factors that
affect equipment sizing.System sizing calculations shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems.New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE R403.6.1
WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION AIRFLOW RATE MINIMUM MINIMUM EFFICACY a AIRFLOW RATE MAXIMUN
(CFM) (CFM/WATT) (CFM)
Range hoods Any 2.8 cfm/watt Any
In-line fan Any 2.8 cfm/watt Any
Bathroom,utility room 10 1.4 cfm/watt <90
Bathroom,utility room 90 2.8 cfm/watt Any
For SI: 1 cfm=28.3 Umin. a. When tested in accordance with HVI Standard 916
3/28/2018 2:39 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.7,or the closest available size provided by the manufacturer's product lines.The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal,rating-test value and shall not be used for equipment sizing.Manufacturer's
expanded performance data shall be used to select cooling-only equipment.This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation(or entering water temperature for water-source equipment),the blower CFM provided by the expanded
performance data,the design value for entering wet-bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet-bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s)is installed in an unconditioned space.
Exceptions:
1. Attached single-and multiple-family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida-registered engineer,in attached single-and multiple-family units,the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1,and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis,such as anticipated additional loads caused by major entertainment events,shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units(Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the IECC—Commercial Provisions in lieu of Section R403.
R403.9 Snow melt and Ice system controls(Mandatory) Snow-and ice-melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F(10°C),and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is.above 40°F(4.8°C).
R403.10 Pools and permanent spa energy consumption(Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on-off switch that is an
integral part of the heater mounted on the exterior of the heater,or external to and within 3 feet(914 mm)of the heater.Operation
of such switch shall not change the setting of the heater thermostat.Such switches shall be in addition to a circuit breaker for the
power to the heater.Gas-fired heaters shall not be equipped with continuously burning ignition pilots.
R403.10.2 Time switches.Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar-and waste-heat-recovery pool heating systems.
3. Where pumps are powered exclusively from on-site renewable generation.
R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor-retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating,computed over an operation season,is from site-recovered
energy,such as from a heat pump or solar energy source,covers or other vapor-retardant means shall not be required.
R403.10.4 Gas-and oil-fired pool and spa heaters. All gas-and oil-fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16,2013,when tested in accordance with ANSI Z 21.56.Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
3/28/2018 2:39 PM EnergyGauge&USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 4 of 5
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160,Table 2,Standard Rating Conditions-Low Air Temperature.A test report from an independent laboratory is
required to verify procedure compliance.Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas(Mandatory,*energy consumption of electric-powered portable spas shall be controlled by the
requirements of APSP-14.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment(Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be
high-efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high-efficacy lamps.
Exception:Low-voltage lighting.
R404.1.1 Lighting equipment(Mandatory)Fuel gas lighting systems shall not have continuously burning pilot lights.
3/28/2018 2:39 PM EnergyGauge®USA-FlaRes2017 -FBC 6th Edition(2017) Complia Page 5 of 5
+'Ili- wrightsoft Manual S Compliance Report Job: Lot 1AAT
Date: 3-27-2018
Entire House By:
Florida Air Service & Engineering
150 Hilden Road 308,Ponte Vedra,Fl 32081 Phone:904-823-9696 Web:WWW.NORTHFLORIDAAIR.COM
Project Information
For:
Cooling Equipment
Design Conditions
Outdoor design DB: 92.8°F Sensible gain: 32894 Btuh Entering coil DB: 76.8°F
Outdoor design WB: 77.0°F Latent gain: 5834 Btuh Entering coil WB: 63.7°F
Indoor design DB: 75.0°F Total gain: 38728 Btuh
Indoor RH: 50% Estimated airflow: 1400 cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Carrier Model: 25HBC548A00300+FX4DNB049L
Actual airflow: 1400 cfm
Sensible capacity: 36556 Btuh 111%of load
Latent capacity: 7781 Btuh 133%of load
Total capacity: 44337 Btuh 114%of load SHR: 82%
Heating Equipment
Design Conditions
Outdoor design DB: 32.5°F Heat loss: 37953 Btuh Entering coil DB: 68.8°F
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Carrier Model: 25HBC548A00300+FX4DNB049L
Actual airflow: 1600 cfm
Output capacity: 37503 Btuh 99%of load Capacity balance: 28 °F
Supplemental heat required: 449 Btuh Economic balance: -99 °F
Backup equipment type: Elec strip
Manufacturer: Model:
Actual airflow: 1600 cfm
Output capacity: 7.1 kW 64%of load Temp. rise: 50 °F
Meets all requirements of ACCA Manual S.
-Si- weight:sof- 2018-Mar-28 14:06:44
_ - Right-Suite®Universal 2018 18.0.11 RSU09479 Page 1
...1Pat Mulligan\Ahem Townhomes\1931 Left End.rup Calc=MJ8 Front Door faces: E
4 wrightsoft Project Summary Job: Lot 1AAT
Date: 3.27-2018
Entire House By:
Florida Air Service & Engineering
150 Hilden Road 308,Ponte Vedra,Fl 32081 Phone:904-823-9696 Web:WWW.NORTHFLORIDAAIR.COM
Pro"ect Information
For:
Notes: Lot 1A Ahern Townhomes
Desi• n Information
Weather: Jacksonville/Intnl., FL, US
Winter Design Conditions Summer Design Conditions
Outside db 33 °F Outside db 93 °F
Inside db 70 °F Inside db 75 °F
Design TD 38 °F Design TD 18 °F
Daily range M
Relative humidity 50 %
Moisture difference 50 grab
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 31627 Btuh Structure 27411 Btuh
Ducts 6325 Btuh Ducts 5482 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 Btuh
Pipi0 Btuhng
load 37953 Btuh Use manufacturer's data y
Rate/swing multiplier 1.00
Infiltration Equipment sensible load 32894 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 2931 Btuh
Ducts 2904 Btuh
Central vent(0 cfm) 0 Btuh
Heating Cooling (none)
Area(ft2) 1931 1931 Equipment latent load 5834 Btuh
Volume(ft3) 22206 22206
Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 38728 Btuh
Equiv.AVF(cfm) 141 74 Req. total capacity at 0.70 SHR 3.9 ton
Heating Equipment Summary Cooling Equipment Summary
Make Carrier Make Carrier
Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING
Model 25HBC548A00300 Cond 25HBC548A00300
AHRI ref 9155626 Coil FX4DNB049L
AHRI ref 9155626
Efficiency 8.5 HSPF Efficiency 12.5 EER, 15 SEER
Heating input Sensible cooling 33250 Btuh
Heating output 45500 Btu h @ 47°F Latent cooling 14250 Btuh
Temperature rise 26 °F Total cooling 47500 Btuh
Actual air flow 1600 cfm Actual air flow 1400 cfm
Air flow factor 0.042 cfm/Btuh Air flow factor 0.043 cfm/Btuh
Static pressure 0.25 in H2O Static pressure 0.25 in H2O
Space thermostat Load sensible heat ratio 0.85
Capacity balance point=28°F
Backup:
Input=7 kW, Output=24267 Btuh, 100 AFUE
Bold/italic values have been manually overridden
.�(� Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
rr� � 2018-Mar-28 14:06:44
Right-Suite®Universal 2018 18.0.11 RSU09479 Page 1
..,\Pat Mulligan\Ahem Townhomes\1931 Left End.rup Calc=MJ8 Front Door faces: E
,
4 wrliphtsott Right-J® Worksheet Job: Lot 1A AT
Entire House Date: 3-27.2018
Florida Air Service & Engineering By:
150 Hilden Road 308,Ponta Vedra,FI 32081 Phone:904-823-9696 Web:WWW.NORTHFLORIDAAIR.COM
2 Exo sed wall m name
Entire House Laundry
396.0 ft
3 Room height 9.4 ft 9.0 ft 20.00.0
ft heat/cool
4 Room dimensions
5 Room area 3047.0 ft' 9.0 x 11.0 ft
r t I I 99.0 ft'
I
Ty Construction U-value Or I HTMArea (ft') I Load Area ')
number (Bt uhlft2-°F (Btuh/ft2 ( or (ft Load
perimeter (ft) (Btuh) I or perimeter (ft) (Btuh)
111
I Heat Cool Gross I N/P/S I Heat 1 Cool I Gross I N/P/S Heat I Cool I
6 W 12A-Osw 0.240 n 9.00 7.25 300 300 2700 2174 0 0 0 0
. W 12E-Osw 0.068 n 1.71 0.96 686 686 1176 661 81 81 207 116
. VI 12A-0sw 0.240 e 9.00 7.25 399 325 2921 2352 0 0 0 0
108-w 0.800 e 22.50 24.68 16 3 370 406 0 0 0 0
11 -C 1D-c2ow 0.570 e 21.38 52.90 4 0 88 212 0 0 0 0
-G 1D-c2ow 0.570 a 21.38 52.90 54 0 1154 2857 0 0 0 0
12E-Osw 0.068 a 2.55 1.43 469 424 1081 608 99 95 242 136
1D-c2ow 0.570 a 21.38 20.18 7 7 150 141 0 0 0 0
1D-c2ow 0.570 e 21.38 30.00 4 3 86 120 4 3 88 120
0
1D-c2ow 0.570 e 21.38 52.90 10 0 214 529 0 0 0
D 1100 0.390 a 14.62 11.78 24 24 351 283 0 0 0 0
W 12A-Osw 0.240 s 9.00 7.25 121 115 1035 834 0 0 0 0
I� 1D-c2ow 0.570 s 21.38 22.23 6 0 128 133 0 0 0 0
12E-Osw 0.068 s 1.83 1.03 853 799 1464 824 0 0 0 0
1D-c2ow 0.570 s 21.38 22.23 54 0 1154 1200 0 0 0 0
W 12A-Osw 0.240 w 9.00 7.25 198 168 1512 1218 0 0 0 0
�G 1D-c2ow 0.570 w 21.38 52.90 30 0 641 1587 0 0 0 0
W 12E-Osw 0.068 w 1.46 0.82 670 588 858 483 0 0 0 0
tom; 1D-c2owd 0.570 w 21.38 33.46 82 46 1744 2730 0 0 0 0
R 12C-Osw 0.091 - 3.41 1.39 252 233 794 324 99 99 338 138
�D 11D0 0.390 n 14.62 11.78 19 19 282 227 0 0 0 0
C 18A-19xd 0.051 - 1.91 1.51 1210 1210 2314 1833 0 0 0 0
F 19C-19cscp 0.049 - 0.64 0.30 700 700 446 212 0 0 0 0
F 22A-tol 0.989 - 19.40 0.00 1210 164 3173 0 99 20 742 0
61 c)AED excursion I 1 1057 -158
Envelope loss/gain 25833 23004 16141 3521
12 a) Infiltration 5794 1448 348 87
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 2 460 0 0
Appliances/other 2500 500
Subtotal(lines 6 to 13) 31827 27411 1962 939
Less external load 0 0 0 0
Less transfer
Redistribution 0 0 0 0
14 Subtotal 0 0 0 0
31627 27411 1962 939
15 Duct loads 20% 20% 6325 5482 20% 20% 392 188
II Total room load I I I 379531 328941 I I I
Air required(cfm) l 1600 1400 2399 11481
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrMptitsaTt 2018-Mar-2814:06:44
Right-Suite®Universal 2018 18.0.11 RSU09479 Page 1
...Tat Mulligan\Ahem Townhomes\1931 Left End.rup Calc=MJ8 Front Door faces: E
4 wrightsoft' Right-J® Worksheet Job: Lot 1A AT
Entire House Date: 3-27-2018
By:
Florida Air Service & Engineering
150 Hilden Road 308,Ponta Vedra,Fl 32081 Phone:904-823-9698 Web:WWW.NORTHFLORIDAAIR.COM
1 Room name
ry Garage
2 Exposed wall 32.0 ft 78.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft uncondit.
4 Room dimensions 1.0 x 169.0 ft 25.0 x 28.0 ft
5 Room area 169.0 f N 700.0 f t'
I I I I I I
Ty Construction U-value Or I HIM I Area If 12) I Load I Area (f t2)
or Load
number (Btuh/ft'-°F (Btuh/ft') or perimeter (ft) (Btuh) per meter (ft) (Btuh)
Heat I Cool 1 Gross I N/P/S Heat 1 Cool 1 Gross I N/P/S Heat I Cool 1
6 W 12A-Osw 0.240 n 9.00 7.25 0 0 0 0 0 0 0 0
. W 12E-Osw 0.068 n 1.71 0.96 0 00 0 225 Z25 0 0
VJ 12A-Osw 0.240 e 9.00 7.25 0 0 0 0 0 0 0 0
-G 1OB-w 0.600 e 22.50 24.68 0 0 0 0 0 0 0 0
11 -G 1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
-G 1D-c2ow 0.570 a 21.38 52.90 0 0 0 0 0 0 0 0
12E-Osw 0.068 e 2.55 1.43 180 156 398 224 0 0 0 0
1D-c2ow 0.570 a 21.38 20.18 0 0 0 0 0 0 0 0
1D-c2ow 0.570 a 21.38 30.00 0 0 0 0 0 0 0 0
1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
11 DO 0.390 e 14.62 11.78 24 24 351 283 0 0 0 0
Vy1-fi 12A-Osw 0.240 s 9.00 7.25 0 0 0 0 0 0 0 0
1 D-c2ow 0.570 s 21.38 22.23 0 0 0 0 0 0 0 0
VLG 12E-Osw 0.068 s 1.83 1.03 81 81 207 116 225 225 0 0
1D-c2ow 0.570 s 21.38 22.23 0 0 0 0 0 0 0 0
12A-Osw 0.240 w 9.00 7.25 0 0 0 0 0 0 0 0
1D-c2ow 0.570 w 21.38 52.90 0 0 0 0 0 0 0 0
V1 12E-Osw 0.068 w 1.46 0.82 27 27 69 39 252 252 0 0
-6 1D-c2owd 0.570 w 21.38 33.46 0 0 0 0 0 0 0 0
R 12C-Osw 0.091 - 3.41 1.39 153 134 456 186 0 0 0 0
1 D 11D0 0.390 n 14.62 11.78 19 19 282 227 0 0 0 0
C 18A-19xd 0.051 - 1.91 1.51 0 0 0 0 0 0 0 0
F 19C-19cscp 0,049 - 0.64 0.30 0 0 0 0 0 0 0 0
F 22A-tol 0.989 - 19.40 0.00 169 32 1187 0 700 78 0 0
1 6 1 cEnvelope)AED excursionloss/gain 1 I 1 29491 900-1751 1 1 01 001
12 a) Infiltration 557 139 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants Cot 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 3507 1039 0 0
Less external load 0 0 0 0
Less transfer
Redistribution 0 0 0 0
0 0 0 0
14 Subtotal 3507 1039 0 0
15 Duct loads 20% 20% 701 208 0% 0% 0 0
I I Air Total
requirroomed lo(cadfm) I I 42081 12471 I I 01 O
177 53 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrsyh.I.L coat 2018-Mar-2814:06:44
Right-Suite Universal 2016 18.0.11 RSU09479 Page 2
..\Pat Mulligan\Ahern Townhomes\1931 Left End.rup Calc=MJ8 Front Door faces: E
•4wrightsoft' Right-J® Worksheet Job: Lot 1AAT
Entire House Date: 3-27.2018
Florida Air Service & Engineering By:
150 Hilden Road 308,Ponta Vedra,FI 32081 Phone:904-823-9896 Web:WW W.NORTHFLORIDAAIR.COM
1 Room name Master M WIC
2 Exposed wall 32.0 ft
3 Room height 19.0 ft
10.0 ft heat/cool 10.0 ft heat/cool
4 Room dimensions
5 Room area 260 0 f t21.0 x 260.0 ft 84.0 f t2 7.0 x 12.0 ft
I I I I
t
Ty Construction U-value OrHTM I Area (f V) Load Area (ft2) Load
number (Bt uh/ft2-°F I (Btuh/ft') or perimeter (ft) ( (Btuh) I or perimeter (ft) (Btuh) I
I
I Heat I Cool Groes I wI p/8 Heat 1 Cool I Gross N/P/S Heat 1 Cool I
6 W 12A-Osw 0.240 n 9.00+ 7.25 140 140 1260 1015 O 0 0 0
. W 12E-Osw 0.068 n 1.71 0.96 0 0 0 0 0 0 0 0
. V/ 12A-Osw 0.240 e 9.00 7.25 0 0 0 0 0 0 0 0
-G 10B-w 0.600 e 22.50 24.68 0 0 0 0 0 0 0 0
11 -G 1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
-G 1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
12E-Osw 0.068 a 2.55 1.43 0 0 0 0 0 0 0 0
1D-c2ow 0.570 a
0.570 a
21.38 20.18 0 0 0 0 0 0 0 0
1D-c2ow 21.38 30.00 0 0 0 0 0 0 0 0
1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
11 DO 0.390 e 14.62 11.78 0 0 0 0 0 0 0 0
12A-Osw 0.240 s 9.00 7.25 0 0 0 0 0 0 0 0
1D-c2ow 0.570 s 21.38 22.23 0 0 0 0 0 0 0 0
W 12E-Osw 0.068 s 1.83 1.03 0 0 0 0 70 64 183 92
L-� 1 D-c ow 0.570 s 21.38 22.23 0 0 0 0 6 0 128 133
12A-Osw 0.240 w 9.00 7.25 180 150 1350 1087 0 0 0 0
1D-c2ow 0.570 w 21.38 52.90 30 0 641 1587 0 0 0 0
V(f 12E-Osw 0.068 w 1.46 0.82 0 0 0 0 120 120 306 172
Iii 1 D-c2owd 0.570 w 21.38 33.46 0 0 0 0 0 0 0 0
12C-Osw 0.091 - 3.41 1.39 0 0 0 0 0 0 0 0
1100 0.390 n 14.62 11.78 0 0 0 0 0 0 0 0
C 18A-19xd 0.051 - 1.91 1.51 150 150 287 227 84 84 161 127
F 19C-19cscp 0.049 - 0.64 0.30 188 188 120 57 30 30 19 9
F 22A-tol 0.989 - 19.40 0.00 72 9 329 0 54 12 453 0
c
D
149
6 I Envelope loss/gain I I 398741221 I 12301476 I
12 a) Infiltration 619 155
b) Room ventilation 368 92
0 0 0 0
13 Internal gains: Occupants Q 230 2 460 0 0
Appliances/other 0
0
Subtotal(lines 6 to 13) 4606 4737 1598 570
Less external load 0 0 0 0
Less transfer
Redistribution 0 0 0 0
14 Subtotal 4606 47377 1598 570
15 Duct loads 20% 20% 921 947 20% 20% 320 114
Ai
Tortalreqrouireomd(cloadfm)
I l I 55271
233 56841
242 I I 1918
81 884291
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
+}► wrssihttacVt Rig ht-Suite®Universa1201818.0.11 RSU09479 2018-Mar-2814:06:44
...\Pat Mulligan\Ahem Townhomes11931 Left End.rup Calc=MJ8 Front Door faces: E Page 3
4 wrightsoft• Right-J® Worksheet Job: Lot 1A AT
Entire House Date: 3-27.2018
By:
Florida Air Service & Engineering
150 Hilden Road 308,Ponte Vedra,Fl 32081 Phone:904-823-9696 Web:WWW.NORTHFLORIDAAIR.COM
1 Room name M Bath Powder
2 Exposed wall 12.0 ft
0 ft
3 Room height 9.0 ft heat/cool 10.0 ft heat/cool
4 Room dimensions 1.0 x 119.0 ft 5.0 x 5.0 ft
5 Room area 119.0 f t' 25.0 10
I 1 I I I I
Ty Construction U-value Or I HTM ( Area (ft') Load I Area (ft') Load
number (Btuh/ft2-°F (Btuh/ft) or perimeter (ft) (Btuh) or perimeter (ft) I (Btuh)
Heat I Cool I Gross I NIP/S Heat I Cool 1 Gross 1 N/P/S I Heat 1 Cool I
6 W 12A-Osw 0.240 n 9.00 7.25 0 0 0 0 0 0 0 0
. W 12E-Osw 0.068 n 1.71 0.96 0 0 0 0 0 0 0 0
. VI 12-Osw 0.240 a 9.00 7.25 0 0 0 0 0 0 0 0
-G 108-w 0.600 e 22.50 24.88 0 0 0 0 0 0 0 0
1 1 -G 1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
-G 1D-c2ow 0.570 a 21.38 52.90 0 0 0 0 0 0 0 0
VN12E-Osw 0.068 e 2.55 1.43 0 0 0 0 0 0 0 0
1D-c2ow 0.570 e 21.38 20.18 0 0 0 0 0 0 0 0
1D-c2ow 0.570 e 21.38 30.00 0 0 0 0 0 0 0 0
1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
11D0 0.390 e 14.62 11.78 0 0 0 0 0 0 0 0
12A-Osw 0.240 s 9.00 7.25 0 0 0 0 0 0 0 0
1D-c2ow 0.570 s 21.38 22.23 0 0 0 0 0 0 0 0
12E-Osw 0.068 s 1.83 1.03 108 102 260 146 0 0 0 0
1D-c2ow 0.570 s 21.38 22.23 6 0 128 133 0 0 0 0
12A-0sw 0.240 w 9.00 7.25 0 0 0 0 0 0 0 0
1D-c2ow 0.570 w 21.38 52.90 0 0 0 0 0 0 0 0
VII 12E-Osw 0.068 w 1.46 0.82 0 0 0 0 0 0 0 0
I--G 1 D-c2owd 0.570 w 21.38 33.46 0 0 0 0 0 0 0 0
R 12C-Osw 0.091 - 3.41 1.39 0 0 0 0 0 0 0 0
�-O
11D0 0.390 n 14.62 11.78 0 0 0 0 0 0 0 0
C 18A-19xd 0.051 - 1.91 1.51 12 12 23 18 0 0 0 0
F 19C-19cscp 0.049 - 0.84 0.30 95 95 61 29 25 25 18 8
F 22A-tol 0.989 - 19.40 0.00 24 2 90 0 0 0 0 0
I 6 I c)AED excursion 20 1
Envelope loss/gain 1 5621 3071 i 161 61
12 a) Infiltration 209 52 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants a 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 8 to 13) 771 359 16 6
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 771 359 16 6
15 Duct loads 20% 20% 154 72 20% 20% 3 1
II Air Totalrequirroomed lo(dadm) I I 9351 4381 I I 191 O
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrbl's tt 2018-Mar-2814:06:44
Right-Su ite®U niv er sal 2018 18.0.11 RSU09479
Page 4
...\Pat Mulligan\Ahem Townhomes\1931 Left End.rup Calc=MJ8 Front Door faces: E
- •
4 wrIghtsott. Right-J® Worksheet Job: Lot 1A AT
Entire House Date: 3-27-2018
By:
Florida Air Service & Engineering
150 HIlden Road 308,Pontos Vedra,FI 32081 Phone:904-823-9696 Web:WWW.NORTHFLORIDAAIR.COM
1 Room name Kitchen
2 Exposed wall 11.0 ft Dining
ft
3 Room height 10.0 ft heat/cool 10.0 ft heat/cool
4 Room dimensions 11.0 x 14.0 ft 10.0 x 12.0 ft
5 Room area 154.0 ft' 120.0 ft'
I r i
I
I
Ty Construction U-value Or 1 HTM 1 Area (ft') Load I Area (ft') Load
number (St uh/ft'-°F (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
IHeat I Cool I Gross I N/P/S Heat I Cool I Gross N/P/S Heat I Cool I
6 W 12A-Osw 0.240 n 9.00 7.25 0 0 0 0 Or 0 0 0
. W 12E-Osw 0.068 n 1.71 0.96 110 110 281 158 0 0 0 0
. W 12A-Osw 0.240 e 9.00 7.25 0 0 0 0 0 0 0 0
-G 108-w 0.600 e 22.50 24.68 0 0 0 0 0 0 0 0
11 -G 1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
-G 1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
12E-Osw 0.068 e 2.55 1.43 0 0 0 0 0 0 0 0
1D-c2ow 0.570 e 21.38 20.18 0 0 0 0 0 0 0 0
1 D-c2ow 0.570 e 21.38 30.00 0 0 0 0 0 0 0 0
1 D c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
11 DO 0.390 e 14.62 11.78 0 0 0 0 0 0 0 0
VLG 12A-Osw 0.240 a 9.00 7.25 0 0 0 0 0 0 0 0
1D-c2ow 0.570 s 21.38 22.23 0 0 0 0 0 0 0 0
12E-Osw 0.068 s 1.83 1.03 0 0 0 0 100 85 217 122
1D-c2ow 0.570 s 21.38 22.23 0 0 0 0 15 0 321 333
W 12A-0sw 0.240 w 9.00 7.25 0 0 0 0 0 0 0 0
1 D-c2ow 0.570 w 21.38 52.90 0 0 0 0 0 0 0 0
12E-Osw 0.068 w 1.46 0.82 0 0 0 0 0 0 0 0
1D-c2owd 0.570 w 21.38 33.46 0 0 0 0 0 0 0 0
R1-d 12C-Osw 0.091 - 3.41 1.39 0 0 0 0 0 0 0 0
1100 0.390 n 14.62 11.78 0 0 0 0 0 0 0 0
C 18A-19xd 0.051 - 1.91 1.51 11 11 21 17 0 0 0 0
F 19C-19cscp 0.049 - 0.64 0.30 154 154 98 47 100 100 64 30
F 22A-tol 0.989 - 19.40 0.00 0 0 0 0 20 2 62 0
1 6 I c)AED excursion -328 9
Envelope loss/gain I 4001 -1071 I 6631 4951
I+
12 a) Infiltration 213 53 194 48
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 2000 0
Subtotal(lines 6 to 13) 613 1946 856 543
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 613 1946 856 543
15 Duct loads 20% 20% 123 389 20% 20% 171 109
Air re ui d(cim) I I 1 735 23361
I 1 1028 6281
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-4.- wrraph`tsoes 2018-Mar-28 14:08:44
Right-Suite®U niv ersal 2018 18.0.11 RSU09479 Page 5
...\Pat Mulligan\Ahem Townhomes\1931 Left End.rup Calc=MJB Front Door faces: E
• I
4 wrightsoft Right-J® Worksheet Job: Lot 1A AT
Entire House Date: 3-27-2018
By:
Florida Air Service & Engineering
150 Hilden Road 308,Ponta Vedra.FI 32081 Phone:904-823-9696 Web:WWW.NORTHFLORIDAAIR.COM
1 Room name Mid Stairs Living
2 Exposed wall 19.0 ft 41.0 ft
3 Room height 10.0 ft heat/cool 10.0 ft heat/cool
4 Room dimensions 8.0 x 10.0 ft 1.0 x 360.0 ft
5 Room area 80.0 ft' 360.0 f t'
Ty r Construction I U-value Or I HTM I Area (ft') Load I Area (ft' Load
number (Bt uh/ft2-°F (Btuh/ft') or perimeter (ft) (Btuh) or )
perimeter (ft) (Btuh)
IHeat I Cool I Gross 1 I N/P/S Heat I Cool I Gross I N/P/S Heat I Cool I
6 W 12A-Osw 0.240 n 9.00 7.25 0 0 0 0 160 160 1440 1160
. W 12E-Osw 0.068 n 1.71 0.96 0 0 0 0 0 0 0 0
. Vi 12A-Osw 0.240 e 9.00 7.25 0 0 0 0 210 156 1404 1131
-G10B-w 0.600 e 22.50 24.68 0 0 0 0 0 0 0 0
11 -G 1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
-G 1D-c2ow 0.570 a 21.38 52.90 0 0 0 0 54 0 1154 2857
12E-Osw 0.068 e 2.55 1.43 100 90 230 129 0 0 0 0
1D-c2ow 0.570 e 21.38 20.18 0 0 0 0 0 0 0 0
1D-c2ow 0.570 e 21.38 30.00 0 0 0 0 0 0 0 0
10-c2ow 0.570 a 21.38 52.90 10 0 214 529 0 0 0 0
1100 0.390 a 14.62 11.78 0 0 0 0 0 0 0 0
Vy 12A-Osw 0.240 s 9.00 7.25 0 0 0 0 40 40 360 290
LG
1D-c2ow 0.570 s 21.38 22.23 0 0 0 0 0 0 0 0
12E-Osw 0.068 a 1.83 1.03 80 85 166 93 0 0 0 0
10-c2ow 0.570 s 21.38 22.23 15 0 321 333 0 0 0 0
V}r 12A-Osw 0.240 w 9.00 7.25 0 0 0 0 0 0 0 0
�G 1 D-c2ow 0.570 w 21.38 52.90 0 0 0 0 0 0 0 0
12E-Osw 0.068 w 1.46 0.82 10 10 26 14 0 0 0 0
1D-c2owd 0.570 w 21.38 33.46 0 0 0 0 0 0 0 0
PL_G 12C-Osw 0.091 - 3.41 1.39 0 0 0 0 0 0 0 0
11D0 0.390 n 14.62 11.78 0 0 0 0 0 0 0 0
C 18A-19xd 0,051 - 1.91 1.51 0 0 0 0 76 76 145 115
F 19C-19cscp 0.049 - 0.64 0.30 0 0 0 0 108 108 69 33
F 22A-tol 0.989 • 19.40 0.00 0 0 0 0 64 7 270 0
1 6 1 Envelope loss/gain
1 9551 -172
9271 1114148431 5698
12 a) Infiltration 368 92 793 198
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants ct 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 1323 1019 5836 5897
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 1323 1019 5636 5897
15 Duct loads 20% 20% 265 204 20% 20% 1127 1179
Ai
Tortalrequirroomed lo(cafmd )
I I 1587 12231 I I 67631 70761
I 87 52 285 301
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-via- Wi'+os'+��Qn- 2018-Mar-2814:06:44
AgtA Right-Suite®Universal 201818.0.11 RSU09479 Page 6
...\Pat Mulligan\Ahern Townhomes\1931 Left End.rup Calc=MJ8 Front Door faces: E
4}+-wrightsott Right-J® Worksheet Job: Lot 1A AT
Entire House Date: 3-27-2018
Florida Air Service & Engineering By:
150 Hilden Road 308,Ponta Vedra,Fl 32081 Phone:904-823-9696 Web:WWW.NORTHFLORIDAAIR.COM
1 Room name Loft Mach
2 Exposed wall 32.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft Oft heat/cool
4 Room dimensions 1.0 x 232.0 ft 8.0 x 3.0 ft
5 Room area 232.0 ft' 18.0 ft'
I I I I
Ty Construction U-value Or I HTM I Area (ft') Load I Area (ft') Load
number (Btuh/ft'-°F (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) I
I
Heat I Cool Gross I N/P/S Heat I Cool I Gross I N/P/S Heat I Cool I
6 W 12A-Oaw 0.240 n 9.00 7.25 0 0 0 01 0 0 01 0
. W 12E-Osw 0.068 n 1.71 0.96 0 0 0 0 0 0 0
W 12A-0sw 0.240 e 9.00 7.25 189 169 1517 1222 0 0 0 0
-G 10B-w 0.800 e 22.50 24.88 18 3 370 406 0 0 0 0
11 -G 1D-c2ow 0.570 e 21.38 52.90 4 0 88 212 0 0 0 0
-G 1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
12E-Osw 0.068 e 2.55 1.43 0 0 0 0 0 0 0 0
1D-c2ow 0.570 e
0.570 a
21.38 20.18 0 0 0 0 0 0 0 0
1D-c2ow 21.38 30.00 0 0 0 0 0 0 0 0
1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
1100 0.390 e 14,62 11.78 0 0 0 0 0 0 0 0
W 12A-Osw 0.240 s 9.00 7.25 81 75 675 544 0 0 0 0
�--G 1D-c2ow 0.570 s 21.38 22.23 6 0 128 133 0 0 0 0
12E-Osw 0.068 8 1.83 1.03 0 0 0 0 0 0 0 0
1D-c2ow 0.570 s 21.38 22.23 0 0 0 0 0 0 0 0
12A-Osw 0.240 w 9.00 7.25 18 18 162 130 0 0 0 0
1D-c2ow 0.570 w 21.38 52.90 0 0 0 0 0 0 0 0
12E-Osw 0.068 w 1.46 0.82 0 0 0 0 0 0 0 0
1D-c2owd 0.570 w 21.38 33.46 0 0 0 0 0 0 0 0
R 12C-Osw 0.091 - 3.41 1.39 0 0 0 0 0 0 0 0
I-D 1100 0.390 n 14.82 11.78 0 0 0 0 0 0 0 0
C 18A-19xd 0.051 - 1.91 1.51 232 232 444 351 18 18 34 27
F 19C-19cscp 0.049 - 0.64 0.30 0 0 0 0 0 0 0 0
F 22A-tpl 0.989 - 19.40 0.00 8 1 41 0 0 0 0 0
61 c)AED excursion
Envelope loss/gain 1 1 1 34221 25611 1 341 23
12 a) Infiltration 557 139 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 3980 2700 34 Y3
Less external load 0 0 0 0
Less transfer
Redistribution 0 0 0 0
17 12 -34 -23
14 Subtotal 3997 2712 0 0
15 Duct loads 20% 20% 799 542 20% 20% 0 0
Total room load I I I 42021 32 91 1 I 01 0I
Air required(dm)
1Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
+� wriOftaoR
r2018-Mar-2814:06:44
Aft. Right-Suite®Universal 2018 18.0.11 RSU09479 Page 7
...\Pat Mulligan\Ahem Townhomes\1931 Left End.rup Calc=MJ8 Front Door faces: E
a
4 wrIghtsoft Right-J® Worksheet Job: Lot 1A AT
Entire House Date: 3-27-2018
By:
Florida Air Service & Engineering
150 Hilden Road 308,Ponte Vedra,Fl 32081 Phone:904-823-9696 Web:WWW.NORTHFLORIDAAIR.COM
1 Room name WIC 1 Bed 1
2 Exposed wall 6.0 ft 30.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 6.0 x 7.0 ft 15.0 x 15.0 ft
5 Room area 42.0 ft' 225.0 11'
II
I II
Ty Construction U-value Or I HTMI Area (ft') Load I Area (118) Load
number (Bt uh/fl-°F (Bluh/ft2) or perimeter (ft) (Btuh) or perimetr (ft)
h)
Heat I Cool I Gross I N/P/S Heat I Cool Gross I N/P/S Heal I
I Cool
6 W 12A-Osw 0.240 n 9.00 7.25 0 0 0 0 0 0 0 0
. W 12E-Osw 0.068 n 1.71 0.96 0 0 0 0 0 0 0 0
. VI 12A-Osw 0.240 e 9.00 7.25 0 0 0 0 0 0 0 0
-G 10B-w 0.600 a 22.50 24.68 0 0 0 0 0 0 0 0
1.1 -G 1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
-G 1D-clow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
li
N12E-Osw 0.068 e 2.55 1.43 0 0 0 0 0 0 0 0
1D-c2ow 0.570 e 21.38 20.18 0 0 0 0 0 0 0 0
1D-c2ow 0.570 a 21.38 30.00 0 0 0 0 0 0 0 0
10-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
11D0 0.390 a 14.62 11.78 0 0 0 0 0 0 0 0
Vy 12A-Osw 0.240 s 9.00 7.25 0 0 0 0 0 0 0 0
�G 1D-c2ow 0.570 s 21.38 2223 0 0 0 0 0 0 0 0
Vy 12E-Osw 0.068 s 1.83 1.03 54 54 138 77 135 123 314 176
�G
10-c2ow 0.570 s 21.38 22.23 0 0 0 0 12 0 257 287
W 12A-Osw 0.240 w 9.00 7.25 0 0 0 0 0 0 0 0
�G 1 D-c2ow 0.570 w 21.38 52.90 0 0 0 0 0 0 0 0
12E-Osw 0.068 w 1.46 0.82 0 0 0 0 135 94 240 135
1D-c2owd 0.570 w 21.38 33.46 0 0 0 0 41 23 872 1365
LD12C-Osw 0.091 - 3.41 1.39 0 0 0 0 0 0 0 0
11D0 0.390 n 14.62 11.78 0 0 0 0 0 0 0 0
C 18A-19xd 0.051 - 1.91 1.51 42 42 80 64 225 225 430 341
F 19C-19cscp 0.049 - 0.64 0.30 0 0 0 0 0 0 0 0
F 22A-tpl 0.989 - 19.40 0.00 0 0 0 0 0 0 0 0
61 c)AED excursion I -24 1039
Envelope Ioss/gain 218 117 I 2113 3324
12 a) Infiltration 105 26 523 131
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 323 143 2835 3454
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 11 8 6 4
14 Subtotal 334 151 2641 3458
15 Duct loads 20% 20% 67 30 20% 20% 528 692
Total room load 401
18113169 4150
Air required(cfm) I I I 17I 8 l I 134( 177 I
Calculations approved bV ACCA to meet all requirements of Manual J 8th Ed.
At
-11.1. ws-Mpt+tsso*r 2018-Mar-2814:06:44 e.
Right-Suite®U niversal 2018 18.0.11 RSU09479 Page 8
...Tat MulliganWhern Townhomes\1931 Left End.rup Calc=MJ8 Front Door faces: E
4 wrightsott• Right-J® Worksheet Job: Lot 1A AT
Entire House Date: 3-27-2018
Florida Air Service & Engineering By:
150 Hilden Road 308,Pante Vedra,Fl 32081 Phone:904-823-9696 Web:WWW.NORTHFLORIDAAIR.COM
1 Room name
2 Exposed wall Bed 2 Bath 1
3 Room height 32.0 ft 22.0 ft
9.0 ft heat/cool 9.0 ft
4 Room dimensionsheat/cool
5 Room area 1.0 x 240.0 ft 12.0 x 10.0 ft
'
240.0 f t
r 120.0 ft.I I I
Ty Construction U-value Or IH
TM I Area (ft2) Load I Area (f t2) Load
number (Bt uh/ft2-°F (Bluh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
II
Heat Cool I Gross 1 N/P/S Heat I Cool I Gross 1 N/P/S I Heat I Cool I
6 W 12A-Osw 0.240 n 9.00 7.25 0 0 0 0 0 0 0 0
. W 12E-Osw 0.068 n 1.71 0.96 162 162 413 232 108 108 275 155
. V/ 12A-Osw 0.240 e 9.00 7.25 0 0 0 0 0 0 0 0
-G 10B-w 0.600 e 22.50 24.88 0 0 0 0 0 0 0 0
11 -C 1D-c2ow 0.570 a 21.38 52.90 0 0 0 0 0 0 0 0
-G 1D-c2ow 0.570 e 21.38 52.90 0 0 0 0 0 0 0 0
12E-Osw 0.068 e 2.55 1.43 0 0 0 0 90 83 212 119
1D-c2ow 0.570 e 21.38 20.18 0 0 0 0 7 7 150 141
1D-c2ow 0.570 e 21.38 30.00 0 0 0 0 0 0 0 0
1D-c2ow 0.570 a 21.38 52.90 0 0 0 0 0 0 0 0
11DO 0.390 a 14.62 11.78 0 0 0 0 0 0 0 0
12A-Osw 0.240 s 9.00 7.25 0 0 0
1D-c2ow 0.570 s 21.38 22.23 0 0 0 0 0 0 0 0
W 12E-Osw 0.068 s 1.83 1.03 0 0 0 0 0 0 0 0
�-G 1D-c2ow 0.570 s 21.38 22.23 0 0 0 0 0 0 0 0
12A-Osw 0.240 w 9.00 7.25 0 0 0 0 0 0 0 0
1D-c2ow 0.570 w 21.38 52.90 0 0 0 0 0 0 0 0
1 12E-Osw 0.068 w 1.46 0.82 126 85 217 122 0 0 0 0
L_ (; 1D-c2owd 0.570 w 21.38 33.46 41 23 872 1365 0 0 0 0
Fj 12C-Osw 0.091 - 3.41 1.39 0 0 0 0 0 0 0 0
�p 11D0 0.390 n 14.62 11.78 0 0 0 0 0 0 0 0
C 18A-19xd 0.051 - 1.91 1.51 240 240 459 364 120 120 229 182
F 19C-19cscp 0.049 - 0.64 0.30 0 0 0 0 0 0 0 0
F 22A-tol 0.989 - 19.40 0.00 0 0 0 0 0 0 0 0
161 c)AED excursion I -100
Envelope loss/gain 1961( 1220 33031 1 8661 4971
12 a) Infiltration 557 139 383 96
b) Room ventilation
0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0
0
Subtotal(lines 6 to 13) 2519 3442 1249 593
Less external load 0 0 0 0
Less transfer
Redistribution 0 0 0 0
0 0 0 0
14 Subtotal 2519 3442 1249 593
15 Duct loads 20% 20% 504 688 20% 20% 250 119
Air
Totalrequirroomed(dloadm) 111 I I I 30271 4131 I I 14631 901
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
r="-'letwessah2018-Mar-2814:06:44
Right-Suite®Universal 2018 18.0.11 RSU09479 Page9
...Tat Mulllgan\Ahern Townhomes\1931 Left End.rup Calc=MJ8 Front Door faces: E
• N
//
teF
1st Floor
cup
=• 0
1n
99 cfmV
•
6 Laundr.
GaragE
177 cfm
Ret Riser '.up RiserEntr)
2114 " 53f 6 "
Job#: Lot 1A AT Florida Air Service & EngineeringScale: 1 : 68
Performed for:
Page 1
150 Hilden Road 308 Right-Suite®Universal 2018
Ponte Vedra,Fl 32081 18.0.11 RSU09479
Phone:904-823-9696 2018-Mar-28 14:07:18
WWW.NORTHFLORIDAAIR.COM ...hem Townhomes\1931 Left End.rup
a I N
2nd Floor
OLAF R;Ol.,1
10 "
Kitchei
•
Master 1 p ' 301 cfm
242cm
6 ° °'4 ivinc
99 cfm
8 " 8 "
4 „ I«!t. x 0 1 ■
4 " ••• • m 1057cf • 16 " 4 "
81 cfm Owl 39 cf Powde 11 4 " 14 "
Sup Ris
Ret Rise 16 " 10.41
14 ° 67 cfm
M WR Dininc
M Batt 43 cfm
Mid Stair
Job #: Lot IA AT Florida Air Service 8� En ineerin Scale: 1 :68
Performed for: 9 9
Page 2
150 Hilden Road 308 RightSuite®Universal 2018
Ponte Vedra,Fl 32081 18.0.11 RSU09479
Phone:904-823-9696 2018-Mar-28 14:07:18
WWW.NORTHFLORIDAAIR.COM ...hem Townhomes\1931 Left End.rup
• N
3rd Floor
Sup Riser
(3(10 "
Bath
Bed `' 176 cfm
63 cfm
4 "
Al 8x .1 7 „
8 "
•
A 202 cfm
1 `
• /l : x 2
• 177 cfm 12 "
4 F/ Lofi I
543fm
"�t:v.er up Riser
Bed 1 p ■4■ • ' 6 "
•
Mem
Job#: Lot 1A AT Florida Air Service & EngineeringScale: 1 : 68
Performed for:
Page 3
150 Hilden Road 308 Right-Suite®Universal 2018
Ponta Vedra,Fl 32081 18.0.11 RSU09479
Phone:904-823-9696 2018-Mar-28 14:07:18
WWW.NORTHFLORIDAAIR.COM ...hem Townhomes\1931 Left End.rup
4 .0 U
4 Duct System Summary Job: Lot 1AAT
wrightsoft Date: 3-27-2018
Entire House By:
Florida Air Service & Engineering
150 Hilden Road 308,Ponte Vedra,Fl 32081 Phone:904-823-9696 Web:WwW.NORTHFLORIDAAIR.COM
Project Information
For:
Heating Cooling
External static pressure 0.25 in H2O 0.25 in H2O
Pressure losses 0 in H2O 0 in H2O
Available static pressure 0.25 in H2O 0.25 in H2O
Supply/return available pressure 0.182/0.068 in H2O 0.182/0.068 in H2O
Lowest friction rate 0.100 in/100ft 0.100 in/100ft
Actual air flow 1600 cfm 1400 cfm
Total effective length(TEL) 307 ft
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln(ft) Ln(ft) Trunk
Bath 1 h 1499 63 30 0.100 4.0 Ox 0 VIFx 15.8 90.0 st2
Bed 1 c 4150 134 177 0.100 8.0 Ox 0 VIFx 18.8 90.0 st2
Bed 2 c 4131 127 176 0.100 8.0 Ox 0 VIFx 16.6 90.0 st2
Dining h 1028 43 28 0.100 4.0 Ox 0 VIFx 27.5 150.0 st5
Entry h 4208 177 53 0.100 7.0 Ox 0 VIFx 44.0 179.0 st4
Kitchen c 2336 31 99 0.100 6.0 Ox 0 VIFx 24.8 150.0 st5
Laundry h 2355 99 48 0.100 6.0 Ox 0 VIFx 30.0 164.0 st4
Living c 7076 285 301 0.100 8.0 Ox 0 VIFx 16.9 130.0 st3
Loft h 4796 202 139 0.100 7.0 Ox 0 VIFx 11.2 90.0 st2
M Bath h 925 39 18 0.100 4.0 Ox 0 VIFx 26.2 150.0 st5
Mwlc h 1918 81 29 0.100 4.0 Oxo VIFx 32.6 150.0 st5
Master c 5684 233 242 0.100 8.0 0x 0 VIFx 28.2 150.0 st5
Mid Stairs h 1587 67 52 0.100 4.0 Ox 0 VIFx 15.8 130.0 st3
Powder h 19 1 0 0.100 4.0 Ox 0 VIFx 22.0 150.0 st5
WIC 1-A h 401 17 8 0.100 4.0 Ox 0 VIFx 24.3 110.0 st2
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
st4 Peak AVF 277 101 0.100 507 10.0 0 x 0 VinlFlx st3
st5 Peak AVF 428 417 0.100 545 12.0 0 x 0 VinIFlx st3
st3 Peak AVF 1057 871 0.100 757 16.0 0 x 0 VinlFlx st1
st1 Peak AVF 1057 871 0.100 757 16.0 0 x 0 VinlFlx
st2 Peak AVF 543 529 0.100 692 12.0 0 x 0 VinIFIx
Bold/Italic values have been manually overridden
yy�h�p�
2018-Mar-28 14:06:45
.n _, ._„_ ..- Right-Suite®Universal 2018 18.0.11 RSU09479 Page 1
...Tat Mulligan\Ahem Townhomes\1931 Left End.rup Calc=MJ8 Front Door faces: E
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk
rb5 Ox 0 1057 871 84.0 0.080 988 14.0 Ox 0 VIFx
rb2 Ox 0 543 529 0 0.080 692 12.0 Ox 0 VIFx
Bold/Itallc values have been manually overridden
4111-
wvr g dam•
2018-Mar-28 14:08:45
_..-., . Right-Suite®U niv ersal 2018 18.0.11 RSU09479 Page 2
ACOPik ...1Pat MulliganWhem Townhomes11931 Left End.rup Calc=MJ8 Front Door faces: E