Loading...
Atlantic Beach Country Club - 41Donna & Mark, for info – will require some mod’s to water plans. Rick Ricky L. Carper, P.E. Public Works Director/City Engineer City of Atlantic Beach 1200 Sandpiper Lane Atlantic Beach, FL 32233 rcarper@coab.us<mailto:rcarper@coab.us> PH: (904) 247-5834 Fax: (904) 247-5843 Florida Public Works - First to Respond, Last to Leave www.apwaflorida.com<http://www.apwaflorida.com> From: Ratliff, Bob [mailto:BRatliff@coj.net] Sent: Tuesday, April 29, 2014 8:19 AM To: 'Pete Rodrigues'; Carper, Rick; Hubsch, Jeremy; Rick Wood (rwood@wooddev.net); Graham, Shirley; Walker, Jennifer; Jones, Mike Cc: 'Doug Maier' (dougmaier@comcast.net); 'Alex Acree' (Alex.Acree@taylorandwhite.com) Subject: RE: Atlantic Beach Country Club Gentlemen, The plans submitted for the Atlantic Beach Country Club are not approved in the submitted status. The following issues must be addressed prior to approval by this office. Regarding the bridge portion: NFPA 1 - 18.2.3.4.5.3 Vehicle load limits shall be posted at both entrances to bridges where required by the AHJ. Post the load limits as reflected in the signed and sealed letter dated April 24, 2014 from Zeyn Burhan Uzman, PE stating a bridge load of 72,000 pounds with occasional 84,000 pound load. Regarding the site plan for Atlantic Country Club: 1. NFPA 1 - 18.2.3.4.1.1 Fire department access roads shall have an unobstructed width of not less than 20 ft. Sheet 10 west side of project north of gated entrance the access road extending north to the second single story building does not meet the above criteria. 2. NFPA 1 - 18.3.1* An approved water supply capable of supplying the required fire flow for fire protection shall be provided to all premises upon which facilities, buildings, or portions of buildings are hereafter constructed or moved into the jurisdiction. Provide a fire hydrant within 500’ of the remote point of the above noted building. Also on the east side of the development to the west and south of the bridge, sheet 56 indicates a cul de sac with no fire hydrant provided. 3. NFPA 1 - 18.4.5.1.1 The minimum fire flow and flow duration requirements for one- and two-family dwellings having a fire flow area that does not exceed 5000 ft2 shall be 1000 gpm for 1 hour. Provide fire flow modeling showing the expected flow rates for the hydrants to be installed in this development that meet or exceed the above required minimum. If this minimum is not provided, reductions may require provision of fire sprinkler systems for each structure. For future developments I would suggest that all parties, including the Fire Marshal’s Office of Plan Review be provided plans for review very early in this process. If you have any questions, please do not hesitate to contact our office. Sincerely, Captain Bob Ratliff, CFPS Jacksonville Fire & Rescue Department Fire Prevention Division Office of Plan Review 214 N. Hogan Street Room 281 Jacksonville, FL 32202 (904) 255-8320 Office (904) 255-8559 Fax CONFIDENTIALITY NOTICE: Please note that under Florida's very broad public records law, e-mail communications to and from city officials are subject to public disclosure. From: Pete Rodrigues [mailto:Pete@rpcgc.com] Sent: Tuesday, April 29, 2014 7:02 AM To: Ratliff, Bob Cc: 'Doug Maier' (dougmaier@comcast.net<mailto:dougmaier@comcast.net>); 'Alex Acree' (Alex.Acree@taylorandwhite.com<mailto:Alex.Acree@taylorandwhite.com>) Subject: RE: Atlantic Beach Country Club Captain Standing by … please copy all addressed on this email Thanks Pete Rodrigues President RPC General Contractors, Inc. 248 Levy Road Atlantic Beach, FL 32233 (904) 241-4416 (904) 241-4427 fax pete@rpcgc.com<mailto:pete@rpcgc.com> www.rpcgc.com<http://www.rpcgc.com> This e-mail is intended for the addressee shown. It contains information that is confidential and protected from disclosure. Any review, dissemination or use of this transmission or its contents by persons or unauthorized employees of the intended organizations is strictly prohibited. From: Ratliff, Bob [mailto:BRatliff@coj.net] Sent: Tuesday, April 29, 2014 6:45 AM To: Pete Rodrigues Subject: RE: Atlantic Beach Country Club Mr. Rodriques, I will be emailing my comments on the plans this morning. Thank you, Captain Bob Ratliff, CFPS Jacksonville Fire & Rescue Department Fire Prevention Division Office of Plan Review 214 N. Hogan Street Room 281 Jacksonville, FL 32202 (904) 255-8320 Office (904) 255-8559 Fax CONFIDENTIALITY NOTICE: Please note that under Florida's very broad public records law, e-mail communications to and from city officials are subject to public disclosure. From: Pete Rodrigues [mailto:Pete@rpcgc.com] Sent: Tuesday, April 29, 2014 6:12 AM To: Ratliff, Bob Subject: Atlantic Beach Country Club Captain Did you have a chance to review the Country Club Plans? We are anxious to get the bridge started. Please call me with any questions 904-545-5911 cell Thanks Pete Rodrigues President RPC General Contractors, Inc. 248 Levy Road Atlantic Beach, FL 32233 (904) 241-4416 (904) 241-4427 fax pete@rpcgc.com<mailto:pete@rpcgc.com> www.rpcgc.com<http://www.rpcgc.com> This e-mail is intended for the addressee shown. It contains information that is confidential and protected from disclosure. Any review, dissemination or use of this transmission or its contents by persons or unauthorized employees of the intended organizations is strictly prohibited.