211 Belvedere RES21-0179 Duct Plan_1Job #: 211 Belvedere Street
Performed by David C Brown for:
Ford Real Estate Capital
211 Belvedere Street
Atlantic Beach, FL 32233
ConsultAir, LLC
Jacksonville, Fl 32224
Phone: (904) 402-1463
www.LoadCalculations.com
Scale: 3/16" = 1'0"
Page 1
Right-Suite® Universal 2021
21.0.05 RSU15431
2021-Mar-17 07:40:54
...\211 Belvedere\211 Belvedere.rup
N
First Floor
Living Rm
Kitchen
Dining Rm
Foyer
,
Pwdr
T
24903 7911 32814 31688
Entire House Heat Loads
Cooling Heating
Sensible Latent Total Total
3.5 ton Split Heat Pump
Min 10kw Electric Heat
5"-6" Pleated Filter at AHU Return Plenum
128 cfm
104 cfm
77 cfm
34 cfm
138 cfm
77 cfm
358 cfm
6 "
7 "
7 "
8 "
5 "
6 "
14"x14" RA Grille
2 Zone Automatic Damper System
2ea 14" Zone Dampers
1ea 10" Bypass Damper
1ea Discharge Air Temp Sensor
Job #: 211 Belvedere Street
Performed by David C Brown for:
Ford Real Estate Capital
211 Belvedere Street
Atlantic Beach, FL 32233
ConsultAir, LLC
Jacksonville, Fl 32224
Phone: (904) 402-1463
www.LoadCalculations.com
Scale: 3/16" = 1'0"
Page 2
Right-Suite® Universal 2021
21.0.05 RSU15431
2021-Mar-17 07:40:54
...\211 Belvedere\211 Belvedere.rup
N
Second Floor
Mstr Bdrm
Bdrm 2
Clst 2
WC
Mstr Bath
Mstr Clst
Bdrm 4
Clst 4
Stairs Up
'
Bdrm 3Clst 3
Bath 2
Laundry
Linen
T
149 cfm
78 cfm
19 cfm
44 cfm
52 cfm
37 cfm
117 cfm
115 cfm
46 cfm
216 cfm
78 cfm
117 cfm
115 cfm
5 "
5 "
8 "
6 "
4 "
6 cfm
4 "
5 "
14 "
10 "
14 "
9 "
9 "8 "
7 "
5 "
7 "
289 cfm
12 "
7 "
7 "
9 "
8 "
6 "
14 "
12 "
12"x12" RA Grille
12"x12" RA Grille
12"x12" RA Grille
12"x12" RA Grille
12"x12" RA Grille
UL 181B mastic shall be used to seal all duct AND insulation joints, seams and/or connections.
Mastic shall be applied to the duct collar prior to sliding the duct inner liner onto the collar.
All supply and return boots that do not have a black inside liner shall be painted black if the inside
Return air grilles to be turned in the direction that allows the least visibility into the return air boot.
Drywall penetration for control wire behind thermostat shall be sealed air tight.
General Notes:
liner/metal will be visisble to occupants.
Repair tears in flexible duct outer jacket with UL 181B metal tape or mastic.
Horizontally installed flexible ducts to be supported every 5' or less and shall have no more than
Vertically installed flexible ducts to be stabilized by support straps at a maximum of every 6'.
1/2" per foot of sag.