1 FLEET LANDING Coleman Bldg Reno COMM21-0042 -MECH permit set_1SHEET PRINTED ON:FILE PATH:DATE:
1414 UNDERWOOD AVE. WAUWATOSA, WI 53213 414.431.3131 TEL 414.431.0531 FAX WWW.AGARCH.COM
AG PROJECT NUMBER:
SHEET INDEX
OWNER
DEVELOPMENT CONSULTANT
Clark Advisory Services
1015 Atlantic Boulevard
Atlantic Beach, FL 32233
904.834.9373
407.235.8053 (C)
One Fleet Landing Boulevard
Atlantic Beach, FL 32233
Fleet Landing
FOOD SERVICE CONSULTANT
Scopos Hospitality Group
300 West Chestnut Street, Suite 201
Ephrata, PA 17522
717.733.5810
INTERIOR DESIGN
Studio 121 Inc.
2305 Kline Ave Suite 100
Nashville, TN 37211
615.469.4121
615.469.6121 (fax)
STRUCTURAL CONSULTANT
McVeigh & Mangum
Engineering, Inc
9133 RG Skinner Pkwy
Jacksonville, FL 62256
904.438.5200
MEP CONSULTANT
Professional Engineering
Consultants
303 South Topeka
Wichita, KS 67202
(316) 206-1456
PERMIT SET
8/5/2021 7:41:53 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvtAtlantic Beach, Florida
Coleman Remodel
6 AUG 2021
200801
SHEET LIST
MP001 MECHANICAL COVER SHEET
M101 1/8" FIRST FLOOR DEMO PLAN - HVAC
M102 1/8" SECOND FLOOR DEMO PLAN - HVAC
M103 1/8" ROOF DEMO PLAN - HVAC
M201 1/8" FIRST FLOOR PLAN - HVAC
M202 1/8" SECOND FLOOR PLAN - HVAC
M203 1/8" FIRST FLOOR PLAN - HYDRONICS
M204 1/8" SECOND FLOOR PLAN - HYDRONICS
M205 1/8" ROOF PLAN - HVAC
M300 1/2" ENLARGED CHILLER PLAN
MT100 HVAC SCHEDULES
MT102 HVAC SCHEDULES
MT103 HVAC SCHEDULES
MT200 HVAC DETAILS
MT201 HVAC DETAILS
MT300 HVAC CONTROLS
MT301 HVAC CONTROLS
P101 1/8" FIRST FLOOR DEMO PLAN - PLUMBING
P102 1/8" SECOND FLOOR DEMO PLAN - PLUMBING
P200 1/8" FIRST FLOOR PLAN - UNDERGROUND PLUMBING
P201 1/8" FIRST FLOOR PLAN - PLUMBING
P202 1/8" SECOND FLOOR PLAN - PLUMBING
P300 1/4" ENALRGED PLANS - PLUMBING
P400 PLUMBING RISER DIAGRAMS
P401 PLUMBING RISER DIAGRAMS
PT100 PLUMBING SCHEDULES AND DETAILS
SHEET NUMBER
WHERE DRAWN
SECTION LETTER
SECTIONS DETAILS
FT-1
TYPICAL
EQUIPMENT
NUMBER
UNIQUE I.D.
(FAN TERMINAL NO. 1)
EQUIPMENT TYPE
(FT=FAN TERMINAL)
DRAWING SYMBOLS
GENERAL NOTES
GENERAL DEMOLITION NOTES
B
M2.1 M3.6
M3.6
B
5
M2.1 M3.6
5
M3.6
1. VERIFY JOB SITE CONDITIONS AND DIMENSIONS BEFORE BEGINNING WORK. PLANS ARE SCHEMATIC IN NATURE.
LAYOUT IS BASED ON BEST AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS AND DIMENSIONS.
2. NO PIPING, DUCTWORK, ETC. SHALL PENETRATE STRUCTURAL MEMBERS.
3. PROVIDE MISCELLANEOUS CUTTING, PATCHING AND REPAIRING OF FINISHES, ROOF, WALLS, ETC., AS REQUIRED
TO ACCOMMODATE THE NEW WORK.
4. G.C. IS TO PATCH ANY OPENINGS IN CORRIDORS REQUIRED TO BE CONSTRUCTED TO LIMIT THE TRANSFER OF
SMOKE AND IN SMOKE BARRIERS AS REQUIRED TO MEET CODE REQUIREMENTS. SEE ARCHITECTURAL
DRAWINGS FOR LOCATIONS.
5. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY EXACT LOCATION, CONFIGURATION AND ROUTING
OF EXISTING SYSTEMS REQUIRED TO REMAIN IN OPERATION DURING THE PROJECT TO PREVENT DAMAGE
DURING DEMOLITION AND PHASING.
6. REMOVE ALL EXISTING EQUIPMENT, DUCTWORK AND PIPING THAT IS NOT REQUIRED FOR A WORKING
INSTALLATION.
7. COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO INSTALLATION.
8. UNLESS OTHERWISE INDICATED, INSTALL ALL SPACE THERMOSTATS AND OTHER OCCUPANT ADJUSTABLE
CONTROL DEVICES SAME HEIGHT AS ADJACENT LIGHT SWITCHES, BUT IN NO CASE HIGHER THAN 48 INCHES
ABOVE FINISHED FLOOR PER ADA REQUIREMENTS. COORDINATE EXACT HEIGHT WITH ARCHITECT PRIOR TO
INSTALLATION.
9. ALL CUTTING AND PATCHING SHALL BE CLOSELY COORDINATED WITH THE G.C.
10. COORDINATE ROUTING OF PLUMBING, AND HVAC PIPING WITH DUCTWORK, LIGHTS, ARCHITECTURAL CEILING
AND STRUCTURAL ELEMENTS. PIPING SHALL RISE AND DROP, JOG OR OFFSET AS REQUIRED TO AVOID
CONFLICTS. DUCTWORK SHALL TAKE PRECEDENCE OVER ALL PIPING, EXCEPT WHERE GRADE MUST BE
MAINTAINED FOR DRAINAGE. REWORK OF INSTALLED WORK TO RESOLVE CONFLICTS RISING FROM LACK OF
COORDINATION SHALL NOT JUSTIFY AN INCREASE IN THE CONTRACT AMOUNT.
11. ALL DIFFUSERS ARE 4-WAY BLOW UNLESS INDICATED OTHERWISE ON THE DRAWINGS.
12. FLEXIBLE DUCTWORK IS ALLOWED ON RUNOUTS TO SUPPLY DIFFUSERS ONLY. UTILIZE ONLY ABOVE LAY-IN
ACCESSIBLE CEILINGS. DO NOT INSTALL FLEX DUCT ABOVE HARD CEILINGS OR WHERE EXPOSED. A MAXIMUM
LENGTH OF 6'-0" MAY BE USED AT EACH CONNECTION.
13. SEAL DUCTWORK AS CALLED OUT BELOW USING HARDCAST DT TAPE AND FTA-20 ADHESIVE OR HARDCAST
AFG-1402 "FOIL GRIP" PER MANUFACTURERS INSTRUCTIONS.
TYPE OF DUCT APPLY TO JOINTS
EXHAUST DUCT (ROUND OR RECT)TRANSVERSE AND LONGITUDINAL
MEDIUM VELOCITY (ROUND)TRANSVERSE AND LONGITUDINAL
MEDIUM VELOCITY (RECTANGULAR)TRANSVERSE AND LONGITUDINAL
LOW VELOCITY SUPPLY AND RETURN (RECT)TRANSVERSE AND LONGITUDINAL
LOW VELOCITY SUPPLY (ROUND)TRANSVERSE AND LONGITUDINAL
14. INSTALL BALANCE DAMPER WITH STANDOFF AND LOCKING QUADRANT IN AN ACCESSIBLE LOCATION AT EACH
RUNOUT TO SUPPLY DIFFUSERS, EXHAUST GRILLES, AND RETURN GRILLES WHERE AIRFLOW IS INDICATED, OR
AS INDICATED OTHERWISE.
15. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE FIRE STOPPED BY THE TRADE MAKING THE
PENETRATION. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR REQUIREMENTS.
16. DO NOT ROUTE PIPING OR DUCTWORK OVER ELECTRICAL PANELS OR EQUIPMENT. PIPING OR DUCTWORK
SHALL NOT BE ROUTED THROUGH ELECTRICAL ROOMS, TELECOM ROOMS OR ELEVATOR EQUIPMENT ROOMS
UNLESS SPECIFICALLY SERVING THAT ROOM. COORDINATE WITH E.C. PROVIDE WATERTIGHT DRIP PAN WITH
DRAIN TO NEAREST APPROVED RECEPTOR WHERE REQUIRED.
17. COORDINATE SIZE AND LOCATION OF ACCESS DOORS IN CONSTRUCTION REQUIRED FOR ACCESS TO
MECHANICAL EQUIPMENT WITH G.C.
18. COORDINATE SIZE AND LOCATION OF MECHANICAL EQUIPMENT PADS WITH G.C.
19. ALL WORK IS TO CONFORM WITH APPLICABLE CODES AND STANDARDS.
20. DUCT SIZES SHOWN ARE ACTUAL INSIDE CLEAR DIMENSIONS. INCREASE SHEET METAL DIMENSIONS AS
REQUIRED TO ACCOMMODATE DUCT LINER WHERE LINER IS SPECIFIED.
21. ALL EQUIPMENT SUPPORT STANDS SHALL BE PRIMED AND PAINTED WITH EPOXY ENAMEL.
22. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL CEILING MOUNTED AIR
DISTRIBUTION DEVICES.
23. PAINT INSIDE OF DUCTWORK BLACK ANYWHERE VISIBLE THROUGH FACE OF GRILLE OR DIFFUSER.
24. WHERE HYDRONIC RUNOUT SIZES ARE NOT INDICATED, SIZE PER THE FOLLOWING:
UP TO 3 GPM -3/4"; UP TO 6 GPM -1"; UP TO 10 GPM -1-1/4"; UP TO 17 GPM -1-1/2".
25. HYDRONIC PIPING SHALL BE MAINTAINED FULL SIZE UP TO COIL CONNECTIONS. SHUT-OFF VALVES, STRAINERS,
BALANCE VALVES, ETC. WILL NOT BE ALLOWED TO REDUCE FROM LINE/RUNOUT SIZE. CONTROL VALVES MAY
BE DOWN SIZED FOR FLOW RATE, NOT TO EXCEED 4 PSIG PRESSURE DROP AT DESIGN FLOW.
26. TEMPERATURE CONTROLS CONTRACTOR (T.C.C.) SHALL FURNISH AND INSTALL ALL LOW VOLTAGE WIRING AND
ASSOCIATED CONDUIT REQUIRED FOR MECHANICAL CONTROL SYSTEM. WIRING SHALL BE IN CONDUIT INSIDE
WALLS, IN ROOMS WITH EXPOSED CEILINGS, AND ABOVE HARD CEILINGS. LINE VOLTAGE WIRING AND
ASSOCIATED CONDUIT SHALL BE PROVIDED AND INSTALLED BY E.C. CONTROL SYSTEM SHALL BE INSTALLED IN
ACCORDANCE WITH SPECIFICATIONS.
27. ALL CONTROL DAMPERS SHALL BE FURNISHED BY T.C.C. AND INSTALLED BY THE M.C. MOTOR OPERATORS
SHALL BE FURNISHED AND INSTALLED BY THE T.C.C.
28. COORDINATE ACCESS TO EQUIPMENT AND VALVES INSTALLED ABOVE 'HARD' CEILINGS AND IN MASONRY
CHASES WITH GENERAL CONTRACTOR. PROVIDE LOCKING ACCESS DOORS FOR INSTALLATION BY
CONTRACTOR AS REQUIRED TO SERVICE CONCEALED DAMPERS, VALVES AND EQUIPMENT. CEILING ACCESS
DOORS FOR FIRE DAMPERS, SMOKE DAMPERS AND FIRE SMOKE DAMPERS FURNISHED AND INSTALLED BY
CONTRACTOR.
29. CONTRACTOR TO INSTALL TEMPORARY FILTERS OVER ALL RETURN AND EXHAUST GRILLES IN WORK AREA
DURING CONSTRUCTION.
30. THESE DRAWINGS ARE ACCOMPANIED BY SPECIFICATIONS. REFER TO SPECIFICATIONS FOR FURTHER
INFORMATION.
31. EQUIPMENT THAT REQUIRES MAINTENANCE SHALL BE LOCATED A MINIMUM OF 10'-0" FROM THE BUILDING ROOF
EDGE WHERE REQUIRED BY CODE.
32. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF TEMPORARY PARTITIONS.
33. SQUARE THROAT NOT ALLOWED ON RADIUS ELBOWS.
34. HYDRONIC AND PLUMBING VALVES, CIRCUIT SETTERS AND OTHER ACCESSORIES REQUIRING ACCESS SHALL BE
ACCESSIBLE VIA A STANDARD LADDER SO COMPONENTS MAY BE REPLACED, REPAIRED, OR UTILIZED WITHOUT
THE NEED FOR EXTENSIVE CEILING REMOVAL, SCAFFOLDING OR A MAN LIFT.WHERE POSSIBLE NO MORE THAN
48”ABOVE THE FINISHED CEILING.
1. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. BRING ANY DISCREPANCIES FROM THE DRAWINGS
AND NOTES TO THE ARCHITECT IMMEDIATELY. MINOR CHANGES IN THE SCOPE OF THE DEMOLITION WORK SHALL
NOT JUSTIFY AN ADDITIONAL COST.
2. REMOVAL OF EXISTING FIXTURES AND EQUIPMENT WILL REQUIRE ISOLATING THE PIPING RISERS OR MAINS VIA
SHUT-OFF VALVES. INSTALL NEW ISOLATION VALVES WHERE REQUIRED FOR COMPLETION OF WORK.
3. REMOVAL OF EXISTING PLUMBING FIXTURES AND EQUIPMENT, ETC. WILL REQUIRE CAPPING AND SEALING EXISTING
MAINS OR BRANCHES AS NECESSARY AND REQUIRED TO ALLOW THE REMAINING SYSTEMS TO FULLY OPERATE
WITHOUT DEGRADATION.
4. CONTRACTOR SHALL PROVIDE PROTECTIVE PLASTIC DROP CLOTHS TO PROTECT THE EXISTING OCCUPIED AREAS
AND EQUIPMENT FROM DUST AND DEBRIS DURING THE CONSTRUCTION WORK, AND SHALL CLEAN THE AREAS OF ALL
CONSTRUCTION DIRT DAILY, AND UPON COMPLETION OF THE WORK.
5. ALL DRAINED PIPING RISERS AND MAINS SHALL BE REFILLED WITH PROPER FLUID AND PROPERLY VENTED BY THIS
CONTRACTOR, ONCE NEW WORK HAS BEEN INSTALLED.
6. COORDINATE WITH GENERAL CONTRACTOR THE REMOVAL AND REPLACEMENT OF ALL EXISTING CEILINGS, WALLS,
ETC. AS REQUIRED FOR MECHANICAL DEMOLITION WORK.
7. EXISTING PIPING AND EQUIPMENT, ETC., NOT TO BE UTILIZED IN THE COMPLETED BUILDING SHALL BE DISCONTINUED
OR REMOVED AS REQUIRED. ALL ENDS OF DISCONTINUED PIPING SHALL BE CAPPED IN THE NEAREST WALL, CEILING
OR FLOOR SO THAT THEY ARE COMPLETELY CONCEALED. OPENINGS LEFT IN WALLS, CEILINGS, ETC., WHERE
EQUIPMENT AND PIPE, ETC., ARE REMOVED AND NOT REPLACED, SHALL BE PATCHED NEATLY WITH SIMILAR
MATERIAL TO ADJACENT CONSTRUCTION. REFER TO DRAWINGS DELINEATING NEW WORK FOR ADDITIONAL
INFORMATION REGARDING SYSTEMS OR PORTIONS OF SYSTEMS WHERE USE IS TO BE DISCONTINUED.
8. EXISTING PIPING, FIXTURES AND EQUIPMENT THAT ARE NOT TO BE REUSED SHALL BE REMOVED AND SHALL REMAIN
THE PROPERTY OF THE OWNER IF THEY WISH TO RETAIN OWNERSHIP OF SAME. IF NOT, EQUIPMENT SHALL BECOME
THE PROPERTY OF THIS CONTRACTOR AND SHALL BE REMOVED FROM THE SITE AS SOON AS PRACTICAL AND
DISPOSED OF IN ACCORDANCE WITH APPLICABLE LAWS AND REGULATIONS.
9. ALL CUTTING AND CHANNELING OF EXISTING BUILDING SHALL BE ACCOMPLISHED IN A NEAT AND WORKMANLIKE
MANNER WITHOUT REMOVAL OF EXCESS MATERIALS. THIS CONTRACTOR SHALL PATCH AND REPLACE WITH
MATERIAL SIMILAR TO ADJACENT CONSTRUCTION.
10. WHERE EXISTING PIPING AND EQUIPMENT, ETC., THAT ARE TO BE UTILIZED IN THE COMPLETED PROGRAM CONFLICT
WITH NEW CONSTRUCTION AND THE REQUIRED DEMOLITION, THEY SHALL BE RELOCATED AND RECONNECTED TO
MAINTAIN THE DESIRED SERVICE.
11. PORTIONS OF EXISTING SYSTEMS MAY BE SHOWN FOR CLARITY EVEN THOUGH IT MAY NOT BE NECESSARY TO
MODIFY OR REVISE THEM. ALL EXISTING SYSTEMS ARE SHOWN BASED ON ORIGINAL OR REMODEL BUILDING
DRAWINGS. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS.
12. ALL WORK MUST BE COORDINATED AND SCHEDULED WITH THE OWNER AND OCCUPANTS OF THIS BUILDING SO AS
TO PROVIDE THE LEAST AMOUNT OF DISRUPTION OF BUILDING ACTIVITIES AS POSSIBLE. MAINTAIN CONDITIONED
SPACE FOR ALL OWNER OCCUPIED AREAS DURING CONSTRUCTION.
13. ALL ACCESSIBLE ABANDONED PIPING AND DUCTWORK SHALL BE REMOVED AND PROPERLY DISPOSED OF.
NOTE: NOT ALL MAY APPLY TO PROJECT
SHEET NUMBER
WHERE REFERENCED
SHEET NUMBER
WHERE DRAWN
DETAIL NUMBER
SHEET NUMBER
WHERE DRAWN
DETAIL NUMBER
SHEET NUMBER
WHERE REFERENCED
EQUIPMENT
CALLOUT
SHEET NUMBER
WHERE DRAWN
SECTION LETTER
111
1
REFER TO PLAN NOTES#ROOM CALLOUT
DEMOLITION PEN WEIGHT -COMPONENT MAY ALSO BE SHADED
CONNECT NEW TO EXISTING. VERIFY EXACT LOCATION.
REVISION NUMBER
EXISTING COMPONENT PEN WEIGHT
EXISTING EQUIPMENT OR MATERIAL DESIGNATION(E)
DISCONNECT FROM EXISTING. VERIFY EXACT LOCATION.
E.C.ELECTRICAL CONTRACTOR
GENERAL CONTRACTORG.C.
P.C.PLUMBING CONTRACTOR
M.C.MECHANICAL CONTRACTOR
TEMPERATURE CONTROL CONTRACTORT.C.C.
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
HVAC & PLUMBING SYMBOL SCHEDULE
GAS COCK / GLOBE VALVE
GATE VALVE -SHUT OFF VALVE
VALVE IN DROP / VALVE IN RISER
BUTTERFLY VALVE
2-WAY / 3-WAY CONTROL VALVE (PNEUMATIC)
BALL VALVE
PLUG VALVE
STRAINER / UNION OR FLANGE CONNECTION
THERMOMETER / PRESSURE GAUGE
CHECK VALVE3 PIECE BALL VALVE / HYDRAULIC VALVE
EMERGENCY VALVE WITH FIRE LINK
2-WAY / 3-WAY CONTROL VALVE (ELECTRIC)
PRESSURE REDUCING VALVE (PRV) / WAFER CHECK VALVE
CIRCUIT SETTER -CALIBRATED BALANCE VALVE
CALIBRATED ORIFICE PLATE FLOW METER
AUTOMATIC FLOW CONTROL VALVE
SPRING HANGER / PIPE HANGER
DOUBLE CHECK BACKFLOW ASSEMBLY
REDUCED PRESSURE ZONE BACKFLOW ASSEMBLY
CAP / CAPPED OUTLET
PIPE DROP / PIPE RISE TOP CONNECTION, 45° OR 90° / BOTTOM CONNECTION, 45° OR 90°
SIDE CONNECTIONDIRECTION OF FLOW / ANCHOR
CONCENTRIC REDUCER OR INCREASER / ECCENTRIC REDUCER
DOMESTIC COLD WATER LINE (CW)ABOVE FLOOR WASTE LINE (W)
BELOW WASTE LINE (W)DOMESTIC HOT WATER LINE (HW)
HOT WATER RECIRC LINE (HWC)PLUMBING VENT LINE (V)
F
RL RAIN LEADER (RL) / OVERFLOW RAIN LEADER (ORL)
FIRE PROTECTION LINE (F)SWS STORM SEWER (SWS)
CD COOLING COIL CONDENSATE DRAIN LINE (CD)
WCO
CO CO
CO
FLOOR DRAIN / TRENCH DRAIN
PLUMBING FIXTURE CALLOUT
WATER HAMMER ARRESTOR -PDI SIZE
P-#
WHA#
DOMESTIC HOT WATER PUMPDHWP
VTR VENT THROUGH ROOF
WALL CLEANOUT / END OF LINE CLEANOUT
CLEANOUT (FLOOR) / 2-WAY CLEANOUT (FLOOR)
HOSE REEL / HOSE BIBB
G NATURAL GAS LINE (G)
BOTTOM OF PIPE ELEVATION ABOVE FLOORBOP
TOP TOP OF PIPE ELEVATION ABOVE FLOOR
ROOF DRAIN / OVERFLOW ROOF DRAIN
VITRIFIED CLAY PIPE / POLYVINYL CHLORIDE PIPE
CI CAST IRON
F/S
WH-#
FILTER-SEPARATOR
WATER HEATER CALLOUT
WALL HYDRANTWH
FS FLOOR SINK
TYP.TYPICAL ALL INSTANCES
NOT ALL MAY BE USED ON PROJECT
THERMOSTATIC MIXING VALVETMV
SR SUPPLY REGISTER
MAKE-UP AIR UNITMAU
HUMIDIFIERH
DP DIFFERENTIAL PRESSURE UH UNIT HEATER
COMPUTER ROOM AIR CONDITIONING UNITCRAC
ULTRAVIOLET STERILE CONDITIONERUV
24x12
24x12
24x12
RETURN DUCT RISER
SUPPLY DUCT DROP / RETURN DUCT DROP
SUPPLY DUCT RISER
FLEXIBLE DUCT
TURNING VANES
(UP)DUCT SEC., POSITIVE PRESSURE-FIRST SIZE IS TOP DIM.(TYP.)
(DOWN) DUCT SECTION, POSITIVE PRESSURE
(UP) DUCT SECTION, NEGATIVE PRESSURE
R
24x12
18x12
BALANCING DAMPER W/ MANUAL LOCKING QUADRANT
SIDE WALL SUPPLY REGISTER
(DOWN) DUCT SECTION, NEGATIVE PRESSURE
DUCT SIZE, FIRST FIGURE IS SIDE SHOWN-CLEAR INSIDE DIM.
DUCT CHANGE OF ELEVATION RISE(R) DROP(D)
FLEXIBLE CONNECTION
BALANCING DAMPER W/ MOTORIZED LOCKING QUADRANT
TH ELECTRIC OR DDC THERMOSTAT (TSTAT)
FIRE DAMPER IN WALLFD
SD SMOKE DAMPER
FD FIRE DAMPER IN FLOOR
ELECTRIC OR DDC HUMIDISTAT (HSTAT)
T
M
H
TEMPERATURE SENSOR
MOTOR
HUMIDITY SENSOR
R RADIATION DAMPER
COMBINATION FIRE/SMOKE DAMPER IN WALLFSD
FSD COMBINATION FIRE/SMOKE DAMPER IN FLOOR
OPPOSED BLADE DAMPEROBD
TOP OF DUCT ELEVATION ABOVE FLOOR
BOD
TOD
FTU / FCU
SF SUPPLY AIR FAN
FAN POWERED TERMINAL UNIT / FAN COIL UNIT
ROOFTOP UNIT / AIR HANDLING UNITRTU / AHU
F FURNACE
SA / OA SUPPLY AIR / OUTSIDE AIR
RETURN AIR / EXHAUST AIRRA / EA
DH DUCT HEATER
BOTTOM OF DUCT ELEVATION ABOVE FLOOR
BOS BOTTOM OF STEEL EF / RG EXHAUST FAN / RETURN GRILLE
VAV VARIABLE AIR VOLUME UNIT
CVR CONSTANT VOLUME REHEAT UNIT
V V R VARIABLE VOLUME REHEAT UNIT
VARIABLE VOLUME VARIABLE TEMPERATUREV V T
RECTANGULAR -OPPOSED BLADE / ROUND -BUTTERFLY
RECTANGULAR -OPPOSED BLADE / ROUND -BUTTERFLY
VARIABLE FREQUENCY DRIVEVFD
CWS CHILLED WATER SUPPLY LINE (CWS)
CWR CHILLED WATER RETURN LINE (CWR)CWP CHILLED WATER PUMP
CWPP / CWSP CHILLED WATER PRIMARY PUMP / SECONDARY PUMP
ORL
FD / TD
RD / ORD
VCP / PVC
HR / HB
UNFILTERED DOMESTIC COLD WATER LINE (UCW)PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:06 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
MP001MECHANICAL COVER SHEET Atlantic BeachFleet LandingColeman RemodelFloridaJDB
SHEET LIST
MP001 MECHANICAL COVER SHEET
M101 1/8" FIRST FLOOR DEMO PLAN - HVAC
M102 1/8" SECOND FLOOR DEMO PLAN - HVAC
M103 1/8" ROOF DEMO PLAN - HVAC
M201 1/8" FIRST FLOOR PLAN - HVAC
M202 1/8" SECOND FLOOR PLAN - HVAC
M203 1/8" FIRST FLOOR PLAN - HYDRONICS
M204 1/8" SECOND FLOOR PLAN - HYDRONICS
M205 1/8" ROOF PLAN - HVAC
M300 1/2" ENLARGED CHILLER PLAN
MT100 HVAC SCHEDULES
MT102 HVAC SCHEDULES
MT103 HVAC SCHEDULES
MT200 HVAC DETAILS
MT201 HVAC DETAILS
MT300 HVAC CONTROLS
MT301 HVAC CONTROLS
P101 1/8" FIRST FLOOR DEMO PLAN - PLUMBING
P102 1/8" SECOND FLOOR DEMO PLAN - PLUMBING
P200 1/8" FIRST FLOOR PLAN - UNDERGROUND PLUMBING
P201 1/8" FIRST FLOOR PLAN - PLUMBING
P202 1/8" SECOND FLOOR PLAN - PLUMBING
P300 1/4" ENALRGED PLANS - PLUMBING
P400 PLUMBING RISER DIAGRAMS
P401 PLUMBING RISER DIAGRAMS
PT100 PLUMBING SCHEDULES AND DETAILS
NO. DATE DESCRIPTION
A
B
C
D
E
F
1 2 3 4 5 6G
DEMO (E) CHILLED WATER AIR
HANDLERS, AHU-1 THRU 6, AND ALL
ASSOCIATED DUCTWORK, CWS/R PIPING,
FAN COILS AND RELATIVE
APPURTENANCES.
(E) EXAHUST SYSTEM FOR
RESTROOM GROUP TO REMAIN.
(E) ELEVATORS AND
ASSOCIATED EQUIPMENT NOT
IN SCOPE.
(E) VESTIBULE HAS JUST FINISHED A
RENOVATION. HVAC FOR VESTIBULE SHALL
BE TIED INTO NEW SYSTEMS.
HVAC DEMO NOTES
1. PLANS ARE SCHEMATIC IN NATURE.
LAYOUT IS BASED ON BEST AVAILABLE
INFORMATION. CONTRACTOR SHALL FIELD
VERIFY EXISTING CONDITIONS AND
DIMENSIONS. BRING ANY DISCREPANCIES
FROM THE DRAWINGS AND NOTES TO THE
OWNER'S REPRESENTATIVE IMMEDIATELY.
MINOR CHANGES IN THE SCOPE OF THE
DEMOLITION WORK SHALL NOT JUSTIFY AN
ADDITIONAL COST.
2. DEMOLISH ALL DUCTWORK, PIPING, AND
EQUIPMENT SHOWN SHADED, DASHED
AND IN A DARK LINE WEIGHT. PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:41:55 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
M1011/8" FIRST FLOOR DEMO PLAN - HVAC Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
A
B
C
D
E
F
1 2 3 4 5 6
G
(E) AIR HANDLERS, AHU-7
AND AHU-8, IN MEZZANINE
ARE TO BE REMOVED AND
REPLACED.(E) AIR HANDLER, AHU-9 IN
MEZZANINE ARE TO BE
REMOVED AND REPLACED.
(E) OUTSIDE AIR DUCT AND
ASSOCIATED HOOD FOR AHU-9
TO BE REMOVED AND
REPLACED WITH NEW.
(E) EXHAUST DUCT AND
ASSOCIATED FAN TO REMAIN.
(E) 22x22 OUTSIDE AIR DUCT AND
ASSOCIATED HOOD SERVING (E)
AHU-7 AND (E)AHU-8 TO BE
REMOVED AND REPLACED.
DEMO (E) SUPPLY AND RETURN DUCT
AS SHOWN. CONTRACTOR SHALL
FIELD VERIFY EXACT LAYOUTS.
(E) KITCHEN HOOD AND ALL ASSOCIATED
DUCTWORK, PIPING AND APPURTENANCES
TO BE REMOVED.
ALL (E) SLOT DIFFUSERS IN ATRIUM
TO BE REMOVED.
(E) KITCHEN NOT IN SCOPE
(E) GRILLES TO BE
REMOVED AND REPLACED
WITH NEW.
(E) GRILLES TO BE
REMOVED.
(E) GRILLES TO BE
REMOVED AND REPLACED
WITH NEW.
24x2438x24
30x30
42x24
8x248x16
24x16
HVAC DEMO NOTES
1. PLANS ARE SCHEMATIC IN NATURE.
LAYOUT IS BASED ON BEST AVAILABLE
INFORMATION. CONTRACTOR SHALL FIELD
VERIFY EXISTING CONDITIONS AND
DIMENSIONS. BRING ANY DISCREPANCIES
FROM THE DRAWINGS AND NOTES TO THE
OWNER'S REPRESENTATIVE IMMEDIATELY.
MINOR CHANGES IN THE SCOPE OF THE
DEMOLITION WORK SHALL NOT JUSTIFY AN
ADDITIONAL COST.
2. DEMOLISH ALL DUCTWORK, PIPING, AND
EQUIPMENT SHOWN SHADED, DASHED
AND IN A DARK LINE WEIGHT. PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:42:02 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
M1021/8" SECOND FLOOR DEMO PLAN - HVAC Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
A
B
C
D
E
F
1 2 3 4 5 6
G
(E) INTAKE HOOD TO BE
REMOVED AND REPLACED.
(E) EXHAUST FAN AND MAKEUP AIR
UNIT FOR (E) KITCHEN HOOD TO
BE REMOVED. CONTRACTOR
SHALL PATCH ROOF AS
NECESSARY AND MATCH (E)
ROOFING.
(E) RESTROOM EF.
(E) INTAKE HOOD TO BE
REMOVED AND REPLACED.
HVAC DEMO NOTES
1. PLANS ARE SCHEMATIC IN NATURE.
LAYOUT IS BASED ON BEST AVAILABLE
INFORMATION. CONTRACTOR SHALL FIELD
VERIFY EXISTING CONDITIONS AND
DIMENSIONS. BRING ANY DISCREPANCIES
FROM THE DRAWINGS AND NOTES TO THE
OWNER'S REPRESENTATIVE IMMEDIATELY.
MINOR CHANGES IN THE SCOPE OF THE
DEMOLITION WORK SHALL NOT JUSTIFY AN
ADDITIONAL COST.
2. DEMOLISH ALL DUCTWORK, PIPING, AND
EQUIPMENT SHOWN SHADED, DASHED
AND IN A DARK LINE WEIGHT. PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:42:11 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
M1031/8" ROOF DEMO PLAN - HVAC Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
T
T
T
TT
T
T
T
T
TT
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
A
B
C
D
E
F
1 2 3 4 5 6
G
CONFERENCE ROOM
118
OFFICE
114
EXISTING WATER SUPPLY
110
EXISTING ELECT
107 ?
?
ELEVATOR EQUIPMENT
104
SOCIAL MAIL
102
WORK ROOM
129
CONFERENCE ROOM
131
EXECUTIVE GATHERING
128
OFFICE
124
OFFICE
125
OFFICE
126
OFFICE
127
OFFICE
133
MECH
132
SALES & FINISHES
135
STAIR 1
001 STAIR 2
002
MARKETING
143
LIBRARY DIRECTOR
142
MECH
139
MKTG DIR
146
SPORTS BAR
155
RECEPTION
122 VEST
123
ELEVATOR LOBBY
121
CORRIDOR
101
IT
138
STORAGE
130
ATRIUM
136
CORRIDOR
137
REAR VEST
134
SALES & MARKETING
140
OFFICE
141
IL SALES
145
AL SALES
147
OFFICE
149
OFFICE
150
SUPPLY
148EXISTING LIBRARY
151
MEN
164
SHOWER
163
TOILET
162
WOMEN
161
EXT'G MECH
109
MECH/ELEC
159
A/C CLOSET
158CORR
160
ELEV 1
E001
ELEV 2
E002
ELEV 3
E003
EXISTNG VESTIBULE
119
IT
156 BAR SERVICE
154
DEVELOPMENT DIRECTOR
103
PANTRY
157
STORAGE
113
MECH
152
OFFICE
116
FOOD SERVICE DIRECTOR
117
CORRIDOR
115
JANITOR
112
EXISTING CORRIDOR
111
SJ6145
SJ8200
SJ10250
SJ10250SJ6165SJ6150
AHU-1
AHU-2
AHU-4
AHU-5
AHU-3
PROVIDE NEW CHILLED WATER VAV AIR
HANDLER TO SERVE FIRST FLOOR.
TYPICAL 5
SJ650
SJ6135
SJ6100 LSE8-1s100
LSE8-1s100
LSE8-1s100
LSE8-1s155
LSE10-2s210
LSE10-2s210
LSE8-1s125
LSE8-1s125
SJ650
SJ6100
SJ650
SJ650
SJ650
SJ8250 SJ10320
SJ8175
SJ8175
SJ8175
SJ8250
LSE10-2s250
LSE8-2s125
LSE8-2s125
SJ6200
LSE8-1s175
LSE8-1s150
LSE8-1s150
LSE8-2s200
SJ680
SJ6170
SJ665
SJ675
SJ675
LSE8-1s150
LSE8-1s150
LSE8-1s150 LSE8-1s150 LSE8-2s200
LSE8-2s200
LSE8-2s200
TERMINATE AHU OA INTAKE
AND RELIEF WITH LOUVER IN
EXTERIOR WALKWAY
CEILING. TYPICAL
TERMINATE AHU OA INTAKE
LOUVER IN EXTERIOR
WALKWAY CEILING.
VAV.4.1 VAV.4.2
VAV.4.3
VAV.4.4 VAV.4.5
VAV.4.6
VAV.4.7
VAV.3.1
VAV.3.2
VAV.2.2
VAV.2.1
VAV.2.3
VAV.1.1 VAV.1.2
VAV.1.3
VAV.1.4
VAV.1.5
VAV.1.6
VAV.5.1
VAV.5.2
VAV.5.3
VAV.5.4
VAV.5.5
VAV.5.6
VAV.5.7
VAV.5.8
VAV.5.9
VAV.5.10 VAV.5.11
VAV.5.12
LSE8-1s150LSE8-1s150
LSE10-2s250
(TYP. 4)
LSE8-2s200
12x12
12x10
12x10
20x1620x16
20x16
12x10
LRE12-4s400
(TYP. 3)
(TYP. 3)
12x12
10x8
14x13
12x10
20x1220x20 26x1626x16
20x20
34x1212x12 12x8 16x12TYPICAL RF DIFFUSER.18x1224x20
24x20
14x10
14x10
12x10 32x1212x1220x88x8
18x10
14x14
14x1412x8LRE10-3s300
(TYP. 3)
12x8
14x10
12x8
10x1024x1214x1010x8
12x812x1012x8SB6100
SA650
SB6125
(E) RESTROOM EXHAUST
FANS TO BE REUSED.14x1214x12
LRD8-3s600
SJ650
SX6x650
SJ675 SJ675
EXISTING HVAC EQUIPMENT
SERVING ELEVATOR ROOM
TO REMAIN.
L-1
L-2
L-3
EXISTING MINI-SPLIT
SREVING IT ROOM TO
REMAIN.16x12SX12x12200
VAV.1.7
L-4
L-5
L-6
L-7
L-8
(TYP. 4)
8"ø
12x8AC.1
14x1214"øSJ10280
PROVIDE INSULATED BACKING
FOR T-STAT ON EXTERIOR WALL.
LRE10-2s250
(TYP. 2)
LSE6-1s85
LSE6-1s90
MECHANICAL GENERAL NOTES
1. DUCT SIZES SHOWN ARE ACTUAL INSIDE
CLEAR DIMENSIONS. INSULATION
THICKNESS HAS NOT BEEN ACCOUNTED
FOR. DUCTWORK EXPOSED TO SPACE
SHALL NOT HAVE EXTERIOR INSULATION.
2. T-STATS AND OTHER CONTROL DEVICES
SHALL BE LOCATED NEXT TO LIGHT
SWITCH WITHIN THE ROOM SHOWN.
COORDINATE WITH GC AND ELECTRICAL
CONTRACTOR TO MATCH HEIGHT AND
LOCATION.
3. AVOID ROUTING DUCTWORK OVER
ELECTRICAL ROOMS AND ELECTRICAL
PANELS. MAINTAIN N.E.C. CLEARANCES.
COORDINATE ROUTING WITH ELECTRICAL
CONTRACTOR.
4. ALL SUPPLY AIR BRANCHES FOR SUPPLY
DIFFUSERS TO HAVE MANUAL BALANCE
DAMPERS, NOT ALL SHOWN FOR CLARITY.
WHERE HARDLID CEILINGS PREVENT
BALANCE DAMPER ACCESS, CONFIRM
WITH GRD SCHEDULE OR ENGINEER TO
USE OBD’S OR REMOTE BALANCE
DAMPERS.
5. ALL DUCTWORK SHALL BE ROUTED AS
HIGH AS POSSIBLE WITHIN THE CEILING
SPACE. UTILIZE JOIST SPACE WHERE
POSSIBLE, ESPECIALLY WHEN CROSSING
OTHER DUCT, PIPE AND ELECTRICAL.
6. PROVIDE FLEXIBLE DUCT AND PIPE
CONNECTIONS TO ALL MOTORIZED
EQUIPMENT.
7. VERIFY ALL EQUIPMENT ACCESS PANELS
WITH MANUFACTURER AND ARCHITECT.
ACCESS PANELS SHALL BE 24X24 U.N.O.
LOCATIONS SHALL BE COORDINATED WITH
THE ARCHITECT AND THE LOCATIONS OF
THE EQUIPMENT THEY SERVE. ACCESS
PANELS SHALL NOT BE INSTALLED IN
WOOD CEILINGS.
8. COORDINATE FINISH OF ALL EXPOSED
DUCT WITH ARCHITECT. DUCTWORK THAT
IS TO BE PAINTED SHALL HAVE A PAINT
GRIP FINISH ACCEPTABLE FOR PAINTING.
9. EXPOSED SPIRAL DUCT GRILLES SHALL BE
INSTALLED AT A 30 DEGREE ANGLE
DOWNWARD BELOW HORIZONTAL.
10. REFER TO GRD SCHEDULE FOR DUCT
CONNECTION SIZES. REFER TO TERMINAL
BOX SCHEDULE FOR INLET DUCT SIZES.
11. CEILING COORDINATION OF ALL MEP
SYSTEMS (LIGHTING, DUCTWORK,
DIFFUSERS, ELECTRICAL, ETC.) MUST BE
COMPLETED BY THE CONTRACTOR PRIOR
TO THE START OF ANY NEW
INSTALLATION.PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:42:30 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
M2011/8" FIRST FLOOR PLAN - HVAC Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
K
T
T
T
T
T
T
A
B
C
D
E
F
1 2 3 4 5 6
G
STAIR 1
001 STAIR 2
002
MENS ACCESSIBLE
208
RESTROOM
211
COATS
212
BEV STATION
209
EXISTING WOMENS
206
EXISTING MENS
207
WOMENS ACCESSIBLE
205
OFFICE
204
EXHIBITION DINING
223
EXHIBITION KITCHEN
222
KITCHEN SUPPORT
221
GALLERY
220
ELEV LOBBY
213
COMMUNITY DINING
210
BEV STATION
218
PRIVATE DINING/WINE
ROOM
219
EXT'G ELEC
217
BEV SUPPLIES
225
BAR/BEV STATION
224
EXISTING MECH
226
EXISTING KITCHEN
201
ELEV 1
E001
ELEV 2
E002
ELEV 3
E003
EXISTING WALK-IN
202
PANTRY
203
J.C.
15
AHU-6
AHU-8
AHU-728x28 OA DUCT DOWN FROM NEW
INTAKE HOOD ON ROOD. BRANCH
DUCT IN MEZZANINE AND ROUTE
30x20 OA TO AHU-6 AND 20x16 TO
AHU-8.
20x18 20x18
14x1214x12
SX22x6400(TYP. 10)40x24UP TO EXISTING EXHAUST
FAN, REBALANCE TO 940 CFM
UP TO NEW
EXHAUST FAN, EF-1.
UP TO NEW MAU
ON ROOF, MAU-1.
(E) KITCHEN NOT IN SCOPE
VAV.7.1
VAV.7.3
VAV.7.4
VAV.7.5
VAV.7.222x2022x20 E ( )42x24
E ( )30x30
UP TO IH-1 AND
RH-1ON ROOF.
34x24
28x2028x2012"ø
14"ø 16x15 E ( )24x16
30x20
22x1414x13
16x14
12x10
16x12
SC650
SJ650
SJ675
SA650 EC6x675
EC675
8x8
10"ø LSE8-1s150
LSE8-1s150
LSE10-2s250(TYP. 6)
LSE6-1s75
(TYP. 10)
RG12x12440
SJ10440
LSE10-2s250(TYP. 2)
E ( )8x24
E ( )8x16
E ( )24x24 E ( )38x24
SJ690
SJ8160
TIE (E) DUCTWORK INTO NEW
AHU. FIELD VERIFY EXISTING
CONNECTIONS.
E ( )16x12
VERIFY FINAL CONNECTIONS TO
HOOD WITH KITCHEN
CONSULTANT DRAWINGS. REFER
TO HOOD DRAWINGS FOR
AIRFLOW BALANCING.
SX18x10700
1
SJ8160
TIE (E) DUCTWORK INTO NEW
AHU. FIELD VERIFY EXISTING
CONNECTIONS.
SX12x10350(TYP. 2)
3 3
3 3
26x2626x26
RX42x365510
E ( )30x30
LRE10-2s250
(TYP. 2)
16x10
ALL EXTERIOR LINEAR SLOT DIFFUSERS TO
HAVE TOP CONNECTIONS TO FIT IN SOFFIT.
CONTRACTOR TO PROVIDE CUSTOM
CONNECTION AS NEEDED.
2
KITCHEN EXHAUST
DUCT
LRE12-4s375
(E)350
(E)200(E)70
(E)125
(E)400(E)375(E)90 E ( )14x14DUCTWORK WITHIN CUSTOM METAL SOFFIT.
DUCTWORK TO BE INSTALLED AT TOP OF
SOFFIT THROUGHOUT TO MAINTAIN ELEVATION
FOR GRILLE CONNECTIONS. DUCTWORK SHALL
BE LINED IN THE SOFFIT; SIZES CALLED OUT
ARE EXTERIOR SHEET METAL, LINING HAS BEEN
ACCOUNTED FOR. COORDINATE WITH
ARCHITECTURAL DRAWINGS.
LRE12-4s700(TYP. 3)
26x1612x1212x1236x36 RETURN DUCT TO
RELIEF HOOD, RH-2.
MECHANICAL GENERAL NOTES
1. DUCT SIZES SHOWN ARE ACTUAL INSIDE
CLEAR DIMENSIONS. INSULATION
THICKNESS HAS NOT BEEN ACCOUNTED
FOR. DUCTWORK EXPOSED TO SPACE
SHALL NOT HAVE EXTERIOR INSULATION.
2. T-STATS AND OTHER CONTROL DEVICES
SHALL BE LOCATED NEXT TO LIGHT
SWITCH WITHIN THE ROOM SHOWN.
COORDINATE WITH GC AND ELECTRICAL
CONTRACTOR TO MATCH HEIGHT AND
LOCATION.
3. AVOID ROUTING DUCTWORK OVER
ELECTRICAL ROOMS AND ELECTRICAL
PANELS. MAINTAIN N.E.C. CLEARANCES.
COORDINATE ROUTING WITH ELECTRICAL
CONTRACTOR.
4. ALL SUPPLY AIR BRANCHES FOR SUPPLY
DIFFUSERS TO HAVE MANUAL BALANCE
DAMPERS, NOT ALL SHOWN FOR CLARITY.
WHERE HARDLID CEILINGS PREVENT
BALANCE DAMPER ACCESS, CONFIRM
WITH GRD SCHEDULE OR ENGINEER TO
USE OBD’S OR REMOTE BALANCE
DAMPERS.
5. ALL DUCTWORK SHALL BE ROUTED AS
HIGH AS POSSIBLE WITHIN THE CEILING
SPACE. UTILIZE JOIST SPACE WHERE
POSSIBLE, ESPECIALLY WHEN CROSSING
OTHER DUCT, PIPE AND ELECTRICAL.
6. PROVIDE FLEXIBLE DUCT AND PIPE
CONNECTIONS TO ALL MOTORIZED
EQUIPMENT.
7. VERIFY ALL EQUIPMENT ACCESS PANELS
WITH MANUFACTURER AND ARCHITECT.
ACCESS PANELS SHALL BE 24X24 U.N.O.
LOCATIONS SHALL BE COORDINATED WITH
THE ARCHITECT AND THE LOCATIONS OF
THE EQUIPMENT THEY SERVE. ACCESS
PANELS SHALL NOT BE INSTALLED IN
WOOD CEILINGS.
8. COORDINATE FINISH OF ALL EXPOSED
DUCT WITH ARCHITECT. DUCTWORK THAT
IS TO BE PAINTED SHALL HAVE A PAINT
GRIP FINISH ACCEPTABLE FOR PAINTING.
9. EXPOSED SPIRAL DUCT GRILLES SHALL BE
INSTALLED AT A 30 DEGREE ANGLE
DOWNWARD BELOW HORIZONTAL.
10. REFER TO GRD SCHEDULE FOR DUCT
CONNECTION SIZES. REFER TO TERMINAL
BOX SCHEDULE FOR INLET DUCT SIZES.
11. CEILING COORDINATION OF ALL MEP
SYSTEMS (LIGHTING, DUCTWORK,
DIFFUSERS, ELECTRICAL, ETC.) MUST BE
COMPLETED BY THE CONTRACTOR PRIOR
TO THE START OF ANY NEW
INSTALLATION.
1. CONNECT NEW 8"ø DUCT TO (E)24x24
SUPPLY MAIN AND ROUTE TO DIFFUSER IN
KITCHEN SUPPORT 221.
2. CONNECT NEW 10"ø DUCT TO (E)42x24
SUPPLY MAIN AND ROUTE TO DIFFUSERS
SERVING BAR/BEV STATION 224 AND BEV
SUPPLIES 225.
3. (E) DUCTWORK TO BE EXTENDED INTO (E)
SOFFIT IN ATRIUM. DUCTWORK TO BE
TERMINATED WITH A SUPPLY GRILLE
THAT THROWS AIR VERTICALLY ALONG
WINDOWS. TOTAL AIR FLOW SHALL BE
1,200 CFM. FIELD VERIFY EXISTING SOFFIT
DIMENSIONS TO DETERMINE GRILLE SIZE.
PLAN NOTES
PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:42:44 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
M2021/8" SECOND FLOOR PLAN - HVAC Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
A
B
C
D
E
F
1 2 3 4 5 6
G
AHU-1
AHU-2
AHU-3
AHU-4
AHU-5
CONFERENCE ROOM
118
OFFICE
114
EXISTING WATER SUPPLY
110
EXISTING ELECT
107 ?
?
ELEVATOR EQUIPMENT
104
SOCIAL MAIL
102
WORK ROOM
129
CONFERENCE ROOM
131
EXECUTIVE GATHERING
128
OFFICE
124
OFFICE
125
OFFICE
126
OFFICE
127
OFFICE
133
MECH
132
SALES & FINISHES
135STAIR 1
001 STAIR 2
002
MARKETING
143LIBRARY DIRECTOR
142
MECH
139
MKTG DIR
146
?
?
SPORTS BAR
155
RECEPTION
122
VEST
123
ELEVATOR LOBBY
121
CORRIDOR
101
IT
138
STORAGE
130
ATRIUM
136
CORRIDOR
137
REAR VEST
134
SALES & MARKETING
140
OFFICE
141
IL SALES
145
AL SALES
147
OFFICE
149
OFFICE
150
SUPPLY
148EXISTING LIBRARY
151
MEN
164
SHOWER
163
TOILET
162
WOMEN
161
EXT'G MECH
109
MECH/ELEC
159
A/C CLOSET
158
CORR
160
ELEV 1
E001
ELEV 2
E002
ELEV 3
E003
EXISTNG VESTIBULE
119
IT
156
BAR SERVICE
154
DEVELOPMENT DIRECTOR
103
PANTRY
157
STORAGE
113
MECH
152
OFFICE
116
FOOD SERVICE DIRECTOR
117
CORRIDOR
115
JANITOR
112
EXISTING CORRIDOR
111
( ) E 6"CWR
( ) E 6"CWS
(E)6" CWS/R PIPES UP
TO SECOND FLOOR.
1-1/2" CWS/R PIPES
TO AHU-2.
1-1/2''CWR
1-1/2''CWS
1-1/4" CWS/R
PIPES TO AHU-1.
2-1/2''CWS
2-1/2''CWR
1-1/2" CWS/R
PIPES TO AHU-3.
2"CWS
2"CWR
2"CWR
2"CWS
2"CWS
2"CWR
2" CWS/R PIPES
TO AHU-5.
1-1/2''CWR
1-1/2''CWS1-1/2" CWS/R PIPES
TO AHU-4.
2"CWS
2"CWR
HYDRONICS GENERAL NOTES
1. PIPING ON EXTERIOR WALLS OR PRE-CAST
CONCRETE WALLS TO BE ROUTED IN
FRAMED WALL ON INTERIOR SIDE OF
INSULATION.
2. AVOID ROUTING PIPING OVER ELECTRICAL
ROOMS OR ELECTRICAL PANELS;
MAINTAIN N.E.C. CLEARANCES.
COORDINATE ROUTING WITH ELECTRICAL
CONTRACTOR.
3. PROVIDE FLEXIBLE PIPE CONNECTIONS
TO ALL MOTORIZED EQUIPMENT.
4. VERIFY ALL EQUIPMENT ACCESS PANELS
WITH MANUFACTURER AND ARCHITECT.
5. REFER TO TERMINAL BOX SCHEDULE FOR
ALL BRANCH HEATING WATER PIPE SIZES.
6. ALL VALVES SHALL BE INSTALLED ABOVE
DROP-IN CEILINGS IN AN ACCESSIBLE
LOCATIONS, OR WITH ACCESS PANELS IN
HARDLID CEILINGS. ACCESS PANELS
SHALL BE 24X24 U.N.O. COORDINATE
PANEL LOCATIONS WITH ARCHITECT.PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:42:50 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
M2031/8" FIRST FLOOR PLAN - HYDRONICS Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
A
B
C
D
E
F
1 2 3 4 5 6
G
STAIR 1
001 STAIR 2
002
?
?
MENS ACCESSIBLE
208
RESTROOM
211
COATS
212
BEV STATION
209
EXISTING WOMENS
206
EXISTING MENS
207
?
?OFFICE
204
EXHIBITION DINING
223
EXHIBITION KITCHEN
222
KITCHEN SUPPORT
221
GALLERY
220
ELEV LOBBY
213
COMMUNITY DINING
210
BEV STATION
218
PRIVATE DINING/WINE
ROOM
219
EXT'G ELEC
217
BEV SUPPLIES
225
BAR/BEV STATION
224
EXISTING MECH
226
EXISTING KITCHEN
201
ELEV 1
E001
ELEV 2
E002
ELEV 3
E003
EXISTING WALK-IN
202
PANTRY
203
ROOF ACCESS
219A
DINING
227
AHU-6
AHU-8
AHU-7
6"CWR
6"CWS
( ) E 6"CWS
( ) E 6"CWR
ROUTE NEW 2" CWS/R
LINES TO AHU-7 IN
MEZZANINE.
2-1/2" CWS/R LINES TO AHU-6
IN MEZZANINE.
3" CWS/R LINES TO AHU-8
IN MEZZANINE.
4"CWS
4"CWR
6" CWS/R PIPIES
FROM FIRST FLOOR.
HYDRONICS GENERAL NOTES
1. PIPING ON EXTERIOR WALLS OR PRE-CAST
CONCRETE WALLS TO BE ROUTED IN
FRAMED WALL ON INTERIOR SIDE OF
INSULATION.
2. AVOID ROUTING PIPING OVER ELECTRICAL
ROOMS OR ELECTRICAL PANELS;
MAINTAIN N.E.C. CLEARANCES.
COORDINATE ROUTING WITH ELECTRICAL
CONTRACTOR.
3. PROVIDE FLEXIBLE PIPE CONNECTIONS
TO ALL MOTORIZED EQUIPMENT.
4. VERIFY ALL EQUIPMENT ACCESS PANELS
WITH MANUFACTURER AND ARCHITECT.
5. REFER TO TERMINAL BOX SCHEDULE FOR
ALL BRANCH HEATING WATER PIPE SIZES.
6. ALL VALVES SHALL BE INSTALLED ABOVE
DROP-IN CEILINGS IN AN ACCESSIBLE
LOCATIONS, OR WITH ACCESS PANELS IN
HARDLID CEILINGS. ACCESS PANELS
SHALL BE 24X24 U.N.O. COORDINATE
PANEL LOCATIONS WITH ARCHITECT.PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:42:54 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
M2041/8" SECOND FLOOR PLAN - HYDRONICS Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
A
B
C
D
E
F
1 2 3 4 5 6
G
(E) RESTROOM EF
KITCHEN HOOD
EXHUAST FAN, EF-1.
NEW MAU FOR
KITCHEN HOOD,
MAU-1.
NEW AHU OA
INTAKE, IH-2.
NEW OA INTAKE FOR
AHU, IH-1.
NEW RELIEF HOOD
FOR AHU, RH-1.
NEW RELIEF HOOD
FOR AHU, RH-2.PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:42:58 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
M2051/8" ROOF PLAN - HVAC Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
(E) CHILLER TO REMAIN.
(E) CHILLED WATER PUMP,
EXPANSION TANK AND AIR
SEPARATOR TO BE REMOVED AND
REPLACED.
(E) EQUIPMENT PAD
(E) CHILLER
VERTICAL DUAL-ARM INLINE
PUMP, P-1.
EXPANSION TANK,
ET-1
AIR SEPARATOR,
AS-1
8"CWS
8"CWR
(E)CWS LINE TO
BUILDING.
(E) CONCRETE
EQUIPMENT PADS.
(E)CWR LINE TO
BUILDING.
REFER TO DETAIL 7/MT201 FOR
AIR SEPARATOR AND
EXPANSION TANK PIPING.PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:04 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
M3001/2" ENLARGED CHILLER PLAN Atlantic BeachFleet LandingColeman RemodelFloridaJDB
0'8'12'4'1/2" = 1'-0"
HVAC DEMOLITION PLAN - CHILLER10'8'12'4'1/2" = 1'-0"
HVAC PLAN - CHILLER2
NO. DATE DESCRIPTION
PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:10 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
MT100HVAC SCHEDULES Atlantic BeachFleet LandingColeman RemodelFloridaJDB
S
R
P
E
L
M
C
U
=
=
=
=
=
=
=
=
SUPPLY DIFFUSER
RETURN GRILLE
PLENUM RETURN GRILLE
EXHAUST GRILLE
SLOT DIFFUSER
LAMINAR FLOW SUPPLY DIFFUSER
SECURITY GRILLE
FLOOR MOUNTED SUPPLY GRILLE
1.
2.
3.
4.
5.
6.
7.
8.
SECOND LETTER DENOTES SEQUENCE. NOT ALL MAY BE USED.
PROVIDE SQUARE TO ROUND ADAPTERS AS REQUIRED TO ACCOMODATE ROUND RUNOUTS.
PROVIDE ALL LAY-IN GRDs WITH 24x24 LAY-IN PANEL AS REQUIRED.
FINISH TO BE WHITE UNLESS OTHERWISE SPECIFIED. COORDINATE AND VERIFY ALL FINISHES WITH ARCHITECT.
ALL SELECTIONS ARE BASED ON A MAXIMUM NC OF 25 UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL VERIFY ALL CEILING TYPES AND ASSOCIATED BORDER TYPES.
LOUVERED GRILLES TO HAVE FRONT BLADES PARALLEL TO LONG DIMENSION UNLESS WALL MOUNTED.
WALL MOUNTED LOUVERED GRILLES TO HAVE FRONT BLADES PARALLEL TO FLOOR.
FIRST LETTER IN MARK:NOTES:
GRILLE, REGISTER, AND DIFFUSER SCHEDULE
MARK TYPE IMAGE
BASED ON MOUNT PANEL SIZE
(FACE SIZE)MATERIAL BLADE SPACING /
SLOT WIDTH DEFLECTION REMARKSMFR MODEL
SA SUPPLY DIFFUSER TITUS TDC-AA LAY-IN
24x24
(6x6)ALUMINUM -- -- LOUVERED FACE
SB SUPPLY DIFFUSER TITUS TDC-AA LAY-IN
24x24
(9x9)ALUMINUM -- -- LOUVERED FACE
SC SUPPLY DIFFUSER TITUS TDC-AA LAY-IN
24x24
(12x12)ALUMINUM -- -- LOUVERED FACE
SJ SUPPLY DIFFUSER TITUS OMNI-AA LAY-IN 24x24 ALUMINUM -- -- --
LSE SLOT DIFFUSER TITUS TBDI-80 LAY-IN 48" WIDTH ALUMINUM 1" -- SEE PLANS FOR SLOT QTY
SX DUCT MOUNTED SUPPLY TITUS 300FS DUCT SEE PLANS ALUMINUM 3/4" DOUBLE --
RF RETURN GRILLE TITUS PAR LAY-IN
24x12
(22x10)ALUMINUM -- -- --
RG RETURN GRILLE TITUS PAR LAY-IN
24x24
(22x22)ALUMINUM -- -- --
LRD SLOT DIFFUSER TITUS TBR-80 LAY-IN 48" WIDTH ALUMINUM 3/4" -- SEE PLANS FOR SLOT QTY
LRE SLOT DIFFUSER TITUS TBR-80 LAY-IN 48" WIDTH ALUMINUM 1" -- SEE PLANS FOR SLOT QTY
RX DUCT MOUNTED RETURN TITUS 350FL/S DUCT SEE PLANS ALUMINUM 3/4" 35° --
EC EXHAUST GRILLE TITUS 350FL SURFACE
12x12
(10x10)ALUMINUM 3/4" 35° --
1.
2.
ALL EXHAUST FANS SHALL HAVE PERMANENTLY LUBRICATED BEARINGS AND DISCONNECT SWITCH PROVIDED AND INSTALLED BY EC.
DOWNBLAST AND UPBLAST EXHAUST FANS SHALL BE PROVIDED WITH ECM MOTOR, FAN SPEED CONTROLLER, BACKDRAFT DAMPER, BIRDSCREEN, INTERNAL WIRING PIGTAIL AND ROOF
CURB. VFD PROVIDED BY EQUIPMENT MANUFACTURER WHERE APPLICABLE.
REMARKS:
EXHAUST FAN SCHEDULE
MARK LOC AT
ROOM TYPE MIN CAP FAN RPM DRIVE
MOTOR (BY M.C.)WT LBS MANUFACTURER AND
MODELCFM SP HP ELEC START
EF-1 ROOF UPBLAST 7,700 0.55 792 DIRECT 5 460/3 VFD - CAPTIVEAIRE DU300HFA
1. UNIT IS BEING INSTALLED OUTSIDE, PROVIDE APPROPRIATE NEMA ENCLOSURE.
REMARKS:
PUMP SCHEDULE - HVAC
MARK LOC AT ROOM TYPE
MIN. CAPACITY MIN. SIZE CONN MOTOR (BY M.C.)MANUFACTURER AND MODELGPM FEET HEAD EFF SUCTION DISCH HP RPM SPEED ELECT STARTER
P-1 CHILLER PLANT DUAL ARLM VERTICAL INLINE 275 40 4 4 5 1740 - 460/3 VFD ARMSTRONG SERIES 4302
VAV-7.5 Price SDV5 10 875 265 450 1.00 0.25 55.00 95.00 2.10 SCRV 480-3 4.10 7.50 15.00 24 (2) -- 12.00 10.00
VAV-7.4 Price SDV5 8 795 240 240 1.00 0.25 55.00 95.00 3.00 SCRV 480-3 3.80 4.50 15.00 22 (2) -- 12.00 10.00
VAV-7.3 Price SDV5 6 425 130 130 1.00 0.25 55.00 95.00 1.50 SCRV 120-1 10 15.60 20.00 23 (2) -- 12.00 8.00
VAV-7.2 Price SDV5 12 1275 385 450 1.00 0.25 55.00 95.00 5.00 SCRV 120-1 6.67 7.50 15.00 22 (2) -- 12.00 8.00
VAV-7.1 Price SDV5 10 940 280 300 1.00 0.25 55.00 95.00 3.50 SCRV 480-3 4.69 5.30 15.00 -- -- 14.00 12.50
VAV-5.12 Price SDV5 8 500 150 410 1.00 0.25 55.00 95.00 5.30 SCRV 480-3 6.37 8.70 15.00 22 (2) -- 12.00 10.00
VAV-5.11 Price SDV5 6 165 65 125 1.00 0.25 55.00 95.00 1.60 SCRV 120-1 13.33 18.20 20.00 -- -- 12.00 8.00
VAV-5.10 Price SDV5 6 150 65 110 1.00 0.25 55.00 95.00 1.40 SCRV 120-1 11.67 15.90 20.00 -- -- 12.00 8.00
VAV-5.9 Price SDV5 6 300 90 90 1.00 0.25 55.00 95.00 1.20 SCRV 120-1 10 13.60 15.00 23 (2) -- 12.00 8.00
VAV-5.8 Price SDV5 6 155 65 65 1.00 0.25 55.00 95.00 0.80 SCRV 120-1 6.67 9.10 15.00 -- -- 12.00 8.00
VAV-5.7 Price SDV5 8 420 125 160 1.00 0.25 55.00 95.00 2.10 SCRV 120-1 17.50 23.80 25.00 -- -- 12.00 10.00
VAV-5.6 Price SDV5 6 200 65 120 1.00 0.25 55.00 95.00 1.60 SCRV 120-1 13.33 18.20 20.00 21 (2) -- 12.00 8.00
VAV-5.5 Price SDV5 6 250 75 75 1.00 0.25 55.00 95.00 0.80 SCRV 120-1 6.67 9.10 15.00 21 (2) -- 12.00 8.00
VAV-5.4 Price SDV5 6 145 65 75 1.00 0.25 55.00 95.00 1.00 SCRV 120-1 8.33 11.30 15.00 -- -- 12.00 8.00
VAV-5.3 Price SDV5 6 150 65 65 1.00 0.25 55.00 95.00 0.80 SCRV 120-1 6.67 9.10 15.00 -- -- 12.00 8.00
VAV-5.2 Price SDV5 6 175 65 65 1.00 0.25 55.00 95.00 0.80 SCRV 120-1 6.67 9.10 15.00 -- -- 12.00 8.00
VAV-5.1 Price SDV5 8 435 130 130 1.00 0.25 55.00 95.00 1.70 SCRV 120-1 14.17 19.30 20.00 20 (2) -- 12.00 10.00
VAV-4.7 Price SDV5 6 320 95 275 1.00 0.25 55.00 95.00 3.60 SCRV 480-3 4.33 5.90 15.00 24 (2) -- 12.00 8.00
VAV-4.6 Price SDV5 6 250 75 140 1.00 0.25 55.00 95.00 1.80 SCRV 120-1 15 20.40 25.00 24 (2) -- 12.00 8.00
VAV-4.5 Price SDV5 8 525 160 320 1.00 0.25 55.00 95.00 4.10 SCRV 480-3 4.93 6.70 15.00 23 (2) -- 12.00 10.00
VAV-4.4 Price SDV5 6 150 65 65 1.00 0.25 55.00 95.00 0.80 SCRV 120-1 6.67 9.10 15.00 -- -- 12.00 8.00
VAV-4.3 Price SDV5 8 500 150 150 1.00 0.25 55.00 95.00 1.90 SCRV 120-1 15.83 21.60 25.00 22 (2) -- 12.00 10.00
VAV-4.2 Price SDV5 6 250 75 100 1.00 0.25 55.00 95.00 1.30 SCRV 120-1 10.83 14.80 15.00 24 (2) -- 12.00 8.00
VAV-4.1 Price SDV5 6 150 65 65 1.00 0.25 55.00 95.00 0.80 SCRV 120-1 6.67 9.10 15.00 -- -- 12.00 8.00
VAV-3.2 Price SDV5 10 1000 300 300 1.00 0.25 55.00 95.00 3.90 SCRV 480-3 4.69 6.40 15.00 21 (2) -- 14.00 12.50
VAV-3.1 Price SDV5 10 800 240 240 1.00 0.25 55.00 95.00 2.90 SCRV 120-1 24.17 32.90 35.00 -- -- 14.00 12.50
VAV-2.3 Price SDV5 8 600 180 320 1.00 0.25 55.00 95.00 4.10 SCRV 480-3 4.93 6.70 15.00 25 (2) -- 12.00 10.00
VAV-2.2 Price SDV5 8 600 180 320 1.00 0.25 55.00 95.00 4.10 SCRV 480-3 4.93 6.70 15.00 25 (2) -- 12.00 10.00
VAV-2.1 Price SDV5 8 555 165 165 1.00 0.25 55.00 95.00 2.10 SCRV 120-1 17.50 23.80 25.00 24 (2) -- 12.00 10.00
VAV-1.7 Price SDV5 6 200 200 200 1.00 0.25 55.00 95.00 2.30 SCRV 120-1 19.17 26.10 30.00 23 (2) -- 12.00 8.00
VAV-1.6 Price SDV5 6 235 70 175 1.00 0.25 55.00 95.00 2.30 SCRV 120-1 19.17 26.10 30.00 23 (2) -- 12.00 8.00
VAV-1.5 Price SDV5 6 250 75 175 1.00 0.25 55.00 95.00 2.30 SCRV 120-1 19.17 26.10 30.00 23 (2) -- 12.00 8.00
VAV-1.4 Price SDV5 6 230 70 70 1.00 0.25 55.00 95.00 0.80 SCRV 120-1 6.67 26.10 30.00 23 (2) -- 12.00 8.00
VAV-1.3 Price SDV5 6 375 115 115 1.00 0.25 55.00 95.00 1.50 SCRV 120-1 12.50 17.00 20.00 27 (2) 21 (3) 12.00 8.00
VAV-1.2 Price SDV5 6 75 65 65 1.00 0.25 55.00 95.00 0.80 SCRV 120-1 6.67 9.10 15.00 -- -- 12.00 8.00
VAV-1.1 Price SDV5 6 375 115 150 1.00 0.25 55.00 95.00 1.90 SCRV 120-1 15.83 21.60 25.00 27 (2) 21 (3) 12.00 8.00
Tag Manufactu... Model Inlet Dia Max Primary (CFM) Min Primary (CFM) Reheat (CFM) Inlet SP (in. w.g.) Downstream SP (in.... EAT (°F) LAT (°F) EC Capacity (kW) Steps Volts Coil Amps MCA MOP Max Dis NC Max Rad NC Dis. W (in) Dis. H (in)
TERMINAL UNIT SCHEDULE
1. PROVIDE WITH ROOF CURB.
REMARKS:
MAKE-UP AIR UNIT SCHEDULE
MARK AIR FILTERS MOTOR (BY M.C.)MANUFACTURER AND MARK CFM ESP FILTER SIZE FILTER TYPE H.P. RPM ELECT STARTER
MAU-1 6160 0.5 16x20x2 MV EZ KLEEN 7.5 1226 460/3 - CAPTIVEAIRE DTP7/54
NO. DATE DESCRIPTION
PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:13 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
MT102HVAC SCHEDULES Atlantic BeachFleet LandingColeman RemodelFloridaJDB
AIR HANDLING UNIT SCHEDULE
MARK CFM
MIN OA
(CFM)
FAN COOLING COIL HEATING COIL
VOLT/PH FILTER
MANUFACTURER &
MODEL
ACCESSORIES
& REMARKSESP (IN) @
S.L.HP TOTAL
MBH SENS MBH EAT
DB/WB
LAT
DB/WB
EWT/LWT
(ºF)GPM EAT ºF LAT ºF kW
AHU-1 1610 240 1.5 1.5 47 34 78/66 55/55 44/56 7.5 59 65 3
460/3 MERV 13 ENGINEERED AIR
LM2/K/C/MV NOTES A,B,C,E
AHU-2 1755 765 1.5 2 92 55 84/71 55/55 44/56 15 50 65 8
460/3 MERV 13 ENGINEERED AIR
LM3/K/C/MV NOTES A,B,C,E
AHU-3 1800 1025 1.5 2.5 97 59 84/71 55/55 44/56 16 49 65 10
460/3 MERV 13 ENGINEERED AIR
LM3/K/C/MV NOTES A,B,C,E
AHU-4 2145 360 1.5 3 78 55 78/66 54/54 44/56 13 60 65 4
460/3 MERV 13 ENGINEERED AIR
LM4/K/C/MV NOTES A,B,C,E
AHU-5 3045 750 1.5 5 113 77 80/68 54/54 44/56 22 55 65 11
460/3 MERV 13 ENGINEERED AIR
LM4/K/C/MV NOTES A,B,C,F
AHU-6 8495 2985 1.5 10 357 257 82/69 55/54 44/56 58 56 75 60
460/3 MERV 13 SEASONS4
AH-80-EC60-CWC
NOTES
A,B,C,D,G
AHU-7 4310 1200 1.5 5 178 120 82/69 55/55 44/56 29 54 65 25
460/3 MERV 13 SEASONS4
AH-60-EC25-CWC
NOTES
A,B,C,D,F
AHU-8 15000 2000 0.75 15 501 394 82/66 56/55 44/56 82 54 75 60
460/3 MERV 13 SEASONS4
AH-150-EC60-CWC
NOTES
A,B,C,D,H
MECHANICAL EQUIPMENT SCHEDULE
MARK SERVICE TYPE CAPACITY/FLOW HP VOLT/ PHASE MANUFACTURER & MODEL
AS-1 CHILLED WATER AIR/DIRT SEPARATOR 360 - - AMTROL 8-ADS
ET-1 CHILLED WATER EXPANSION TANK 53 GALLONS - - AMTROL 200-L
NOTES:
A. INDOOR AHU'S WITH CHILLED WATER COILS AND ELECTRIC HEAT. PROVIDE SCR CONTROL OF ELECTRIC HEATING COIL.
B. PROVIDE CORROSION RESISTANT COILS AND SUPPLY FAN WITH VFD CONTROL.
C. UNITS ARE SPECIFICALLY SELECTED AND SIZED TO FIT INTO ASSOCIATED MECHANICAL CLOSETS AND MEZZANINES.
D. AIR HANDLING UNIT SUPPLY FAN VFD AND CONTROL SECTION TO BE REMOTELY MOUNTED IN MEZZANINE.
E. PROVIDE ATMOS AIR MATTERHORN 1000 BIPOLAR IONIZATION FOR AIR HANDLER.
F. PROVIDE ATMOS AIR MATTERHORN 1002 BIPOLAR IONIZATION FOR AIR HANDLER.
G. PROVIDE ATMOS AIR 500FC BIPOLAR IONIZATION FOR AIR HANDLER.
H. PROVIDE ATMOS AIR 508FC BIPOLAR IONIZATION FOR AIR HANDLER.
1.
2.
PROVIDE WITH BERNER AIR SMART CONTROLLER, MAGNETIC REED DOOR SWITCH AND DISCONNECT SWITCH.
PROVIDE LOW VOLTAGE CIRCUIT FOR UNIT ACTIVATION (BAS CONNECTION) WHEN AUTOMATIC DOOR OPENS.
REMARKS:
AIR CURTAIN SCHEDULE
MARK NOZZLE WIDTH (IN) MAX FPM AT NOZZLE CFM AT NOZZLE HEATER kW MOTOR HP VOLTAGE AMPS WEIGHT MANUFACTURER & MODEL
AC.1 72 5,444 3,014 NO HEAT (2) @ 1/2 208/1 8.6 185
BERNER
ARD12-2072A-B-R-WCA-SS
1.... PROVIDE WITH BAROMETRIC DAMPER....
REMARKS:
ROOF HOOD SCHEDULE
MARK SERVES INTAKE OR RELIEF
HOOD SIZE (IN)CAPACITY MAXIMUM VELOCITY
(FPM)REMARKSTHROAT SIZE HOOD SIZE HEIGHT CFM MAX P.D. IN H20
IH-1 AHU-7 OA INTAKE INTAKE 24x24 48x36 19 3,620 0.1 905 NOTE 1
IH-2 AHU-6 & 8 OA INTAKE INTAKE 42x48 72x84 23 10,500 0.1 750 NOTE 1
RH-1 AHU-7 RA RELIEF RELIEF 22x24 32x36 19 3,620 0.2 1,000 NOTE 2
RH-2 AHU-6 RELIEF RELIEF 36x36 54x48 19 9,000 0.2 1,000 NOTE 2
1. LOUVER MOUNTED IN EAVE OVERHANG.
REMARKS:
LOUVER SCHEDULE
MARK TYPE MATERIAL APPROX. SIZE DEPTH FINISH USE DESIGN CFM MAX APD
MIN. FREE
AREA
TOP AT
AFF REMARKS
L-1 INTAKE ALUMINUM 24x24 4" PER ARCH INTAKE 1,085 0.05 1.94 NOTE 1 AHU-3 OA INTAKE
L-2 RELIEF ALUMINUM 30x24 4" PER ARCH RELIEF 2,145 0.05 2.47 NOTE 1 AHU-4 RA RELIEF
L-3 INTAKE ALUMINUM 30x30 4" PER ARCH INTAKE 2,145 0.05 3.23 NOTE 1 AHU-4 OA INTAKE
L-4 INTAKE ALUMINUM 36x36 4" PER ARCH INTAKE 3,005 0.05 4.49 NOTE 1 AHU-5 OA INTAKE
L-5 RELIEF ALUMINUM 30x30 4" PER ARCH RELIEF 3,005 0.05 3.23 NOTE 1 AHU-5 RA RELIEF
L-6 INTAKE ALUMINUM 18x12 4" PER ARCH INTAKE 220 0.05 0.54 NOTE 1 AHU-1 OA INTAKE
L-7 INTAKE ALUMINUM 30x24 4" PER ARCH INTAKE 1,755 0.05 2.47 NOTE 1 AHU-2 OA INTAKE
L-8 RELIEF ALUMINUM 24x24 4" PER ARCH RELIEF 1,755 0.05 1.94 NOTE 1 AHU-2 RA RELIEF
NO. DATE DESCRIPTION
PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
REVISIONS200332-0006 AUG 2021
200801
MT103HVAC SCHEDULES Atlantic BeachFleet LandingColeman RemodelFloridaJDB
0.14 241 0.150
Xs... Vot... % OA...
System OA Intake required is Vot.RTU Total
220.10 1610
(Vou)220.1 Vps 240
VAV.1.7 Occupiable storage rooms for dry... 265 0 0.06 5 15.9 1 1.06 0.91 15.9 0.080 200 30
VAV.1.6 Office space 265 1 0.06 5 20.9 1 1.05 0.91 20.9 0.089 235 35
VAV.1.5 Office space 255 1 0.06 5 20.3 1 1.05 0.91 20.3 0.090 225 35
VAV.1.4 Office space 191 1 0.06 5 16.46 1 1.01 0.91 16.46 0.132 125 20
VAV.1.3 Conference/meeting 395 12 0.06 5 83.7 1 0.91 0.91 83.7 0.223 375 55
VAV.1.2 Office space 164 1 0.06 5 14.84 1 0.94 0.91 14.84 0.198 75 10
VAV.1.1 Lobbies 550 3 0.06 5 48 1 1.01 0.91 48 0.128 375 55
Supply... OA...
Zone Type of Space
Zone
Area...
Zone
Population...
cfm/ft2
(Ra)
cfm/person
(Rp)
Vbz
(Az*Ra) +...
Ez
(Table...
Evz
(1+Xs-Zd)
Ev
(min Evz)
Voz
(Vbz/Ez)
Zp
(Voz/Vpz)
Design Airflows CFM's
System: AHU-1 ZONE OA...
Multi Zone...
0.16 313 0.178
Xs... Vot... % OA...
System OA Intake required is Vot.RTU Total
289.20 1755
(Vou)289.2 Vps 765
VAV.2.3 Restaurant dining rooms 470 8 0.18 7.5 144.6 1 0.92 0.92 144.6 0.241 600 105
VAV.2.2 Restaurant dining rooms 470 8 0.18 7.5 144.6 1 0.92 0.92 144.6 0.241 600 105
VAV.2.1 Occupiable storage rooms for dry... 0 0 0.06 5 0 1 1.16 0.92 0 0.000 555 555
Supply... OA...
Zone Type of Space
Zone
Area...
Zone
Population...
cfm/ft2
(Ra)
cfm/person
(Rp)
Vbz
(Az*Ra) +...
Ez
(Table...
Evz
(1+Xs-Zd)
Ev
(min Evz)
Voz
(Vbz/Ez)
Zp
(Voz/Vpz)
Design Airflows CFM's
System: AHU-2 ZONE OA...
Multi Zone...
0.18 748 0.246
Xs... Vot... % OA...
System OA Intake required is Vot.RTU Total
536.48 3045
(Vou)536.48 Vps 750
VAV.5.12 Office space 307 1 0.06 5 23.42 1 1.13 0.72 23.42 0.047 500 125
VAV.5.11 Office space 146 1 0.06 5 13.76 1 1.09 0.72 13.76 0.083 165 40
VAV.5.10 Office space 165 1 0.06 5 14.9 1 1.08 0.72 14.9 0.099 150 35
VAV.5.09 Breakrooms Office 689 11 0.12 5 137.68 1 0.72 0.72 137.68 0.459 300 75
VAV.5.08 Reception areas 236 3 0.06 5 29.16 1 0.99 0.72 29.16 0.188 155 40
VAV.5.07 Lobbies 494 15 0.06 5 104.64 1 0.93 0.72 104.64 0.249 420 105
VAV.5.06 Office space 132 1 0.06 5 12.92 1 1.11 0.72 12.92 0.065 200 50
VAV.5.05 Lobbies 369 6 0.06 5 52.14 1 0.97 0.72 52.14 0.209 250 60
VAV.5.04 Office space 157 1 0.06 5 14.42 1 1.08 0.72 14.42 0.099 145 35
VAV.5.03 Office space 271 2 0.06 5 26.26 1 1.00 0.72 26.26 0.175 150 35
VAV.5.02 Conference/meeting 190 10 0.06 5 61.4 1 0.83 0.72 61.4 0.351 175 45
VAV.5.01 Office space 513 3 0.06 5 45.78 1 1.07 0.72 45.78 0.105 435 105
Supply... OA...
Zone Type of Space
Zone
Area...
Zone
Population...
cfm/ft2
(Ra)
cfm/person
(Rp)
Vbz
(Az*Ra) +...
Ez
(Table...
Evz
(1+Xs-Zd)
Ev
(min Evz)
Voz
(Vbz/Ez)
Zp
(Voz/Vpz)
Design Airflows CFM's
System: AHU-5 ZONE OA...
Multi Zone...
0.14 362 0.169
Xs... Vot... % OA...
System OA Intake required is Vot.RTU Total
302.24 2145
(Vou)302.24 Vps 360
VAV.4.7 Office space 136 1 0.06 5 13.16 1 1.10 0.83 13.16 0.041 320 55
VAV.4.6 Office space 155 1 0.06 5 14.3 1 1.08 0.83 14.3 0.057 250 40
VAV.4.5 Office space 294 3 0.06 5 32.64 1 1.08 0.83 32.64 0.062 525 90
VAV.4.4 Office space 227 3 0.06 5 28.62 1 0.95 0.83 28.62 0.191 150 25
VAV.4.3 Libraries 1026 6 0.12 5 153.12 1 0.83 0.83 153.12 0.306 500 85
VAV.4.2 Office space 370 3 0.06 5 37.2 1 0.99 0.83 37.2 0.149 250 40
VAV.4.1 Office space 220 2 0.06 5 23.2 1 0.99 0.83 23.2 0.155 150 25
Supply
(Vpz)
OA
(Vpz x %OA)
Zone Type of Space
Zone
Area
(Az)
Zone
Population
(Pz)
cfm/ft2
(Ra)
cfm/person
(Rp)
Vbz
(Az*Ra) +
(Pz*Rp)
Ez
(Table
6.2)
Evz
(1+Xs-Zd)
Ev
(min Evz)
Voz
(Vbz/Ez)
Zp
(Voz/Vpz)
Design Airflows CFM's
System: AHU-4 ZONE OA...
Multi Zone...
0.41 1029 0.571
Xs... Vot... % OA...
System OA Intake required is Vot.RTU Total
732.12 1800
(Vou)732.12 Vps 1025
VAV.3.2 Bars, cocktail lounges 645 8 0.18 7.5 176.1 1 1.23 0.71 176.1 0.176 1000 570
VAV.3.1 Bars, cocktail lounges 1839 30 0.18 7.5 556.02 1 0.71 0.71 556.02 0.695 800 455
Supply... OA...
Zone Type of Space
Zone
Area...
Zone
Population...
cfm/ft2
(Ra)
cfm/person
(Rp)
Vbz
(Az*Ra) +...
Ez
(Table...
Evz
(1+Xs-Zd)
Ev
(min Evz)
Voz
(Vbz/Ez)
Zp
(Voz/Vpz)
Design Airflows CFM's
System: AHU-3 ZONE OA...
Multi Zone...
8495 2985
225 Bev Supplies 216 6 0.06 5 42.96 1 43.0 43.0 160 60
224 Bar/Bev Station 146 3 0.06 5 23.76 1 23.8 23.8 100 35
220 Atrium 1524 0 0.06 5 91.44 1 91.4 91.4 2400 840
223 Exhibition Dining 4392 150 0.18 7.5 1915.56 1 1915.6 1915.6 5400 1890
222 Exhibition Kitchen 525 2 0.12 7.5 78 1 78.0 78.0 260 95
221 Kitchen Support 222 3 0.12 7.5 49.14 1 49.1 49.1 175 65
Supply
(Vpz)OAType of Space
Zone
Area
(Az)
Zone
Population
(Pz)
cfm/ft2
(Ra)
cfm/person
(Rp)
Vbz
(Az*Ra) +
(Pz*Rp)
Ez
(Table 6.2)
Voz
(Vbz/Ez)
Vot
(Voz)
Design Airflows CFM's
System: AHU-6
Single Zone Recirculati...
0.23 1197 0.278
Xs... Vot... % OA...
System OA Intake required is Vot.RTU Total
1004.24 4310
(Vou)1004.24 Vps 1200
VAV.7.5 Restaurant dining rooms 750 28 0.18 7.5 345 1 0.84 0.84 345 0.394 875 245
VAV.7.4 Lobbies 525 0 0.06 5 31.5 1 1.19 0.84 31.5 0.040 795 220
VAV.7.3 Lobbies 319 10 0.06 5 69.14 1 1.07 0.84 69.14 0.163 425 120
VAV.7.2 Restaurant dining rooms 770 28 0.18 7.5 348.6 1 0.96 0.84 348.6 0.273 1275 355
VAV.7.1 Restaurant dining rooms 500 16 0.18 7.5 210 1 1.01 0.84 210 0.223 940 260
Supply... OA...
Zone Type of Space
Zone
Area...
Zone
Population...
cfm/ft2
(Ra)
cfm/person
(Rp)
Vbz
(Az*Ra) +...
Ez
(Table...
Evz
(1+Xs-Zd)
Ev
(min Evz)
Voz
(Vbz/Ez)
Zp
(Voz/Vpz)
Design Airflows CFM's
System: AHU-7 ZONE OA...
Multi Zone...
NO. DATE DESCRIPTION
INSULATED PLENUMINSULATED FLEXIBLE DUCT RUNOUT
MAXIMUM LENGTH = 6'-0" RUNOUT
INSULATED PLENUM
CROSS NOTCH OPTION ON
48"LONG SLOTS
INSTALL 48"LONG DIFFUSERS
OVER TEE-BAR GRID
TEE-BAR GRID
INSTALL 2-WAY BLOW DIFFUSERS OVER TEE-BAR
GRID. G.C. SHALL TRIM CEILING TILE AS REQUIRED.
LAY-IN CEILING GRID
TEE-BAR GRID
INSTALL 1-WAY BLOW
DIFFUSERS OVER TEE-
BAR GRID. G.C. SHALL
TRIM CEILING TILE AS
REQUIRED.
NOTES:
DETAILS TYPICAL FOR 1,2,3 AND
4-SLOT DIFFUSERS.
GREASE TROUGH
FACTORY ROOF CURB AND
EXTENSION. CURB SHALL
INTEGRATE WITH ROOF SYSTEM.
WELDED GREASE EXHAUST DUCT. PROVIDE FIRE
RATED INSULATION BY PABCO OR THERMAL
CERAMICS. EXTEND ENCLOSURE DOWN TO
HOOD CONNECTION. REFER ALSO TO
SPECIFICATIONS.
NOTES:
1. DETAIL APPLIES FOR EXHAUST FANS EXHAUSTING GREASE LADEN AIR.
2. FABRICATE CURB TO PROVIDE LEVEL FAN INSTALLATION.41" MIN.24" MIN.
DIRECTION OF AIRFLOW.RECTANGULAR MAIN
OR TRUNK DUCT
MANUAL OPPOSED BLADE
BALANCING DAMPER WITH LOCKING
QUADRANT, ON BRANCH DUCT OR
WHERE INDICATED. NO OBD ON
MEDIUM PRESSURE DUCTS BEFORE
VAVS. TYPICAL.
STANDOFF FOR INSULATION
THICKNESS. TYPICAL.
SUPPLY
EXHAUST
RETURN
L=4" MINIMUM OR 1/4 OF "W"
W
45°LROUND MAIN OR
TRUNK DUCT
"LOW-LOSS" 45°F
ENTRY FITTING
GASKET
HIGH EFFICIENCY
TAKEOFF (HETO).
SUPPLY
EXHAUST
RETURN
45°
STRAIGHT GALV. INSULATED
DUCT MINIMUM DISTANCE
OF 3.0 TIMES BOX INLET
DUCT DIAMETER
AIRFLOW SENSOR
HEATING COIL
TRANSITION TO LOW
VELOCITY DUCTWORK
FLEX CONNECTION
LOW VELOCITY SUPPLY AIR DUCT SEE
FLOOR PLANS FOR SIZE AND ROUTING.
TRANSITION AS REQUIRED TO MATCH
BOX OUTLET SIZE
MIN. 36" CLEAR
CONTROL BOX
SHEET METAL TRANSITION
AS REQUIRED (REFER TO
ACTUAL SUBMITTAL)
HIGH EFFICIENCY TAKEOFF
MEDIUM VELOCITY
TRUNK DUCT
FLOW FLOW
MINIMUM OF 12" STRAIGHT DUCT,
SAME AS VAV BOX OUTLET, OR AS
REQUIRED BY MFR PRIOR TO
TAKEOFFS, ELBOWS, OR FITTINGS.
COIL
STRAINER WITH BLOWDOWN
VALVE, HOSE THREAD AND CAP
SUPPLY
RETURN
COIL
ISOLATION VALVE, 2"
AND BELOW BALL
VALVE, 2-1/2" AND
ABOVE BUTTERFLY
VALVE, TYP.
FLEX CONNECTION
CALIBRATED
BALANCING VALVE
TCC CONTROL
VALVE
NOTES:
1. COIL PIPING AND CONTROL VALVE TYPE FOR DIVERTING FLOW.
2. FLEXIBLE PIPE CONNECTOR REQ'D FOR EQUIPMENT CONTAINING FANS OR COMPRESSORS. BRAIDED STAINLESS STEEL ONLY, NO RUBBER.
3. PIPE ALL MULTI-ROW COILS FOR COUNTERFLOW (WATER ENTERS MOST DOWNSTREAM COIL, LEAVES MOST UPSTREAM COIL).
4. REFER TO CONTROLS DRAWINGS FOR ADDITIONAL INFORMATION.
5. 2-WAY VALVE NORMALLY OPEN FOR HEATING AND NORMALLY CLOSED FOR COOLING.
6. COILS WITH MORE OR LESS THAN 2 CONNECTIONS SHALL BE INSTALLED IN A SIMILAR ARRANGEMENTS WITH ALL ACCESSORIES SHOWN
HERE FOR EACH COIL SECTION.
7. CONFIRM SUPPLY AND RETURN CONNECTION LOCATIONS WITH EQUIPMENT MANUFACTURER'S LITERATURE PRIOR TO INSTALLATION.
8. MEET MANUFACTURER'S REQUIREMENTS FOR ACTUATOR CLEARANCES AND STEM ORIENTATION.
9. COORDINATE PIPING LOCATION WITH EQUIPMENT ACCESS DOORS, ELECTRICAL JUNCTION BOXES AND DRAIN PIPING.
MANUAL AIR VENT AT
HIGHEST POINT IN PIPING.
PRESS.-TEMP TAP
THERMOMETER
PRESSURE GAUGE
DRAIN DOWN
WITH HOSE
THREAD AND CAP
RETURN
COIL
ISOLATION VALVE, 2" AND BELOW BALL
VALVE, 2-1/2" AND ABOVE BUTTERFLY
VALVE, TYP.
PRESS.-TEMP
TAP
FLEX
CONNECTION
CALIBRATED
BALANCING VALVE
COIL
ISOLATION VALVE, 2" AND
BELOW BALL VALVE, 2-1/2"
AND ABOVE BUTTERFLY
VALVE, TYP.
TCC CONTROL
VALVE
STRAINER WITH
BLOWDOWN VALVE,
HOSE THREAD AND CAP
MANUAL AIR
VENT AT HIGHEST
POINT IN PIPING
NOTES:
1. FLEXIBLE PIPE CONNECTOR REQ'D FOR EQUIPMENT CONTAINING FANS OR COMPRESSORS. BRAIDED STAINLESS STEEL ONLY, NO
RUBBER.
2. PIPE ALL MULTI-ROW COILS FOR COUNTERFLOW (WATER ENTERS MOST DOWNSTREAM COIL, LEAVES MOST UPSTREAM COIL).
3. REFER TO CONTROLS DRAWINGS FOR ADDITIONAL INFORMATION.
4. 2-WAY VALVE NORMALLY OPEN FOR HEATING AND NORMALLY CLOSED FOR COOLING.
5. COILS WITH MORE OR LESS THAN 2 CONNECTIONS SHALL BE INSTALLED IN A SIMILAR ARRANGEMENTS WITH ALL ACCESSORIES SHOWN
HERE FOR EACH COIL SECTION.
6. CONFIRM SUPPLY AND RETURN CONNECTION LOCATIONS WITH EQUIPMENT MANUFACTURER'S LITERATURE PRIOR TO INSTALLATION.
7. MEET MANUFACTURER'S REQUIREMENTS FOR ACTUATOR CLEARANCES AND STEM ORIENTATION.
8. COORDINATE PIPING LOCATION WITH EQUIPMENT ACCESS DOORS, ELECTRICAL JUNCTION BOXES AND DRAIN PIPING.
SUPPLY
PRESSURE GAUGE
THERMOMETER
DRAIN DOWN
WITH HOSE
THREAD AND CAP
TOP VIEW
NOTE:PUMPS CONTROLLED BY VFD'S SHALL HAVE INVERTER DUTY RATED MOTORS AND
1,600 VOLT INSULATION. REFER TO SPECIFICATIONS FOR ADDITIONAL MOTOR REQUIREMENTS.
PUMP 2
ACTUATOR
BY THE TCC.
CHANGE OVER
VALVE WITH PUMP
BUILT IN CHECK VALVE.
PUMP 1
PIPING SUPPORT. REFER TO
SPECIFICATIONS, TYPICAL.
LONG-RADIUS ELBOW
SUPPORT PUMP PER
MANUFACTURER'S
RECOMMENDATIONS.
COMBINATION FLOW,
CHECK, AND SHUT-OFF
VALVE (TRIPLE DUTY).
THERMOMETER.
ORIFICE PLATE FLOW
METER. PROVIDE
LENGTH OF STRAIGHT
PIPE UP AND
DOWNSTREAM PER
MANUFACTURER.
BUTTERFLY VALVE.
VERTICAL INLINE PUMP.
PETE'S PLUG. PROVIDE
EXTENSION WHERE
INSULATION OCCURS,
TYPICAL.
FLOOR.
1/2" MANIFOLD
SUPPORTED FROM
PIPE OR WALL.
TRUMPET VALVE
NOT ALLOWED.
1/4" GAUGE
COCK, TYPICAL.
1/4" STAINLESS STEEL
TUBING, TYPICAL.
WELD-O-LET.
SUPPORT SUCTION DIFFUSER
PER MANUFACTURER'S
RECOMMENDATIONS.
CAPPED DRAIN BALL
VALVE WITH 3/4" MALE
HOSE THREAD OUTLET.
SUCTION DIFFUSER WITH
STRAINER. MAINTAIN
PULL CLEARANCE. PROVIDE
START-UP STRAINER.
4" THICK CONCRETE
HOUSEKEEPING PAD.
CONCENTRIC REDUCER
PRESSURE
GAUGE, TYPICAL._2D MIN._DREFER TO PLANS
FOR PIPE SIZES
(TYPICALLY 3D IN)
(TYPICALLY 5D OUT)MI
N
1.5
D
SHORT RADIUS RIGID METAL ELBOWS
WHERE 1.50 FLEX ELBOW CAN NOT BE
MAINTAINED
1 1/2" DUCT WRAP
INSULATION
MIN. 1.5" STANDOFF
BUTTERFLY DAMPER WITH ARM &
LOCKING QUADRANT
GASKET
HIGH EFFICIENCY
TAKEOFF (HETO)
ROUND BRANCH DUCT,
REFER TO PLANS FOR SIZE
FLEX DUCT REFER TO
SPECIFICATIONS FOR MAX.
ALLOWABLE LENGTH
(TYPICAL)
STRAP HANGER
SUPPLY
NYLON STRAP
FASTENER (TYP)
LOW VELOCITY
SUPPLY DUCT
PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:20 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
MT200HVAC DETAILS Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO SCALE
DIFFUSER DETAIL - SLOT - ADJUSTABLE BLADE8
NO SCALE
EXHAUST FAN DETAIL - KITCHEN UPBLAST7
NO SCALE
DUCT TAKEOFF DETAILS4
NO SCALE
TERMINAL UNIT REHEAT DETAIL3
NO SCALE
AHU/RTU COIL PIPING - 3-WAY6
NO SCALE
AHU/RTU COIL PIPING - 2-WAY2
NO SCALE
PUMP PIPING DETAIL - DUAL ARM VERTICAL IN-LINE5
NO SCALE
DIFFUSER INSTALLATION DETAIL1
NO. DATE DESCRIPTION
1"x6"x18 GA. GALV. STRAP
POP RIVET TO SUPPORT
CHANNEL
PVC OR CPVC PIPE
HANGER ROD TO
STRUCTURE ABOVE
VEE BOTTOM CLEVIS
HANGER
18 GA GALVANIZED PIPE
SUPPORT CHANNEL
CONTINUOUS BETWEEN
HANGERS
PIPE
ADJUSTABLE SPLIT
RING HANGER,
ANVIL FIG. 104
ALL THREAD
ROD (TYP)
'C' CLAMP WITH
LOCK NUT ANVIL
FIG. 86
SIDE BEAM
BRACKET ANVIL
FIG. 202
BOLT WITH
LOCK NUT
AND WASHER
STRUCTURAL
SUPPORTS
REFER TO SPECIFICATIONS
FOR HANGER SPACING.
FIELD BUILT CURB BY G.C. FLASH &
COUNTERFLASH AS REQ'D.
FRESH-AIR INTAKE HOOD
MIN 12"BACKDRAFT DAMPER
1" #16F FLATTENED
EXPANDED STEEL
W/ 78% FREE AREA
CURB BY M.C. FLASH &
COUNTERFLASH BY G.C.
STEEL ANGLE FRAME
INSECT SCREEN
RELIEF HOOD
MIN 8"FRAMING BY G.C.
BIRD SCREEN
CAULK
EXTENDED SILL
SHEET METAL SLEEVE
LOUVER
CAULK
FRAMING BY G.C.
EXTENDED SILL WALL OPENING AND
FLASHING BY WALL
PANEL SUPPLIER.
DRIP CAP
(METAL BUILDING)
NOTE:
COORDINATE LOUVER COLOR WITH ARCHITECT PER THE
MANUFACTURER'S STANDARD COLOR CHART.
BIRD SCREEN
CONTROL DAMPER
24V
SHEETMETAL SLEEVE
ELECTRIC OPERATOR
LOUVER
FROM
EQUIPMENT
AIR SEPARATOR
FILL CONNECTION
FROM CITY WATER
PRESSURE RELIEF VALVE
PIPE TO FLOOR DRAIN
TO PUMP(S)PRESSURE GAUGE (TYP)
AUTOMATIC
AIR VENT (TYP)
BALL VALVE (TYP)
ASME EXPANSION
TANK. REFER TO
SCHEDULE FOR TYPE.
4" HIGH
HOUSEKEEPING PAD
3/4" DRAIN. DO NOT PIPE
DRAIN LINE ON BLADDER
TYPE EXPANSION TANKS.
FINISHED FLOOR
3/4" DRAIN VALVE
W/CAPPED HOSE BIBB
SLOPE
CONNECT TO SIDE OF RETURN LINE
REFER TO PLANS FOR EXACT LOCATION
PLUG VALVE
BY-PASS LINE
REDUCED PRESSURE
BACKFLOW
PREVENTER (RPZ)
REFER TO PLANS
FOR PIPE SIZES.
STRAINER
PRESSURE REDUCING VALVE
PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:22 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
MT201HVAC DETAILS Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO SCALE
PIPE SUPPORT DETAIL - CHANNEL2
NO SCALE
PIPE SUPPORT DETAIL - SWIVEL RING3
0'8'12'4'NO SCALE
HOOD DETAIL - INTAKE1
0'8'12'4'NO SCALE
HOOD DETAIL - RELIEF4
0'8'12'4'NO SCALE
LOUVER DETAIL - STATIONARY5
0'8'12'4'NO SCALE
LOUVER/CONTROL DAMPER DETAIL6
0'8'12'4'NO SCALE
EXPANSION TANK/AIR SEPARATOR DETAIL - CITY WATER MAKE-UP7
NO. DATE DESCRIPTION
AFMS
DM
3
3
5
5
5
5
2
1
3
4
2
1
3
OA
RELIEF
SA
RA
T.C.C. LOCATE DUCT STATIC PRESSURE
SENSOR 2/3 DOWN MAIN DUCT.
AIR FLOW MEASURING STATION(S)
PROVIDED BY EQUIP. MFG.
INSTALLATION NOTES:
SMOKE DAMPERS FURNISHED BY
OTHERS
GS
GR
MANUAL RESET LIMIT SWITCHES TO
DISABLE FANS ON ALARM
DO-S/S
DI-ALARM
DI-STATUS
AO-SPEED
AI-PRESS
AI-PRESS
AI-PRESS
AI-FLOW
DI-LTD
AI-PRESS
AI-PRESS
AI-FLOW
DI-HI PRESS
MNL RST
AO
AI-PRESS
AO
NC
NO
NC
CC
C
E
F
M
A
S
AI-TEMP
AI-TEMP
T
AI
H
AI
AI
T
AI
H
AI
AI-TEMP
T
AI
H
AI
AI
AI
HAI
RELATIVE
HUMIDITY
DI DI
AI
AI
AI
AI-TEMP
T
AI
H
AI
DI
AO
PRE-FILTER
CHILLED WATER
COOLING COIL
FINAL
FILTER
FAN WALL
STAT DI CSR
DOSST
DIALA
AOSPD
EMS SN
PWR
STAT DI CSR
DOSST
DIALA
AOSPD
EMS SN
ECM MOTOR BY
EQUIP. MFG.
MOTOR OVERLOAD
CENTER BY AHU
MANUFACTURER
BUILDING AUTOMATION SYSTEM INTERFACE:
THE BUILDING AUTOMATION SYSTEM (BAS) SHALL SEND THE CONTROLLER OCCUPIED BYPASS, MORNING WARM-UP / PRE-COOL, OCCUPIED / UNOCCUPIED AND HEAT / COOL MODES. IF A BAS IS NOT
PRESENT, OR COMMUNICATION IS LOST WITH THE BAS THE CONTROLLER SHALL OPERATE USING DEFAULT MODES AND SETPOINTS.
OCCUPIED MODE:
UNITS SHALL OPERATE CONTINUOSLY
UNOCCUPIED MODE:
UNITS SHALL OPERATE CONTINUOSLY
OPTIMAL START:
THE BAS SHALL MONITOR THE SCHEDULED OCCUPIED TIME, OCCUPIED SPACE SETPOINTS AND SPACE TEMPERATURE TO CALCULATE WHEN THE OPTIMAL START OCCURS.
MORNING WARM-UP MODE:
DURING OPTIMAL START, IF THE SPACE TEMPERATURE IS BELOW THE OCCUPIED HEATING SETPOINT A MORNING WARM-UP MODE SHALL BE ACTIVATED. WHEN MORNING WARM-UP IS INITIATED THE UNIT
SHALL ENABLE THE HEATING AND SUPPLY FAN. THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED. WHEN THE SPACE TEMPERATURE REACHES THE OCCUPIED HEATING SETPOINT (ADJ.), THE UNIT SHALL
TRANSITION TO THE OCCUPIED MODE.
PRE-COOL MODE:
DURING OPTIMAL START, IF THE SPACE TEMPERATURE IS ABOVE THE OCCUPIED COOLING SETPOINT, PRE-COOL MODE SHALL BE ACTIVATED. WHEN PRE-COOL IS INITIATED THE UNIT SHALL ENABLE THE
FAN AND COOLING OR ECONOMIZER. THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED, UNLESS ECONOMIZING. WHEN THE SPACE TEMPERATURE REACHES OCCUPIED COOLING SETPOINT (ADJ.), THE
UNIT SHALL TRANSITION TO THE OCCUPIED MODE.
OPTIMAL STOP:
THE BAS SHALL MONITOR THE SCHEDULED UNOCCUPIED TIME, OCCUPIED SETPOINTS AND SPACE TEMPERATURE TO CALCULATE WHEN THE OPTIMAL STOP OCCURS. WHEN THE OPTIMAL STOP MODE IS
ACTIVE THE UNIT CONTROLLER SHALL MAINTAIN THE SPACE TEMPERATURE TO THE SPACE TEMPERATURE OFFSET SETPOINT.
OCCUPIED BYPASS:
THE BAS SHALL MONITOR THE STATUS OF THE “ON ” AND “CANCEL ” BUTTONS OF THE SPACE TEMPERATURE SENSOR. WHEN AN OCCUPIED BYPASS REQUEST IS RECEIVED FROM A SPACE SENSOR, THE
UNIT SHALL TRANSITION FROM ITS CURRENT OCCUPANCY MODE TO OCCUPIED BYPASS MODE AND THE UNIT SHALL MAINTAIN THE SPACE TEMPERATURE TO THE OCCUPIED SETPOINTS (ADJ.).
COOLING MODE:
THE UNIT CONTROLLER SHALL MONITOR SPACE TEMPERATURE AND SPACE TEMPERATURE COOLING SETPOINT TO DETERMINE WHEN TO INITIATE REQUESTS FOR COOLING. WHEN THE SPACE
TEMPERATURE RISES ABOVE THE SPACE TEMPERATURE COOLING SETPOINT, THE UNIT CONTROLLER SHALL MODULATE THE ECONOMIZER OR MODULATE THE COOLING COIL VALVE AS REQUIRED TO
MAINTAIN THE SPACE TEMPERATURE COOLING SETPOINT. THE SUPPLY FAN SHALL MODULATE ABOVE MINIMUM SPEED TO MEET ZONE REQUIREMENTS. ONCE THE SPACE TEMPERATURE FALLS BELOW
THE SETPOINT THE CHILLED WATER VALVE SHALL BE MODULATE DOWN AND THE FAN SHALL MODULATE TO MINIMUM SPEED.
HEATING MODE:
THE UNIT CONTROLLER SHALL MONITOR SPACE TEMPERATURE AND SPACE TEMPERATURE HEATING SETPOINT TO DETERMINE WHEN TO INITIATE REQUESTS FOR HEAT. WHEN THE SPACE TEMPERATURE
DROPS BELOW THE SPACE TEMPERATURE HEATING SETPOINT, THE CONTROLLER SHALL ENABLE THE ELECTRIC HEATING COIL TO SATISFY THE SPACE TEMPERATURE HEATING SETPOINT. THE SUPPLY
FAN SPEED SHALL VARY TO MEET ZONE HEATING REQUIREMENTS IN CONJUNCTION WITH THE ELECTRIC HEATING COIL. ONCE THE SPACE TEMPERATURE RISES ABOVE THE SETPOINT, THE HEATING
CYCLE SHALL BE DISABLED.
ECONOMIZER CONTROL / REFERENCE DRY BULB:
THE SUPPLY AIR SENSOR SHALL MEASURE THE DRY BULB TEMPERATURE OF THE AIR LEAVING THE EVAPORATOR COIL WHILE ECONOMIZING. WHEN ECONOMIZING IS ENABLED AND THE UNIT IS
OPERATING IN THE COOLING MODE, THE ECONOMIZER DAMPER SHALL MODULATE BETWEEN ITS MINIMUM POSITION AND 100% TO MAINTAIN THE SPACE TEMPERATURE SETPOINT. MINIMUM POSITION
SHALL BE CALCULATED BASED ON SUPPLY FAN SPEED. IF THE MIXED AIR TEMPERATURE STARTS TO FALL BELOW 53.0 DEG. F, THE ECONOMIZER STARTS TO CLOSE, AT 50.0 DEG. F, THE DAMPER SHALL BE
AT MINIMUM POSITION. COMPRESSORS SHALL BE DELAYED FROM OPERATING UNTIL THE ECONOMIZER HAS OPENED TO 100% FOR 5 MINUTES.
REFERENCE DRY BULB:
OUTSIDE AIR (OA) TEMPERATURE IS COMPARED WITH A REFERENCE DRY BULB POINT. THE ECONOMIZER IS ENABLED WHEN OA TEMPERATURE IS LESS THAN REFERENCE DRY BULB POINT. THE
ECONOMIZER IS DISABLED WHEN OA TEMPERATURE IS GREATER THAN REFERENCE DRY BULB POINT + 5.0 DEG. F.
DEHUMIDIFICATION:
THE UNIT SHALL BE IN DEHUMIDIFICATION MODE IF THE RETURN AIR HUMIDITY IS ABOVE THE DEHUMIDIFICATION SETPOINT. IN THE DEHUMIDIFICATION MODE, THE SUPPLY AIR FAN SHALL BE ENABLED,
THE OUTSIDE AIR DAMPER SHALL BE COMMANDED TO MINIMUM POSITION, AND THE UNIT CONTROLLER SHALL ENERGIZE MECHANICAL COOLING AND THE REHEAT SOLENOID.
MULTI CIRCUIT UNITS:
DURING DEHUMIDIFICATION MODE THE OUTSIDE AIR TEMPERATURE SHALL BE MONITORED. IF THIS TEMPERATURE RISES ABOVE THE REHEAT CAPACITY LIMIT SETPOINT, OR FALLS BELOW THE REHEAT
CAPACITY LIMIT SETPOINT – 3.0 DEG. F, THE UNIT SHALL STAGE DOWN OR STAGE UP THE COMPRESSORS RESPECTIVELY TO MEET FULL OR PART LOAD CAPACITY REQUIREMENTS BASED ON AMBIENT
TEMPERATURE.
SUPPLY FAN OPERATION:
THE SUPPLY FAN SHALL BE ENABLED WHILE IN THE OCCUPIED MODE AND CYCLED ON DURING THE UNOCCUPIED MODE. THE UNIT CONTROLLER SHALL VARY THE SUPPLY FAN SPEED TO OPTIMIZE
MINIMUM FAN SPEED IN ALL COOLING AND HEATING MODES. A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FAN. IF THE SWITCH DOES NOT OPEN WITHIN
40 SECONDS AFTER A REQUEST FOR FAN OPERATION A FAN FAILURE ALARM SHALL BE ANNUNCIATED, THE UNIT SHALL STOP, REQUIRING A MANUAL RESET.
BUILDING PRESSURE CONTROL:
THE BAROMETRIC RELIEF DAMPERS SHALL OPEN WITH INCREASED BUILDING PRESSURE. AS THE BUILDING PRESSURE INCREASES, THE PRESSURE IN THE UNIT RETURN SECTION ALSO INCREASES,
OPENING THE DAMPERS AND RELIEVING AIR.
SMOKE DETECTOR SHUTDOWN:
THE UNIT SHALL SHUT DOWN IN RESPONSE TO A SIGNAL FROM EITHER SMOKE DETECTOR INDICATING THE PRESENCE OF SMOKE. THE SMOKE DETECTORS SHALL BE INTERLOCKED TO THE UNIT
THROUGH THE DRY CONTACTS OF THE SMOKE DETECTORS. A MANUAL RESET OF THE SMOKE DETECTORS SHALL BE REQUIRED TO RESTART THE UNIT.
FILTER STATUS:
A DIFFERENTIAL PRESSURE SWITCH SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FILTER WHEN THE FAN IS RUNNING. IF THE SWITCH CLOSES FOR 2 MINUTES AFTER A REQUEST FOR FAN
OPERATION A DIRTY FILTER ALARM SHALL BE ANNUNCIATED AT THE BAS.
VARIABLE
FRQUENCY
DRIVE VFD
ERUW
VARIABLE
FRQUENCY
DRIVE VFD
ERUW
RELATIVE
HUMIDITY
RELATIVE
HUMIDITY
RELATIVE
HUMIDITY
RELATIVE
HUMIDITY
F
M
A
S
F
M
A
S
T.C.C. VERIFY # MOTORS/AHU & PROVIDE
STATUS SWITCHES FOR ALL MOTORS.
BAROMETRIC
ELECTRIC HEAT
COIL
CONTROL NOTES:
THE SYSTEM CONSISTS OF A PRESSURE INDEPENDENT VARIABLE AIR VOLUME BOX COMPLETE WITH MOTORIZED DAMPER, THREE STAGE
ELECTIC HEATING COIL, AND AIR FLOW PRESSURE TRANDUCER.
SCHEDULING:
THE ROOM TEMPERATURE SETPOINT SHALL BE SCHEDULED THROUGH THE OPERATOR WORKSTATION SUCH THAT HEATING ROOM
TEMPERATURE SETPOINT AND COOLING ROOM TEMPERATURE SETPOINT ARE SET UP AND SET BACK RESPECTIVELY DURING UNOCCUPIED
MODES. A THERMOSTAT MOUNTED TIMED OVERRIDE BUTTON SHALL ALLOW ROOM OCCUPANTS TO OVERRIDE THE VAV BOX INTO AN
OCCUPIED MODE FOR A SET TIME DURATION SHOULD OCCUPANTS DESIRE TO USE THE SPACE DURING UNOCCUPIED TIMES. THE
RESPECTIVE AIR HANDLING UNIT SHALL BE OPERATIONAL WHENEVER VAV BOX IS IN OCCUPIED MODE.
CONTROL
THE AIRFLOW PRESSURE TRANDUCER SHALL INDICATE TO THE UNIT MOUNTED DDC CONTROLLER MEASURED AIRFLOW. THE DDC
CONTROLLER SHALL MODULATE THE VAV BOX DAMPER TO MAINTAIN AIRFLOW AT SETPOINT. AIRFLOW SETPOINT SHALL BE RESET BASED
ON THE DIFFERENCE BETWEEN SPACE TEMPERATURE AND SPACE SETPOINT. UPON A RISE IN SPACE TEMPERATURE ABOVE SETPOINT
AIRFLOW SHALL MODULATE TO THE MAXIMUM SETPOINT. UPON A FALL IN SPACE TEMPERATURE BELOW SPACE TEMPERATURE SETPOINT
AIRFLOW SHALL MODULATE TO THE MINIMUM SETPOINT AND SUBSEQUENTLY ELECTRIC HEATING STAGES ONE THROUGH THREE SHALL
ENERGIZE ON. A SPACE MOUNTED TEMPERATURE SENSOR SHALL INCORPORATE A WARMER/COOLER ADJUSTMENT ALLOWING ZONE
OCCUPANTS TO BIAS THE SPACE TEMPERATURE SETPOINT BY A FIXED AMOUNT IN EITHER DIRECTION.
FEATURES
SPACE TEMPERATURE SHALL BE TRENDED HOURLY
SPACE TEMPERATURE SETPOINT 5 DEGREES OR MORE ABOVE OR BELOW SETPOINT SHALL ALARM
AI AI BI AI BO BO BO AIBO
SA
TE
SPACE MOUNTED T-STAT
FROM AHU
BO
PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:24 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
MT300HVAC CONTROLS Atlantic BeachFleet LandingColeman RemodelFloridaJDB
0'8'12'4'NO SCALE
AIR HANDLING UNIT CONTROLS1
0'8'12'4'1/8" = 1'-0"
VAV REHEAT CONTROLS2
NO. DATE DESCRIPTION
ALL NEW HVAC EQUIPMENT CONTROLS SHALL BE ABLE TO CONNECT AND
COMMUNICATE WITH EXISTING JCI METASYS BAS SYSTEM.
GENERAL CONTROLS NOTE:
CONTROLS NOTES:
DESCRIPTION - MAKEUP AIR HANDLING UNIT AND EXHAUST FAN COMPLETE WITH FILTER SECTION, VARIABLE
VOLUME EXHAUST FAN AND VARIABLE VOLUME SUPPLY FAN. DAMPERS, AND THEIR ACTUATORS SHALL BE
FACTORY PROVIDED. VFDS, SENSORS FOR HOOD HEAT AND PARTICULATES AND SPACE THERMOSTAT SHALL
BE PROVIDED AND CONTROLLED BY KITCHEN EQUIPMENT HOOD SUPPLIER. REFER TO KITCHEN
CONSULTANT SPECIFICATION FOR SCOPE REQUIRED OF TEMPERATURE CONTROLS CONTRACTOR.
COORDINATE EQUIPMENT MOTOR HP WITH KITCHEN EQUIPMENT SUPPLIER FOR PROPER VFD SELECTION.
SCHEDULING -THIS UNIT IS NOT SCHEDULED AND SHALL BE INTERLOCKED WITH THE KITCHEN HOOD
EXHAUST SYSTEM TO PROVIDE CONDITIONED MAKE UP AIR WHENEVER THE KITCHEN HOOD EXHAUST
SYSTEM IS OPERATING. OA DAMPERS SHALL OPEN WHEN EXHAUST FAN IS ACTIVATED. OA DAMPERS SHALL
BE CLOSED WHEN EXHAUST FAN IS DE-ENERGIZED. EXHAUST FAN SHALL BE ENERGIZED BY HEAT AND/OR
OPTIC SENSORS BY KITCHEN EQUIPMENT SUPPLIER.
FAN SPEED CONTROL: KITCHEN HOOD CONTROLS SHALL VARY THE EXHAUST AND MAKEUP AIR FAN SPEED
BETWEEN 50% AND 100% DEPENDING ON HEAT AND OPTIC SENSOR REQUIREMENTS.
FEATURES -
1. GENERATE AN ALARM SHOULD ANY FAN STATUS NOT MATCH FAN COMMAND.
2. IN THE EVENT OF A FIRE AT THE HOOD, THE FIRE SUPPRESSION SHALL ACTIVATE.
HOOD EXHAUST/MUA CONTROL CONSOLE.
REFER TO KITCHEN CONSULTANT PLANS
FOR MORE INFORMATION
HEAT OR OPTICS
SENSOR.EAVFD
EF-S
EF-C
COOK-I
OA
VFD
OAD-OOA-T
FIL-DP
SF-S
SF-C
DA-T
APHI-A SD-S
DA
AFMS PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:25 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
MT301HVAC CONTROLS Atlantic BeachFleet LandingColeman RemodelFloridaJDB
0'8'12'4'NO SCALE
KITCHEN MAU-EXHAUST CONTROLS1
NO. DATE DESCRIPTION
A
B
C
D
E
F
1 2 3 4 5 6
G
DEMO (E) MOP SINK AND ALL
ASSOCIATED ACCESSORIES.
DEMO (E) DRINKING FOUNTAIN AND ALL ASSOCIATED
ACCESSORIES. DEMO WASTE, VENT AND DOMESTIC
WATER LINES BACK TO RESPECTIVE MAINS AND CAP.
FAUCETS AND DOMESTIC WATER
LINES IN (E) RESTROOMS ARE TO
BE REMOVED AND REPLACED WITH
NEW.
(E) 1-1/4" CW UP TO
KITCHEN TO REMAIN.
(E) 2-1/2" WATER ENTRY
TO REMAIN.
DEMO (E) DRINKING FOUNTAIN
AND ALL ASSOCIATED
ACCESSORIES.
(E) 3/4" CW LINE TO HOSE BIBB.
HOSE BIBB TO REMAIN.
(E) CW AND HW RISERS TO (E)
BATHROOM GROUPS ON 2ND FLOOR
TO BE DEMO'D. REFER TO SHEET P201
FOR NEW ROUTING.
(E) CW AND HW MAINS ARE BEING
REMOVED AND REPLACED. REFER
TO SHEET P201.
(E) 1-1/4" CW UP TO
KITCHEN TO REMAIN.
(E) WATER HEATER AND ALL
ASSOCIATED APPURTENANCES
TO BE REMOVED.
(E) HOSE BIBB TO REMAIN.
(E) HOSE BIBB TO BE
REMOVED.
(E) 4" V UP TO KITCHEN
TO REMAIN.
(E) COMMON VENT TO REMAIN AND
BE REUSED.
(E) 750 GALLON SOI
TO BE REMOVED.
(E) CHILLER HEAT RECLAIM TANK AND
ALL ASSOCIATED APPURTNENANCES
TO BE REMOVED.
PLUMBING DEMO NOTES
1. PLANS ARE SCHEMATIC IN NATURE,
LAYOUT IS BASED ON BEST AVAILABLE
INFORMATION. CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS AND
DIMENSIONS. BRING ANY
DISCREPANCIES FROM THE DRAWINGS
AND NOTES TO THE OWNER'S
REPRESENTATIVE IMMEDIATELY. MINOR
CHANGES IN THE SCOPE OF THE
DEMOLITION WORK SHALL NOT JUSTIFY
AN ADDITIONAL COST.
2. CONTRACTOR SHALL CLEAN ALL
EXISTING PLUMBING FIXTURES TO
REMAIN OR BE REUSED IN AREA OF
WORK AND PROVIDE A LIST OF ANY
DEFICIENCIES TO OWNER'S
REPRESENTATIVE.
3. DEMOLISH ALL DUCTWORK, PIPING AND
EQUIPMENT SHOWN SHADED IN A DARK
LINE WEIGHT.PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:30 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
P1011/8" FIRST FLOOR DEMO PLAN - PLUMBING Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
A
B
C
D
E
F
1 2 3 4 5 6
G
DEMO (E) PLUMBING FIXTURES ASSOCIATED WITH BAR.
DEMO (E) WASTE, VENT AND WATER LINES BACK TO MAIN AND CAP.
DEMO (E) PLUMBING FIXTURES ASSOCIATED
WITH (E) KITCHEN. DEMO (E) WASTE, VENT AND
WATER LINES BACK TO MAIN AND CAP.
FAUCETS AND DOMESTIC WATER
LINES IN (E) RESTROOMS ARE TO
BE REMOVED AND REPLACED WITH
NEW.
(E) GAS LINE THAT IS CONNECTED TO (E) OVEN
THAT IS BEING REUSED, SHALL BE
DISCONNECTED AND ROUTED TO NEW OVEN
LOCATION. REFER TO KITCHEN CONSULTANT.
(E) WATER HEATERS AND ALL
ASSOCIATED APPURTENANCES TO BE
REMOVED AND REPLACED.
(E) FLOOR DRAIN IN MECH CLOSET TO
REMAIN.
( ) E 1-1/4''G
PLUMBING DEMO NOTES
1. PLANS ARE SCHEMATIC IN NATURE,
LAYOUT IS BASED ON BEST AVAILABLE
INFORMATION. CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS AND
DIMENSIONS. BRING ANY
DISCREPANCIES FROM THE DRAWINGS
AND NOTES TO THE OWNER'S
REPRESENTATIVE IMMEDIATELY. MINOR
CHANGES IN THE SCOPE OF THE
DEMOLITION WORK SHALL NOT JUSTIFY
AN ADDITIONAL COST.
2. CONTRACTOR SHALL CLEAN ALL
EXISTING PLUMBING FIXTURES TO
REMAIN OR BE REUSED IN AREA OF
WORK AND PROVIDE A LIST OF ANY
DEFICIENCIES TO OWNER'S
REPRESENTATIVE.
3. DEMOLISH ALL DUCTWORK, PIPING AND
EQUIPMENT SHOWN SHADED IN A DARK
LINE WEIGHT.PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:33 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
P1021/8" SECOND FLOOR DEMO PLAN - PLUMBING Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
A
B
C
D
E
F
1 2 3 4 5 6
G
CONFERENCE ROOM
118
OFFICE
116
FOOD SERVICE DIRECTOR
117
CORRIDOR
115
OFFICE
114
JANITOR
112
EXISTING CORRIDOR
111
EXISTING WATER SUPPLY
110
EXT'G MECH
109
EXISTING STORAGE
106
EXISTING ELECT
107
?
?
ELEVATOR EQUIPMENT
104
SOCIAL MAIL
102
WORK ROOM
129
CONFERENCE ROOM
131
EXECUTIVE GATHERING
128
OFFICE
124
OFFICE
125
OFFICE
126
OFFICE
127
OFFICE
133
MECH
132
SALES & FINISHES
135STAIR 1
001 STAIR 2
002
MARKETING
143LIBRARY DIRECTOR
142
MECH
139
MKTG DIR
146
?
?
SPORTS BAR
155
RECEPTION
122
VEST
123
ELEVATOR LOBBY
121
CORRIDOR
101
IT
138
STORAGE
130
DEVELOPMENT DIRECTOR
103
ATRIUM
136
CORRIDOR
137
REAR VEST
134
SALES & MARKETING
140
OFFICE
141
IL SALES
145
AL SALES
147
OFFICE
149
OFFICE
150
SUPPLY
148
EXISTING LIBRARY
151
MSB.1
DF.1
PROVIDE NEW 4" GREASE WASTE LINE
FOR ADDED KITCHEN FIXTURES. ROUTE
TO (E) GREASE INTERCEPTOR.
SK.2
SK.1
NEW 1,500 GALLON GREASE
INTERCEPTOR (SCHIER GGI-1500).
CONTRACTOR TO FIELD VERIFY
EXISTING CONNECTIONS AND
MODIFY AS NEEDED TO CONNECT
TO NEW INTERCEPTOR.
4"CO
FS
FS
FD FD
FS
2"W
( ) E 4"W( ) E 4"W( ) E 4"W
( ) E 6"W
( ) E 6"W
( ) E 4"W
( ) E 4"W
( ) E 4"W
4"W4"W
( ) E 6"W
( ) E 4"W
4"GW
4"GW
4"GW4"GW
4"GW
4"CO
( ) E 4"W
( ) E 4"W
(E) WASTE LINES SERVING
PLUMBING FIXTURES TO
REMAIN.
(E)3" W UP TO SECOND FLOOR
MEZZANINE TO REMAIN.
(E)CO (E)CO
(E)CO
2"W
2"W
( ) E 3"W
( ) E 6"W
( ) E 4"GW
(E)4" GW
SERVING 2ND
FLOOR KITCHEN.
P300
3
4"W
1
1
1
2
1
1
4"CO
4"CO
4"CO
4"GW
4"GW
4"GW
4"GW
4"GW
1
4
4
4
3
3
1
4"CO
4"CO
FS
PLUMBING GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE,
LAYOUT IS BASED ON BEST AVAILABLE
INFORMATION. CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS AND
DIMENSIONS. BRING ANY
DISCREPANCIES FROM THE DRAWINGS
AND NOTES TO THE OWNER'S
REPRESENTATIVE IMMEDIATELY. MINOR
CHANGES IN THE SCOPE OF THE
DEMOLITION WORK SHALL NOT JUSTIFY
AN ADDITIONAL COST.
2. REFER TO THE PLUMBING FIXTURE
SCHEDULE FOR PIPE SIZES TO
INDIVIDUAL FIXTURES.
3. NOT ALL REQUIRED CLEANOUTS ARE
NECESSARILY SHOWN ON THESE PLANS.
PROVIDE CLEANOUTS ON WASTE, VENT
AND STORM PIPING AS REQUIRED BY
CODE AND FOR REASONABLE
MAINTENANCE BASED ON ACTUAL FIELD
INSTALLATION.
4. PIPING ON EXTERIOR WALLS OR PRE-
CAST WALLS TO BE ROUTED IN FRAMED
WALL ON INTERIOR SIDE OF INSULATION.
5. TERMINATE PLUMBING VENTS NOT LESS
THAN 12”ABOVE ROOF AND A MINIMUM
OF 10’-0”FROM MECHANICAL OUTDOOR
AIR INTAKES.
6. AVOID ROUTING OVER ELECTRICAL
ROOMS AND ELECTRICAL PANELS;
MAINTAIN N.E.C. CLEARANCES.
COORDINATE ROUTING WITH
ELECTRICAL CONTRACTOR.
7. ROUTE DOMESTIC HOT WATER
RECIRCULATION PIPES DOWN THE WALL
TO WITHIN 2’OF ALL PUBLIC LAVATORIES
WITH A ½”RUNOUT. IF TWO OR MORE
LAVATORIES SHARE A ¾”OR LARGER
BRANCH PIPE, THE HOT WATER
RECIRCULATION PIPE SHALL CONNECT
TO WITHIN 6”OF EACH LAVATORY.
8. ALL VALVES SHALL BE INSTALLED ABOVE
DROP-IN CEILINGS IN ACCESSIBLE
LOCATIONS, OR WITH ACCESS PANELS IN
HARD-LID CEILINGS.
9. ACCESS PANELS SHALL BE 24X24, U.N.O.
LOCATIONS SHOWN ARE APPROXIMATE,
EXACT LOCATIONS SHALL BE
COORDINATED WITH THE ARCHITECTS
DRAWINGS AND WITH EQUIPMENT
LOCATIONS.
10. ALL PIPING SHALL BE ROUTED AS HIGH
AS POSSIBLE IN THE CEILNG SPACE.
UTILIZE JOIST SPACE WHEN POSSIBLE,
ESPECIALLY WHERE CROSSING OTHER
PIPES, DUCTS AND ELECTRICAL.
11. PROVIDE ACCESSIBLE SHUT-OFF VALVES
TO ALL APPLIANCES AND EQUIPMENT.
12. TRAP GUARDS SHALL BE INSTALLED AT
ALL FLOOR RECEPTORS THAT DO NOT
RECEIVE REGULAR DISCHARGE. INSTALL
IN ACCORDANCE WITH FLORIDA
PLUMBING CODE.
13. VERIFY AND REFER TO ARCHITECTURAL
DIMENSIONAL FLOOR PLAN FOR EXACT
LOCATIONS OF ALL FIXTURES AND
EQUIPMENT.
1. 4" GW UP TO 1ST FLOOR CEILING SPACE.
2. 2" GW UP TO 1ST FLOOR CEILING SPACE.
3. 2" W UP TO 1ST FLOOR CEILING SPACE.
4. 4" W UP TO 1ST FLOOR CEILING SPACE.
PLAN NOTES
PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:39 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
P2001/8" FIRST FLOOR PLAN - UNDERGROUND PLUMBING Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
A
B
C
D
E
F
1 2 3 4 5 6
CONFERENCE ROOM
118
OFFICE
116
FOOD SERVICE DIRECTOR
117
CORRIDOR
115
OFFICE
114
JANITOR
112EXISTING CORRIDOR
111
EXISTING WATER SUPPLY
110
EXT'G MECH
109
EXISTING ELECT
107
?
?ELEVATOR EQUIPMENT
104
SOCIAL MAIL
102
WORK ROOM
129
CONFERENCE ROOM
131
EXECUTIVE GATHERING
128
OFFICE
124
OFFICE
125
OFFICE
126
OFFICE
127
OFFICE
133
MECH
132
SALES & FINISHES
135STAIR 1
001 STAIR 2
002
MARKETING
143LIBRARY DIRECTOR
142
MECH
139
MKTG DIR
146
?
?
SPORTS BAR
155
RECEPTION
122
VEST
123
ELEVATOR LOBBY
121
CORRIDOR
101
IT
138
STORAGE
130
DEVELOPMENT DIRECTOR
103
ATRIUM
136
CORRIDOR
137
REAR VEST
134
SALES & MARKETING
140
OFFICE
141
IL SALES
145
AL SALES
147
OFFICE
149
OFFICE
150
SUPPLY
148
EXISTING LIBRARY
151
G
MSB.1
SK.2
SK.1
MECH
152
DUMBWAITER
156DUMBWAITER MECHANICAL
153
A/C CLOSET
158
NEW WATER
SOFTENER, WS.1
P300
1
1-1/2" CW, 1" HW AND 3/4" HWC UP
TO SECOND FLOOR BATHROOM
GROUP. REFER TO SHEET P300
FOR CONTINUATION.
(E) 3/4" CW TO HOSE
BIBB IN WALKWAY.
RECONNECT TO (E)1-1/4" CW
LINE SERVING 2ND FLOOR
KITCHEN FIXTURES.
2" CW, 1-1/2" HW AND 3/4" HWC
UP TO WATER HEATERS ON 2ND
FLOOR. REFER TO SHEET P202.
(E) 2" GAS LINE. COORDINATE
(E) METER SIZE WITH UTILITY.
(E) 2" GAS LINE UP TO
2ND FLOOR.
ROUTE NEW 1-1/2" GAS
LINE TO KITCHEN
EQUIPMENT.
1-1/2" GAS UP TO KITCHEN EQUIPMENT.
CONTRACTOR SHALL MAKE CONNECTION
TO SYSTEM REGULATOR. EQUIPMENT
MANUFACTURER TO MAKE FINAL
CONNECTIONS.
(E) 2-1/2" COLD WATER MAIN
(UNFILTERED). LINE TO BE REROUTED
TO NEW WATER SOFTENER.
(E) WASTE AND VENT PIPING TO
REMAIN AND BE REUSED IN (E)
BATHROOMS. ONLY DOMESTIC
WATER PIPING IS BEING REDONE.
1-1/4" CW, 1" HW AND 1/2" HWC
DOWN TO BELOW GRADE.
PROVIDE SHUT OFF VALVES IN
WALL AND PROVIDE ACCESS
PANEL. REFER TO 3/P300.
1
1
2
2
1
1
2
2
1
4"GW4"GW
4"GW
4"GW
2
1
2
21
2
1
4"GW
1-1/2''G
1-1/2''G
(E) 4" GW RISER
SERVING 2ND FLOOR
KITCHEN.
(E) 3" W SERVING 2ND
FLOOR MEZZANINE.
3/4"CW
4
5
3
3
5 4"W
6
6
6
7
7 7
7
7
9
8
88
10
11
12
1-1/4''CW
3/4"HWC
3/4"HW
1-1/4''CW
3/4"HWC
1"HW
1-1/2''CW
3/4"HWC
1"HW
PROVIDE STUDOR
MINI-VENT AT SINK.
PROVIDE STUDOR
MINI-VENT AT SINK.
1-1/2''CW
1"HW
3/4"HWC
2"CW
1"HW
3/4"HWC
2"CW
1-1/4''HW 3/4"HWC
2"CW
1-1/2''HW
2-1/2''UCW
3/4"HWC
2-1/2''CW
1-1/2''CW
1-1/4''HW
3/4"HWC
3/4"HWC
1"HW
1-1/2''CW
1-1/4''CW
1"HW
3/4"HWC
2"CW
1-1/2''HW
3/4"HWC
2"CW
3/4"HWC
1-1/2''HW
1-1/4''CW
1-1/2''HW
3/4"HWC
(E)4" V UP TO
2ND FLOOR.
3
5
7
13
13
13
13
DF.1
1
4"GW
TMV-1 UNDER SINK
HB-1
TMV-1
UNDER SINK
2-1/2''UCW
7
PLUMBING GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE,
LAYOUT IS BASED ON BEST AVAILABLE
INFORMATION. CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS AND
DIMENSIONS. BRING ANY
DISCREPANCIES FROM THE DRAWINGS
AND NOTES TO THE OWNER'S
REPRESENTATIVE IMMEDIATELY. MINOR
CHANGES IN THE SCOPE OF THE
DEMOLITION WORK SHALL NOT JUSTIFY
AN ADDITIONAL COST.
2. REFER TO THE PLUMBING FIXTURE
SCHEDULE FOR PIPE SIZES TO
INDIVIDUAL FIXTURES.
3. NOT ALL REQUIRED CLEANOUTS ARE
NECESSARILY SHOWN ON THESE PLANS.
PROVIDE CLEANOUTS ON WASTE, VENT
AND STORM PIPING AS REQUIRED BY
CODE AND FOR REASONABLE
MAINTENANCE BASED ON ACTUAL FIELD
INSTALLATION.
4. PIPING ON EXTERIOR WALLS OR PRE-
CAST WALLS TO BE ROUTED IN FRAMED
WALL ON INTERIOR SIDE OF INSULATION.
5. TERMINATE PLUMBING VENTS NOT LESS
THAN 12”ABOVE ROOF AND A MINIMUM
OF 10’-0”FROM MECHANICAL OUTDOOR
AIR INTAKES.
6. AVOID ROUTING OVER ELECTRICAL
ROOMS AND ELECTRICAL PANELS;
MAINTAIN N.E.C. CLEARANCES.
COORDINATE ROUTING WITH
ELECTRICAL CONTRACTOR.
7. ROUTE DOMESTIC HOT WATER
RECIRCULATION PIPES DOWN THE WALL
TO WITHIN 2’OF ALL PUBLIC LAVATORIES
WITH A ½”RUNOUT. IF TWO OR MORE
LAVATORIES SHARE A ¾”OR LARGER
BRANCH PIPE, THE HOT WATER
RECIRCULATION PIPE SHALL CONNECT
TO WITHIN 6”OF EACH LAVATORY.
8. ALL VALVES SHALL BE INSTALLED ABOVE
DROP-IN CEILINGS IN ACCESSIBLE
LOCATIONS, OR WITH ACCESS PANELS IN
HARD-LID CEILINGS.
9. ACCESS PANELS SHALL BE 24X24, U.N.O.
LOCATIONS SHOWN ARE APPROXIMATE,
EXACT LOCATIONS SHALL BE
COORDINATED WITH THE ARCHITECTS
DRAWINGS AND WITH EQUIPMENT
LOCATIONS.
10. ALL PIPING SHALL BE ROUTED AS HIGH
AS POSSIBLE IN THE CEILNG SPACE.
UTILIZE JOIST SPACE WHEN POSSIBLE,
ESPECIALLY WHERE CROSSING OTHER
PIPES, DUCTS AND ELECTRICAL.
11. PROVIDE ACCESSIBLE SHUT-OFF VALVES
TO ALL APPLIANCES AND EQUIPMENT.
12. TRAP GUARDS SHALL BE INSTALLED AT
ALL FLOOR RECEPTORS THAT DO NOT
RECEIVE REGULAR DISCHARGE. INSTALL
IN ACCORDANCE WITH FLORIDA
PLUMBING CODE.
13. VERIFY AND REFER TO ARCHITECTURAL
DIMENSIONAL FLOOR PLAN FOR EXACT
LOCATIONS OF ALL FIXTURES AND
EQUIPMENT.
1. 4" GW UP TO FLOOR SINK ON 2ND FLOOR.
2. 2" GW UP TO FLOOR DRAIN ON 2ND
FLOOR.
3. 2" W UP TO LAV ON 2ND FLOOR.
4. 2" W UP TO DF ON 2ND FLOOR.
5. 4" W UP TO WATER CLOSET ON 2ND
FLOOR.
6. 4" W DOWN TO BELOW GRADE. REFER TO
SHEET P200.
7. 4" GW DOWN TO BELOW GRADE. REFER
TO SHEET P200.
8. 2" W DOWN TO BELOW GRADE. REFER TO
SHEET P200.
9. 2" GW DOWN TO BELOW GRADE. REFER
TO SHEET P200.
10. 2" W, 3/4" CW AND 1/2 HW UP TO HAND
SINK. ROUTE 3/4" CW LINE UNDER
COUNTER TO OVEN AND FILTER SYSTEM.
INSTALL THERMOSTATIC MIXING VALVE
AT HAND SINK TO TEMPER WATER TO
105º. COORDINATE WITH KITCHEN
CONSULTANT.
11. 1/2" CW AND 1/2" HW UP TO PREP SINK.
COODINATE WITH KITCHEN
CONSULTANT.
12. 1" CW AND 3/4" HW UP TO KITCHEN
FIXTURES ON SECOND FLOOR. ROUTE
HOT AND COLD WATER LINES TO
KITCHEN EQUIPMENT AS NEEDED. REFER
TO KITCHEN CONSULTANT DRAWINGS
FOR FIXTURE CONNECTIONS.
13. 3/4" CW AND 3/4" HW UP TO KITCHEN
FIXTURES ON SECOND FLOOR. ROUTE
1/2" CW AND HW TO PREP SINK AND
HAND SINK. INSTALL THERMOSTATIC
MIXING VALVE AT HAND SINK.
PLAN NOTES
PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:47 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
P2011/8" FIRST FLOOR PLAN - PLUMBING Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
K
A
B
C
D
E
F
1 2 3 4 5 6
G
STAIR 1
001 STAIR 2
002
MENS ACCESSIBLE
208
RESTROOM
211
COATS
212
BEV STATION
209
EXISTING WOMENS
206
EXISTING MENS
207
?
?
OFFICE
204
EXHIBITION DINING
223
EXHIBITION KITCHEN
222
KITCHEN SUPPORT
221
GALLERY
220
ELEV LOBBY
213
COMMUNITY DINING
210
BEV STATION
218
PRIVATE DINING/WINE
ROOM
219
EXT'G ELEC
217
BEV SUPPLIES
225
BAR/BEV STATION
224
EXISTING MECH
226
EXISTING KITCHEN
201
ELEV 1
E001
ELEV 2
E002
ELEV 3
E003
EXISTING WALK-IN
202
PANTRY
203
J.C.
15
(E) KITCHEN NOT IN SCOPE
DF.1 WC.1
LAV.1
LAV.1 WC.1
REFER TO KITCHEN
CONSULTANT FOR EXACT
FIXTURE LOCATIONS AND
CONNECTIONS.
REFER TO KITCHEN
CONSULTANT FOR EXACT
FIXTURE LOCATIONS AND
CONNECTIONS.
REFER TO KITCHEN
CONSULTANT FOR EXACT
FIXTURE LOCATIONS AND
CONNECTIONS.
REFER TO KITCHEN
CONSULTANT FOR EXACT
FIXTURE LOCATIONS AND
CONNECTIONS.
LAV.1
WC.1
P300
2
1"CW
1/2"HW
WH-1 AND WH-2 IN EXISTING MECH
ROOM. CONNECT WATER HEATERS TO
(E) 1" GAS SUPPLIES FROM DEMO'D
WH'S.
( ) E 1-1/4''G
(E)2" GAS FROM 1ST FLOOR.
3/4"HWC
(E) WASTE AND VENT PIPING TO
REMAIN AND BE REUSED IN (E)
BATHROOMS. ONLY DOMESTIC
WATER PIPING IS BEING REDONE.
2" CW, 1-1/2" HW AND 3/4" HWC
LINES DOWN TO 1ST FLOOR.
FD FD
FSFS
FD
FS
FS
FD
(E)3" W LINE FROM
MEZZANINE FLOOR
DRAIN.
FD
FS
FD
FS 3/4" CW, HW AND HWC LINES
DOWN TO FIRST FLOOR.
2"V
( ) E 3"V
2"V
2"V
(E)4" VTR
COMBINE VENTS FROM FLOOR
SINK AND FLOOR DRAIN AND
ROUTE 3" VTR.
CONNECT NEW 2" V LINE
FROM KITCHEN EQUIPMENT
INTO (E)4" VTR.
2"V
2"V
2"V2"V
3" VTR
FS
C100.1
C105.1
E100E100
S113.1
S302
S110
S300
S100
S303
W100
W105.1
W107
W301
W302
W300
A106
A302
A300
A108
A301
P200 P201P202
P204
A102.2
TMV-1 UNDER SINK
TMV-1 UNDER SINK
TMV-1 UNDER SINK
TMV-1 UNDER SINK
TMV-1 UNDER SINK
TMV-1 UNDER P201 AND P202
PLUMBING GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE,
LAYOUT IS BASED ON BEST AVAILABLE
INFORMATION. CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS AND
DIMENSIONS. BRING ANY
DISCREPANCIES FROM THE DRAWINGS
AND NOTES TO THE OWNER'S
REPRESENTATIVE IMMEDIATELY. MINOR
CHANGES IN THE SCOPE OF THE
DEMOLITION WORK SHALL NOT JUSTIFY
AN ADDITIONAL COST.
2. REFER TO THE PLUMBING FIXTURE
SCHEDULE FOR PIPE SIZES TO
INDIVIDUAL FIXTURES.
3. NOT ALL REQUIRED CLEANOUTS ARE
NECESSARILY SHOWN ON THESE PLANS.
PROVIDE CLEANOUTS ON WASTE, VENT
AND STORM PIPING AS REQUIRED BY
CODE AND FOR REASONABLE
MAINTENANCE BASED ON ACTUAL FIELD
INSTALLATION.
4. PIPING ON EXTERIOR WALLS OR PRE-
CAST WALLS TO BE ROUTED IN FRAMED
WALL ON INTERIOR SIDE OF INSULATION.
5. TERMINATE PLUMBING VENTS NOT LESS
THAN 12”ABOVE ROOF AND A MINIMUM
OF 10’-0”FROM MECHANICAL OUTDOOR
AIR INTAKES.
6. AVOID ROUTING OVER ELECTRICAL
ROOMS AND ELECTRICAL PANELS;
MAINTAIN N.E.C. CLEARANCES.
COORDINATE ROUTING WITH
ELECTRICAL CONTRACTOR.
7. ROUTE DOMESTIC HOT WATER
RECIRCULATION PIPES DOWN THE WALL
TO WITHIN 2’OF ALL PUBLIC LAVATORIES
WITH A ½”RUNOUT. IF TWO OR MORE
LAVATORIES SHARE A ¾”OR LARGER
BRANCH PIPE, THE HOT WATER
RECIRCULATION PIPE SHALL CONNECT
TO WITHIN 6”OF EACH LAVATORY.
8. ALL VALVES SHALL BE INSTALLED ABOVE
DROP-IN CEILINGS IN ACCESSIBLE
LOCATIONS, OR WITH ACCESS PANELS IN
HARD-LID CEILINGS.
9. ACCESS PANELS SHALL BE 24X24, U.N.O.
LOCATIONS SHOWN ARE APPROXIMATE,
EXACT LOCATIONS SHALL BE
COORDINATED WITH THE ARCHITECTS
DRAWINGS AND WITH EQUIPMENT
LOCATIONS.
10. ALL PIPING SHALL BE ROUTED AS HIGH
AS POSSIBLE IN THE CEILNG SPACE.
UTILIZE JOIST SPACE WHEN POSSIBLE,
ESPECIALLY WHERE CROSSING OTHER
PIPES, DUCTS AND ELECTRICAL.
11. PROVIDE ACCESSIBLE SHUT-OFF VALVES
TO ALL APPLIANCES AND EQUIPMENT.
12. TRAP GUARDS SHALL BE INSTALLED AT
ALL FLOOR RECEPTORS THAT DO NOT
RECEIVE REGULAR DISCHARGE. INSTALL
IN ACCORDANCE WITH FLORIDA
PLUMBING CODE.
13. VERIFY AND REFER TO ARCHITECTURAL
DIMENSIONAL FLOOR PLAN FOR EXACT
LOCATIONS OF ALL FIXTURES AND
EQUIPMENT.PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:43:53 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
P2021/8" SECOND FLOOR PLAN - PLUMBING Atlantic BeachFleet LandingColeman RemodelFloridaJDB
NO. DATE DESCRIPTION
B
C
1
1"CW
3/4"CW
3/4"HW
1/2"HWC
1/2"HWC
1/2"HW
1"CW
3/4"HW
3/4"CW
1/2"HWC
1-1/2''CW
1-1/4''CW1-1/4''CW
3/4"CW
3/4"HW
1/2"HWC
(E) LAV FAUCETS ARE TO BE
REMOVED AND REPLACED WITH
KOHLER K-104B87-SANA.
(E) LAV FAUCET TO BE
REMOVED AND
REPLACED WITH
KOHLER K-104B87-SANA.
(E) LAV FAUCET TO BE
REMOVED AND
REPLACED WITH
KOHLER K-104B87-SANA.
(E) LAV FAUCETS ARE TO BE
REMOVED AND REPLACED WITH
KOHLER K-104B87-SANA.
TMV-1 UNDER
SINK
TMV-1 UNDER
SINK
TMV-1 UNDER
SINK
TMV-1 UNDER
SINK
F
3 4
DF.1
1"CW
3/4"CW
WC.1
LAV.1
WC.1
LAV.1
(E) LAV FAUCETS ARE TO BE REMOVED
AND REPLACED WITH KOHLER K-104B87-
SANA.
TMV-1
UNDER SINK
TMV-1 UNDER
SINKS, TYP. (4)
TMV-1
UNDER SINK
B
C
3 4
1-1/4"CW, 1" HW AND 1/2" HWC UP TO
FIRST FLOOR CEILING SPACE. REFER TO
SHEET P201.
ALL UNDERGROUND
PLUMBING TO BE SLEEVED.
ROUTE 3/4" PIPE UP ABOVE SLAB TO
COUNTER. ROUTE 3/4" CW LINE TO
WATER FILTER SYSTEM, B141.1. BRANCH
3/8" LINE AND ROUTE WITHIN COUNTER
TO ESPRESSO MACHINE, B141. REFER TO
KITCHEN CONSULTANT.
ROUTE 1" CW LINE UP ABOVE SLAB AND
BRANCH INTO 3/4" LINES TO SERVE
WATER FILTER SYSTEMS, B122.1 AND
B129.1. REFER TO KITCHEN CONSULTANT.
PROVIDE THERMOSTATIC
MIXING VALVE AT HAND SINK,
B133, TO TEMPER WATER TO
110º.
ROUTE 1-1/4" CW AND HW UP TO VIEGA MANABLOC
DISTRIBUTION MANIFOLD UNDER 4-COMP SINK (B134).
CONTRACTOR TO ROUTE HOT AND COLD WATER LINES
TO KITCHEN EQUIPMENT FROM MANIFOLD WITHIN THE
BAR SYSTEM. REFER TO KITCHEN CONSULTANT FOR
FIXTURES AND CONNECTION SCHEDULE.
1-1/4''CW
1-1/4''HW
3/4"HWC 1"CW
B134
B122
B133
B129
B129
B125 B124
B122.1 B124B125B129.1
PLUMBING GENERAL NOTES
1. PLANS ARE SCHEMATIC IN NATURE,
LAYOUT IS BASED ON BEST AVAILABLE
INFORMATION. CONTRACTOR SHALL
FIELD VERIFY EXISTING CONDITIONS AND
DIMENSIONS. BRING ANY
DISCREPANCIES FROM THE DRAWINGS
AND NOTES TO THE OWNER'S
REPRESENTATIVE IMMEDIATELY. MINOR
CHANGES IN THE SCOPE OF THE
DEMOLITION WORK SHALL NOT JUSTIFY
AN ADDITIONAL COST.
2. REFER TO THE PLUMBING FIXTURE
SCHEDULE FOR PIPE SIZES TO
INDIVIDUAL FIXTURES.
3. PIPING ON EXTERIOR WALLS OR PRE-
CAST WALLS TO BE ROUTED IN FRAMED
WALL ON INTERIOR SIDE OF INSULATION.
4. AVOID ROUTING OVER ELECTRICAL
ROOMS AND ELECTRICAL PANELS;
MAINTAIN N.E.C. CLEARANCES.
COORDINATE ROUTING WITH
ELECTRICAL CONTRACTOR.
5. ROUTE DOMESTIC HOT WATER
RECIRCULATION PIPES DOWN THE WALL
TO WITHIN 2’OF ALL PUBLIC LAVATORIES
WITH A ½”RUNOUT. IF TWO OR MORE
LAVATORIES SHARE A ¾”OR LARGER
BRANCH PIPE, THE HOT WATER
RECIRCULATION PIPE SHALL CONNECT
TO WITHIN 6”OF EACH LAVATORY.
6. ALL VALVES SHALL BE INSTALLED ABOVE
DROP-IN CEILINGS IN ACCESSIBLE
LOCATIONS, OR WITH ACCESS PANELS IN
HARD-LID CEILINGS.
7. ACCESS PANELS SHALL BE 24X24, U.N.O.
LOCATIONS SHOWN ARE APPROXIMATE,
EXACT LOCATIONS SHALL BE
COORDINATED WITH THE ARCHITECTS
DRAWINGS AND WITH EQUIPMENT
LOCATIONS.
8. ALL PIPING SHALL BE ROUTED AS HIGH
AS POSSIBLE IN THE CEILNG SPACE.
UTILIZE JOIST SPACE WHEN POSSIBLE,
ESPECIALLY WHERE CROSSING OTHER
PIPES, DUCTS AND ELECTRICAL.
9. PROVIDE ACCESSIBLE SHUT-OFF VALVES
TO ALL APPLIANCES AND EQUIPMENT.
10. VERIFY AND REFER TO ARCHITECTURAL
DIMENSIONAL FLOOR PLAN FOR EXACT
LOCATIONS OF ALL FIXTURES AND
EQUIPMENT.PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:44:00 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
P3001/4" ENALRGED PLANS - PLUMBING Atlantic BeachFleet LandingColeman RemodelFloridaJDB
0'8'12'4'1/4" = 1'-0"
PLUMBING PLAN - 1ST FLOOR ENLARGED BATHROOM1
0'8'12'4'1/4" = 1'-0"
PLUMBING PLAN - 2ND FLOOR ENLARGED BATHROOM2
0'8'12'4'1/4" = 1'-0"
PLUMBING PLAN - ENLARGED BAR3
NO. DATE DESCRIPTION
SK.2
SK.1
1"CW
(E) URINALS
3/4"CW
(3)(E) WATER CLOSETS
1-1/2''CW
1-1/4''HW
3/4"HWC
1"CW
WC.1LAV.1
1-1/4''CW
1"CW
DF.1
(E) LAVS
1"CW
1"CW
WC.1
LAV.1
1"CW
WC.1
LAV.1
1-1/2''CW
1"HW
3/4"HWC
1-1/4''CW
1"HW
3/4"HWC
HOSE BIBB
TO KITCHEN EQUIPMENT. REFER TO
KITCHEN CONSULTANT DRAWINGS.
HOSE BIBB
3/4"CW
1-1/4''CW
3/4"HW
3/4"HWC
3/4"CW
3/4"HW
2"CW
1"HW
3/4"HWC
RISER TO SECOND FLOOR
BATHROOM GROUPS.
3/4"CW
TO (E) HOSE BIBB
(E)1/1-4" CW LINE TO
(E) KITCHEN.
(E)2-1/2" UNFILTERED COLD
WATER LINE FROM METER.
WH-1 AND WH-2
2"CW
1-1/2''HW
3/4"HWC
UP TO WATER HEATERS
ON SECOND FLOOR.
TO KITCHEN EQUIPMENT. REFER TO
KITCHEN CONSULTANT DRAWINGS.
2"CW
1-1/2''HW
3/4"HWC
2-1/2''UCW
1/2"HW
3/4"CW
3/4"CW
3/4"HW
1/2"HW
1/2"CW
3/4"CW
3/4"HW
1-1/2''CW
1-1/4''HW
3/4"HWC
TO NEW WATER SOFTENER.
2-1/2''CW
DF.1
1"CW 2-1/2''CW
2"CW
1-1/2''HW
3/4"HWC
(E) LAV'S
(E) LAV
(E) WC
(E) UR'S
(E) LAV
(E) SHWR
(E) WC'S
(E) LAV'S
1"CW3/4"CW
3/4"HW
1"CW
1/2"HWC
1/2"HWC
1/2"HW
1"CW
3/4"CW
3/4"HW
1/2"HWC
1/2"CW
1/2"HW
1/2"HWC
TO KITCHEN EQUIPMENT. REFER TO
KITCHEN CONSULTANT DRAWINGS.
1-1/2''CW
1"HW
3/4"HWC
3/4"HWC
1"HW
1-1/4''CW
TO KITCHEN EQUIPMENT. REFER TO
KITCHEN CONSULTANT DRAWINGS.
3/4"HWC
1-1/4''HW
1-1/4''CW
3/4"HWC
3/4"HW
3/4"CW
1"HW
PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:44:07 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
P400PLUMBING RISER DIAGRAMS Atlantic BeachFleet LandingColeman RemodelFloridaJDB
0'8'12'4'
WATER RISER1
NO. DATE DESCRIPTION
FD
FS
FS
FD FS
FD FS
FS
FD
FS
FD
FS
FD
FS
FD
FS
4"CO
4"CO
4"CO
4"CO
4"CO
4"CO
4"CO
FD
FS
4"CO
2"GW
4"GW
4"GW
4"GW
4"GW
4"GW4"GW
4"GW
4"GW
4"GW
4"GW
4"GW
4"GW
4"GW
4"GW
4"GW
4"GW
4"GW
4"GW
( ) E 4"GW
(E) 4" GREASE WASTE
SERVING (E) KITCHEN.
TO (E) GREASE
INTERCEPTOR
( ) E 4"W
( ) E 4"W
(E)4"CO
( ) E 6"W
( ) E 6"W
( ) E 6"W
( ) E 4"W
( ) E 4"W
( ) E 4"W
( ) E 4"W
CONTRACTOR SHALL FIELD
VERIFY (E) WASTE MAINS PRIOR
TO CONSTRUCTION.
CONTRACTOR SHALL FIELD
VERIFY (E) WASTE MAINS PRIOR
TO CONSTRUCTION.
( ) E 4"W
( ) E 4"W
( ) E 4"W
(E) WASTE FROM
GREASE INTERCEPTOR.
2"W
2"W
( ) E 3"W
4"W
4"W
4"W
4"W
( ) E 4"V
( ) E 4"V
( ) E 4"V
2"V
( ) E 4"V PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:44:14 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
P401PLUMBING RISER DIAGRAMS Atlantic BeachFleet LandingColeman RemodelFloridaJDB
0'8'12'4'
GREASE WASTE1
0'8'12'4'
WASTE2
NO. DATE DESCRIPTION
DS
GDS
COLD WATER SUPPLY
HWC FROM FIXTURES
DIAPHRAGM TYPE
EXPANSION TANK.
AMTROL OR EQUIVALENT
RELIEF VALVE, PIPE
INDIRECT TO DRAIN PAN
OR FLOOR DRAIN, TYP.
GAS SUPPLY.
DOMESTIC HW
RECIRC. PUMP
GAS
WATER
HEATER
140º HOT WATER TO
SYSTEM
GAS COCK (TYP)
GAS
WATER
HEATER
CONCRETE
HOUSEKEEPING PAD, TYP.
THERMOMETER,
TYP.
BALL VALVE, TYP.
UNION, TYP.
CHECK VALVE, TYP.
CALIBRATED
BALANCE VALVE
AQUASTAT TO
CYCLE PUMP
A
NOTES:
1. REFER TO PLANS FOR PIPE SIZES.
2. INDICATE FLOW DIRECTION AND LABEL ALL PIPING AND EQUIPMENT.
3. REFER TO PLANS FOR FLUE AND COMBUSTION AIR PIPE ROUTING. CONTRACTOR
SHALL VERIFY VENTING REQUIREMENTS WITH UNIT MANUFACTURER.
4. 120V ELECTRICAL CONNECTION REQUIRED FOR GAS WATER HEATERS.
5. PROVIDE COMMON MANIFOLD. ALL PIPING, VALVING, AND FITTINGS SHALL BE EQUAL
AND SYMMETRICAL FOR EQUAL DEMAND AT EACH HEATER.
6. WATER HEATERS SHALL PROVIDE 140º WATER. POINT OF USE THERMOSTATIC
MIXING VALVES WILL BE INSTALLED WHERE NECESSARY. REFER TO PLANS.
CLEANOUT, TYP.
TWO-WAY
CLEANOUT
FITTING
CLEANOUT AT
GRADE, TYP.
INLET
REINFORCED
CONCRETE TANK
24"∅RETAINING
WALL (TYPICAL)
OUTLET MUST BE
AT LEAST 2"
LOWER THAN INLET
USE 2ea DEETER 1261 FOR
HEAVY DUTY OR EQUAL
PAVEMENT
SECTION VIEW
PLAN VIEW
NOTES:
1. CONSTRUCTION OF TANK AND INSTALLATION SHALL COMPLY WITH ALL
FEDERAL, STATE AND LOCAL CODE REQUIREMENTS.
2. FIELD VERIFY ALL REQUIRED WASTE FLOW LINES FOR CONNECTION TO TANK
PRIOR TO TANK CONSTRUCTION.
3. CONSTRUCT TANK AS REQUIRED TO PROVIDE SPECIFIED RETAINAGE CAPACITY.
4. BOX DESIGN LOAD: H-20 TRAFFIC WITH 1' TO 6' SOIL COVER.
5. ADDITIONAL PIPING MAY BE REQUIRED. COORDINATE EXACT EQUIPMENT AND
PIPING REQUIREMENTS WITH EQUIPMENT SUPPLIER.
NOTE:
REFER TO PLANS
FOR PIPE SIZES
FLOOR/HUB DRAIN FLOOR
CLOSED
DIAPHRAGM
WASTE PIPE
OPEN DIAPHRAGM
WASTE PIPE
NOTES:
TRAP GUARD DIAPHRAGM AS MANUFACTURED BY PROSET SYSTEMS, INC. REFER
TO SPECIFICATION. WHERE ALLOWED BY LOCAL CODE, TRAP GUARD MAY BE
USED IN LIEU OF TRAP PRIMER. TYPICAL ALL FLOOR DRAINS.
BRINE
MAKER
PIPE TO FLOOR DRAIN
UNIT CONTROL CENTER
PRESSURE GAGE
WATER
SOFTENER TANK
WATER METER
UNION (TYP)
BALL VALVE (TYP)
BY-PASS VALVE
SOFTENED WATERHARD CW
THIS DETAIL IS FOR REFERENCE
ONLY. COORDINATE EXACT PIPING
AND INSTALLATION REQUIREMENTS
WITH MANUFACTURER.PROFESSIONAL ENGINEERING CONSULTANTS, P.A.316-262-2691 www.pec1.com303 SOUTH TOPEKA, WICHITA, KS 67202PEC PROJECT NUMBER:DATE
THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE
THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL
NOT BE COPIED IN ANY FORM OR MANNER WITHOUT
WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR
SHEET NO.
PROJECT
SHEET PRINTED ON:FILE PATH:REVISIONS200332-0008/5/2021 7:44:16 AMBIM 360://200801-Fleet Coleman Remodel/200332-000-MASTER MECH-R20.rvt6 AUG 2021
200801
PT100PLUMBING SCHEDULES AND DETAILS Atlantic BeachFleet LandingColeman RemodelFloridaJDB
FIXTURE CONNECTION SCHEDULE
MARK FIXTURE
WATER WASTE
VENT REMARKSCOLD HOT RUNOUT CONN.RUNOUT CONN. RUNOUT CONN.
LAV LAVATORY 1/2" 3/8" 1/2" 3/8" 2" 1-1/4" 1-1/2"
MSB MOP BASIN 3/4" 1/2" 3/4" 1/2" 3" 3" 2"
SK KITCHEN SINK 1/2" 3/8" 1/2" 3/8" 2" 1-1/4" 1-1/2"
WC WATER CLOSET (TANK) 3/4" 1/2" -- -- 4" 3" 2"
PLUMBING FIXTURE SCHEDULE
MARK FIXTURE TYPE ADA FINISH MANUFACTURER & MODEL FAUCET TRIM MANF & MODEL HARDWARE, PLUG OR
BATTERY POWERED ACCESSORIES REMARKS
DF.1 BI-LEVEL ADA WATER COOLER
BOTTLE FILLER YES LIGHT GRAY
GRANITE ELKAY EZSTL8WSVRLK - PLUG - 120/1 (6 FLA)
FD FLOOR DRAIN -
NICKEL
BRONZE ZURN Z415B - -
SELF CLOSING TRAP SEAL BY
PROSEAL OR SURE SEAL 3" OUTLET U.N.O.
FS FLOOR SINK -
STAINLESS
STEEL ZURN Z1750 - -
SELF CLOSING TRAP SEAL BY
PROSEAL OR SURE SEAL 3" OUTLET U.N.O.
HB-1 WALL HYDRANT - CHROME WOODFORD B65 - - - -
LAV.1 UNDERMOUNT LAVATORY-ROUND YES
WHITE
VITREOUS
CHINA
KOHLER K-2210 KOHLER K-104B87-SANA BATTERY - 0.5 GPM
MSB.1 MOP SINK -
MOLDED
STONE FIAT TSB-3010 CHICAGO FACUET 897-CCP - - 24x24x12
SK.1 BAR SINK YES
STAINLESS
STEEL ELKAY BCR15 ELKAY LKAV3021 - - -
SK.2 DOUBLE BOWL KITCHEN SINK YES
STAINLESS
STEEL ELKAY GECR3321 ELKAY LKAV3021 - - 1.8 GPM
TMV-1 THERMOSTATIC MIXING VALVE - - WATTS LFE480 - - ASSE 1070 SET AT 105 DEG.
F
WC.1 FLUSH TANK WATER CLOSET YES
WHITE
VITREOUS
CHINA
AMERICAN STANDARD 2467.016 - - ADA TOILET SEAT
WATER CLOSET
TO MATCH
EXISTING.
WS.1 WATER SOFTENER - - KINETICO HYDRUS HS230s - - - NOTE A
1.
2.
WHERE REQUIRED BY LOCAL STATE AND FEDERAL AUTHORITIES HAVING JURISDICTION, CONTRACTOR SHALL PROVIDE ALL REQUIREMENTS FOR WATER HEATERS
CONSIDERED BOILERS INCLUDING EMERGENCY SHUTOFF SWITCH.
PROVIDE WITH COMMON CONCENTRIC VENT KIT AND SINGLE AMTROL ST-12 EXPANSION TANK
REMARKS:
WATER HEATER SCHEDULE
MARK LOC. AT ROOM TYPE
MIN. CAPACITY GAS
MANUFACTURER AND MODEL RECIRC PUMP
REFGAL
STOR
GPH RECOVERY
AT 100° RISE
INPUT
MBH
VENT
DIA.
VENT MOTOR
H.P. ELECT
WH-1 E MECH 226 STORAGE 119 499.9 AO SMITH BTH-500 DHWP-1
WH-2 E MECH 226 STORAGE 119 399.9 AO SMITH BTH-400 DHWP-1
NO SCALE
WATER HEATER DETAIL - GAS - DUPLEX, RECIRC.1
1.
REMARKS:
PUMP SCHEDULE
MARK LOC AT
ROOM TYPE MIN CAPACITY MIN SIZE CONN MOTOR (BY M.C.)MANUFACTURER AND MODELGPM FEET HEAD EFF SUCTION DISCH HP RPM SPEED ELECT STARTER
DHWP-1 E MECH 226 INLINE 12 20 - 1" 1" 1/8 - - 120/1 - B&G ECOCIRC
0'8'12'4'NO SCALE
GREASE INTERCEPTOR DETAIL2
0'8'12'4'NO SCALE
FLOOR DRAIN TRAP GUARD DETAIL3
0'8'12'4'NO SCALE
WATER SOFTENER DETAIL4
NOTES:
A. PROVIDE WITH (2) BRINE TANKS AND HYDRUS SMART CONTROLLER, BASE. COORDINATE WITH CGC WATER TREATMENT.
NO. DATE DESCRIPTION