Loading...
1955 Francis RES21-0217 Wood Connector.Anchoring Tie Down Evaluation Report rev 7-23-21_1 ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Servi ce, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright © 2020 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 31 ICC-ES Evaluation Report ESR-2552 Reissued March 2020 Revised December 2020 This report is subject to renewal March 2021. www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ® DIVISION: 06 00 00—WOOD, PLASTICS AND COMPOSITES Section: 06 05 23—Wood, Plastic, and Composite Fastenings REPORT HOLDER: SIMPSON STRONG-TIE COMPANY INC. EVALUATION SUBJECT: SIMPSON STRONG-TIE® FACE-MOUNT HANGERS FOR SAWN LUMBER, STRUCTURAL COMPOSITE LUMBER (SCL), PREFABRICATED WOOD I-JOISTS AND GLULAM BEAMS (ENGINEERED WOOD PRODUCTS) 1.0 EVALUATION SCOPE Compliance with the following codes: ◼ 2021, 2018, 2015, 2012 and 2009 International Building Code® (IBC) ◼ 2021, 2018, 2015, 2012 and 2009 International Residential Code® (IRC) For evaluation for compliance with codes adopted by the Los Angeles Department of Building and Safety (LADBS), see ESR-2552 LABC and LARC Supplement. Property evaluated: Structural 2.0 USES The Simpson Strong-Tie® face-mount hangers described in this report are used as wood framing connectors in wood construction in accordance with Section 2304.10.4 of the 2021 IBC, 2304.10.3 of the 2018 and 2015 IBC and Section 2304.9.3 of the 2012 and 2009 IBC. The face-mount hangers may also be used in structures regulated under the IRC when an engineered design is submitted in accordance with Section R301.1.3 of the IRC. 3.0 DESCRIPTION 3.1 General: With the exception of the CBH Hangers Series, the Simpson Strong-Tie face-mount hangers described in this report are U-shaped hangers that have prepunched holes for the installation of nails or Simpson Strong-Drive SDS screws, depending on the hanger model, into the face of the supporting wood header or beam or ledger. The CBH Hanger is a die-formed steel plate with a welded stud and prepunched holes for the installation of Simpson Strong- Drive SDS screws. 3.1.1: LU Series Hangers: The LU series hangers are formed from No. 20 gage galvanized steel. See Table 1 for hanger dimensions, required fasteners, and allowable loads; and Figure 1 for a drawing of a typical LU series hanger. 3.1.2 LUCZ Series Hangers: The LUCZ hangers have concealed flanges to allow for installation near the end of a supporting member such as a ledger or header. The hangers are formed from No. 18 gage galvanized steel coated with a G185 zinc coating. See Table 2 and Figure 2 for hanger dimensions, required fastener schedule, allowable loads and a typical installation detail. 3.1.3 Hangers: The U series hangers are formed from No. 16 gage galvanized steel. The hangers are face-nailed to the supporting wood header, and nailed to the supported solid sawn lumber, structural composite lumber or prefabricated wood I-joists with web stiffeners to accept the required size and number of joist nails shown in Table 3. See Table 3 for the U series hanger model numbers, hanger dimensions, required fasteners, and allowable loads. See Figure 3 for a drawing of a typical U series joist hanger. 3.1.4 HU and HUC Series Hangers: The HU and HUC series hangers are formed from No. 14 gage galvanized steel, and are face-nailed to the supporting wood header/beam and nailed to the solid sawn lumber, supported structural composite lumber or prefabricated wood I-joists with web stiffeners. HU hangers having a seat width (W) equal to or greater than 29/16 inches (65 mm) are available with concealed flanges and are specified with the model designation HUC. See Table 4 for hanger model numbers, hanger dimensions, required fasteners (minimum and maximum) and allowable loads based on the minimum and maximum nailing. The HU and HUC hangers have triangular and round holes in both the U-shaped portion supporting the wood joist and in the flanges attached to the supporting wood header/beam. The minimum allowable loads are achieved by filling only the round holes with the type and size of nails shown in Table 4, and the maximum allowable loads are achieved by filling all holes (both the round and triangular) with size of nails shown in Table 4. See Figures 4A and 4B for drawings of typical HU and HUC hangers, and Figure 4C shows a typical installation of an HU hanger supporting a prefabricated wood I-joist with approved web stiffeners. 3.1.5 HUCQ Series Hangers: The HUCQ series hangers are formed from No. 14 gage galvanized steel and are used to support glulam beams or other approved wood members. Other approved wood members must be laterally supported at the ends in accordance with Section 2308.4.6 of the IBC and Section R502.7 of the IRC. The hangers have ESR-2552 | Most Widely Accepted and Trusted Page 2 of 31 prepunched holes for the installation of Simpson Strong- Drive SDS series wood screws (SDS). See Table 5 for the HUCQ series model numbers, hanger dimensions, required fasteners and allowable loads. See Figure 5 for a drawing of the HUCQ series hanger. 3.1.6 LUS Series Hangers: The LUS series hangers are formed from No. 18 gage galvanized steel. The hangers have prepunched holes for the installation of nails that are driven at a 45-degree angle through the joist and into the header, which is described as double shear nailing in the installation instructions. See Table 6 for the hanger dimensions, required fasteners, and allowable loads; and Figure 6 for a drawing of a typical LUS series hanger. 3.1.7: MUS Joist Hanger: The MUS series hangers are formed from No. 18 gage galvanized steel. The U-shaped portion of the hangers has prepunched holes for the installation of joist nails that are driven at an angle through the joist and into the header, which is described as double shear nailing in the installation instructions. See Table 7 for the hanger dimensions, required fasteners, and allowable loads; Figure 7 for a drawing of a typical MUS series hanger. 3.1.8 HUS and HUSC Series Hangers: The HUS and HUSC series hangers having a seat width, W, of 39/16 inches (90 mm) are formed from No. 14 gage galvanized steel. The HUS1.81/10 hanger with a seat width, W, of 113/16 inches (46 mm) is formed from No. 16 gage galvanized steel. The HUS models having a seat width, W, of 39/16 inches (90 mm) are available with concealed flanges, which are specified with the model designation HUSC. The hangers have prepunched holes for the installation of nails that are driven at a 45-degree angle through the joist and into the header, which is described as double shear nailing in the installation instructions. See Table 8 for HUS series hanger models, hanger dimensions, required fasteners, and allowable loads. See Figure 8 for a drawing of a typical HUS hanger. 3.1.9 HHUS Series Hangers: The HHUS series hangers are formed from No. 14 gage galvanized steel. The hangers have pre-punched holes for the installation of nails that are driven at a 45 degree angle through the joist and into the header, which is described as double shear nailing in the installation instructions. See Table 9 for the hanger model numbers, hanger dimensions, required fasteners, and allowable loads. See Figure 9 for a drawing of a typical HHUS hanger. 3.1.10 HGUS Series Hangers: The HGUS series hangers are formed from No. 12 gage galvanized steel and are used to support glulam beams or other approved wood members. Other approved wood members must be laterally supported at the ends in accordance with Section 2308.4.6 of the IBC and Section R502.7 of the IRC. The hangers have prepunched holes for the installation of nails that are driven at a 45-degree angle through the joist and into the header, which is described as double shear nailing in the installation instructions. See Table 10 for the HGUS series hanger model numbers, hanger dimensions, required fasteners and allowable loads. See Figure 10 for a drawing of a typical HGUS hanger. 3.1.11 HTU Series Hangers: The HTU hangers are designed to support trusses installed with full or partial heel heights and gaps between the truss and the supporting girders of up to, but not exceeding, 1/2 inch (12.7 mm), as shown in Tables 11A and 11C, and 1/8 inch (3.2 mm) as shown in Table 11B. Minimum and maximum nailing options are given in Tables 11A, 11B, and 11C to address varying heel heights and support conditions. The HTU hangers are formed from No. 16 gage galvanized steel. See Table 11A and Figures 11A and 11B for hanger dimensions, required fastener schedule, allowable loads and an installation detail for installations in which the gap between the truss and the supporting girders is less than or equal to 1/2 inch (12.7 mm). See Table 11B and Figures 11A and 11B for hanger dimensions, required fastener schedule, allowable loads and an installation detail for installations in which the gap between the truss and the supporting girders is less than or equal to 1/8 inch (3.2 mm). See Table 11C and Figures 11A and 11C for hanger dimensions, required fastener schedule, allowable loads and an installation detail for installations in which the minimum allowable number of nails is driven into the supporting girder, and the gap between the truss and supporting girder is less than or equal to 1/2 inch (12.7 mm). 3.1.12 LGU, MGU, HGU and HHGU Series Hangers: The LGU and MGU series hangers are formed from No. 10 gage galvanized steel; HGU series hangers are formed from No. 7 gage galvanized steel; and HHGU series hangers are formed from No. 3 gage steel. The LGU, MGU, HGU and HHGU series hangers are used to support glulam beams or other approved wood members. Other approved wood members must be laterally supported at the ends in accordance with Section 2308.4.6 of the IBC and Section R502.7 of the IRC. The hangers have pre-punched holes for the installation of Simpson Strong-Drive SDS series wood screws (SDS). See Table 12 for the LGU, MGU, HGU and HHGU series model numbers, hanger dimensions, required fasteners and allowable loads. See Figure 12 for a drawing of the HHGU series hanger and a typical installation detail. 3.1.13 SUR/L Series Hangers: The SUR/L series hangers are formed from No. 16 gage galvanized steel. The SUR and SUL hangers are identical except they are skewed at 45 degrees to the right (SUR) and the left (SUL), respectively. See Table 13 for hanger models, hanger dimensions, required fasteners, and allowable loads. See Figure 13A for a drawing of a typical SUL hanger and Figure 13B for a typical SUR hanger installation. 3.1.14 HSUR/L Series Hangers: The HSUR/L series hangers are formed from No. 14 gage galvanized steel. The HSUR and HSUL hangers are identical except they are skewed at 45 degrees to the right (HSUR) and the left (HSUL), respectively, and are designed to support prefabricated wood I-joists having approved web stiffeners, and structural composite lumber (SCL). See Table 14 for the hanger model numbers, hanger dimensions, required fasteners, and allowable loads. See Figure 14A for a drawing of a typical HSUR hanger, and Figure 14B for a typical HSUR hanger installation. 3.1.15 IUS Series Hangers: The IUS series hangers are formed from No. 18 gage galvanized steel and are used exclusively to support prefabricated wood I-joists to a supporting wood member. See Table 15A for the IUS series hanger model numbers, hanger dimensions, and required fasteners; and Table 15B for allowable loads. See Figures 15A, 15B, and 15C for drawings of a typical IUS hanger and a typical IUS hanger installation. 3.1.16 MIU Series Joist Hangers: The MIU series hangers are formed from No. 16 gage galvanized steel and are used to support prefabricated wood I-joists or other approved wood members. Other approved wood members must be laterally supported at the ends in accordance with Section 2308.8.2 of the IBC and Section R502.7 of the IRC. See Table 16 for the MIU series hanger model numbers, hanger dimensions, required fasteners, and allowable loads. See Figure 16A for a drawing of a typical MIU hanger and Figure 16B for a drawing of a typical MIU hanger installation. ESR-2552 | Most Widely Accepted and Trusted Page 3 of 31 3.1.17 DU, DHU and DHUTF Series Hangers: The DU, DHU and DHUTF series hangers are face-mount and top-flange hangers that are formed from either No. 14 gage or No. 12 gage galvanized steel. They are designed to transfer joist floor loads to a wood stud wall through two layers of 5/8-inch-thick (15.9 mm) gypsum board complying with ASTM C1396, and are installed using a combination of nails and Simpson Strong-Drive SDS series wood screws (SDS), which are recognized under ESR-2236. These hangers are installed after the two layers of 5/8” Type X gypsum board is installed and fastened using, at a minimum, the fastener schedule in Item 14.1-5 in IBC Table 721.1(2). See Table 17A for hanger dimensions and allowable loads. See Table 17B for fastener schedule. See Figure 17 for a drawing of the DU, DHU and DHUTF hangers and a typical installation. 3.1.18 CBH Series Hangers: The CBH series hangers are face-mounted and installed in inverted pairs. They are formed from No. 3 gage steel. They are used to support glulam beams or other approved wood members and are installed using Simpson Strong-Drive SDS series wood screws (SDS), which are recognized under ESR-2236. See Table 18A & 18B for hanger dimensions, fastener schedules and allowable loads. See Figure 18 for a drawing of the CBH hangers and a typical installation. 3.2 Materials: 3.2.1 Steel: All hangers described in this report, with the exception of the CBH, HTU, HGUS and HHGU series hangers, are manufactured from galvanized steel complying with ASTM A653, SS designation, Grade 33, with a minimum yield strength, Fy, of 33,000 psi (227 MPa) and a minimum tensile strength, Fu, of 45,000 psi (310 MPa). The HTU and HGUS series hangers are manufactured from galvanized steel complying with ASTM A653, SS designation, Grade 40, with a minimum yield strength, Fy, of 40,000 psi (276 MPa) and a minimum tensile strength, Fu, of 55,000 psi (379 MPa). The HHGU and CBH series hangers are manufactured from nongalvanized steel complying with ASTM A1011 SS, Grade 33, with a minimum yield strength, Fy, of 33,000 psi (227 MPa) and a minimum tensile strength, Fu, of 52,000 psi (358 MPa). Base-metal thicknesses for the hangers in this report are as follows: NOMINAL THICKNESS (gage) MINIMUM BASE-METAL THICKNESS (inch) No. 3 0.2285 No. 7 0.1715 No. 10 0.1275 No. 12 0.0975 No. 14 0.0685 No. 16 0.0555 No. 18 0.0444 No. 20 0.0335 For SI: 1 inch = 25.4 mm. The galvanized zinc coating conforms to ASTM A924 and ASTM A653 with a G90 designation. Some models (designated with a model number ending with Z) are available with a G185 zinc coating specification in accordance with ASTM A653. Some models (designated with a model number ending with HDG) are available with a hot-dip galvanization, also known as “batch” galvanization, in accordance with ASTM A123, with a minimum specified coating weight of 2.0 ounces of zinc per square foot of surface area (600 g/m2), total for both sides. With the exception of the LUCZ, model numbers in this report do not include the Z or HDG ending, but the information shown applies. The lumber treater or holder of this report (Simpson Strong-Tie Company) should be contacted for recommendations on minimum corrosion resistance of steel connectors in contact with the specific proprietary preservative treated or fire retardant treated lumber. 3.2.2 Wood: Wood headers/beams to which the connectors are face-nailed must be either sawn lumber, structural glued-laminated timber, or engineered lumber having a minimum specific gravity of 0.50 (minimum equivalent specific gravity of 0.50 for engineered lumber), and having a maximum moisture content of 19 percent (16 percent for engineered lumber) except as noted in Section 4.1. The thickness of the supporting wood member (header) must be equal to or greater than the length of the fasteners specified in the tables in this report, or as required by wood member design, whichever is greater. Supported wood members that are prefabricated wood I-joists or SCL must be recognized in a current evaluation report, which will specify the allowable shear capacity and allowable reactions at supports for the proprietary engineered wood lumber. When required, web stiffeners for prefabricated wood I-joists must comply with specifications noted in the applicable evaluation report for the I-joists. The hangers described in this evaluation report may support I-joists having a current ICC-ES evaluation report. The evaluation report for the prefabricated wood I-joist must specify a minimum bearing length that is equal to or less than the hanger bearing length. When the hangers are used to support prefabricated wood I-joists, joist end reactions must not exceed the allowable joist end reaction per the I-joist manufacturer’s code report. For installation with engineered wood members, minimum allowable fastener spacing and end and edge distances, as specified in the applicable evaluation report for the engineered wood product, must be met. 3.2.3 Fasteners: Nails used for hangers described in this report must comply with ASTM F1667 and have the following minimum fastener dimensions and bending yield strengths (Fyb): FASTENERS SHANK DIAMETER (inches) NAIL LENGTH (inches) Fyb (psi) 10d × 11/2 0.148 11/2 90,000 10d 0.148 3 90,000 16d × 21/2 0.162 21/2 90,000 16d 0.162 31/2 90,000 For SI: 1 inch = 25.4 mm, 1 psi = 6.895 kPa. Some of the joist hangers described in this report are attached to the wood members using Simpson Strong-Drive SDS series wood screws as described in ESR-2236. Fasteners used in contact with preservative treated or fire retardant treated lumber must comply with Section 2304.10.6 of the 2021 IBC, 2304.10.5 of the 2018 and 2015 IBC, Section 2304.9.5 of the 2012 and 2009 IBC, 2015, and applicable sections of the IRC. The chemical treatment manufacturer or this report holder (Simpson Strong-Tie Company) should be contacted for recommendations on minimum corrosion resistance of fasteners and connection capacities of fasteners used with the specific proprietary preservative treated or fire retardant treated lumber. Unless otherwise indicated, fasteners listed in this report as 10d and 16d are 10d common and 16d common nails, respectively. ESR-2552 | Most Widely Accepted and Trusted Page 4 of 31 4.0 DESIGN AND INSTALLATION 4.1 Design: The tabulated allowable loads shown in this report are based on allowable stress design (ASD) and include the load duration factor, CD, corresponding with the applicable loads in accordance with the NDS. Tabulated allowable loads apply to products connected to wood used under dry conditions and where sustained temperatures are 100ºF (37.8ºC) or less. When products are installed to wood having a moisture content greater than 19 percent (16 percent for engineered wood products), or where wet service is expected, the allowable loads must be adjusted by the wet service factor, CM, specified in the NDS. When connectors are installed in wood that will experience sustained exposure to temperatures exceeding 100ºF (37.8ºC), the allowable loads in this report must be adjusted by the temperature factor, Ct, specified in the NDS. Connected wood members must be analyzed for load- carrying capacity at the connection in accordance with the NDS and the applicable evaluation report for engineered wood products. 4.2 Installation: Installation of the connectors must be in accordance with this evaluation report and the manufacturer’s published installation instructions. In the event of a conflict between this report and the manufacturer’s published installation instructions, this report governs. 5.0 CONDITIONS OF USE The Simpson Strong-Tie face-mount hangers described in this report comply with, or are suitable alternatives to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 The connectors must be manufactured, identified and installed in accordance with this report and the manufacturer’s published installation instructions. A copy of the instructions must be available at the jobsite at all times during installation. 5.2 Calculations showing compliance with this report must be submitted to the code official. The calculations must be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. 5.3 Adjustment factors noted in Section 4.1 and the applicable codes must be considered, where applicable. 5.4 Connected wood members and fasteners must comply, respectively, with Sections 3.2.2 and 3.2.3 of this report. 5.5 Use of connectors with preservative or fire retardant treated lumber must be in accordance with Section 3.2.1 of this report. Use of fasteners with preservative treated or fire retardant treated lumber must be in accordance with Section 3.2.3 of this report. 6.0 EVIDENCE SUBMITTED Data in accordance with the ICC-ES Acceptance Criteria for Joist Hangers and Similar Devices (AC13), dated March 2018 (editorially revised December 2020). Tests and calculations in accordance with the ICC-ES Acceptance Criteria for Dowel-Type Threaded Fasteners used in Wood (AC233), dated February 2020. 7.0 IDENTIFICATION 7.1 The products described in this report are identified with a die-stamped or an adhesive label indicating the name of the manufacturer (Simpson Strong-Tie) the model number, and the number of an index evaluation report (ESR-2523) that is used as an identifier for the products recognized in this report. 7.2 The report holder’s contact information is the following: SIMPSON STRONG TIE COMPANY INC. 5956 WEST LAS POSITAS BOULEVARD PLEASANTON, CALIFORNIA 94588 (800) 999-5099 www.strongtie.com ESR-2552 | Most Widely Accepted and Trusted Page 5 of 31 TABLE 1—ALLOWABLE LOADS FOR THE LU SERIES JOIST HANGERS MODEL No. DIMENSIONS1 (inches) FASTENERS2 (Quantity-Type) ALLOWABLE LOADS3,4,5 (lbf) W H B Header5 Joist Uplift6 Download CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 10d 16d 10d 16d 10d 16d LU24 19/16 31/8 11/2 4 2-10d x 11/2 240 465 555 530 630 570 655 LU26 19/16 43/4 11/2 6 4-10d x 11/2 540 695 835 800 950 860 1,030 LU28 19/16 63/8 11/2 8 6-10d x 11/2 850 930 1,110 1,065 1,180 1,145 1,180 LU210 19/16 713/16 11/2 10 6-10d x 11/2 850 1,160 1,390 1,330 1,580 1,430 1,615 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1Refer to Figure 1 for definitions of hanger nomenclature (W, H, B). 2Refer to Section 3.2.3 of this report for nail sizes and required minimum physical properties. 3Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 4LU Series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to its vertical position is 0.125 inch (3.2 mm). The height, H, of the joist hanger must be at least 60 percent of the height of the joist unless additional lateral restraint is provided, as designed by others. 5The quantity of 10d or 16d common nails specified in the “Header” column under “Fasteners” is required to achieve the tabulated allowable loads shown in the Allowable Download “10d” or “16d” columns. 6Allowable uplift loads are for hangers installed with either 10d or 16d common nails into the supporting header/beam, and have been increased for wind or earthquake loading with no further increase allowed. The allowable uplift loads must be reduced when other load durations govern. FIGURE 1—LU SERIES HANGER (See Table 1) ESR-2552 | Most Widely Accepted and Trusted Page 6 of 31 TABLE 2—DIMENSIONS, NAILING SCHEDULES AND DESIGN VALUES FOR LUCZ SERIES HANGERS MODEL No. DIMENSIONS (inches) FASTENERS 1 (Quantity-Type) ALLOWABLE LOADS 2, 3, 4, 5 (lbf) W H Into Supporting Member Into Supported Member Uplift 6 Download CD=1.60 CD =0.9 CD =1.0 CD =1.15 CD =1.25 CD =1.60 LUC26Z 19/16 43/4 6 - 10dx11/2 4 - 10d x 11/2 730 640 710 810 875 1,100 6 - 10d 730 640 710 810 875 1,100 6 - 16d 730 760 845 965 1,040 1,315 LUC210Z 19/16 73/4 10 - 10d x 11/2 6 - 10d x 11/2 985 1,065 1,185 1,345 1,455 1,830 10 - 10d 985 1,065 1,185 1,345 1,455 1,830 10 - 16d 985 1,270 1,410 1,605 1,735 2,180 For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N. 1Allowable loads correspond to installations where all pre-punched nail holes in the hanger are filled with nails. Refer to Section 3.2.3 of this report for nail sizes and required minimum physical properties. 2Tabulated allowable loads are for installations in wood members complying with Section 3.2.2 of this report. 3Tabulated loads must be selected based on the applicable load duration factor, CD, as permitted by the applicable building code. See Sections 4.1 and 4.2 for design and installation requirements. 4The maximum allowable gap between the joist end and the supporting member is 1/8 inch (3.2 mm). 5LUCZ series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to its vertical position is 0.125 inch (3.2 mm), for nominal 2x6 joists supported by the LUC26Z and nominal 2x10 joists supported by the LUC210Z. 6Allowable uplift loads have been increased for wind or earthquake loading with no further increase allowed. The tabulated allowable uplift loads must be reduced proportionally when other load durations govern. FIGURE 2⎯LUCZ SERIES HANGER AND INSTALLATION DETAIL ESR-2552 | Most Widely Accepted and Trusted Page 7 of 31 TABLE 3—ALLOWABLE LOADS FOR THE U SERIES JOIST HANGERS MODEL No. DIMENSIONS1 (inches) FASTENERS2 (Quantity-Type) ALLOWABLE LOADS4,5,6 (lbf) Uplift 6 Download W H B Header5 Joist CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 10d 16d 10d 16d 10d 16d U24 1 9/16 31/8 2 4 2-10d x 11/2 240 490 575 550 650 590 705 U26 19/16 43/4 2 6 4-10d x 11/2 535 730 865 830 980 890 1,055 U210 19/16 713/16 2 10 6-10d x 11/2 990 1,220 1,440 1,380 1,565 1,480 1,565 U214 19/16 10 2 12 8-10d x 11/2 990 1,465 1,730 1,655 1,955 1775 2,110 U14 113/16 101/4 2 14 6-10d x 11/2 970 - 2,015 - 2,285 - 2,465 U24R 21/16 3 5/8 2 4 2-10d x 11/2 240 490 575 550 650 590 705 U26R 21/16 5 5/8 2 8 4-10d x 11/2 535 975 1,150 1,105 1,305 1,185 1,410 U210R 21/16 9 1/8 2 14 6-10d x 11/2 990 1,710 2,015 1,930 2,280 2,070 2,465 U3510/14 25/16 9 2 14 6-10d x 11/2 970 - 2,015 - 2,285 - 2,465 U3510/20 25/16 10 5/16 2 16 6-10d x 11/2 970 - 2,305 - 2,615 - 2,820 U34 29/16 3 3/8 2 4 2-10d x 11/2 240 490 575 550 650 590 705 U36 29/16 5 3/8 2 8 4-10d x 11/2 535 975 1,150 1,105 1,305 1,185 1,410 U310 29/16 8 7/8 2 14 6-10d x 11/2 990 1,710 2,015 1,930 2,280 2,070 2,465 U314 29/16 10 1/2 2 16 6-10d x 11/2 990 1,950 2,305 2,210 2,610 2,370 2,815 U24-2 3 1/8 3 2 4 2-10d 240 490 575 550 650 590 705 U26-2 3 1/8 5 2 8 4-10d 535 975 1,150 1,105 1,305 1,185 1,410 U210-2 3 1/8 8 1/2 2 14 6-10d 990 1,750 2,015 1,930 2,280 2,070 2,465 U44 39/16 2 7/8 2 4 2-10d 240 490 575 550 650 590 705 U46 39/16 4 7/8 2 8 4-10d 535 975 1,150 1,105 1,305 1,185 1,410 U410 39/16 8 3/8 2 14 6-10d 990 1,710 2,015 1,930 2,280 2,070 2,465 U414 39/16 10 2 16 6-10d 990 1,950 2,305 2,210 2,610 2,370 2,815 U44R 41/16 2 5/8 2 4 2-16d 240 490 575 550 650 590 705 U46R 41/16 4 5/8 2 8 4-16d 535 975 1,150 1,105 1,305 1,185 1,410 U410R 41/16 8 1/8 2 14 6-16d 990 1,710 2,015 1,930 2,280 2,070 2,465 U26-3 45/8 4 1/4 2 8 4-10d 535 975 1,150 1,105 1,305 1,185 1,410 U210-3 45/8 7 3/4 2 14 6-10d 990 1,710 2,015 1,930 2,280 2,070 2,465 U3510-2 43/4 8 3/4 2 14 6-10d x 11/2 970 - 2,015 - 2,285 - 2,465 U3512-2 43/4 11 1/4 2 16 6-10d x 11/2 970 - 2,305 - 2,615 - 2,820 U66 51/2 5 2 8 4-10d 535 975 1,150 1,105 1,305 1,185 1,410 U610 51/2 8 1/2 2 14 6-10d 990 1,710 2,015 1,930 2,280 2,070 2,465 U610 51/2 8 1/2 2 14 6-10d x 11/2 970 1,705 2,015 1,930 2,285 2,075 2,465 U66R 6 5 2 8 4-16d 535 975 1,150 1,105 1,305 1,185 1,410 U610R 6 8 1/2 2 14 6-16d 990 1,710 2,015 1,930 2,280 2,070 2,465 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1Refer to Figure 3 (this page) for definitions of hanger nomenclature (W, H, B). 2Refer to Section 3.2.3 of this report for nail sizes and required minimum physical properties. 3Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 4U Series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to the vertical position of the joist is 0.125 inch (3.2 mm). The height, H, of the joist hanger must be at least 60 percent of the height of the joist unless additional lateral restraint is provided, as designed by others. 5The quantity of 10d or 16d common nails specified in the “Header” column under “Fasteners” is required to achieve the tabulated allowable loads shown in the Allowable Download “10d” or “16d” columns. 6Allowable uplift loads are for hangers installed with either 10d or 16d common nails into the supporting header/beam, and have been increased for wind or earthquake loading with no further increase allowed. The allowable uplift loads must be reduced when other load d urations govern. FIGURE 3—U SERIES JOIST HANGER ESR-2552 | Most Widely Accepted and Trusted Page 8 of 31 TABLE 4 - ALLOWABLE LOADS FOR THE HU HANGER SERIES MODEL NO. HANGER DIMENSIONS1 (inches) FASTENERS2 ALLOWABLE LOADS (lbf)2,3,4 (Quantity-Type) W H B Header Joist Uplift5 Download CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 HU26 1 9/16 3 1/16 2 1/4 4-16d 2-10d x 1 1/2 305 595 670 720 HU28 5 1/4 6-16d 4-10d x 11/2 605 895 1,010 1,080 HU210 7 1/8 8-16d 4-10d x 11/2 605 1,190 1,345 1,440 HU212 9 10-16d 6-10d x 11/2 1,135 1,490 1,680 1,800 HU214 10 1/8 12-16d 6-10d x 11/2 1,135 1,790 2,015 2,160 HU216 12 15/16 18-16d 8-10d x 11/2 1,510 2,680 3,025 3,240 HU1.81/5 1 13/16 5 3/8 2 1/2 16-16d 6-10d x 11/2 915 2,380 2,685 2,890 HU7 6 11/16 16-16d 8-10d x 11/2 1,515 2,380 2,685 2,890 HU9 9 5/16 24-16d 10-10d x 11/2 1,795 3,570 4,030 4,335 HU11 11 1/16 30-16d 10-10d x 11/2 1,795 4,465 4,705 4,810 HU14 13 11/16 36-16d 14-10d x 11/2 1,795 5,055 5,275 5,420 HU2.1/9 2 1/8 9 3/16 2 1/2 14-16d 6-10d x 11/2 915 2,085 2,350 2,530 HU2.1/11 11 16-16d 6-10d x 11/2 915 2,380 2,685 2,890 HU359 2 3/8 8 15/16 2 1/2 18-16d 10-10d x 11/2 1,795 2,680 3,020 3,250 HU3511 11 1/16 22-16d 10-10d x 11/2 1,795 3,275 3,695 3,970 HU3514 13 1/2 24-16d 12-10d x 11/2 1,795 3,570 4,030 4,335 HU3516/22 14 1/4 20-16d 8-10d x 11/2 1,515 2,975 3,360 3,610 HU3524/30 18 24-16d 14-10d x 11/2 1,795 3,570 4,030 4,335 HU34 2 9/16 3 3/8 2 1/2 4-16d 2-10d x 11/2 380 595 670 720 HU36 5 3/16 8-16d 4-10d x 11/2 605 1,190 1,345 1,440 HU38 6 9/16 10-16d 4-10d x 11/2 605 1,490 1,680 1,800 HU310 8 7/8 14-16d 6-10d x 11/2 915 2,085 2,350 2,530 HU312 10 5/8 16-16d 6-10d x 11/2 915 2,380 2,685 2,890 HU314 12 3/8 18-16d 8-10d x 11/2 1,515 2,680 3,020 3,250 HU316 14 1/8 20-16d 8-10d x 11/2 1,515 2,975 3,360 3,610 HU2.75/10 2 3/4 9 2 1/2 18-16d 10-10d x 11/2 1,795 2,680 3,020 3,250 HU2.75/12 10 3/4 22-16d 10-10d x 11/2 1,795 3,275 3,695 3,970 HU2.75/14 13 24-16d 14-10d x 11/2 1,795 3,570 4,030 4,335 HU2.75/16 14 1/16 26-16d 14-10d x 11/2 1,795 3,870 4,365 4,695 HU24-2 3 1/8 3 1/16 2 1/2 4-16d 2-10d 380 595 670 720 HU26-2 4 15/16 8-16d 4-10d 755 1,190 1,345 1,440 HU28-2 6 5/16 10-16d 4-10d 755 1,490 1,680 1,800 HU210-2 8 9/16 18-16d 10-10d 1,795 2,680 3,020 3,250 HU212-2 10 9/16 22-16d 10-10d 1,795 3,275 3,695 3,970 HU214-2 12 1/8 18-16d 8-10d 1,510 2,680 3,025 3,240 HU216-2 13 7/8 26-16d 12-10d 1,795 3,870 4,365 4,695 HU3.25/10.5 3 1/4 9 2 1/2 22-16d 10-10d 1,795 3,275 3,695 3,970 HU3.25/12 11 24-16d 12-10d 1,795 3,570 4,030 4,335 Please refer to next page for continuation of Table 4. ESR-2552 | Most Widely Accepted and Trusted Page 9 of 31 TABLE 4 (CONTINUED) - ALLOWABLE LOADS FOR THE HU HANGER SERIES MODEL NO. HANGER DIMENSIONS1 FASTENERS2 ALLOWABLE LOADS (lbf)3,4,5 (inches) (Quantity-Type) W H B Header Joist Uplift6 Download CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 HU44 3 9/16 2 7/8 2 1/2 4-16d 2-10d 380 595 670 720 HU46 4 11/16 8-16d 4-10d 755 1,190 1,345 1,440 HU48 6 3/32 10-16d 4-10d 755 1,490 1,680 1,800 HU410 8 3/8 14-16d 6-10d 1,135 2,085 2,350 2,520 HU412 10 5/16 16-16d 6-10d 1,135 2,385 2,690 2,880 HU414 11 7/8 18-16d 8-10d 1,510 2,680 3,025 3,240 HU416 13 5/8 20-16d 8-10d 1,510 2,980 3,360 3,600 HU4.12/9 4 1/8 8 5/8 2 1/2 18-16d 10-10d 1,795 2,680 3,020 3,250 HU4.12/11 10 5/16 22-16d 10-10d 1,795 3,275 3,695 3,970 HU4.28/9 4 9/32 9 2 1/2 18-16d 8-10d 1,515 2,680 3,020 3,250 HU4.28/11 11 22-16d 8-10d 1,515 3,275 3,695 3,970 HU26-3 4 11/16 4 9/16 2 1/2 8-16d 4-10d 755 1,190 1,345 1,440 HU210-3 8 14-16d 6-10d 1,135 2,085 2,350 2,520 HU212-3 9 3/4 16-16d 6-10d 1,135 2,385 2,690 2,880 HU214-3 12 1/16 18-16d 8-10d 1,510 2,680 3,025 3,240 HU216-3 13 7/8 20-16d 8-10d 1,510 2,980 3,360 3,600 HU4.75/9 4 3/4 9 2 1/2 18-16d 8-10d 1,515 2,680 3,020 3,250 HU4.75/11 11 22-16d 8-10d 1,515 3,275 3,695 3,970 HU3514-2 13 1/4 18-16d 8-10d 1,515 2,680 3,020 3,250 HU3516-2 15 1/4 26-16d 12-10d 1,795 3,870 4,365 4,695 HU3520-2 19 1/4 26-16d 12-10d 1,795 3,870 4,365 4,695 HU310-2 5 1/8 7 13/16 2 1/2 14-16d 6-10d 1,135 2,085 2,350 2,530 HU312-2 10 5/8 16-16d 6-10d 1,135 2,380 2,685 2,890 HU314-2 12 5/8 18-16d 8-10d 1,510 2,680 3,020 3,250 HU5.125/12 5 1/4 10 1/4 2 1/2 22-16d 8-16d 1,515 3,275 3,695 3,970 HU5.125/13.5 13 1/4 26-16d 12-16d 2,695 3,870 4,365 4,695 HU5.125/16 13 7/8 26-16d 12-16d 2,695 3,870 4,365 4,695 HU66 5 1/2 4 3/16 2 1/2 8-16d 4-16d 895 1,190 1,345 1,440 HU68 5 13/16 10-16d 4-16d 895 1,490 1,680 1,800 HU610 7 5/8 14-16d 6-16d 1,345 2,085 2,350 2,520 HU612 9 3/8 16-16d 6-16d 1,345 2,385 2,690 2,880 HU614 11 5/8 18-16d 8-16d 1,780 2,680 3,025 3,240 HU616 13 3/8 20-16d 8-16d 1,780 2,980 3,360 3,600 HU210-4 6 1/8 8 3/8 2 1/2 14-16d 6-16d 1,345 2,085 2,350 2,520 HU410-2 7 1/8 8 9/16 2 1/2 18-16d 8-16d 1795 2680 3020 3250 HU412-2 10 13/16 22-16d 8-16d 1795 3275 3695 3970 HU414-2 13 7/8 26-16d 12-16d 2695 3870 4365 4695 HU88 7 1/2 6 5/8 2 1/2 10-16d 4-16d 895 1,490 1,680 1,800 HU810 8 3/8 14-16d 6-16d 1,345 2,085 2,350 2,520 HU812 10 1/8 16-16d 6-16d 1,345 2,385 2,690 2,880 HU814 11 7/8 18-16d 8-16d 1,780 2,680 3,025 3,240 HU816 13 5/8 20-16d 8-16d 1,780 2,680 3,360 3,600 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1Refer to Figures 4a and 4b for definitions of hanger nomenclature (W, H, B). 2The Fastener column with “minimum quantity” refers to hangers installed with the designated type of nails into only round pre-punched holes of the hanger, and the Fastener column with “maximum quantity” refers to HU series and HUC series hangers installed with the designated type of nails into both round and triangle pre-punched holes of the hanger. The hanger size and fastener quantity are used to determine allowable loads listed in the table. 3Refer to Section 3.2.3 of this report for nail sizes and required minimum physical properties. 4HU series hangers with widths (W) equal to or greater than 2 9/16 inches (65 mm) are available with header flanges turned in (concealed) and are identified with the model designation HUC#. See Figure 4b. 5Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. ESR-2552 | Most Widely Accepted and Trusted Page 10 of 31 6HU Series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to the vertical position of the joist is 0.125 inch (3.2 mm). The height, H, of the joist hanger must be at least 60 percent of the height of the joist unless additional lateral restraint is provided, as designed by others. 7Allowable uplift loads have been increased for wind or earthquake loading with no further increase allowed. The allowable uplift loads must be reduced when other load durations govern. FIGURE 4A—HU SERIES HANGER FIGURE 4B—HUC SERIES HANGER (See Table 4) (See Table 4, Footnote 4) FIGURE 4C—TYPICAL HU HANGER INSTALLATION ESR-2552 | Most Widely Accepted and Trusted Page 11 of 31 TABLE 5—ALLOWABLE LOADS FOR THE HUCQ SERIES JOIST HANGERS MODEL NO. DIMENSIONS1 (inches) FASTENERS (Quantity-Type) ALLOWABLE LOADS2,3,4 (lbs) Uplift4 Download W H B Header Joist CD=1.6 CD=1.0 CD=1.15 CD=1.25 HUCQ1.81/9-SDS 1 13/16 9 3 8-SDS1/4" x 1 3/4" 4-SDS1/4" x 1 3/4" 1,310 2,000 2,300 2,500 HUCQ1.81/11-SDS 1 13/16 11 3 10-SDS1/4" x 1 3/4" 4-SDS1/4" x 1 3/4" 1,310 2,500 2,875 3,125 HUCQ310-SDS 2 9/16 9 3 8-SDS1/4" x 2 1/2" 4-SDS1/4" x 2 1/2" 1,220 3,120 3,590 3,685 HUCQ210-2-SDS 3 1/4 9 3 12-SDS1/4" x 2 1/2" 6-SDS1/4" x 2 1/2" 1,220 4,680 4,865 4,865 HUCQ410-SDS 3 9/16 9 3 12-SDS1/4" x 2 1/2" 6-SDS1/4" x 2 1/2" 2,365 4,500 4,500 4,500 HUCQ412-SDS 3 9/16 11 3 14-SDS1/4" x 2 1/2" 6-SDS1/4" x 2 1/2" 2,365 5,045 5,045 5,045 HUCQ210-3-SDS 4 5/8 9 3 12-SDS1/4" x 2 1/2" 6-SDS1/4" x 2 1/2" 2,215 4,680 4,865 4,865 HUCQ5.25/9-SDS 5 1/4 9 3 12-SDS1/4" x 2 1/2" 6-SDS1/4" x 2 1/2" 2,365 4,500 4,500 4,500 HUCQ5.25/11-SDS 5 1/4 11 3 14-SDS1/4" x 2 1/2" 6-SDS1/4" x 2 1/2" 2,365 5,045 5,045 5,045 HUCQ610-SDS 5 9/16 9 3 12-SDS1/4" x 2 1/2" 6-SDS1/4" x 2 1/2" 2,365 4,680 5,210 5,210 HUCQ612-SDS 5 9/16 11 3 14-SDS1/4" x 2 1/2" 6-SDS1/4" x 2 1/2" 2,365 5,210 5,210 5,210 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1Refer to Figure 5 (this page) for definitions of hanger nomenclature (W, H, B). 2Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 3The uplift loads have been increased for wind or earthquake loading with no further increase allowed. The allowable uplift loads must be reduced when other load durations govern. 4For supported members other than glulam beams, lateral support must be provided at the ends in accordance with Section 2308.8 .2 of the IBC or Section R502.7 of the IRC. FIGURE 5—DIMENSIONS AND TYPICAL INSTALLATION OF THE HUCQ SERIES HANGERS ESR-2552 | Most Widely Accepted and Trusted Page 12 of 31 TABLE 6 ALLOWABLE LOADS FOR THE LUS SERIES JOIST HANGERS MODEL NO. DIMENSIONS1 (inches) COMMON NAILS2 (Quantity-Type) ALLOWABLE LOADS3,4 (lbf) W H B Header Joist5 Uplift6 Download CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 LUS24 1 9/16 3 1/8 1 3/4 4-10d 2-10d 435 670 765 820 LUS26 1 9/16 4 3/4 1 3/4 4-10d 4-10d 1,165 865 990 1,060 LUS28 1 9/16 6 5/8 1 3/4 6-10d 4-10d 1,165 1,100 1,260 1,350 LUS210 1 9/16 7 13/16 1 3/4 8-10d 4-10d 1,165 1,335 1,530 1,640 LUS36 2 9/16 5 1/4 2 4-16d 4-16d 1,060 1,030 1,170 1,265 LUS310 2 9/16 7 9/32 2 6-16d 4-16d 1,070 1,315 1,490 1,610 LUS24-2 3 1/8 3 1/8 2 4-16d 2-16d 410 800 905 980 LUS26-2 3 1/8 4 15/16 2 4-16d 4-16d 1,060 1,030 1,170 1,265 LUS28-2 3 1/8 7 2 6-16d 4-16d 1,060 1,315 1,490 1,610 LUS210-2 3 1/8 8 15/16 2 8-16d 6-16d 1,445 1,830 2,075 2,245 LUS214-2 3 1/8 10 15/16 2 10-16d 6-16d 1,445 2,110 2,395 2,590 LUS44 3 9/16 3 2 4-16d 2-16d 410 800 905 980 LUS46 3 9/16 4 3/4 2 4-16d 4-16d 1,060 1,030 1,170 1,265 LUS48 3 9/16 6 3/4 2 6-16d 4-16d 1,060 1,315 1,490 1,610 LUS410 3 9/16 8 3/4 2 8-16d 6-16d 1,445 1,830 2,075 2,245 LUS414 3 9/16 10 3/4 2 10-16d 6-16d 1,445 2,110 2,395 2,590 LUS26-3 4 5/8 4 1/8 2 4-16d 4-16d 1,060 1,030 1,170 1,265 LUS28-3 4 5/8 6 1/4 2 6-16d 4-16d 1,060 1,315 1,490 1,610 LUS210-3 4 5/8 8 13/16 2 8-16d 6-16d 1,445 1,830 2,075 2,245 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1Refer to Figure 6 (this page) for definitions of hanger nomenclature (W, H, B). 2Refer to Section 3.2.3 of this report for nail sizes and required minimum physical properties. 3Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 4LUS Series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to the vertical position of the joist is 0.125 inch (3.2 mm). The height, H, of the joist hanger must be at least 60 percent of the height of the joist unless additional lateral restraint is provided, as designed by others. 5Joist nails must be driven at a 45 degree angle through the joist into the header/beam (double shear nailing) to achieve the tabulated loads. 6Allowable uplift loads have been increased for wind or earthquake loading with no further increase is allowed. The allowable uplift loads must be reduced when other load durations govern. FIGURE 6—LUS SERIES HANGER (See Table 6) ESR-2552 | Most Widely Accepted and Trusted Page 13 of 31 TABLE 7—ALLOWABLE LOADS FOR THE MUS SERIES HANGERS MODEL NO. DIMENSIONS1 (inches) COMMON NAILS2 (Quantity-Type) ALLOWABLE LOADS3,4 (lbf) W H B Header Joist5 Uplift6 Download CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 MUS26 19/16 53/16 2 6–10d 6–10d 930 1,295 1,480 1,560 MUS28 19/16 63/4 2 8–10d 8–10d 1,320 1,730 1,975 2,125 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1Refer to Figure 7 (this page) for definitions of hanger nomenclature (W, H, B). 2Refer to Section 3.2.3 of this report for nail sizes and required minimum physical properties. 3Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 4MUS series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to the vertical position of the joist is 0.125 inch (3.2 mm). The height, H, of the joist hanger must be at least 60 percent of the height of the joist unless additional lateral restraint is provided, as designed by others. 5Joist nails must be driven at a 45 degree angle through the joist into the header/beam (double shear nailing) to achieve the tabulated loads. 6Allowable uplift loads have been increased for wind or earthquake loading with no further increase is allowed. The allowable uplift loads must be reduced when other load durations govern. FIGURE 7—MUS HANGER (See Table 7) ESR-2552 | Most Widely Accepted and Trusted Page 14 of 31 TABLE 8—ALLOWABLE LOADS FOR THE HUS AND HUSC SERIES HANGERS MODEL NO. DIMENSIONS1 (inches) COMMON NAILS2 (Quantity-Type) ALLOWABLE LOADS3,4,7 (lbf) W H B Header Joist5 Uplift6 Download CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 HUS26 15/8 53/8 3 14-16d 6-16d 1,320 2,735 3095 3230 HUS28 15/8 71/16 3 22-16d 8-16d 1,760 4095 4095 4095 HUS210 15/8 91/16 3 30-16d 10-16d 2,635 5,450 5,795 5,830 HUS1.81/10 113/16 87/8 3 30-16d 10-16d 2,675 5,510 5,830 5,830 HUS46 39/16 45/16 2 4-16d 4-16d 1,165 1,090 1,225 1,320 HUS48 39/16 615/16 2 6-16d 6-16d 1,320 1,630 1,840 1,980 HUS410 39/16 815/16 2 8-16d 8-16d 3,265 2,175 2,455 2,640 HUS412 39/16 103/4 2 10-16d 10-16d 3,435 2,720 3,070 3,300 HUS26-2 31/8 53/16 2 4-16d 4-16d 1,165 1,090 1,225 1,320 HUS28-2 31/8 73/16 2 6-16d 6-16d 1,320 1,630 1,840 1,980 HUS210-2 31/8 93/16 2 8-16d 8-16d 3,285 2,175 2,455 2,640 HUS212-2 31/8 11 2 10-16d 10-16d 3,435 2,720 3,070 3,300 For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N. 1Refer to Figure 8 (this page) for definitions of hanger nomenclature (W, H, B). 2Refer to Section 3.2.3 of this report for nail sizes and required minimum physical properties. 3Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 4HUS series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to the vertical position of the joist is 0.125 inch (3.2 mm). The height, H, of the joist hanger must be at least 60 percent of the height of the joist unless additional lateral restraint is provided, as designed by others. 5Joist nails must be driven at a 45 degree angle through the joist into the header/beam (double shear nailing) to achieve the tabulated loads. 6Allowable uplift loads have been increased for wind or earthquake loading with no further increase is allowed. The allowable uplift loads must be reduced when other load durations govern. 7HUS series hangers with widths (W) equal to or greater than 39/16 inches (90 mm) are available with header flanges turned in (concealed) and are identified with the model designation HUSC#. FIGURE 8—HUS SERIES HANGER (See Table 8) ESR-2552 | Most Widely Accepted and Trusted Page 15 of 31 TABLE 9 - ALLOWABLE LOADS FOR THE HHUS SERIES HANGERS MODEL NO. DIMENSIONS1 (inches) COMMON NAILS2 (Quantity-Type) ALLOWABLE LOADS3,4 (lbf) W H B Header Joist5 Uplift6 Download CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 HHUS26-2 3 5/16 5 7/16 3 14-16d 6-16d 1,320 2,820 3,185 3,425 HHUS28-2 3 5/16 7 1/2 3 22-16d 8-16d 1,760 4,255 4,800 5,165 HHUS210-2 3 5/16 9 1/8 3 30-16d 10-16d 3,550 5,690 6,420 6,485 HHUS46 3 5/8 5 1/4 3 14-16d 6-16d 1,320 2,820 3,185 3,425 HHUS48 3 5/8 7 1/8 3 22-16d 8-16d 1,760 4,255 4,800 5,165 HHUS410 3 5/8 9 3 30-16d 10-16d 3,550 5,690 6,420 6,485 HHUS5.50/10 5 1/2 9 3 30-16d 10-16d 3,550 5,690 6,420 6,485 HHUS7.25/10 7 1/4 9 3 5/16 30-16d 10-16d 3,550 5,690 6,420 6,485 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1Refer to Figure 9 (this page) for definitions of hanger nomenclature (W, H, B). 2Refer to Section 3.2.3 of this report for nail sizes and required minimum physical properties. 3Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 4HUS series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to the vertical position of the joist is 0.125 inch (3.2 mm). The height, H, of the joist hanger must be at least 60 percent of the height of the joist unless additional lateral restraint is provided, as designed by others. 5Joist nails must be driven at a 45 degree angle through the joist into the header/beam to achieve the tabulated loads. 6Allowable uplift loads have been increased for wind or earthquake loading with no further increase is allowed. The allowable uplift loads must be reduced when other load durations govern. FIGURE 9—HHUS SERIES HANGER (See Table 9) ESR-2552 | Most Widely Accepted and Trusted Page 16 of 31 TABLE 10—ALLOWABLE LOADS FOR THE HGUS SERIES JOIST HANGERS MODEL NO. DIMENSIONS1 (Inches) FASTENERS2 (Quantity-Type) ALLOWABLE LOADS3,5,6 (lbs) Uplift4 Download W H B Header Joist3 CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 HGUS26 1 5/8 5 3/8 5 20-16d 8-16d 875 4,340 4,850 5,170 HGUS28 1 5/8 7 1/8 5 36-16d 12-16d 1,650 7,275 7,275 7,275 HGUS210 1 5/8 9 1/8 5 46-16d 16-16d 2,090 9,100 9,100 9,100 HGUS2.75/10 2 3/4 8 7/8 4 46-16d 16-16d 4,095 9,100 9,100 9,100 HGUS2.75/12 2 3/4 10 7/8 4 56-16d 20-16d 5,040 9,400 9,400 9400 HGUS2.75/14 2 3/4 12 7/8 4 66-16d 22-16d 5,515 9,695 9,695 9,695 HGUS3.25/10 3 1/4 8 5/8 4 46-16d 16-16d 4,095 9,100 9,100 9,100 HGUS3.25/12 3 1/4 10 5/8 4 56-16d 20-16d 5,040 9,400 9,400 9,400 HGUS26-2 3 7/16 5 7/16 4 20-16d 8-16d 2,155 4,340 4,850 5,170 HGUS28-2 3 7/16 7 3/16 4 36-16d 12-16d 3,235 7,460 7,460 7,460 HGUS210-2 3 7/16 9 3/16 4 46-16d 16-16d 4,095 9,100 9,100 9,100 HGUS46 3 5/8 5 5/16 4 20-16d 8-16d 2,155 4,360 4,885 5,230 HGUS48 3 5/8 7 1/16 4 36-16d 12-16d 3,235 7,460 7,460 7,460 HGUS410 3 5/8 9 1/16 4 46-16d 16-16d 4,095 9,100 9,100 9,100 HGUS412 3 5/8 10 7/16 4 56-16d 20-16d 5,040 9,400 9,400 9,400 HGUS414 3 5/8 12 7/16 4 66-16d 22-16d 5,515 9,695 9,695 9,695 HGUS26-3 4 15/16 5 7/16 4 20-16d 8-16d 2,155 4,340 4,850 5,170 HGUS28-3 4 15/16 7 3/16 4 36-16d 12-16d 3,235 7,460 7,460 7,460 HGUS210-3 4 15/16 9 3/16 4 46-16d 16-16d 4,095 9,100 9,100 9,100 HGUS212-3 4 15/16 10 3/4 4 56-16d 20-16d 5,205 11,835 13,215 14,085 HGUS214-3 4 15/16 12 3/4 4 66-16d 22-16d 5,360 13,735 14,360 14,360 HGUS5.25/10 5 1/4 9 1/16 4 46-16d 16-16d 4,095 9,100 9,100 9,100 HGUS5.25/12 5 1/4 10 5/8 4 56-16d 20-16d 5,040 9,400 9,400 9,400 HGUS5.5/8 5 1/2 6 15/16 4 36-16d 12-16d 3,235 7,460 7,460 7,460 HGUS5.5/10 5 1/2 8 15/16 4 46-16d 16-16d 4,095 9,100 9,100 9,100 HGUS5.5/12 5 1/2 10 1/2 4 56-16d 20-16d 5,040 9,400 9,400 9,400 HGUS5.5/14 5 1/2 12 1/2 4 66-16d 22-16d 5,515 9,695 9,695 9,695 HGUS5.62/10 5 5/8 8 7/8 4 46-16d 16-16d 4,095 9,100 9,100 9,100 HGUS5.62/12 5 5/8 10 7/16 4 56-16d 20-16d 5,040 9,400 9,400 9,400 HGUS5.62/14 5 5/8 12 7/16 4 66-16d 22-16d 5,515 9,695 9,695 9,695 HGUS26-4 6 9/16 5 7/16 4 20-16d 8-16d 2,155 4,340 4,850 5,170 HGUS28-4 6 9/16 7 3/16 4 36-16d 12-16d 3,235 7,460 7,460 7,460 HGUS210-4 6 9/16 9 3/16 4 46-16d 16-16d 4,095 9,100 9,100 9,100 HGUS212-4 6 9/16 10 9/16 4 56-16d 20-16d 5,205 11,835 13,215 14,085 HGUS214-4 6 9/16 12 9/16 4 66-16d 22-16d 5,360 13,735 14,360 14,360 HGUS6.88/10 6 7/8 8 13/16 4 46-16d 16-16d 4,095 9,100 9,100 9,100 HGUS6.88/12 6 7/8 10 13/16 4 56-16d 20-16d 5,045 9,400 9,400 9,400 HGUS6.88/14 6 7/8 12 13/16 4 66-16d 22-16d 5,515 9,695 9,695 9,695 HGUS7.25/8 7 1/4 7 1/4 4 36-16d 12-16d 3,235 7,460 7,460 7,460 HGUS7.25/10 7 1/4 8 5/8 4 46-16d 16-16d 4,095 9,100 9,100 9,100 HGUS7.25/12 7 1/4 10 5/8 4 56-16d 20-16d 5,040 9,400 9,400 9,499 HGUS7.25/14 7 1/4 12 5/8 4 66-16d 22-16d 5,515 9,695 9,695 9,695 HGUS7.37/10 7 3/8 8 9/16 4 46-16d 16-16d 4,065 9,095 9,095 9,095 HGUS7.37/12 7 3/8 10 9/16 4 56-16d 20-16d 5,205 11,835 13,215 14,085 HGUS7.37/14 7 3/8 12 9/16 4 66-16d 22-16d 5,515 13,735 14,360 14,360 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. ESR-2552 | Most Widely Accepted and Trusted Page 17 of 31 1Refer to Figure 10 (this page) for definitions of hanger nomenclature (W, H, B). 2Refer to Section 3.2.3 of this report for nail sizes and required minimum physical properties. 3Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 4Joist nails must be driven at a 45 degree angle through the joist into the header/beam (double shear nailing) to achieve tabulated loads. 5Allowable uplift loads have been increased for wind or earthquake loading with no further increase allowed. The allowable uplift loads must be reduced when other load durations govern. 6HGUS series hangers provide torsional resistance, which is defined as the moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to the vertical position of the joist is 0.125” (3.2 mm). The height, H, of the joist hanger must be at least 60 percent of the height of the joist unless additional lateral restraint is provided, as designed by others. FIGURE 10⎯HGUS SERIES JOIST HANGER ESR-2552 | Most Widely Accepted and Trusted Page 18 of 31 TABLE 11A—DIMENSIONS, NAILING SCHEDULES AND DESIGN VALUES FOR HTU SERIES HANGERS (1/2 Inch Maximum Gap between Supporting Member and Supported Member – Maximum Number of Nails into Supporting Member) MODEL No. DIMENSIONS 3 (inches) FASTENERS 4 (Quantity-Type) ALLOWABLE LOADS 5, 6, 7 (lbf) W H B Into Supporting Member Into Supported Member Uplift 8 Download CD=1.6 CD=0.9 CD=1.0 CD=1.15 CD=1.25 CD=1.6 Single 2X Sizes HTU26 (1/2” Gap – Min Nail)1 15/8 57/16 31/2 20-16d 11-10dx11/2 635 2,395 2,395 2,395 2,395 2,395 15/8 57/16 31/2 20-16d 14-10dx11/2 1,175 2,640 2,940 3,100 3,100 3,100 HTU26 (1/2” Gap – Max Nail)2 15/8 57/16 31/2 20-16d 20-10dx11/2 1,215 2,640 2,940 3,320 3,580 3,630 HTU28 (1/2” Gap – Min Nail)1 15/8 71/16 31/2 26-16d 14-10dx11/2 1,110 3,430 3,770 3,770 3,770 3,770 HTU28 (1/2” Gap – Max Nail)2 15/8 71/16 31/2 26-16d 26-10dx11/2 1,920 3,430 3,820 4,315 4,655 5,015 HTU210 (1/2” Gap – Min Nail)1 15/8 91/16 31/2 32-16d 14-10dx11/2 1250 3,600 3,600 3,600 3,600 3,600 HTU210 (1/2” Gap – Max Nail)2 15/8 91/16 31/2 32-16d 32-10dx11/2 3255 4,225 4,705 5,020 5,020 5,020 Double 2X Sizes HTU26-2 (1/2” Gap – Min Nail)1 35/16 57/16 31/2 20-16d 14-10d 1,515 2,640 2,940 3,320 3,500 3,500 HTU26-2 (1/2” Gap – Max Nail)2 35/16 57/16 31/2 20-16d 20-10d 1,910 2,640 2,940 3,320 3,500 3,500 HTU28-2 (1/2” Gap – Min Nail)1 35/16 71/16 31/2 26-16d 14-10d 1,490 3,430 3,820 3,980 3,980 3,980 HTU28-2 (1/2” Gap – Max Nail)2 35/16 71/16 31/2 26-16d 26-10d 3,035 3,430 3,820 4,315 4,655 5,520 HTU210-2 (1/2” Gap – Min Nail)1 35/16 91/16 31/2 32-16d 14-10d 1,755 4,225 4,255 4,255 4,255 4,255 HTU210-2 (1/2” Gap – Max Nail)2 35/16 91/16 31/2 32-16d 32-10d 3,855 4,225 4,705 5,310 5,730 6,470 For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N. 1The suffix ‘(1/2” Gap – Min Nail)’ corresponds to installed conditions where the gap between the supporting member and supported member is more than 1/8 inch (3.2 mm) and less than or equal to 1/2 inch (12.7 mm), and, at a minimum, the number of nails specified in the table above are installed into the supported wood truss. Refer to Figure 11B on page 19 for a typical installation detail. 2The suffix ‘(1/2” Gap – Max Nail)’ corresponds to installed conditions where the gap between the supporting member and supported member is more than 1/8 inch (3.2 mm) and less than or equal to 1/2 inch (12.7 mm), and all of the pre-punched nail holes in the U-shaped portion of the hanger supporting the truss (joist) are filled with nails. This is designated in the table as “Max Nail” and is shown in Figure 11B. 3Refer to Figure 11A for definitions of hanger nomenclature (W, H, B). 4Allowable loads correspond to installations where the maximum possible number of nails is driven into the supporting member. Refer to Section 3.2.3 of this report for nail sizes and required minimum physical properties. 5Tabulated allowable loads are for instal1ations in wood members complying with Section 3.2.2 of this report. 6Tabulated loads must be selected based on the applicable load duration factor, CD, as permitted by the applicable building code. See Sections 4.1 and 4.2 for design and installation requirements. 7HTU series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to its vertical position is 0.125 inch (3.2 mm), for joists having a height no greater than the height (H) of the hanger. 8Allowable uplift loads have been increased for wind or earthquake loading with no further increase allowed. The tabulated allowable uplift loads must be reduced proportionally when other load durations govern. FIGURE 11A—HTU SERIES HANGER ESR-2552 | Most Widely Accepted and Trusted Page 19 of 31 TABLE 11B—DIMENSIONS, NAILING SCHEDULES AND DESIGN VALUES FOR HTU SERIES HANGERS (1/8 Inch Maximum Gap between Supporting Member and Supported Member – Maximum Number of Nails into Supporting Member) MODEL No. DIMENSIONS 3 (inches) FASTENERS 4 (Quantity-Type) ALLOWABLE LOADS 5, 6, 7 (lbf) W H B Into Supporting Member Into Supported Member Uplift 8 Download CD=1.6 CD=0.9 CD=1.0 CD=1.15 CD=1.25 CD=1.6 Single 2X Sizes HTU26 (1/8” Gap – Min Nail)1 15/8 57/16 31/2 20-16d 11-10dx11/2 640 2,640 2,670 2,670 2,670 2,670 15/8 57/16 31/2 20-16d 14-10dx11/2 1,250 2,640 2,940 3,200 3,200 3,200 HTU26 (1/8” Gap – Max Nail)2 15/8 57/16 31/2 20-16d 20-10dx11/2 1,555 2,640 2,940 3,320 3,580 4,010 HTU28 (1/8” Gap – Min Nail)1 15/8 71/16 31/2 26-16d 14-10dx11/2 1,235 3,430 3,820 3,895 3,895 3,895 HTU28 (1/8” Gap – Max Nail)2 15/8 71/16 31/2 26-16d 26-10dx11/2 2,020 3,430 3,820 4,315 4,655 5,435 HTU210 (1/8” Gap – Min Nail)1 15/8 91/16 31/2 32-16d 14-10dx11/2 1,330 4,225 4,300 4,300 4,300 4,300 HTU210 (1/8” Gap – Max Nail)2 15/8 91/16 31/2 32-16d 32-10dx11/2 3,315 4,225 4,705 5,310 5,730 5,995 Double 2X Sizes HTU26-2 (1/8” Gap – Min Heel)1 35/16 57/16 31/2 20-16d 14-10d 1,515 2,640 2,940 3,320 3,580 3,910 HTU26-2 (1/8” Gap – Max Nail)2 35/16 57/16 31/2 20-16d 20-10d 2,175 2,640 2,940 3,320 3,580 4,480 HTU28-2 (1/8” Gap – Min Nail)1 35/16 71/16 31/2 26-16d 14-10d 1,530 3,430 3,820 4,310 4,310 4,310 HTU28-2 (1/8” Gap – Max Nail)2 35/16 71/16 31/2 26-16d 26-10d 3,485 3,430 3,820 4,315 4,655 5,825 HTU210-2 (1/8” Gap – Min Nail)1 35/16 91/16 31/2 32-16d 14-10d 1,755 4,225 4,705 4,815 4,815 4,815 HTU210-2 (1/8” Gap – Max Nail)2 35/16 91/16 31/2 32-16d 32-10d 4,110 4,225 4,705 5,310 5,730 6,515 For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N. 1The suffix ‘(1/8” Gap – Min Nail)’ corresponds to installed conditions where the gap between the supporting member and supported wood truss is 1/8 inch (3.2 mm) or less, and at a minimum, the number of nails specified in the table above are installed into the supported wo od truss. Refer to Figure 10B for a typical installation detail. 2The suffix ‘(1/8” Gap – Max Nail)’ corresponds to installed conditions where the gap between the supporting member and supported wood truss is 1/8 inch (3.2 mm) or less, and the all of the pre-punched nail holes in the U-shaped portion of the hanger supporting the truss (joist) are filled with nails. This is designated in the table as “Max Nail” and is shown in Figure 11B on this page. 3Refer to Figure 11A for definitions of hanger nomenclature (W, H, B). 4Allowable loads correspond to installations where the maximum possible number of nails is installed into the supporting member. Refer to Section 3.2.3 of this report for nail sizes and required minimum physical properties. 5Tabulated allowable loads are for installations in wood members complying with Section 3.2.2 of this report. 6Tabulated loads must be selected based on the applicable load duration factor, CD, as permitted by the applicable building code. See Sections 4.1 and 4.2 for design and installation requirements. 7HTU series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to its vertical position is 0.125 inch (3.2 mm), for joists having a height no greater than the height (H) of the hanger. 8Allowable uplift loads have been increased for wind or earthquake loading with no further increase allowed. The tabulate d allowable uplift loads must be reduced proportionally when other load durations govern. FIGURE 11B—TYPICAL HTU INSTALLATION ESR-2552 | Most Widely Accepted and Trusted Page 20 of 31 TABLE 11C—DIMENSIONS, NAILING SCHEDULES AND DESIGN VALUES FOR HTU SERIES HANGERS – ALTERNATE INSTALLATION (1/2 Inch Maximum Gap between Supporting Member and Supported Member - Minimum Number of Nails into Supporting Member) For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N. 1The suffix ‘(1/2” Gap – Min Nail)’ corresponds to installed conditions where the gap between the supporting member and supported member is more than 1/8 inch (3.2 mm) and less than or equal to 1/2 inch (12.7 mm), and at a minimum, the number of nails specified in the tabl e above are installed into the supported wood truss. Refer to Figure 11C for an alternate installation detail. 2The suffix ‘(1/2” Gap – Max Nail)’ corresponds to installed conditions where the gap between the supporting member and supported member is more than 1/8 inch (3.2 mm) and less than or equal to 1/2 inch (12.7 mm), and the all of the pre-punched nail holes in the U-shaped portion of the hanger supporting the truss (joist) are filled with nails. This is designated in the table as “Max Nail” and is shown in Figure 10C. 3Refer to Figure 11A for definitions of hanger nomenclature (W, H, B). 4Allowable loads correspond to installations where the minimum allowable number of nails is installed into the supporting memb er. Refer to Section 3.2.3 of this report for nail sizes and required minimum physical properties. 5Tabulated allowable loads are for installations in wood members complying with Section 3.2.2 of this report. 6Tabulated loads must be selected based on the applicable load duration factor, CD, as permitted by the applicable building code. See Sections 4.1 and 4.2 for design and installation requirements. 7HTU series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the de pth of the joist at which the lateral movement of the top or bottom of the joist with respect to its vertical position is 0.125 inch (3.2 mm), fo r joists having a height no greater than the height (H) of the hanger. 8Allowable uplift loads have been increased for wind or earthquake loading with no further increase allowed. The tabulated allowable uplift loads must be reduced proportionally when other load durations govern. MODEL No. 1, 2 DIMENSIONS 3 (inches) FASTENERS 4 (Quantity-Type) ALLOWABLE LOADS 5, 6, 7 (lbf) W H B Into Supporting Member Into Supported Member Uplift 8 Download CD=1.6 CD=0.9 CD=1.0 CD=1.15 CD=1.25 CD=1.6 HTU26 (1/2” Gap – Min Nail)1 15/8 57/16 31/2 10-16d 14-10dx11/2 845 1,320 1,470 1,660 1,790 1,875 HTU26 (1/2” Gap – Max Nail)2 15/8 57/16 31/2 10-16d 20-10dx11/2 1,240 1,320 1,470 1,660 1,790 2,220 HTU28 (1/2” Gap – Max Nail)2 15/8 71/16 31/2 20-16d 26-10dx11/2 1,920 2,640 2,940 3,320 3,580 3,905 HTU210 (1/2” Gap – Max Nail)2 15/8 91/16 31/2 20-16d 32-10dx11/2 2,880 2,640 2,940 3,320 3,580 3,905 FIGURE 11C—ALTERNATE HTU INSTALLATION ESR-2552 | Most Widely Accepted and Trusted Page 21 of 31 TABLE 12—ALLOWABLE LOADS FOR THE LGU, MGU, HGU AND HHGU SERIES HANGERS MODEL No. DIMENSIONS1 (inches) FASTENERS (Quantity-Type) ALLOWABLE LOADS2,6,7 (lbs) Uplift5 Download W H4 (min) B ha3 a Header Joist CD=1.6 CD=1.0 CD=1.15 CD=1.25 LGU3.25-SDS 31/4 8 41/2 73/8 31/4 16 SDS1/4"x 21/2" 12 SDS1/4"x 21/2" 5,555 6,720 7,310 7,310 LGU3.63-SDS 35/8 LGU5.25-SDS 51/4 MGU3.63-SDS 35/8 91/4 41/2 85/8 4 24 SDS1/4"x 21/2" 16 SDS1/4"x 21/2" 7,260 9,450 9,450 9,450 MGU5.25-SDS 51/4 MGU5.50-SDS 51/2 MGU5.62-SDS 55/8 MGU7.00-SDS 7 HGU3.63-SDS 35/8 11 51/4 103/8 43/4 36 SDS1/4"x 21/2" 24 SDS1/4"x 21/2" 9.460 13,160 13,160 13,160 HGU5.25-SDS 51/4 HGU5.50-SDS 51/2 HGU5.62-SDS 55/8 HGU7.00-SDS 7 HGU7.25-SDS 71/4 HGU9.00-SDS 9 HHGU5.25-SDS 51/4 13 51/4 123/8 43/4 44 SDS1/4"x 21/2" 28 SDS1/4"x 21/2" 10,050 18,480 20,455 20,455 HHGU5.50-SDS 51/2 HHGU5.62-SDS 55/8 HHGU7.00-SDS 7 14,550 18,480 20,455 20,445 HHGU7.25-SDS 71/4 HHGU9.00-SDS 9 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1Refer to Figure 12 (this page) for definitions of hanger nomenclature (W, H, B, ha and a). 2Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 3The supporting member (header) height must be at least at high as the flange height, ha. 4The H dimension must be specified. The maximum H dimension is 30 inches. 5The uplift loads have been increased for wind or earthquake loading with no further increase allowed. The allowable uplift loads must be reduced when other load durations govern. 6The allowable loads are based on the use of an engineered wood joist member with an allowable Fc┴ of 650 psi. When use is to support members having an Fc┴ of less than 650 psi, it must be verified that the combination of bearing capacity and joist nail capacity is adequate. 7For supported members other than glulam beams, lateral support must be provided at the ends in accordance with Section 2308.8.2 of the IBC or Section R502.7 of the IRC. FIGURE 12—DIMENSIONS AND TYPICAL INSTALLATION OF THE LGU, MGU, HGU AND HHGU SERIES HANGERS ESR-2552 | Most Widely Accepted and Trusted Page 22 of 31 TABLE 13—ALLOWABLE LOADS FOR THE SUR/SUL SERIES JOIST HANGERS MODEL NO. DIMENSIONS1 (inches) FASTENERS (Quantity-Type) ALLOWABLE LOADS2,6,7 (lbs) Uplift5 Download W H B A1 A2 Header Joist CD=1.6 CD=1.0 CD=1.15 CD=1.25 SUR/L24 19/16 31/16 2 11/8 11/4 4-16d 4-10d x 11/2 395 575 650 705 SUR/L26 19/16 5 2 11/8 15/16 6-16d 6-10d x 11/2 675 865 980 1,055 SUR/L210 19/16 8 2 11/8 15/16 10-16d 10-10d x 11/2 1,445 1,440 1,635 1,760 SUR/L214 19/16 10 2 11/8 15/16 12-16d 12-10d x 11/2 1,890 1,730 1,960 2,115 SUR/L1.81/9 113/16 9 3 15/8 25/16 12-16d 2-10d x 11/2 2103,4 1,730 1,955 1,955 SUR/L1.81/11 113/16 11 3 15/8 25/16 16-16d 2-10d x 11/2 2103,4 2,300 2,560 2,560 SUR/L1.81/14 113/16 133/4 3 15/8 25/16 20-16d 2-10d x 11/2 2103,4 2,560 2,560 2,560 SUR/L2.06/9 21/16 91/16 33/16 15/8 21/8 14-16d 2-10d x 11/2 2103 2,015 2,285 2,465 SUR/L2.06/11 21/16 111/4 33/16 15/8 21/8 16-16d 2-10d x 11/2 2103 2,300 2,610 2,665 SUR/L2.06/14 21/16 135/8 33/16 15/8 21/8 18-16d 2-10d x 11/2 2103 2,590 2,665 2,665 SUR/L2.1/9 21/8 91/16 33/16 19/16 21/8 14-16d 2-10d x 11/2 2103 2,015 2,285 2,465 SUR/L2.1/11 21/8 113/16 33/16 19/16 21/8 16-16d 2-10d x 11/2 2103 2,300 2,610 2,665 SUR/L2.1/14 21/8 139/16 33/16 19/16 21/8 18-16d 2-10d x 11/2 2103 2,590 2,665 2,665 SUR/L2.37/9 23/8 815/16 33/16 15/16 21/8 14-16d 2-10d x 11/2 2103 2,015 2,285 2,465 SUR/L2.37/11 23/8 113/16 33/16 15/16 21/8 16-16d 2-10d x 11/2 2103 2,300 2,610 2,665 SUR/L2.37/14 23/8 137/16 33/16 15/16 21/8 18-16d 2-10d x 11/2 2103 2,590 2,665 2,665 SUR/L2.56/9 29/16 813/16 33/16 11/8 21/8 14-16d 2-10d x 11/2 2103 2,015 2,285 2,465 SUR/L2.56/11 29/16 113/16 33/16 11/8 21/8 16-16d 2-10d x 11/2 2103 2,300 2,615 2,665 SUR/L2.56/14 29/16 135/16 33/16 11/8 21/8 18-16d 2-10d x 11/2 2103 2,590 2,665 2,665 SUR/L26-2 31/8 415/16 25/8 11/2 23/8 8-16d 4-16d x 21/2 725 1.150 1,305 1,325 SUR/L210-2 31/8 811/16 25/8 17/16 23/8 14-16d 6-16d x 21/2 1,160 2,015 2,285 2,345 SUR/L214-2 31/8 1211/16 27/16 17/16 23/8 18-16d 8-16d x 21/2 1,505 2,345 2,345 2,345 SUR/L46 39/16 43/4 25/8 1 23/8 8-16d 4-16d 730 1,150 1,305 1,325 SUR/L410 39/16 81/2 25/8 1 23/8 14-16d 6-16d 1,160 2,015 2,285 2,345 SUR/L414 39/16 121/2 25/8 1 23/8 18-16d 8-16d 1,490 2,345 2,345 2,345 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1Refer to Figure 13a (this page) for definitions of hanger nomenclature (W, H, B, A1, A2). 2Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 3Optional triangle holes may be filled (requires web stiffeners for I-joist) for additional uplift resistance. When a total of six 10dx11/2" nails are installed into the joist for 9- and 11-inch models, an uplift value of 825 lbs may be used. When a total of eight 10dx11/2" nails are installed into the joist for 14-inch models, an uplift value of 1,190 lbs may be used. 4Uplift value based on use of solid sawn lumber or LVL joist member. When using an I-joist as the joist member, allowable uplift must be taken as 140 lbs. 5The uplift loads have been increased for wind or earthquake loading with no further increase allowed. The allowable uplift loads must be reduced when other load durations govern. 6SUR/L series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to its vertical position is 0.125 inch (3.2 mm). The height (H) of the hanger must be at least 60 percent of the height of the joist unless additional lateral restraint is provided, as designed by others. 7The 2-2x ans 4x SUR/L models are available with the A2 flanges concealed and are specified with the model designation SUR/LC FIGURE 13A—SUL SERIES JOIST HANGER FIGURE 13B—TYPICAL SUR HANGER INSTALLATION ESR-2552 | Most Widely Accepted and Trusted Page 23 of 31 TABLE 14—ALLOWABLE LOADS FOR THE HSUR/HSUL SERIES JOIST HANGERS MODEL NO. DIMENSIONS1 (inches) FASTENERS (Quantity-Type) ALLOWABLE LOADS2,3,6,7 (lbs) W H B A1 A2 Header Joist Uplift4 Download CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 HSUR/L26-2 31/8 415/16 27/16 13/4 23/8 12-16d 4-16d x 21/2 725 1,785 1,795 1,795 HSUR/L210-2 31/8 811/16 27/16 13/4 23/8 20-16d 6-16d x 21/2 1,160 2,975 3,355 3,410 HSUR/L214-2 31/8 1211/16 27/16 13/4 23/8 26-16d 8-16d x 21/2 1,490 3,865 4,360 4,685 HSUR/L46 39/16 43/4 27/16 1 23/16 12-16d 4-16d 725 1,785 1,795 1,795 HSUR/L410 39/16 81/2 27/16 1 23/16 20-16d 6-16d 1,150 2,975 3,355 3,410 HSUR/L414 39/16 121/2 27/16 1 23/16 26-16d 8-16d 1,490 3,865 4,360 4.685 HSUR/L4.12/9 41/8 9 3 17/16 23/8 12-16d 2-10d x 11/2 1454 1,725 1,725 1,725 HSUR/L4.12/11 41/8 111/8 3 17/16 23/8 16-16d 2-10d x 11/2 1454 2,380 2,685 2,885 HSUR/L4.12/14 41/8 133/4 3 17/16 23/8 20-16d 2-10d x 11/2 1454 2,975 3,330 3,330 HSUR/L4.12/16 41/8 153/4 3 17/16 23/8 24-16d 2-10d x 11/2 1454 3,330 3,330 3,330 HSUR/L4.28/9 45/16 9 3 17/16 23/8 12-16d 2-10d x 11/2 1454 1,7255 1,725 1,725 HSUR/L4.28/11 45/16 111/8 3 17/16 23/8 16-16d 2-10d x 11/2 1454 2,380 2,685 2,885 HSUR/L4.75/9 43/4 815/16 23/4 17/16 23/8 12-16d 2-10d x 11/2 1454 1,725 1,725 1,725 HSUR/L4.75/11 43/4 1015/16 23/4 17/16 23/8 16-16d 2-10d x 11/2 1454 2,380 2,685 2,885 HSUR/L4.75/14 43/4 133/4 23/4 17/16 23/8 20-16d 2-10d x 11/2 1454 2,975 3,330 3,330 HSUR/L4.75/16 43/4 153/4 23/4 17/16 23/8 24-16d 2-10d x 11/2 1454 3,330 3,330 3,330 HSUR/L5.12/9 51/8 9 213/16 17/16 23/8 12-16d 2-10d x 11/2 1454 1,725 1,725 1,725 HSUR/L5.12/11 51/8 11 213/16 17/16 23/8 16-16d 2-10d x 11/2 1454 2,380 2,685 2,885 HSUR/L5.12/14 51/8 133/4 213/16 17/16 23/8 20-16d 2-10d x 11/2 1454 2,975 3,330 3,330 HSUR/L5.12/16 51/8 153/4 213/16 17/16 23/8 24-16d 2-10d x 11/2 1454 3,330 3,330 3,330 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1Refer to Figure 14a (this page) for definitions of hanger nomenclature (W, H, B, A1, A2). 2Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 3When I-joists are the supported member as shown in Figure 7b, each I-joist must have web stiffeners installed in accordance with the I-joist manufacturer’s evaluation report, and the minimum required quantity and type of nails, as specified in the column entitled FA STENERS must be nailed directly into the web stiffeners and/or I-joist. 4Optional triangular holes may be filled (requires web stiffeners) for additional uplift. When a total of six 10d x 11/2" nails are installed into the joist, an uplift value of 505 lbs may be used. 5The uplift loads have been increased for wind or earthquake loading with no further increase allowed. The allowable uplift loads must be reduced when other load durations govern. 6HSUR/L series hangers provide torsional resistance, which is defined as a moment of not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to its vertical position is 0.125 inch (3.2 mm). The height (H) of the hanger must be at least 60 percent of the height of the joist unless additional lateral restraint is provided, as designed by others. 7The 2-2x ans 4x HSUR/L models are available with the A2 flanges concealed and are specified with the model designation HSUR/LC FIGURE 14A—HSUR JOIST HANGER FIGURE 14B—TYPICAL HSUR JOIST HANGER INSTALLATION (Web Stiffeners not shown for Clarity–See Footnote 3 to Table 7) ESR-2552 | Most Widely Accepted and Trusted Page 24 of 31 TABLE 15A—APPLICABLE MODEL NUMBERS FOR THE IUS SERIES I-JOIST HANGERS1 MODEL NO. DIMENSIONS2 (Inches) FASTENERS (Quantity-Type) MODEL NO. DIMENSIONS2 (Inches) FASTENERS (Quantity-Type) W H B Header Joist W H B Header Joist IUS2.37/16(min) 27/16 16 2 14-10d ― IUS2.37/16(max) 16-10d ― IUS1.81/9.5 17/8 91/2 2 8-10d ― IUS2.56/9.25 25/8 91/4 2 8-10d ― IUS1.81/11.88 117/8 10-10d ― IUS2.56/9.5 91/2 8-10d ― IUS1.81/14(min) 14 12-10d ― IUS2.56/11.88 117/8 10-10d ― IUS1.81/14(max) 14-10d ― IUS2.56/14(min) 14 12-10d ― IUS1.81/16(min) 16 14-10d ― IUS2.56/14(max) 14-10d ― IUS1.81/16(max) 16-10d ― IUS2.56/16(min) 16 14-10d ― IUS2.06/9.5 21/8 91/2 2 8-10d ― IUS2.56/16(max) 16-10d ― IUS2.06/11.88 117/8 10-10d ― IUS3.56/9.5 35/8 91/2 2 10-10d ― IUS2.06/14(min) 14 12-10d ― IUS3.56/11.88 117/8 12-10d ― IUS2.06/14(max) 14-10d ― IUS3.56/14(min) 14 12-10d ― IUS2.06/16(min) 16 14-10d ― IUS3.56/14(max) 14-10d ― IUS2.06/16(max) 16-10d ― IUS3.56/16(min) 16 14-10d ― IUS2.37/9.5 27/16 91/2 2 8-10d ― IUS3.56/16(max) 16-10d ― IUS2.37/11.88 117/8 10-10d ― (This section of the table is intentionally blank) IUS2.37/14(min) 14 12-10d ― IUS2.37/14(max) 14-10d ― For SI: 1 inch = 25.4 mm. 1Model numbers ending with (min) refer to nails installed into only round holes of the hanger, and the model numbers ending with (max) refer to nails installed into both round and triangle holes of the hanger. 2Refer to Figures 1a and 1b (next page) for definitions of hanger nomenclature (W, H, B). TABLE 15B—ALLOWABLE LOADS FOR THE IUS SERIES I-JOIST HANGERS MODEL NO. DIMENSIONS1 (inches) COMMON NAILS (Quantity-Size) ALLOWABLE LOADS2,5 (lbs) Uplift 3,4 Download W H B Header Joist CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 IUS 17/8 to 25/8 91/4 to 16 2 8-10d — 70 950 1,080 1,165 10-10d — 70 1,185 1,345 1,455 12-10d — 70 1,420 1,615 1,745 14-10d — 70 1,660 1,805 1,805 16-10d — 70 1,805 1,805 1,805 IUS 211/16 to 35/8 91/2 to 16 2 10-10d — 70 1,185 1,345 1,455 12-10d — 70 1,420 1,615 1,745 14-10d — 70 1,660 1,805 1,805 16-10d — 70 1,805 1,805 1,805 For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N. 1Refer to Figures 1a and 1b (next page) for definitions of hanger nomenclature (W, H, B). 2Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 3The uplift loads have been increased for wind or earthquake loading with no further increase allowed. The allowable uplift loads need not be reduced when other load durations govern. 4Additional uplift capacity is available when installing 2-10dx11/2-inch-long nails through the triangular holes that are pre-punched in the U-shaped portion of the hanger and into the stiffened web of the prefabricated wood I-joist. When these additional nails are used, the maximum allowable uplift load is 345 lbs (CD = 1.6). 5The allowable loads are based on the use of prefabricated wood I-joists having flanges with an allowable compression perpendicular-to-grain, Fc┴, of 750 psi. When use is to support wood I-joists with flanges having an Fc┴ of less than 750 psi, it must be verified that the combination of bearing capacity and joist nail capacity is adequate. ESR-2552 | Most Widely Accepted and Trusted Page 25 of 31 FIGURE 15A TYPICAL IUS HANGER (SEAT STYLE A) FIGURE 15B TYPICAL IUS HANGER (SEAT STYLE B) FIGURE 15C—TYPICAL IUS HANGER INSTALLATION (Supported Wood I-joist without Web Stiffeners) ESR-2552 | Most Widely Accepted and Trusted Page 26 of 31 TABLE 16—ALLOWABLE LOADS FOR THE MIU SERIES JOIST HANGERS MODEL NO. DIMENSIONS1 (in.) FASTENERS3,4 ALLOWABLE LOADS (lbs) 2,5,6,7 Uplift3,4,5 Download W H B Header Joist CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 MIU1.56/7 19/16 615/16 21/2 10-16d 4-10d x 11/2 555 1,440 1,635 1,760 MIU1.56/9 815/16 16-16d 6-10d x 11/2 965 2,305 2,615 2,820 MIU1.56/11 111/16 20-16d 6-10d x 11/2 965 2,880 3,135 3,135 MIU1.56/14 137/16 22-16d 6-10d x 11/2 965 3,170 3,550 3,610 MIU1.81/7 113/16 615/16 21/2 10-16d 4-10d x 11/2 555 1,440 1,635 1,760 MIU1.81/9 813/16 16-16d 6-10d x 11/2 965 2,305 2,615 2,820 MIU1.81/11 111/16 20-16d 6-10d x 11/2 965 2,880 3,135 3,135 MIU1.81/14 135/16 22-16d 6-10d x 11/2 965 3,170 3,595 3,875 MIU1.81/16 155/16 24-16d 6-10d x 11/2 965 3,455 3,902 4,045 MIU1.81/18 17 5/16 26-16d 6-10d x 11/2 965 3,745 4,020 4,045 MIU2.1/11 21/8 111/16 21/2 20-16d 6-10d x 11/2 965 2,880 3,135 3,135 MIU2.37/7 23/8 615/16 21/2 10-16d 4-10d x 11/2 555 1,440 1,635 1,760 MIU2.37/9 9 16-16d 6-10d x 11/2 965 2,305 2,615 2,820 MIU2.37/11 111/16 20-16d 6-10d x 11/2 965 2,880 3,135 3,135 MIU2.37/14 131/2 22-16d 6-10d x 11/2 965 3,170 3,595 3,875 MIU2.37/16 151/2 24-16d 6-10d x 11/2 965 3,455 3,920 4,045 MIU2.37/18 171/2 26-16d 6-10d x 11/2 965 3,745 4,045 4,045 MIU2.37/20 191/2 28-16d 6-10d x 11/2 965 4,030 4,060 4,060 MIU2.56/9 29/16 815/16 21/2 16-16d 6-10d x 11/2 965 2,305 2,615 2,820 MIU2.56/11 111/16 20-16d 6-10d x 11/2 965 2,880 3,135 3,135 MIU2.56/13 121/4 20-16d 6-10d x 11/2 965 2,880 3,135 3,135 MIU2.56/14 137/16 22-16d 6-10d x 11/2 965 3,170 3,595 3,875 MIU2.56/16 157/16 24-16d 6-10d x 11/2 965 3,455 3,920 4,045 MIU2.56/18 177/16 26-16d 6-10d x 11/2 965 3,745 4,045 4,045 MIU2.56/20 197/16 28-16d 6-10d x 11/2 965 4,030 4,060 4,060 MIU3.12/9 31/8 91/16 21/2 16-16d 6-10d x 11/2 965 2,305 2,615 2,820 MIU3.12/11 111/8 20-16d 6-10d x 11/2 965 2,880 3,135 3,135 MIU3.56/9 39/16 813/16 21/2 16-16d 6-10d x 11/2 965 2,305 2,615 2,820 MIU3.56/11 111/8 20-16d 6-10d x 11/2 965 2,880 3,135 3,135 MIU3.56/14 135/16 22-16d 6-10d x 11/2 965 3,170 3,595 3,875 MIU3.56/16 155/16 24-16d 6-10d x 11/2 965 3,455 3,920 4,045 MIU3.56/18 175/16 26-16d 6-10d x 11/2 965 3,745 4,045 4,045 MIU3.56/20 195/16 28-16d 6-10d x 11/2 965 4,030 4,060 4,060 MIU4.12/9 41/8 91/16 21/2 16-16d 6-10d x 11/2 965 2,305 2,615 2,820 MIU4.12/11 111/8 20-16d 6-10d x 11/2 965 2,880 3,135 3,135 MIU4.12/14 139/16 22-16d 6-10d x 11/2 965 3,170 3,595 3,875 MIU4.12/16 159/16 24-16d 6-10d x 11/2 965 3,455 3,920 4,045 MIU4.28/9 45/16 9 21/2 16-16d 6-10d x 11/2 965 2,305 2,615 2,820 MIU4.28/11 111/8 20-16d 6-10d x 11/2 965 2,880 3,135 3,135 MIU4.28/14 131/2 22-16d 6-10d x 11/2 965 3,170 3,595 3,875 MIU4.28/16 151/2 24-16d 6-10d x 11/2 965 3,455 3,920 4,045 Please refer to next page for continuation of Table 16. ESR-2552 | Most Widely Accepted and Trusted Page 27 of 31 TABLE 16—ALLOWABLE LOADS FOR THE MIU SERIES JOIST HANGERS (Continued) MODEL NO. DIMENSIONS1 (in.) FASTENERS3,4 ALLOWABLE LOADS (lbs)2,5,6,7 Uplift3,4,5 Download W H B Header Joist CD = 1.6 CD = 1.0 CD = 1.15 CD = 1.25 MIU4.75/9 43/4 9 21/2 16-16d 6-10d x 11/2 965 2,305 2,615 2,820 MIU4.75/11 111/16 20-16d 6-10d x 11/2 965 2,880 3,135 3,135 MIU4.75/14 131/2 22-16d 6-10d x 11/2 965 3,170 3,595 3,875 MIU4.75/16 151/2 24-16d 6-10d x 11/2 965 3,455 3,920 4,045 MIU4.75/18 171/2 26-16d 6-10d x 11/2 965 3,745 4,045 4,045 MIU4.75/20 191/2 28-16d 6-10d x 11/2 965 4,030 4,060 4,060 MIU5.12/7 51/8 615/16 21/2 10-16d 4-10d x 11/2 555 1,440 1,635 1,760 MIU5.12/9 813/16 16-16d 6-10d x 11/2 965 2,305 2,615 2,820 MIU5.12/11 111/8 20-16d 6-10d x 11/2 965 2,880 3,135 3,135 MIU5.12/14 135/16 22-16d 6-10d x 11/2 965 3,170 3,595 3,875 MIU5.12/16 155/16 24-16d 6-10d x 11/2 965 3,455 3,920 4,045 MIU5.12/18 175/16 26-16d 6-10d x 11/2 965 3,745 4,045 4,045 MIU5.12/20 195/16 28-16d 6-10d x 11/2 965 4,030 4,060 4,060 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1Refer to Figure 8a (this page) for definitions of hanger nomenclature (W, H and B). 2Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. 3The uplift loads have been increased for wind or earthquake loading with no further increase allowed. The allowable uplift loads must be reduced when other load durations govern. 4Total number of joist nails specified in the table must be installed to resist tabulated uplift loads. The bottom two 10dx11/2 nails must be installed at a 45-degree angle into the bottom flange of the prefabricated wood I-joist, as shown in the detail in Figure 8b (on this page). These nails are designated as PAN nails. 5Web stiffeners must be installed on wood I-joists, with the following exception: An alternate reduced uplift capacity of 230 lbs can be obtained without using web stiffeners and all of the specified joist nails indicated in the table by installing two angled PAN nails at the hanger seat into the bottom flange of the wood I-joist as shown in the detail in Figure 8b (on this page). 6For joist members other than prefabricated wood I-joists, lateral support must be provided at the ends in accordance with Section 2308.8.2 of the IBC or Section R502.7 of the IRC. 7The tabulated allowable loads are based on the use of prefabricated wood I-joists having flanges with an allowable compression perpendicular- to-grain, Fc┴, of 750 psi. When use is to support members having an Fc┴ of less than 750 psi, it must be verified that the combination of bearing capacity and joist nail capacity is adequate. FIGURE 16A—MIU JOIST HANGER FIGURE 16B—ALTERNATE MIU JOIST HANGER INSTALLATION (See Footnotes 3 and 4 to Table 16) ESR-2552 | Most Widely Accepted and Trusted Page 28 of 31 TABLE 17A—ALLOWABLE LOADS FOR DU, DHU AND DHUTF SERIES JOIST HANGERS MODEL SERIES PRODUCT DIMENSIONS (inches) INSTALLATION CONDITION 1,6,7 ALLOWABLE LOADS (lbs) W H Ga B Uplift CD=1.603,4 Download CD=1.002 DU 19/16 to 23/8 91/8 to 1515/16 14 2.5 Over (2) layers 5/8" gypsum wallboard 95 1,110 DHU DHUTF 19/16 to 39/16 91/8 to 2315/16 12 3 Over (2) layer 5/8" gypsum wallboard 95 1,4105 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45N. 1Loads assume two layers of 5/8-inch-thick Type X gypsum wallboard fastened using, at a minimum, the fastener schedule in Items 14.1-5 in IBC Table 721.1(2). Wall assembly must consist of minimum two 2x4 top plate members with studs spaced not more than 16 inches on center. Top plate member splices must occur at a stud location. 2Hangers spaced closer than 16 inches on center shall reduce capacity proportionately. 3Triangle nail holes may be filled with (4) additional 10d x 11/2 inch long nails to achieve an allowable uplift load of 750 lbs. 4DF carried members with minimum 1½ inches x 21/2 inches solid sawn dimensions increase the allowable uplift load to 170 lbs. 5Allowable download may be increased to 1,610 lbf for DF/SP using the DHU3.56/24 or DHUTF3.56/24 model hangers. 6DU and DHU are mounted with the top of the hanger flush with the top of the wall and tight to the gypsum wallboard. 7Wall top plates must be restrained to prevent rotation. Use an SSP stud plate tie to connect the wall top plate to each wall stud on the opposite face of the wall or provide equivalent restraint by another method as determined by the designer. The Simpson Strong-tie Company SSP is a cold-formed, galvanized steel, strap connector that has a bent end that when installed bears on the top of the wall top plate. The SSP is to be attached to the side of the wall top plates with three 10d common nails, and attached to the wall stud with four 10d common nails. TABLE 17B—FASTENER SCHEDULE FOR DHU, DHU AND DHUTF SERIES HANGERS SERIES FASTENERS Joist1 Face Top DU (2) 10d x 11/2'' (4) SDS 1/4'' x 3.5'' - DHU (2) 10d x 11/2'' (8) SDS 1/4'' x 3.5'' - DHUTF (2) 10d x 11/2'' (8) SDS 1/4'' x 3.5'' (6) 10d x 11/2'' 1The two nails must be installed in the positive angle nailing (PAN) holes close to the hanger seat. DHU (DU Similiar) DHUTF Typical DHU Installation FIGURE 17—DU, DHU AND DHUTF HANGERS ESR-2552 | Most Widely Accepted and Trusted Page 29 of 31 TABLE 18A - CBH JOIST TO BEAM ALLOWABLE LOADS MODEL NO. DIMENSIONS1 (inches) FASTENERS (Quantity-Type) ALLOWABLE DOWNLOADS2 W H Joist Beam CD=1.00/ 1.15/1.25 CBH2.37x5.5 2 3/8 5 1/2 13-SDS1/4"x6" 13-SDS1/4"x3" 4830 CBH2.37x7.63 2 3/8 7 5/8 18-SDS1/4"x6" 18-SDS1/4"x3" 6510 CBH2.37x9.75 2 3/8 9 3/4 23-SDS1/4"x6" 23-SDS1/4"x3" 8785 TABLE 18B - CBH JOIST TO COLUMN ALLOWABLE LOADS MODEL NO. DIMENSIONS1 (inches) FASTENERS (Quantity-Type) ALLOWABLE DOWNLOADS2 W H Joist Beam CD=1.00/ 1.15/1.25 CBH2.37x5.5 2 3/8 5 1/2 13-SDS1/4"x6" 13-SDS1/4"x6" 5455 CBH2.37x7.63 2 3/8 7 5/8 18-SDS1/4"x6" 18-SDS1/4"x6" 6630 CBH2.37x9.75 2 3/8 9 3/4 23-SDS1/4"x6" 23-SDS1/4"x6" 8940 For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N. 1Refer to Figure 18 (this page) for definitions of hanger nomenclature (W, H). 2Tabulated allowable loads must be selected based on duration of load as permitted by the applicable building code. CBH Series Hanger Typical CBH Beam-Beam Installation Typical CBH Assembly Beam-Column Installation Similar FIGURE 18—CBH CONCEALED BEAM HANGERS ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright © 2020 ICC Evaluation Service, LLC. All rights reserved. Page 30 of 31 ICC-ES Evaluation Report ESR-2552 LABC and LARC Supplement Reissued March 2020 Revised December 2020 This report is subject to renewal March 2021. www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ® DIVISION: 06 00 00—WOOD, PLASTICS AND COMPOSITES Section: 06 05 23—Wood, Plastic, and Composite Fastenings REPORT HOLDER: SIMPSON STRONG-TIE COMPANY INC. EVALUATION SUBJECT: SIMPSON STRONG-TIE® FACE-MOUNT HANGERS FOR SAWN LUMBER, STRUCTURAL COMPOSITE LUMBER (SCL), PREFABRICATED WOOD I-JOISTS AND GLULAM BEAMS (ENGINEERED WOOD PRODUCTS) 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that Simpson Strong-Tie® face-mount hangers for sawn lumber, structural composite lumber (SCL), prefabricated wood I-joists and glulam beams (engineered wood products), described in ICC-ES evaluation report ESR-2552, have also been evaluated for compliance with the codes noted below as adopted by the Los Angeles Department of Building and Safety (LADBS). Applicable code editions:  2020 City of Los Angeles Building Code (LABC)  2020 City of Los Angeles Residential Code (LARC) 2.0 CONCLUSIONS The Simpson Strong-Tie® face mount hangers for sawn lumber, structural composite lumber (SCL), prefabricated wood I-joists and glulam beams (engineered wood products), described in Sections 2.0 through 7.0 of the evaluation report ESR-2552, comply with the LABC Chapter 23, and the LARC, and are subjected to the conditions of use described in this supplement. 3.0 CONDITIONS OF USE The Simpson Strong-Tie® face mount hangers for sawn lumber, structural composite lumber (SCL), prefabricated wood I-joists and glulam beams (engineered wood products), described in this evaluation report supplement, must comply with all of the following conditions:  All applicable sections in the evaluation report ESR-2552.  The design, installation, conditions of use and identification are in accordance with the 2018 International Building Code® (2018 IBC) provisions noted in the evaluation report ESR-2552.  The design, installation and inspection are in accordance with additional requirements of LABC Chapters 16 and 17, as applicable.  The supported end of joist or beam must be within 1/4-inch from the supporting member.  Solid blocking must be required for all joist hangers supporting roof joists having one end twisted more than one-half degree per foot of length relative to the other end, except as specifically noted in the evaluation report.  Under the LARC, an engineered design in accordance with LARC Section R301.1.3 must be submitted. This supplement expires concurrently with the evaluation report, reissued March 2020 and revised December 2020. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright © 2020 ICC Evaluation Service, LLC. All rights reserved. Page 31 of 31 ICC-ES Evaluation Report ESR-2552 FBC Supplement Issued July 2020 Revised December 2020 This report is subject to renewal March 2021 www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ® DIVISION: 06 00 00—WOOD, PLASTICS, AND COMPOSITES Section: 06 05 23—Wood, Plastic, and Composite Fastenings REPORT HOLDER: SIMPSON STRONG-TIE COMPANY INC. EVALUATION SUBJECT: SIMPSON STRONG-TIE® FACE-MOUNT HANGERS FOR SAWN LUMBER, STRUCTURAL COMPOSITE LUMBER (SCL), PREFABRICATED WOOD I-JOISTS AND GLULAM BEAMS (ENGINEERED WOOD PRODUCTS) 1.0 REPORT PURPOSE AND SCOPE Purpose: The purpose of this evaluation report supplement is to indicate that the Simpson Strong-Tie® face-mount hangers, described in ICC-ES evaluation report ESR-2552, have also been evaluated for compliance with the codes noted below. Applicable code editions:  2020 and 2017 Florida Building Code—Building  2020 and 2017 Florida Building Code—Residential 2.0 CONCLUSIONS The Simpson Strong-Tie® face-mount hangers, described in Sections 2.0 through 7.0 of ICC-ES evaluation report ESR- 2552, comply with the Florida Building Code—Building, and the Florida Building Code—Residential, provided the design requirements are determined in accordance with the Florida Building Code—Building or the Florida Building Code— Residential, as applicable. The installation requirements noted in ICC-ES evaluation report ESR-2552 for the 2018 and 2015 International Building Code® meet the requirements of the Florida Building Code—Building or the Florida Building Code— Residential, as applicable. Use of the Simpson Strong-Tie® face-mount hangers has also been found to be in compliance with the High-Velocity Hurricane Zone provisions of the Florida Building Code—Building, and the Florida Building Code—Residential with the following condition: a. For connections subject to uplift, the connection must be designed for no less than 700 pounds (3114 N). For products falling under Florida Rule 61G20-3, verification that the report holder’s quality assurance program is audited by a quality assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the responsibility of an approved validation entity (or the code official when the report holder does not possess an approval by the Commission). This supplement expires concurrently with the evaluation report ESR-2552, reissued March 2020 and revised December 2020.