Loading...
447 ATLANTIC BLVD 3 COMM22-0005 Returned for Corrections FIRE COMMENTSReturned for Corrections: The plans submitted for review have been returned for corrections. Please correct and or provide the additional requested information to obtain plans approval. When resubmitting corrected sheets, provide a type written itemized narrative letter responding to our comments and directing the plans reviewer to the sheets the changes have taken place. FAILURE TO SUPPLY RESPONSE LETTER “WILL” RESULT IN A RETURNED FOR CORRECTIONS PERMIT STATUS. Revised sheets should be clouded, clearly showing areas were changes or corrections have occurred and re-inserted with the original set of drawings with old sheets removed. Unbound plans will not be reviewed. If this is an electronic submission please make sure that written narrative is submitted under correspondence along with a “complete set” (not just the revised sheets) of electronic documents. When submitting electronic plans, each discipline shall upload a single PDF file containing multiple sheets rather than separate PDFs for each sheet.  Please re-upload in this fashion. 1. Required Occupant Load Calculation: • Provide design occupant load using table 7.3.1.2 of NFPA 101 2015 edition. Area calculations should be shown with graphic seating configurations or fixtures in order to substantiate occupant load chosen. 2. Provide required Fire Code specific code summary: Please Reference 7th Edition Florida Fire Prevention Code Based on NFPA, 1 Fire Code 2018  Edition & NFPA 101 Life Safety Code 2018  Edition. 3.address  on plan different from one permit application   //plan # 1    //appl  # 3 / Miguel   Di Pierri Fire Safety Inspector / Plan Reviewer Hispanic Advocate / MHAAB