Behrens Engineering, LLC|1949 Jersey Street, Suite C, Jacksonville, FL 32210 | p: (904) 626-6598| e: Andrew@Behrens-Engineering.com
Page 1 of 3
October 1, 2021
Contractor:
Mark Boyles
Hygema House Movers, Inc.
P.O. Box 2655
Jacksonville, FL 32203
Project Address:
193 Beach Ave 2 – Lintel Repair
193 Beach Ave 2
Atlantic Beach, FL 32233
Dear Mr. Boyles,
Please accept this letter as the Engineers’ repairs for an existing concrete window lintel at the
above project address. This concrete lintel located on the west side of the existing two-story structure
was experiencing spalling concrete at the bottom of the member. Upon removal of the spalled concrete
there was no grout discovered within the continuous cell of the lintel. Additionally, both sides of the
window opening were missing vertical reinforcement and grout. Please refer to the image below on
page 2 with instructions on how to repair and reinforce the existing concrete lintel and vertical CMU
members on either side of the window opening in conjunction with the originally provided Behrens
Engineering, LLC. structural plans:
DocuSign Envelope ID: 5F17F00D-0151-4CF3-AEF8-FEB5A2EDAD3B
Behrens Engineering, LLC|1949 Jersey Street, Suite C, Jacksonville, FL 32210 | p: (904) 626-6598| e: Andrew@Behrens-Engineering.com
Page 2 of 3
See rebar anit-corrosive products and
grout products per Behrens Engineering,
LLC. structural plans dated 9-11-2021,
sheet S1.1
Drill & epoxy ea. #5
vertical bar into exist.
foundation a min. of 4"
embed. @ both
locations.
Open faces of all
vertical cells (full height
of reinforcement) and
add (1) new full length
#5 vertical rebar to ea.
side of window
opening. Lap 36" min.
as needed. Filling all
vertical CMU cells on
ea. side of window with
high strength 3000 psi
grout.
Remove and replace
exist. full length
corroded rebar member
with same size full
length member.
Add new full length #4
bar at bottom of lintel
prior to filling with high
strength 3000 psi grout.
Add new #3 stirrup bar
to ea. damaged exist.
stirrup bar present. Drill
& epoxy into lintel min.
4" embed.
Exist. concrete lintel.
DocuSign Envelope ID: 5F17F00D-0151-4CF3-AEF8-FEB5A2EDAD3B
Behrens Engineering, LLC|1949 Jersey Street, Suite C, Jacksonville, FL 32210 | p: (904) 626-6598| e: Andrew@Behrens-Engineering.com
Page 3 of 3
Should you need additional information or have questions, please feel free to contact me at
904-626-6598.
Sincerely,
Andrew Behrens, PE, CGC
Professional Engineer
FL License Number 88483
DocuSign Envelope ID: 5F17F00D-0151-4CF3-AEF8-FEB5A2EDAD3B
10/1/2021