Loading...
1 FLEET LANDING Coleman Bldg Reno COMM21-0042 Mechanical COMcheck_1COMcheck Software Version COMcheckWeb Mechanical Compliance Certificate Project Title: 2020 Florida Building Code, Energy Conservation Project Type:Alteration Location:Atlantic Beach, Florida Climate Zone:2a Construction Site: 1 Fleet Landing Blvd Atlantic Beach, Florida 32233 Owner/Agent:Designer/Contractor: Project Information Energy Code: Fleet Landing - Coleman Remodel Mechanical Systems List QuantitySystem Type & Description Heating: 1 each - Central Furnace, Electric, Capacity = 10 kBtu/h No minimum efficiency requirement applies Cooling: 1 each - Hydronic Coil, Capacity = 47 kBtu/h, Unknown Economizer No minimum efficiency requirement applies Fan System: AHU-1 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes Fans: FAN 1 Supply, Single-Zone VAV, 1610 CFM, 1.5 motor nameplate hp, 1.27 fan energy index 1 HVAC System, AHU-1 (Multiple-Zone): Heating: 1 each - Central Furnace, Electric, Capacity = 27 kBtu/h No minimum efficiency requirement applies Cooling: 1 each - Hydronic Coil, Capacity = 92 kBtu/h, Air Economizer No minimum efficiency requirement applies Fan System: AHU-2 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes Fans: FAN 2 Supply, Single-Zone VAV, 1755 CFM, 2.0 motor nameplate hp, 1.27 fan energy index 1 HVAC System, AHU-2 (Multiple-Zone): Heating: 1 each - Central Furnace, Electric, Capacity = 34 kBtu/h No minimum efficiency requirement applies Cooling: 1 each - Hydronic Coil, Capacity = 97 kBtu/h, No Economizer, Economizer exception: Low Operating Hours No minimum efficiency requirement applies Fan System: AHU-3 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes Fans: FAN 3 Supply, Single-Zone VAV, 1800 CFM, 2.5 motor nameplate hp, 1.26 fan energy index 1 HVAC System, AHU-3 (Multiple-Zone): Heating: 1 each - Central Furnace, Electric, Capacity = 14 kBtu/h No minimum efficiency requirement applies Cooling: 1 each - Hydronic Coil, Capacity = 55 kBtu/h, Air Economizer No minimum efficiency requirement applies Fan System: AHU-4 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes Fans: FAN 4 Supply, Single-Zone VAV, 2145 CFM, 3.0 motor nameplate hp, 1.24 fan energy index 1 HVAC System, AHU-4 (Multiple-Zone): Heating: 1 each - Central Furnace, Electric, Capacity = 38 kBtu/h No minimum efficiency requirement applies Cooling: 1 each - Hydronic Coil, Capacity = 113 kBtu/h, Air Economizer No minimum efficiency requirement applies Fan System: AHU-5 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes 1 HVAC System, AHU-5 (Multiple-Zone): Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 314 ofPage QuantitySystem Type & Description Fans: FAN 7 Supply, Single-Zone VAV, 3045 CFM, 5.0 motor nameplate hp, 1.24 fan energy index Heating: 1 each - Central Furnace, Electric, Capacity = 205 kBtu/h No minimum efficiency requirement applies Cooling: 1 each - Hydronic Coil, Capacity = 357 kBtu/h, Air Economizer No minimum efficiency requirement applies Fan System: AHU-6 -- Compliance (Brake HP and fan efficiency method) : Passes Fans: FAN 6 Supply, Single-Zone VAV, 8495 CFM, 10.0 motor nameplate hp, 7.2 design brake hp (7.2 max. BHP), 0.95 fan energy index 1 HVAC System, AHU-6 (Multiple-Zone): Heating: 1 each - Central Furnace, Electric, Capacity = 85 kBtu/h No minimum efficiency requirement applies Cooling: 1 each - Hydronic Coil, Capacity = 178 kBtu/h, Air Economizer No minimum efficiency requirement applies Fan System: AHU-7 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes Fans: FAN 8 Supply, Single-Zone VAV, 4310 CFM, 5.0 motor nameplate hp, 1.10 fan energy index 1 HVAC System, AHU-7 (Multiple-Zone): Heating: 1 each - Central Furnace, Electric, Capacity = 205 kBtu/h No minimum efficiency requirement applies Cooling: 1 each - Hydronic Coil, Capacity = 501 kBtu/h, No Economizer, Economizer exception: Low Operating Hours No minimum efficiency requirement applies Fan System: AHU-8 -- Compliance (Motor nameplate HP and fan efficiency method) : Passes Fans: FAN 9 Supply, Single-Zone VAV, 15000 CFM, 15.0 motor nameplate hp, 0.95 fan energy index 1 HVAC System, AHU-8 (Multiple-Zone): Gas Storage Water Heater, Capacity: 119 gallons, Input Rating: 499 kBtu/h w/ Circulation Pump No minimum efficiency requirement applies 1 Water Heater, WH-1: Gas Storage Water Heater, Capacity: 119 gallons, Input Rating: 399 kBtu/h w/ Circulation Pump No minimum efficiency requirement applies 1 Water Heater, WH-2: Mechanical Compliance Statement Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the 2020 Florida Building Code, Energy Conservation requirements in COMcheck Version COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 315 ofPage Jake Brown - Design Engineer 8/4/2021 Inspection Checklist Requirements: 100.0% were addressed directly in the COMcheck software COMcheck Software Version COMcheckWeb Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2020 Florida Building Code, Energy Conservation Section # & Req.ID Plan Review Complies?Comments/Assumptions C103.2 [PR2]1 Plans, specifications, and/or calculations provide all information with which compliance can be determined for the mechanical systems and equipment and document where exceptions to the standard are claimed. Load calculations per acceptable engineering standards and handbooks. Complies Does Not Not Observable Not Applicable Requirement will be met. C103.2 [PR3]1 Plans, specifications, and/or calculations provide all information with which compliance can be determined for the service water heating systems and equipment and document where exceptions to the standard are claimed. Hot water system sized per manufacturer's sizing guide. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 316 ofPage Section # & Req.ID Footing / Foundation Inspection Complies?Comments/Assumptions C403.2.4. 5 [FO9]3 Snow/ice melting system and freeze protection systems have sensors and controls configured to limit service for pavement temperature and outdoor temperature. future connection to controls. Complies Does Not Not Observable Not Applicable Exception: Requirement does not apply. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 317 ofPage Section # & Req.ID Plumbing Rough-In Inspection Complies?Comments/Assumptions C404.6.1, C404.6.2 [PL3]1 Automatic time switches installed to automatically switch off the recirculating hot-water system or heat trace. Complies Does Not Not Observable Not Applicable Requirement will be met. C404.6.1, C404.6.2 [PL3]1 Automatic time switches installed to automatically switch off the recirculating hot-water system or heat trace. Complies Does Not Not Observable Not Applicable Requirement will be met. C404.6.3 [PL7]3 Pumps that circulate water between a heater and storage tank have controls that limit operation from startup to <= 5 minutes after end of heating cycle. Complies Does Not Not Observable Not Applicable Requirement will be met. C404.6.3 [PL7]3 Pumps that circulate water between a heater and storage tank have controls that limit operation from startup to <= 5 minutes after end of heating cycle. Complies Does Not Not Observable Not Applicable Requirement will be met. C404.7 [PL8]3 Demand recirculation water systems have controls that start the pump upon receiving a signal from the action of a user of a fixture or appliance and limits the temperature of the water entering the cold-water piping to 104°F. Complies Does Not Not Observable Not Applicable Requirement will be met. C404.7 [PL8]3 Demand recirculation water systems have controls that start the pump upon receiving a signal from the action of a user of a fixture or appliance and limits the temperature of the water entering the cold-water piping to 104°F. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 318 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C402.2.6 [ME41]3 Thermally ineffective panel surfaces of sensible heating panels have insulation >= R-3.5. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.10 [ME61]2 HVAC piping insulation insulated in accordance with Table C403.2.10. Insulation exposed to weather is protected from damage and is provided with shielding from solar radiation. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.10 [ME61]2 HVAC piping insulation insulated in accordance with Table C403.2.10. Insulation exposed to weather is protected from damage and is provided with shielding from solar radiation. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.10 [ME61]2 HVAC piping insulation insulated in accordance with Table C403.2.10. Insulation exposed to weather is protected from damage and is provided with shielding from solar radiation. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.10 [ME61]2 HVAC piping insulation insulated in accordance with Table C403.2.10. Insulation exposed to weather is protected from damage and is provided with shielding from solar radiation. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.10 [ME61]2 HVAC piping insulation insulated in accordance with Table C403.2.10. Insulation exposed to weather is protected from damage and is provided with shielding from solar radiation. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.10 [ME61]2 HVAC piping insulation insulated in accordance with Table C403.2.10. Insulation exposed to weather is protected from damage and is provided with shielding from solar radiation. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.10 [ME61]2 HVAC piping insulation insulated in accordance with Table C403.2.10. Insulation exposed to weather is protected from damage and is provided with shielding from solar radiation. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.10 [ME61]2 HVAC piping insulation insulated in accordance with Table C403.2.10. Insulation exposed to weather is protected from damage and is provided with shielding from solar radiation. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .1 [ME65]3 HVAC fan systems at design conditions do not exceed allowable fan system motor nameplate hp or fan system bhp. Complies Does Not Not Observable Not Applicable Requirement will be met. See the Mechanical Systems list for values. C403.2.12 .1 [ME65]3 HVAC fan systems at design conditions do not exceed allowable fan system motor nameplate hp or fan system bhp. Complies Does Not Not Observable Not Applicable Requirement will be met. See the Mechanical Systems list for values. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 319 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.2.12 .2 [ME21]2 HVAC fan motors not oversized beyond allowable limits. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .3 [ME117]2 Fans have energy index (FEI) >= 1.00 in accordance with AMCA 208. Fans for VAV systems shall have an FEI >= 0.95. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .3 [ME117]2 Fans have energy index (FEI) >= 1.00 in accordance with AMCA 208. Fans for VAV systems shall have an FEI >= 0.95. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .4 [ME142]2 Motors for fans that are not less than 1/12 hp and less than 1 hp are electronically commutated motors or have a minimum motor efficiency of 70 percent. These motors have the means to adjust motor speed. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .4 [ME142]2 Motors for fans that are not less than 1/12 hp and less than 1 hp are electronically commutated motors or have a minimum motor efficiency of 70 percent. These motors have the means to adjust motor speed. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .4 [ME142]2 Motors for fans that are not less than 1/12 hp and less than 1 hp are electronically commutated motors or have a minimum motor efficiency of 70 percent. These motors have the means to adjust motor speed. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .4 [ME142]2 Motors for fans that are not less than 1/12 hp and less than 1 hp are electronically commutated motors or have a minimum motor efficiency of 70 percent. These motors have the means to adjust motor speed. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .4 [ME142]2 Motors for fans that are not less than 1/12 hp and less than 1 hp are electronically commutated motors or have a minimum motor efficiency of 70 percent. These motors have the means to adjust motor speed. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .4 [ME142]2 Motors for fans that are not less than 1/12 hp and less than 1 hp are electronically commutated motors or have a minimum motor efficiency of 70 percent. These motors have the means to adjust motor speed. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .4 [ME142]2 Motors for fans that are not less than 1/12 hp and less than 1 hp are electronically commutated motors or have a minimum motor efficiency of 70 percent. These motors have the means to adjust motor speed. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .4 [ME142]2 Motors for fans that are not less than 1/12 hp and less than 1 hp are electronically commutated motors or have a minimum motor efficiency of 70 percent. These motors have the means to adjust motor speed. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3110 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.2.12 .5 [ME143]2 Each DX cooling system > 65 kBtu and chiller water/evaporative cooling system with fans > 1/4 hp are designed to vary the indoor fan airflow as a function of load and comply with detailed requirements of this section. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5 [ME143]2 Each DX cooling system > 65 kBtu and chiller water/evaporative cooling system with fans > 1/4 hp are designed to vary the indoor fan airflow as a function of load and comply with detailed requirements of this section. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5 [ME143]2 Each DX cooling system > 65 kBtu and chiller water/evaporative cooling system with fans > 1/4 hp are designed to vary the indoor fan airflow as a function of load and comply with detailed requirements of this section. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5 [ME143]2 Each DX cooling system > 65 kBtu and chiller water/evaporative cooling system with fans > 1/4 hp are designed to vary the indoor fan airflow as a function of load and comply with detailed requirements of this section. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5 [ME143]2 Each DX cooling system > 65 kBtu and chiller water/evaporative cooling system with fans > 1/4 hp are designed to vary the indoor fan airflow as a function of load and comply with detailed requirements of this section. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5 [ME143]2 Each DX cooling system > 65 kBtu and chiller water/evaporative cooling system with fans > 1/4 hp are designed to vary the indoor fan airflow as a function of load and comply with detailed requirements of this section. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5 [ME143]2 Each DX cooling system > 65 kBtu and chiller water/evaporative cooling system with fans > 1/4 hp are designed to vary the indoor fan airflow as a function of load and comply with detailed requirements of this section. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5 [ME143]2 Each DX cooling system > 65 kBtu and chiller water/evaporative cooling system with fans > 1/4 hp are designed to vary the indoor fan airflow as a function of load and comply with detailed requirements of this section. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.3 [ME55]2 HVAC equipment efficiency verified.Complies Does Not Not Observable Not Applicable See the Mechanical Systems list for values. C403.2.4. 4 [ME112]3 Zone isolation devices and controls installed where applicable. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 4 [ME112]3 Zone isolation devices and controls installed where applicable. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3111 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.2.4. 4 [ME112]3 Zone isolation devices and controls installed where applicable. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 4 [ME112]3 Zone isolation devices and controls installed where applicable. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 4 [ME112]3 Zone isolation devices and controls installed where applicable. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 4 [ME112]3 Zone isolation devices and controls installed where applicable. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 4 [ME112]3 Zone isolation devices and controls installed where applicable. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 4 [ME112]3 Zone isolation devices and controls installed where applicable. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 7 [ME113]2 Fault detection and diagnostics installed with air-cooled unitary DX units having economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 7 [ME113]2 Fault detection and diagnostics installed with air-cooled unitary DX units having economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 7 [ME113]2 Fault detection and diagnostics installed with air-cooled unitary DX units having economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 7 [ME113]2 Fault detection and diagnostics installed with air-cooled unitary DX units having economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 7 [ME113]2 Fault detection and diagnostics installed with air-cooled unitary DX units having economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.6 [ME59]1 Natural or mechanical ventilation is provided in accordance with Florida Building Code Chapter 4. Mechanical ventilation has capability to reduce outdoor air supply to minimum per Florida Building Code Chapter 4. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3112 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.2.6. 1 [ME59]1 Demand control ventilation provided for spaces >500 ft2 and >25 people/1000 ft2 occupant density and served by systems with air side economizer, auto modulating outside air damper control, or design airflow >3,000 cfm. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.6. 2 [ME115]3 Enclosed parking garage ventilation has automatic contaminant detection and capacity to stage or modulate fans to 50% or less of design capacity. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 8 [ME141]3 HVAC systems serving guestrooms in Group R-1 buildings with > 50 guestrooms: Each guestroom is provided with controls that automatically manage temperature setpoint and ventilation (see sections C403.2.4.8.1 and C403.2.4.8.2). Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.7 [ME57]1 Exhaust air energy recovery on systems meeting Table C403.2.7(1) and C403.2.7(2). Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.8 [ME116]3 Kitchen exhaust systems comply with replacement air and conditioned supply air limitations, and satisfy hood rating requirements and maximum exhaust rate criteria. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.9. 1, C403.2.9. 2 [ME60]2 HVAC ducts and plenums insulated in accordance with C403.2.9.1 and constructed in accordance with C403.2.9.2, verification may need to occur during Foundation Inspection. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3, C403.3.1, C403.3.2 [ME62]1 Air economizers provided where required, meet the requirements for design capacity, control signal, ventilation controls, high-limit shut-off, integrated economizer control, and provide a means to relieve excess outside air during operation. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3, C403.3.1, C403.3.2 [ME62]1 Air economizers provided where required, meet the requirements for design capacity, control signal, ventilation controls, high-limit shut-off, integrated economizer control, and provide a means to relieve excess outside air during operation. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3, C403.3.1, C403.3.2 [ME62]1 Air economizers provided where required, meet the requirements for design capacity, control signal, ventilation controls, high-limit shut-off, integrated economizer control, and provide a means to relieve excess outside air during operation. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3, C403.3.1, C403.3.2 [ME62]1 Air economizers provided where required, meet the requirements for design capacity, control signal, ventilation controls, high-limit shut-off, integrated economizer control, and provide a means to relieve excess outside air during operation. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3113 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.3, C403.3.1, C403.3.2 [ME62]1 Air economizers provided where required, meet the requirements for design capacity, control signal, ventilation controls, high-limit shut-off, integrated economizer control, and provide a means to relieve excess outside air during operation. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 3 [ME124]1 Air economizers automatically reduce outdoor air intake to the design minimum outdoor air quantity when outdoor air intake will not reduce cooling energy usage. See Table C403.3.3.3 for applicable device types and climate zones. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 3 [ME124]1 Air economizers automatically reduce outdoor air intake to the design minimum outdoor air quantity when outdoor air intake will not reduce cooling energy usage. See Table C403.3.3.3 for applicable device types and climate zones. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 3 [ME124]1 Air economizers automatically reduce outdoor air intake to the design minimum outdoor air quantity when outdoor air intake will not reduce cooling energy usage. See Table C403.3.3.3 for applicable device types and climate zones. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 3 [ME124]1 Air economizers automatically reduce outdoor air intake to the design minimum outdoor air quantity when outdoor air intake will not reduce cooling energy usage. See Table C403.3.3.3 for applicable device types and climate zones. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 3 [ME124]1 Air economizers automatically reduce outdoor air intake to the design minimum outdoor air quantity when outdoor air intake will not reduce cooling energy usage. See Table C403.3.3.3 for applicable device types and climate zones. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 4 [ME125]1 System capable of relieving excess outdoor air during air economizer operation to prevent overpressurizing the building. The relief air outlet located to avoid recirculation into the building. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 4 [ME125]1 System capable of relieving excess outdoor air during air economizer operation to prevent overpressurizing the building. The relief air outlet located to avoid recirculation into the building. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 4 [ME125]1 System capable of relieving excess outdoor air during air economizer operation to prevent overpressurizing the building. The relief air outlet located to avoid recirculation into the building. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3114 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.3.3. 4 [ME125]1 System capable of relieving excess outdoor air during air economizer operation to prevent overpressurizing the building. The relief air outlet located to avoid recirculation into the building. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 4 [ME125]1 System capable of relieving excess outdoor air during air economizer operation to prevent overpressurizing the building. The relief air outlet located to avoid recirculation into the building. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 5 [ME126]1 Return, exhaust/relief and outdoor air dampers used in economizers have motorized dampers that automatically shut when not in use and meet maximum leakage rates. Reference section C403.2.4.3 for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 5 [ME126]1 Return, exhaust/relief and outdoor air dampers used in economizers have motorized dampers that automatically shut when not in use and meet maximum leakage rates. Reference section C403.2.4.3 for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 5 [ME126]1 Return, exhaust/relief and outdoor air dampers used in economizers have motorized dampers that automatically shut when not in use and meet maximum leakage rates. Reference section C403.2.4.3 for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 5 [ME126]1 Return, exhaust/relief and outdoor air dampers used in economizers have motorized dampers that automatically shut when not in use and meet maximum leakage rates. Reference section C403.2.4.3 for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.3.3. 5 [ME126]1 Return, exhaust/relief and outdoor air dampers used in economizers have motorized dampers that automatically shut when not in use and meet maximum leakage rates. Reference section C403.2.4.3 for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.1 [ME75]2 Hydronic and multizone HVAC system controls are VAV fans driven by mechanical or electrical variable speed drive per Table C403.2.12.5. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.1 [ME75]2 Hydronic and multizone HVAC system controls are VAV fans driven by mechanical or electrical variable speed drive per Table C403.2.12.5. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.1 [ME75]2 Hydronic and multizone HVAC system controls are VAV fans driven by mechanical or electrical variable speed drive per Table C403.2.12.5. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.1 [ME75]2 Hydronic and multizone HVAC system controls are VAV fans driven by mechanical or electrical variable speed drive per Table C403.2.12.5. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3115 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.2.12 .5.1 [ME75]2 Hydronic and multizone HVAC system controls are VAV fans driven by mechanical or electrical variable speed drive per Table C403.2.12.5. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.1 [ME75]2 Hydronic and multizone HVAC system controls are VAV fans driven by mechanical or electrical variable speed drive per Table C403.2.12.5. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.1 [ME75]2 Hydronic and multizone HVAC system controls are VAV fans driven by mechanical or electrical variable speed drive per Table C403.2.12.5. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.1 [ME75]2 Hydronic and multizone HVAC system controls are VAV fans driven by mechanical or electrical variable speed drive per Table C403.2.12.5. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.2 [ME67]2 VAV fans have static pressure sensors located so controller setpoint <=1.2 w.c.. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.2 [ME67]2 VAV fans have static pressure sensors located so controller setpoint <=1.2 w.c.. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.2 [ME67]2 VAV fans have static pressure sensors located so controller setpoint <=1.2 w.c.. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.2 [ME67]2 VAV fans have static pressure sensors located so controller setpoint <=1.2 w.c.. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.2 [ME67]2 VAV fans have static pressure sensors located so controller setpoint <=1.2 w.c.. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.2 [ME67]2 VAV fans have static pressure sensors located so controller setpoint <=1.2 w.c.. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.2 [ME67]2 VAV fans have static pressure sensors located so controller setpoint <=1.2 w.c.. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.2 [ME67]2 VAV fans have static pressure sensors located so controller setpoint <=1.2 w.c.. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.3 [ME24]2 Reset static pressure setpoint for DDC controlled VAV boxes reporting to central controller based on the zones requiring the most pressure. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3116 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.2.12 .5.3 [ME24]2 Reset static pressure setpoint for DDC controlled VAV boxes reporting to central controller based on the zones requiring the most pressure. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.3 [ME24]2 Reset static pressure setpoint for DDC controlled VAV boxes reporting to central controller based on the zones requiring the most pressure. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.3 [ME24]2 Reset static pressure setpoint for DDC controlled VAV boxes reporting to central controller based on the zones requiring the most pressure. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.3 [ME24]2 Reset static pressure setpoint for DDC controlled VAV boxes reporting to central controller based on the zones requiring the most pressure. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.3 [ME24]2 Reset static pressure setpoint for DDC controlled VAV boxes reporting to central controller based on the zones requiring the most pressure. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.3 [ME24]2 Reset static pressure setpoint for DDC controlled VAV boxes reporting to central controller based on the zones requiring the most pressure. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.12 .5.3 [ME24]2 Reset static pressure setpoint for DDC controlled VAV boxes reporting to central controller based on the zones requiring the most pressure. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 1 [ME50]2 Three-pipe hydronic systems using a common return for hot and chilled water are not used. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 1 [ME50]2 Three-pipe hydronic systems using a common return for hot and chilled water are not used. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 1 [ME50]2 Three-pipe hydronic systems using a common return for hot and chilled water are not used. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 1 [ME50]2 Three-pipe hydronic systems using a common return for hot and chilled water are not used. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 1 [ME50]2 Three-pipe hydronic systems using a common return for hot and chilled water are not used. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 1 [ME50]2 Three-pipe hydronic systems using a common return for hot and chilled water are not used. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3117 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.4.2. 1 [ME50]2 Three-pipe hydronic systems using a common return for hot and chilled water are not used. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 1 [ME50]2 Three-pipe hydronic systems using a common return for hot and chilled water are not used. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 6 [ME26]3 Chilled water plants with multiple chillers have capability to reduce flow automatically through the chiller plant when a chiller is shut down. Boiler plants with multiple boilers have the capability to reduce flow automatically through the boiler plant when a boiler is shut down. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 6 [ME26]3 Chilled water plants with multiple chillers have capability to reduce flow automatically through the chiller plant when a chiller is shut down. Boiler plants with multiple boilers have the capability to reduce flow automatically through the boiler plant when a boiler is shut down. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 6 [ME26]3 Chilled water plants with multiple chillers have capability to reduce flow automatically through the chiller plant when a chiller is shut down. Boiler plants with multiple boilers have the capability to reduce flow automatically through the boiler plant when a boiler is shut down. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 6 [ME26]3 Chilled water plants with multiple chillers have capability to reduce flow automatically through the chiller plant when a chiller is shut down. Boiler plants with multiple boilers have the capability to reduce flow automatically through the boiler plant when a boiler is shut down. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 6 [ME26]3 Chilled water plants with multiple chillers have capability to reduce flow automatically through the chiller plant when a chiller is shut down. Boiler plants with multiple boilers have the capability to reduce flow automatically through the boiler plant when a boiler is shut down. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 6 [ME26]3 Chilled water plants with multiple chillers have capability to reduce flow automatically through the chiller plant when a chiller is shut down. Boiler plants with multiple boilers have the capability to reduce flow automatically through the boiler plant when a boiler is shut down. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3118 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.4.2. 6 [ME26]3 Chilled water plants with multiple chillers have capability to reduce flow automatically through the chiller plant when a chiller is shut down. Boiler plants with multiple boilers have the capability to reduce flow automatically through the boiler plant when a boiler is shut down. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.2. 6 [ME26]3 Chilled water plants with multiple chillers have capability to reduce flow automatically through the chiller plant when a chiller is shut down. Boiler plants with multiple boilers have the capability to reduce flow automatically through the boiler plant when a boiler is shut down. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4 [ME130]3 Supply air systems serving multiple zones have VAV systems with controls configured to reduce the volume of air that is reheated, recooled or mixed in each zone. See section for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4 [ME130]3 Supply air systems serving multiple zones have VAV systems with controls configured to reduce the volume of air that is reheated, recooled or mixed in each zone. See section for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4 [ME130]3 Supply air systems serving multiple zones have VAV systems with controls configured to reduce the volume of air that is reheated, recooled or mixed in each zone. See section for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4 [ME130]3 Supply air systems serving multiple zones have VAV systems with controls configured to reduce the volume of air that is reheated, recooled or mixed in each zone. See section for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4 [ME130]3 Supply air systems serving multiple zones have VAV systems with controls configured to reduce the volume of air that is reheated, recooled or mixed in each zone. See section for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4 [ME130]3 Supply air systems serving multiple zones have VAV systems with controls configured to reduce the volume of air that is reheated, recooled or mixed in each zone. See section for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4 [ME130]3 Supply air systems serving multiple zones have VAV systems with controls configured to reduce the volume of air that is reheated, recooled or mixed in each zone. See section for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4 [ME130]3 Supply air systems serving multiple zones have VAV systems with controls configured to reduce the volume of air that is reheated, recooled or mixed in each zone. See section for details. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 1 [ME131]3 Single-duct VAV systems use terminal devices configured to reduce the supply of primary supply air before reheating or recooling takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3119 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.4.4. 1 [ME131]3 Single-duct VAV systems use terminal devices configured to reduce the supply of primary supply air before reheating or recooling takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 1 [ME131]3 Single-duct VAV systems use terminal devices configured to reduce the supply of primary supply air before reheating or recooling takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 1 [ME131]3 Single-duct VAV systems use terminal devices configured to reduce the supply of primary supply air before reheating or recooling takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 1 [ME131]3 Single-duct VAV systems use terminal devices configured to reduce the supply of primary supply air before reheating or recooling takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 1 [ME131]3 Single-duct VAV systems use terminal devices configured to reduce the supply of primary supply air before reheating or recooling takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 1 [ME131]3 Single-duct VAV systems use terminal devices configured to reduce the supply of primary supply air before reheating or recooling takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 1 [ME131]3 Single-duct VAV systems use terminal devices configured to reduce the supply of primary supply air before reheating or recooling takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 2 [ME132]3 Systems that have 1 warm air duct and 1 cool air duct use terminal devices configured to reduce the flow from one duct to a minimum before mixing of air from the other duct takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 2 [ME132]3 Systems that have 1 warm air duct and 1 cool air duct use terminal devices configured to reduce the flow from one duct to a minimum before mixing of air from the other duct takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 2 [ME132]3 Systems that have 1 warm air duct and 1 cool air duct use terminal devices configured to reduce the flow from one duct to a minimum before mixing of air from the other duct takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 2 [ME132]3 Systems that have 1 warm air duct and 1 cool air duct use terminal devices configured to reduce the flow from one duct to a minimum before mixing of air from the other duct takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 2 [ME132]3 Systems that have 1 warm air duct and 1 cool air duct use terminal devices configured to reduce the flow from one duct to a minimum before mixing of air from the other duct takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3120 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.4.4. 2 [ME132]3 Systems that have 1 warm air duct and 1 cool air duct use terminal devices configured to reduce the flow from one duct to a minimum before mixing of air from the other duct takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 2 [ME132]3 Systems that have 1 warm air duct and 1 cool air duct use terminal devices configured to reduce the flow from one duct to a minimum before mixing of air from the other duct takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 2 [ME132]3 Systems that have 1 warm air duct and 1 cool air duct use terminal devices configured to reduce the flow from one duct to a minimum before mixing of air from the other duct takes place. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 3 [ME133]3 Individual dual-duct or mixing heating and cooling systems with a single fan and with total capacities > 90,000 Btu/h not equipped with air economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 3 [ME133]3 Individual dual-duct or mixing heating and cooling systems with a single fan and with total capacities > 90,000 Btu/h not equipped with air economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 3 [ME133]3 Individual dual-duct or mixing heating and cooling systems with a single fan and with total capacities > 90,000 Btu/h not equipped with air economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 3 [ME133]3 Individual dual-duct or mixing heating and cooling systems with a single fan and with total capacities > 90,000 Btu/h not equipped with air economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 3 [ME133]3 Individual dual-duct or mixing heating and cooling systems with a single fan and with total capacities > 90,000 Btu/h not equipped with air economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 3 [ME133]3 Individual dual-duct or mixing heating and cooling systems with a single fan and with total capacities > 90,000 Btu/h not equipped with air economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 3 [ME133]3 Individual dual-duct or mixing heating and cooling systems with a single fan and with total capacities > 90,000 Btu/h not equipped with air economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 3 [ME133]3 Individual dual-duct or mixing heating and cooling systems with a single fan and with total capacities > 90,000 Btu/h not equipped with air economizers. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 5 [ME134]3 Multiple zone HVAC systems have supply air temperature reset controls. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3121 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.4.4. 5 [ME134]3 Multiple zone HVAC systems have supply air temperature reset controls. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 5 [ME134]3 Multiple zone HVAC systems have supply air temperature reset controls. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 5 [ME134]3 Multiple zone HVAC systems have supply air temperature reset controls. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 5 [ME134]3 Multiple zone HVAC systems have supply air temperature reset controls. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 5 [ME134]3 Multiple zone HVAC systems have supply air temperature reset controls. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 5 [ME134]3 Multiple zone HVAC systems have supply air temperature reset controls. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 5 [ME134]3 Multiple zone HVAC systems have supply air temperature reset controls. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 7 [ME136]3 Parallel-flow fan-powered VAV air terminals have automatic controls configured to 1) turn off the terminal fan except when space heating is required or where required for ventilation, 2) turn on the terminal fan as the first stage of heating before the heating coil is activated, and 3) during heating for warmup or setback temperature control, either operate the terminal fan and heating coil without primary air or, reverse the terminal damper logic and provide heating from the central air handler by primary air. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 7 [ME136]3 Parallel-flow fan-powered VAV air terminals have automatic controls configured to 1) turn off the terminal fan except when space heating is required or where required for ventilation, 2) turn on the terminal fan as the first stage of heating before the heating coil is activated, and 3) during heating for warmup or setback temperature control, either operate the terminal fan and heating coil without primary air or, reverse the terminal damper logic and provide heating from the central air handler by primary air. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3122 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.4.4. 7 [ME136]3 Parallel-flow fan-powered VAV air terminals have automatic controls configured to 1) turn off the terminal fan except when space heating is required or where required for ventilation, 2) turn on the terminal fan as the first stage of heating before the heating coil is activated, and 3) during heating for warmup or setback temperature control, either operate the terminal fan and heating coil without primary air or, reverse the terminal damper logic and provide heating from the central air handler by primary air. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 7 [ME136]3 Parallel-flow fan-powered VAV air terminals have automatic controls configured to 1) turn off the terminal fan except when space heating is required or where required for ventilation, 2) turn on the terminal fan as the first stage of heating before the heating coil is activated, and 3) during heating for warmup or setback temperature control, either operate the terminal fan and heating coil without primary air or, reverse the terminal damper logic and provide heating from the central air handler by primary air. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 7 [ME136]3 Parallel-flow fan-powered VAV air terminals have automatic controls configured to 1) turn off the terminal fan except when space heating is required or where required for ventilation, 2) turn on the terminal fan as the first stage of heating before the heating coil is activated, and 3) during heating for warmup or setback temperature control, either operate the terminal fan and heating coil without primary air or, reverse the terminal damper logic and provide heating from the central air handler by primary air. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 7 [ME136]3 Parallel-flow fan-powered VAV air terminals have automatic controls configured to 1) turn off the terminal fan except when space heating is required or where required for ventilation, 2) turn on the terminal fan as the first stage of heating before the heating coil is activated, and 3) during heating for warmup or setback temperature control, either operate the terminal fan and heating coil without primary air or, reverse the terminal damper logic and provide heating from the central air handler by primary air. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3123 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.4.4. 7 [ME136]3 Parallel-flow fan-powered VAV air terminals have automatic controls configured to 1) turn off the terminal fan except when space heating is required or where required for ventilation, 2) turn on the terminal fan as the first stage of heating before the heating coil is activated, and 3) during heating for warmup or setback temperature control, either operate the terminal fan and heating coil without primary air or, reverse the terminal damper logic and provide heating from the central air handler by primary air. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 7 [ME136]3 Parallel-flow fan-powered VAV air terminals have automatic controls configured to 1) turn off the terminal fan except when space heating is required or where required for ventilation, 2) turn on the terminal fan as the first stage of heating before the heating coil is activated, and 3) during heating for warmup or setback temperature control, either operate the terminal fan and heating coil without primary air or, reverse the terminal damper logic and provide heating from the central air handler by primary air. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.4. 6 [ME135]3 Multiple zone VAV systems with DDC of individual zone boxes have controls to reduce outdoor intake airflow below design rates based on ventilation efficiency as defined by Florida Building and Mechanical Code. Complies Does Not Not Observable Not Applicable Requirement will be met. See the Mechanical Systems list for values. C403.4.4. 6 [ME135]3 Multiple zone VAV systems with DDC of individual zone boxes have controls to reduce outdoor intake airflow below design rates based on ventilation efficiency as defined by Florida Building and Mechanical Code. Complies Does Not Not Observable Not Applicable Requirement will be met. See the Mechanical Systems list for values. C403.4.4. 6 [ME135]3 Multiple zone VAV systems with DDC of individual zone boxes have controls to reduce outdoor intake airflow below design rates based on ventilation efficiency as defined by Florida Building and Mechanical Code. Complies Does Not Not Observable Not Applicable Requirement will be met. See the Mechanical Systems list for values. C403.4.4. 6 [ME135]3 Multiple zone VAV systems with DDC of individual zone boxes have controls to reduce outdoor intake airflow below design rates based on ventilation efficiency as defined by Florida Building and Mechanical Code. Complies Does Not Not Observable Not Applicable Requirement will be met. See the Mechanical Systems list for values. C403.4.4. 6 [ME135]3 Multiple zone VAV systems with DDC of individual zone boxes have controls to reduce outdoor intake airflow below design rates based on ventilation efficiency as defined by Florida Building and Mechanical Code. Complies Does Not Not Observable Not Applicable Requirement will be met. See the Mechanical Systems list for values. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3124 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C403.4.4. 6 [ME135]3 Multiple zone VAV systems with DDC of individual zone boxes have controls to reduce outdoor intake airflow below design rates based on ventilation efficiency as defined by Florida Building and Mechanical Code. Complies Does Not Not Observable Not Applicable Requirement will be met. See the Mechanical Systems list for values. C403.4.4. 6 [ME135]3 Multiple zone VAV systems with DDC of individual zone boxes have controls to reduce outdoor intake airflow below design rates based on ventilation efficiency as defined by Florida Building and Mechanical Code. Complies Does Not Not Observable Not Applicable Requirement will be met. See the Mechanical Systems list for values. C403.4.4. 6 [ME135]3 Multiple zone VAV systems with DDC of individual zone boxes have controls to reduce outdoor intake airflow below design rates based on ventilation efficiency as defined by Florida Building and Mechanical Code. Complies Does Not Not Observable Not Applicable Requirement will be met. See the Mechanical Systems list for values. C403.4.5 [ME31]3 Condenser heat recovery system that can heat water to 85 ºF or provide 60% of peak heat rejection is installed for preheating of service hot water. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.5 [ME31]3 Condenser heat recovery system that can heat water to 85 ºF or provide 60% of peak heat rejection is installed for preheating of service hot water. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.5 [ME31]3 Condenser heat recovery system that can heat water to 85 ºF or provide 60% of peak heat rejection is installed for preheating of service hot water. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.5 [ME31]3 Condenser heat recovery system that can heat water to 85 ºF or provide 60% of peak heat rejection is installed for preheating of service hot water. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.5 [ME31]3 Condenser heat recovery system that can heat water to 85 ºF or provide 60% of peak heat rejection is installed for preheating of service hot water. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.5 [ME31]3 Condenser heat recovery system that can heat water to 85 ºF or provide 60% of peak heat rejection is installed for preheating of service hot water. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.5 [ME31]3 Condenser heat recovery system that can heat water to 85 ºF or provide 60% of peak heat rejection is installed for preheating of service hot water. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.4.5 [ME31]3 Condenser heat recovery system that can heat water to 85 ºF or provide 60% of peak heat rejection is installed for preheating of service hot water. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3125 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C404.2.1 [ME111]2 Gas-fired water-heating equipment installed in new buildings: where a singular piece of water-heating equipment >= 1,000 kBtu/h serves the entire building, thermal efficiency >= 90 Et. Where multiple pieces of water-heating equipment serve the building with combined rating >= 1,000 kBtu/h, the combined input- capacity-weighted-average thermal efficiency >= 90 Et. Exclude input rating of equipment in individual dwelling units and equipment <= 100 kBtu/h. Complies Does Not Not Observable Not Applicable Requirement will be met. C404.2.1 [ME111]2 Gas-fired water-heating equipment installed in new buildings: where a singular piece of water-heating equipment >= 1,000 kBtu/h serves the entire building, thermal efficiency >= 90 Et. Where multiple pieces of water-heating equipment serve the building with combined rating >= 1,000 kBtu/h, the combined input- capacity-weighted-average thermal efficiency >= 90 Et. Exclude input rating of equipment in individual dwelling units and equipment <= 100 kBtu/h. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.2. 1 [ME53]3 Air outlets and zone terminal devices have means for air balancing. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.2. 2 [ME54]3 HVAC hydronic heating and cooling coils have means to balance and have pressure test connections. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.2. 2 [ME54]3 HVAC hydronic heating and cooling coils have means to balance and have pressure test connections. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.2. 2 [ME54]3 HVAC hydronic heating and cooling coils have means to balance and have pressure test connections. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.2. 2 [ME54]3 HVAC hydronic heating and cooling coils have means to balance and have pressure test connections. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.2. 2 [ME54]3 HVAC hydronic heating and cooling coils have means to balance and have pressure test connections. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.2. 2 [ME54]3 HVAC hydronic heating and cooling coils have means to balance and have pressure test connections. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3126 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C408.2.2. 2 [ME54]3 HVAC hydronic heating and cooling coils have means to balance and have pressure test connections. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.2. 2 [ME54]3 HVAC hydronic heating and cooling coils have means to balance and have pressure test connections. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.5, C403.5.1, C403.5.2 [ME123]3 Refrigerated display cases, walk-in coolers or walk-in freezers served by remote compressors and remote condensers not located in a condensing unit, have fan-powered condensers that comply with Sections C403.5.1 and refrigeration compressor systems that comply with C403.5.2.. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3127 ofPage Section # & Req.ID Final Inspection Complies?Comments/Assumptions C403.2.1 [FI50]3 HVAC systems and equipment design loads calculated in accordance with ANSI/ASHRAE/ACCA Standard 183 or by an approved equivalent computational procedure Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.2 [FI27]3 HVAC systems and equipment capacity does not exceed calculated loads. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 1 [FI47]3 Heating and cooling to each zone is controlled by a thermostat control. Minimum one humidity control device per installed humidification/dehumidification system. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 1 [FI47]3 Heating and cooling to each zone is controlled by a thermostat control. Minimum one humidity control device per installed humidification/dehumidification system. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 1 [FI47]3 Heating and cooling to each zone is controlled by a thermostat control. Minimum one humidity control device per installed humidification/dehumidification system. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 1 [FI47]3 Heating and cooling to each zone is controlled by a thermostat control. Minimum one humidity control device per installed humidification/dehumidification system. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 1 [FI47]3 Heating and cooling to each zone is controlled by a thermostat control. Minimum one humidity control device per installed humidification/dehumidification system. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 1 [FI47]3 Heating and cooling to each zone is controlled by a thermostat control. Minimum one humidity control device per installed humidification/dehumidification system. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 1 [FI47]3 Heating and cooling to each zone is controlled by a thermostat control. Minimum one humidity control device per installed humidification/dehumidification system. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 1 [FI47]3 Heating and cooling to each zone is controlled by a thermostat control. Minimum one humidity control device per installed humidification/dehumidification system. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 1.2 [FI38]3 Thermostatic controls have a 5 °F deadband. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3128 ofPage Section # & Req.ID Final Inspection Complies?Comments/Assumptions C403.2.4. 1.3 [FI20]3 Temperature controls have setpoint overlap restrictions. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 2 [FI39]3 Each zone equipped with setback controls using automatic time clock or programmable control system. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 2.1, C403.2.4. 2.2 [FI40]3 Automatic Controls: Setback to 55°F (heat) and 85°F (cool); 7-day clock, 2- hour occupant override, 10-hour backup Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 2.3 [FI41]3 Systems include optimum start controls as a function of space temperature, occupied setpoint temperature, outdoor temperature and amount of time prior to occupancy. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 2.3 [FI41]3 Systems include optimum start controls as a function of space temperature, occupied setpoint temperature, outdoor temperature and amount of time prior to occupancy. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 2.3 [FI41]3 Systems include optimum start controls as a function of space temperature, occupied setpoint temperature, outdoor temperature and amount of time prior to occupancy. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 2.3 [FI41]3 Systems include optimum start controls as a function of space temperature, occupied setpoint temperature, outdoor temperature and amount of time prior to occupancy. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 2.3 [FI41]3 Systems include optimum start controls as a function of space temperature, occupied setpoint temperature, outdoor temperature and amount of time prior to occupancy. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 2.3 [FI41]3 Systems include optimum start controls as a function of space temperature, occupied setpoint temperature, outdoor temperature and amount of time prior to occupancy. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 2.3 [FI41]3 Systems include optimum start controls as a function of space temperature, occupied setpoint temperature, outdoor temperature and amount of time prior to occupancy. Complies Does Not Not Observable Not Applicable Requirement will be met. C403.2.4. 2.3 [FI41]3 Systems include optimum start controls as a function of space temperature, occupied setpoint temperature, outdoor temperature and amount of time prior to occupancy. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3129 ofPage Section # & Req.ID Final Inspection Complies?Comments/Assumptions C404.3 [FI11]3 Heat traps installed on supply and discharge piping of non-circulating systems. Complies Does Not Not Observable Not Applicable Exception: Tank inlets/outlets associated with solar water heating systems. C404.3 [FI11]3 Heat traps installed on supply and discharge piping of non-circulating systems. Complies Does Not Not Observable Not Applicable Requirement will be met. C404.4 [FI25]2 All recirculation piping, first 8 feet of outlet or branch piping, inlet piping and piping that is externally heated shall be insulated in accordance with section details and Table C403.2.10 Complies Does Not Not Observable Not Applicable Requirement will be met. C404.4 [FI25]2 All recirculation piping, first 8 feet of outlet or branch piping, inlet piping and piping that is externally heated shall be insulated in accordance with section details and Table C403.2.10 Complies Does Not Not Observable Not Applicable Requirement will be met. C404.6.1 [FI12]3 Controls are installed that limit the operation of a recirculation pump installed to maintain temperature of a storage tank. System return pipe is a dedicated return pipe or a cold water supply pipe. Complies Does Not Not Observable Not Applicable Requirement will be met. C404.6.1 [FI12]3 Controls are installed that limit the operation of a recirculation pump installed to maintain temperature of a storage tank. System return pipe is a dedicated return pipe or a cold water supply pipe. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.1 [FI28]1 Commissioning plan developed by registered design professional or approved agency. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.3. 1 [FI31]1 HVAC equipment has been tested to ensure proper operation. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.3. 2 [FI10]1 HVAC control systems have been tested to ensure proper operation, calibration and adjustment of controls. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.3. 3 [FI32]1 Economizers have been tested to ensure proper operation. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.4 [FI29]1 Preliminary commissioning report completed and certified by registered design professional or approved agency. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.5. 1 [FI7]3 Furnished HVAC as-built drawings submitted within 90 days of system acceptance. Complies Does Not Not Observable Not Applicable Requirement will be met. 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3130 ofPage Section # & Req.ID Final Inspection Complies?Comments/Assumptions C408.2.5. 3 [FI43]1 An air and/or hydronic system balancing report is provided for HVAC systems. Complies Does Not Not Observable Not Applicable Requirement will be met. C408.2.5. 4 [FI30]1 Final commissioning report due to building owner within 90 days of receipt of certificate of occupancy. Complies Does Not Not Observable Not Applicable Requirement will be met. Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Fleet Landing - Coleman Remodel 08/04/21Report date: 3131 ofPage