Timothy Thompson
RE: Fire Flow Test for 45 Simmons Road
Per your request, the City flow tested the fire hydrant at 1950 Francis Avenue in Atlantic Beach, Florida.
Tested by: John Doyle, Distribution Operator
Test Date: 1/28/22
Test Time: 8:30 AM
Port Diameter: 2.5-inch port
Static Pressure: 46 PSI
Residual Pressure: 44 PSI
Test Flow Rate: 932.5 gpm
The following computational results based on the above variables and NFPA section 291, AWWA M-17 are as follows:
1/28/22 – Estimated flow at 20 psi: 3723 gpm
Should you need additional information, please call me at (904) 247-5886 or email me at cwalker@coab.us.