533 Atlantic Beach Ct Blower Door, Env Leakage
Testing Company: Name:Donovan Heat & Air Address:315 6th Ave South Jacksonville Beach, FLORIDA 32250 Phone: 904-270-2665 Donovanac.com Technician: Name:Stephen Keiler Credentials:FSEC Rater 1521 11/18 Email:steve@donovanac.com Building Information: Project ID:Blower Door 533 Address:533 Atlantic Beach Court Atlantic Beach, FLORIDA 32233 Geo-Tag Data:Latitude: 30.345194 Longitude: -81.407662 Timestamp: 2019-10-31 15:20:21 Customer Information: Name:Calddagh Constructors Address:533 Atlantic Beach Court Atlantic Beach, FLORIDA 32233 Phone: 904-8131-1728 Email: mattcladdagh@yahoo.com Measured Leakage:2,350.2 CFM50 Test ID:50 pa env Purpose of Test:50 Pa Env. Leakage Measured ACH50:3.62 Effective Leakage Area: 129.3 in² Building Volume:38,973.0 ft³Enclosure Surface Area: 3,543.0 ft² Flow Coefficient (C):184.8 Exponent (n): 0.650 (assumed) Test Standard:RESNET 380 One-Point Test Mode: Depressurize Test Characteristics:Indoor Temp: 82 °F Altitude: 20.0 ft Outdoor Temp: 83 °F Time Average Period: 10 seconds Test Date and Time:2019-10-31 15:39:15 Envelope Leakage Test Test Readings: Target (Pa)Bldg (Pa)Adj Bldg (Pa)Fan (Pa)Flow (cfm)Config Baseline -2.2 -50.0 -49.1 -46.8 -155.5 2,226.4 Ring A Test Equipment: Flow Device:Model 3 110V Fan Pressure Gauge:DG1000 Serial #: 2523 Calibration Date: 2018-10-12 Deviations from Standard: None Comments: Envelope Leakage Test (Page 2) Report generated by TEC Auto Test version 1.6.1 (1), © 2019 by The Energy Conservatory, Inc.