Fire Plan Review Updates - 14Jennifer,
Kade Bender with Bender and Modlin Fire Sprinkler, Inc. has provided adequate corrected information and we now have approved plans for all three of their sprinkler jobs. I hope to deliver
the approved plans to your office by close of business today.
Thank you,
Captain Bob Ratliff, CFPS
Jacksonville Fire & Rescue Department
Fire Prevention Division
Office of Plan Review
214 N. Hogan Street
Room 281
Jacksonville, FL 32202
(904) 255-8320 Office
(904) 255-8559 Fax
CONFIDENTIALITY NOTICE:
Please note that under Florida's very broad public records law, e-mail communications to and from city officials are subject to public disclosure.
From: Ratliff, Bob
Sent: Monday, June 16, 2014 10:18 AM
To: Walker, Jennifer (jwalker@coab.us); Jones, Mike (mjones@coab.us); 'Graham Shirley' (sgraham@coab.us)
Subject: Fire Plan Review Updates
The following plans have been reviewed by this office:
Nancy House Fire Sprinkler:
5500 Fleet Landing
Awaiting additional information regarding protection for covered patio portions.
Atlantic Beach Country Club
1600 Selva Marina
Golf Cart Shelter Structural Plans
Approved as submitted
Cabana / Fitness Bldg. Sprinkler Plans
Approved as submitted
Clubhouse
Not Approved:
NFPA 13 (2010)
(1) 7.2.3.1* The system capacity (volume) controlled by a dry pipe valve shall be determined by 7.2.3.2, 7.2.3.3, 7.2.3.4, 7.2.3.5, or 7.2.3.7.
7.2.3.2 System size shall be such that initial water is discharged from the system test connection in not more than
60 seconds, starting at the normal air pressure on the system and at the time of fully opened inspection test connection.
7.2.3.3 A system size of not more than 500 gal shall be permitted without a quick-opening device and shall not be required to meet any specific water delivery requirement to the inspection
test connection.
(2) No fire sprinkler inspector test valve indicated on plans.
If you require any additional information, give me a call. I will update you when we receive the requested information from the sprinkler contractor.
Thank you,
Captain Bob Ratliff, CFPS
Jacksonville Fire & Rescue Department
Fire Prevention Division
Office of Plan Review
214 N. Hogan Street
Room 281
Jacksonville, FL 32202
(904) 255-8320 Office
(904) 255-8559 Fax
CONFIDENTIALITY NOTICE:
Please note that under Florida's very broad public records law, e-mail communications to and from city officials are subject to public disclosure.