705 Atlantic Blvd, Unit 32 - COMM22-0018 Elec PlansPOWER INTEGRATION, LLCELECTRICAL ENGINEERING CONSULTANTCA#31167PH: 904.307.9077EMAIL: sukutb@comcast.netSukumaran T BaskaranDigitally signed by Sukumaran T Baskaran Date: 2022.04.08 18:37:17 -04'00'By Toni Gindlesperger at 4:37 pm, Apr 15, 2022\ I SECTION 260500 COMMON MATERIALS ANO METHOOS PART 1 GENERAL 1.1 SUMMARY A. GROUNDING ANO BONOING. 8. CONNECTION OF llTIUZATION EQUIPMENT. C. SUPPORTS. D. IDENTIFICATION. 1.2 SUBMITTAI..S A. PRODUCT DATA: FOR REVIEW; PROVIDE CATALOG DATA FOR GROUNDING AND BONDING DEVICES. 1.3 REGULATORY REQUIREMENTS A. CONFORM TO REQUIREMENTS OF NFPA 70. B, FURNISH PRODUCTS LISTED BY UL OR OTHER TESTING FIRM ACCEPTABLE TO AUTHORllY HAVING JURISDICTION. C. FLORIDA BUILDING CODE 1.4 PROJECT CONDmONS A. VERIFY FIELD MEASUREMENTS AND CIRCUmNG ARRANGEMENTS ARE AS SHOWN ON DRAWINGS. PART 2 PRODUCTS 2.1 GROUNDING MATERIALS A. GROUND ROD: COPPER-CLAD STEEL 3/4-INCH DIAMETER 10 FEET LENGTH. B. MECHANICAL CONNECTORS: BRONZE. Af»;£. GRADE ONLY. C. EXOTHERMIC WELDS: BELOW GRADE CONNECTORS. 2.2 BASIC MATERIALS A. STEEL CHANNEL: GALVANIZED B. MISCELLANEOUS HARDWARE: TREAT FOR CORROSION RESISTANCE. C. NAMEPLATES: ENGRAVED THREE-LAYER LAMINATED PLASTIC, BLACK LETTERS ON WHITE BACKGROUND. D. WIRE AND CABLE MARKERS: CLOTH MARKERS, SPLIT SLEEVE OR TlUBING TYPE. PART 3 EXECllTION 3. 1 INSTALLATION A. INSTALL WORK ACCORDING TO NECA "STANDARD OF 2.5 BUILDING WIRE AND CABLE INSTALLATION." B. PROVIDE BONDING TO MEET REGULATORY REQUIREMENTS. C. MAKE ELECTRICAL CONNECTIONS TO llTIUZATION EQUIPMENT IN ACCORDANCE WITH EQUIPMENT MANUFACTIURER'S INSTRUCTIONS. 1. VERIFY THAT WIRING AND OUTLET ROUGH-IN WORK IS COMPLETE AND THAT llTIUZATION EQUIPMENT IS READY FOR ELECTRICAL CONNECTION, WIRING, AND ENERGIZING. 2. MAKE WIRING CONNECTIONS IN CONTROL PANEL OR IN WIRING COMPARTMENT OF PRE-WIRED EQUIPMENT. PROVIDE INTERCONNECTING WIRING WHERE INDICATED. 3. INSTALL AND CONNECT DISCONNECT SWITCHES, CONTROLLERS, CONTROL STATIONS, AND CONTROL DEVICES AS INDICATED. 4. MAKE CONDUIT CONNECTIONS TO EQUIPMENT USING FLEXIBLE CONDUIT. USE UQUIDTIGHT FLEXIBLE CONDUIT IN DAMP OR WET LOCATIONS. 5. INSTALL PRE-FABRICATED CORD SET WHERE CONNECTION WITH ATTACHMENT PLUG IS INDICATED OR SPECIFIED, OR USE ATTACHMENT PLUG WITH SUITABLE STRAIN-RELIEF CLAMPS. 6. PROVIDE SUITABLE STRAIN-RELIEF CLAMPS FOR CORD CONNECTIONS TO OUTLET BOXES AND EQUIPMENT CONNECTION BOXES. D. INSTALL SUPPORT SYSTEMS SIZED AND FASTENED TO ACCOMMODATE WEIGHT OF EQUIPMENT AND CONDUIT, INCLUDING WIRING, WHICH THEY CARRY. 3.2 EXAMINATION AND PREPARATION A. SUPPORTS 1. FASTEN HANGER RODS, CONDUIT CLAMPS, AND OUTLET AND JUNCTION BOXES TO BUILDINGS STRUCTURE USING PRECAST INSERT SYSTEM BEAM CLAMPS. 2. USE TOGGLE BOLTS OR HOLLOW WALL FASTENERS IN HOLLOW MASONRY, PLASTER, OR GYPSUM BOARD PARTlTlONS AND WALLS; EXPANSION ANCHORS OR PRESET INSERTS IN SOLID MASONRY WALLS; SELF-DRILLING ANCHORS OR EXPANSION ANCHOR ON CONCRETE SURFACES; SHEET METAL SCREWS IN SHEET METAL STUDS; AND WOOD SCREWS IN WOOD CONSTRUCTION. 3. DO NOT FASTEN SUPPORTS TO PIPING, CEILING SUPPORT WIRES, DUCTWORK, MECHANICAL EQUIPMENT, OR CONDUIT. 4. DO NOT USE POWER-ACTIUATED ANCHORS. 5. DO NOT DRILL STRUCTURAL STEEL MEMBERS. 6. FABRICATE SUPPORTS FROM STRUCTURAL STEEL OR STEEL CHANNEL B. IDENTIFY ELECTRICAL DISTRIBllTION AND CONTROL EQUIPMENT, AND LDADS SERVED, TO MEET REGULATORY REQUIREMENTS AND AS SCHEDULED. 1. DEGREASE AND CLEAN SURFACES TO RECEIVE NAMEPLATES AND TAPE LABELS. 2. SECURE NAMEPLATES TO EQUIPMENT FRONTS USING SCREWS, RIVETS, OR ADHESIVE, WITH EDGES PARALLEL TO EQUIPMENT LINES. SECURE NAMEPLATE TO INSIDE FACE OF RECESSED PANELBDARD DOORS IN FINISHED LOCATIONS. 3. USE NAMEPLATES WITH 1 /B INCH LETTERING TO IDENTIFY INDMDUAL SWITCHES AND CIRCUIT BREAKERS, RECEPTACLE CIRCUITS, AND LOADS SERVED. 4. USE NAMEPLATES WITH 1 / 4 INCH TO IDENTIFY DISTRIBllTION AND CONTROL EQUIPMENT. C. INSTALL WIRE MARKERS ON EACH CONDUCTOR IN PANELBOARD GUTTERS, PULL BOXES, Ol11l.ET AND JUNCTION BOXES, AND AT LOAD CONNECTIONS. 1. USE BRANCH CIRCUIT OR FEEDER NUMBER TO IDENTIFY POWER AND LIGHTING CIRCUITS. 2. USE CONTROL WIRE NUMBER AS INDICATED ON FROM FOUNDATION WALL: PLASTIC CONDUIT. PROVIDE EQUIPMENT MANUFACTIURER'S SHOP DRAWINGS TO IDENTIFY CONTROL WIRING. SECTION 260550 WIRING METHODS PART 1 GENERAL 1. 1 REGULATORY REQUIREMENTS A. CONFORM TO REQUIREMENTS OF NFPA 70. B. FURNISH PRODUCTS LISTED BY UL OR OTHER TESTING FIRM ACCEPTABLE TO AUTHORITY HAVING JURISDICTION. PART 2 PRODUCTS 2.1 PRODUCT REQUIREMENTS A. USE ONLY SPECIFIED RACEWAY IN THE FOLLOWING LOCATIONS UNLESS DIRECTED OTHERWISE ON DRAWINGS: 1. INSTALLATIONS IN OR UNDER CONCRETE SLAB, OR UNDERGROUND WITHIN 5 FEET FROM FOUNDATION WALL: PVC SCHEDULE 40 CONDUIT. 2. IN SLAB ABOit.. GRADE: PLASTIC CONDUIT. 3. EXPOSED OUTDOOR LOCATIONS: RIGID STEEL CONDUIT OR ELECTRICAL METALLIC TlUBING. USE THREADED OR RAINTIGHT FITTlNGS. 4. WET INTERIOR LOCATIONS; RIGID STEEL CONDUIT OR ELECTRICAL METALLIC TlUBING. USE THREADED OR RAINTIGHT FITTlNGS FOR METAL CONDUIT. 5. DRY INTERIOR LOCATIONS: RIGID STEEL CONDUIT OR ELECTRICAL METALLIC TlUBING. B. USE WIRE AND CABLE IN LOCATIONS AS FOLLOWS: 1. ALL POWER WIRES AND CABLES SHALL BE IN RACEWAY C. USE NO WIRE SMALLER THAN 12 AWG FOR POWER AND LIGHTING CIRCUITS, AND NO SMALLER THAN 14 AWG FOR CONTROL WIRING. USE 10 AWG CONDUCTOR FOR 20 AMPERE, 120 VOLT BRANCH CIRCUIT HOME RUNS LONGER THAN 75 FEET; AND FOR 30 AMPERE. 2.2 CONDUIT AND FITTlNGS A. CONDUIT: 1. METAL CONDUIT AND TlUBING: GALVANIZED STEEL 2. FLEXIBLE CONDUIT: STEEL 3. LIQUID TIGHT FLEXIBLE CONDUIT: FLEXIBLE CONDUIT WITH PVC JACKET. 4. PLASTIC CONDUIT AND TlUBING: NEMA TC 2, PVC. USE SCHEDULE 40 CONDUIT. B. CONDUIT FITTlNGS: 1. METAL FITTlNGS AND CONDUIT BODIES: NEMA FB 1. 2. PLASTIC FITTlNGS AND CONDUIT BODIES: NEMA TC 3. 3. EMT FITTlNGS: STEEL COMPRESSION TYPE FOR WET LOCATION. STEEL SET SCREW FOR DRY LOCATION. 4. PROVIDE INSULATED CONNECTOR AT TERMINATlONS AND TRANSmONS TO FLEX CONDUIT. 2.3 ACCESS PANELS A. PROVIDE CEILING ACCESS PANELS FOR EQUIPMENT, DEVICES, BOXES AND OTHER LIKE ITEMS REQUIRING ADJUSTMENT, MAINTENANCE OR ACCESSIBILITY IF THEY ARE NOT LOCATED OVER LAY-IN TYPE CEILING OR ARE NOT OTHERWISE ACCESSIBLE, OBTAIN APPROVAL FROM ARCHITECT FOR TYPE AND LOCATION OF ACCESS PANELS. 2.4 ELECTRICAL BOXES A. BOXES: 1. SHEET METAL: NEMA OS 1, GALVANIZED STEEL 2. CAST METAL: CAST FERALLOY, DEEP TYPE, GASKETED COVER, THREADED HUBS. 2.5 BUILDING WIRE AND CABLE A. FEEDERS AND BRANCH CIRCUITS LARGER THAN 6 AWG: COPPER STRANDED CONDUCTOR, 600 VOLT INSULATION, THHN/THWN AND XHHW. B. FEEDERS AND BRANCH CIRCUITS 6 AWG AND SMALLER: COPPER CONDUCTOR, 600 VOLT INSULATION, THHN/THWN, XHHW 6 AND 8 AWG, STRANDED CONDUCTOR; SMALLER THAN 8 AWG, SOLID CONDUCTOR. C. CONTROL CIRCUITS: COPPER, STRANDED CONDUCTOR, 600 VOLT INSULATION, THW. 2.6 REMOTE CONTROL AND SIGNAL CABLE A. CONTROL CABLE FOR CLASS 1 REMOTE CONTROL AND SIGNAL CIRCUITS: COPPER CONDUCTOR, 600 VOLT INSULATION, RATED 60 DEGREE C, INDMDUAL CONDUCTORS TWISTED TOGETHER, SHIELDED, AND COVERED WITH PVC JACKET. (PLENUM RATED) B. CONTROL CABLE FOR CLASS 2 OR CLASS 3 REMOTE CONTROL AND SIGNAL CIRCUITS: COPPER CONDUCTOR, 300 VOLT INSULATION, RATED 60 DEGREE C, INDMDUAL CONDUCTORS TWISTED TOGETHER, SHIELDED, AND COVERED WITH PVC JACKET; UL LISTED. (PLENUM RATED) PART 3 EXECllTIDN 3.1 EXAMINATION AND PREPARATION A. VERIFY THAT INTERIOR OF BUILDING IS PHYSICALLY PROTECTED FROM WEATHER. B. VERIFY THAT MECHANICAL WORK THAT IS LIKELY TO DAMAGE CONDUCTORS HAS BEEN COMPLETED. C. COMPLETELY AND THOROUGHLY SWAB RACEWAY SYSTEM BEFORE INSTALLING CONDUCTORS. D. ELECTRICAL BOXES ARE SHOWN ON DRAWINGS IN APPROXIMATE LOCATIONS UNLESS DIMENSIONED. 1. OBTAIN VERIFICATION FROM ENGINEER OF JUNCTION BOX LOCATIONS, AND LOCATIONS OF OUTLETS IN OFFICES AND WORK AREAS, PRIOR TO ROUGH-IN. 2. IT SHALL BE UNDERSTOOD THAT ANY OUTLET MAY BE RELOCATED A DISTANCE NOT EXCEEDING 5FT FROM THE LOCATION SHOWN ON THE DRAWINGS PRIOR TO OR DURING ROUGH-IN, IF SO DIRECTED BY THE ARCHITECT-ENGINEER WITHOUT ADDmONAL COST TO THE OWNER. 3. LOCAL SWITCHES WHICH ARE SHOWN NEAR DOORS SHALL BE LOCATED AT THE STRIKE SIDE OF THE DOOR AS FINALLY HUNG, REGARDLESS OF SWING ON THE DRAWINGS. 3.2 INSTALLATION A. PERFORM WORK ACCORDING TO NECA STANDARD OF INSTALLATION. B. ARRANGE CONDUIT TO MAINTAIN HEADROOM AND TO PRESENT NEAT APPEARANCE. 1. ROUTE EXPOSED RACEWAY PARALLEL AND PERPENDICULAR TO WALLS AND ADJACENT PIPING. 2. MAINTAIN MINIMUM 6-INCH CLEARANCE TO PIPING AND 12" CLEARANCE TO HEAT SURFACES SUCH AS FLUES, STEAM PIPES, AND HEATING APPLIANCES. 3. MAINTAIN REQUIRED FIRE, ACOUSTIC, AND VAPOR BARRIER RATING WHEN PENETRATING WALLS, FLOORS, AND CEILINGS. 4. ROUTE CONDUIT THROUGH ROOF OPENINGS FOR PIPING AND DUCTWORK WHERE POSSIBLE; OTHERWISE, ROUTE THROUGH ROOF JACK WITH PITCH POCKET. 5. GROUP IN PARALLEL RUNS WHERE PRACTICAL USE RACK CONSTRUCTED OF STEEL CHANNEL MAINTAIN SPACING BETWEEN RACEWAYS OR DERATE CIRCUIT AMPACmES TO NFPA 70 REQUIREMENTS. 6. USE CONDUIT HANGERS AND CLAMPS; DO NOT FASTEN WITH WIRE OR PERFORATED PIPE STRAPS. 7. USE CONDUIT BODIES TO MAKE SHARP CHANGES IN DIRECTION. 8. TERMINATE CONDUIT STUBS WITH INSULATED BUSHINGS. 9. USE SUITABLE CAPS TO PROTECT INSTALLED RACEWAY AGAINST ENTRANCE OF DIRT AND MOISTURE. 10. PROVIDE NO. 12 AWG INSULATED CONDUCTOR OR SUITABLE PULL STRING IN EMPTY RACEWAYS, EXCEPT SLEEVES AND NIPPLES. 11. INSTALL EXPANSION JOINTS WHERE RACEWAY CROSSES BUILDING EXPANSION OR SEISMIC JOINTS. 12. INSTALL PLASTIC CONDUIT AND TlUBING ACCORDING TO MANUFACTIURER'S INSTRUCTIONS. 13. USE STEEL COMPRESSION TYPE FITTlNGS WITH EMT CONDUITS. C. INSTALL ELECTRICAL BOXES AS SHOWN ON THE DRAWINGS, AND AS REQUIRED FOR SPLICES, TAPS, WIRE PULLING, EQUIPMENT CONNECTIONS AND REGULATORY REQUIREMENTS. 1. USE CAST Ol11l.ET BOX IN EXTERIOR LOCATIONS EXPOSED TO WEATHER AND WET LOCATIONS. 2. USE HINGED COVER ENCLOSURE FOR INTERIOR PULL AND JUNCTION BOX LARGER THAN 12 INCHES IN ANY DIMENSION. 3. LOCATE AND INSTALL ELECTRICAL BOXES TO ALLOW ACCESS. PROVIDE ACCESS PANELS IF REQUIRED. 4. LOCATE AND INSTALL ELECTRICAL BOXES TO MAINTAIN HEADROOM AND TO PRESENT NEAT MECHANICAL APPEARANCE. 5. INSTALL PULL BOXES AND JUNCTION BOXES ABOVE ACCESSIBLE CEILINGS OR IN UNFINISHED AREAS. 6. PROVIDE KNOCKOUT CLOSURES FOR UNUSED OPENINGS. 7. ALIGN WALL-MOUNTED Ol11l.ET BOXES FOR SWITCHES, THERMOSTATS, AND SIMILAR DEVICES. 8. COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF OUTLETS ABOVE COUNTERS AND BACKSPLASHES. 9. USE RECESSED OUTLET BOXES IN FINISHED AREAS AND WHERE INDICATED. 10, SECURE BOXES TO INTERIOR WALL AND PARTlTlON STUOS, ACCURATELY POSmONING TO ALLOW FOR SURFACE FINISH THICKNESS. 11. USE STAMPED STEEL STUD BRIDGES FOR FLUSH OUTLETS IN HOLLOW STUD WALL, AND ADJUSTABLE STEEL CHANNEL FASTENERS FOR FLUSH CEILING Ol11l.ET BOXES. 12. LOCATE BOXES IN MASONRY WALLS TO REQUIRE CUTTING CORNER ONLY. COORDINATE MASONRY CUTTING TO ACHIEVE NEAT OPENINGS FOR BOXES. 13. DO NOT INSTALL BOXES BACK-TO-BACK IN WALLS; PROVIDE 6 INCHES SEPARATION, MINIMUM; EXCEPT PROVIDE 24 INCHES SEPARATION, MINIMUM IN ACOUSTIC-RATED WALLS. 14. DO NOT DAMAGE INSULATION. D. INSTALL CABLE AND WIRE ACCORDING TO MANUFACTIURER'S INSTRUCTIONS 1. NEATLY TlRAIN AND SECURE WIRING INSIDE BOXES, EQUIPMENT, AND PANELBOARDS. 2. USE WIRE PULLING WBRICANT FOR PULLING + AWG AND LARGER WIRES. 3. SUPPORT CABLES ABOVE ACCESSIBLE CEILINGS TON KEEP THEM FROM RESTING ON CEILING TILES. 4. MAKE SPLICES, TAPS, AND TERMINATIONS TO CARRY FULL AMPACllY OF CONDUCTORS WITHOUT PERCEPTIBLE TEMPERATlURE RISE. 5. TERMINATE SPARE CONDUCTORS WITH ELECTRICAL TAPE. E. INSTALL WIRING DEVICES ACCORDING TO MANUFACTIURER'S INSTRUCTIONS. F. INSTALL WALL PLATES FLUSH AND LEVEL 1. INSTALL PLATES ON SWITCH, RECEPTACLE, AND BLANK OUTLETS IN FINISHED AREAS, USING JUMBO SIZE PLATES FOR OUTLETS INSTALLED IN MASONRY WALLS. 2. INSTALL GALVANIZED STEEL PLATES ON Ol11l.ET BOXES AND JUNCTION BOXES IN UNFINISHED AREAS, ABOVE ACCESSIBLE CEILINGS, AND ON SURFACE-MOUNTED OUTLETS. G. INSTALL SERVICE FITTlNGS ACCORDING TO MANUFACTIURER'S INSTRUCTIONS. H. BEFORE INSTALLING RACEWAYS AND PULLING WIRE TO ANY MECHANICAL EQUIPMENT OR PWMBING EQUIPMENT, VERIFY ELECTRICAL CHARACTERISTICS WITH FINAL SUBMITTAL ON EQUIPMENT TO ASSURE PROPER NUMBER AND AWG OF CONDUCTORS. I. UNDERGROUND CABLE AND CONDUIT INSTALLATION SHALL CONFORM TO ANSI C2 AND NEC EXCEPT AS OTHERWISE INDICATED. THE CONTRACTOR SHALL PROMPTLY REPAIR ANY UTILITY LINES OR SYSTEM DAMAGED BY HIS OPERATION. THE TOP OF UNDERGROUND CONDUIT SHALL NOT BE LESS THAN 24 INCHES BELOW GRADE. THE BOTTOM OF CONDUITS TRENCH SHALL BE GRADED SMOOTH, WHERE ROCK AND SHARP EDGED MATERIAL ARE ENCOUNTERED, THE BOTTOM SHALL BE EXCAVATED FOR ADDmONAL 3 INCHES, FILLED AND TAMPED LEVEL TO THE ORIGINAL BOTTOM WITH SAND OR EARTH FREE FROM ROCKS AND SHARP MATERIALS. PROVIDE MAGNETIC YELLOW WARNING TAPE ABOVE THE ENTIRE LENGTH OF UNDERGROUND CONDUITS TAPE SHALL BE BURIED 12" BELOW GRADE. J. SURFACES DISTURBED DURING THE INSTALLATION OF UNDERGROUND CONDUITS SHALL BE RESTORED TO THEIR ORIGINAL CONDmONS. PROVIDE SOD OF QUALllY EQUAL TO THAT REMOVED, PATCH PAVEMENT, SIDEWALK CURB, ETC. EXCAVATED MATERIAL NOT REQUIRED OR SUITABLE FOR BACKFILL SHALL BE REMOVED FROM PROJECT SITE. REMOVE WATER FROM EXCAVATION BY PUMPING OR OTHER APPROVED METHOD. BACKFILL SHALL BE FREE FROM LARGE CLOOS OF EARTH OR STONES OVER 1 INCH IN SIZE. SECTION 262700 SERVICE AND DISTRIBllTION PART 1 GENERAL 1.1 SUBMITTAI..S ONLY. SHOP DRAWINGS: FOR REVIEW; INDICATE CONSTRUCTION DETAILS FOR THE FOLLOWING: 1. PANELBOAROS. ONLZ. PRODUCT DATA: FOR REVIEW; PROVIDE RATINGS AND COMPONENT DETAILS FOR THE FOLLOWING: 1. ENCLOSED SWITCHES. 2. FUSES. 3. CIRCUIT BREAKERS. C. TEST REPORTS: FOR INFORMATION. D. OPERATING AND MAINTENANCE INSTRUCTIONS: FOR PROJECT CLOSEOUT; INCLUDE THE FOLLOWING: 1. PANELBOARD: SUBMIT NEMA PB 2.1 1.2 REGULATORY REQUIREMENTS A CONFORM TO REQUIREMENTS OF NFPA 70. B. FURNISH PRODUCTS LISTED BY UL OR OTHER TESTING FIRM ACCEPTABLE TO AUTHORllY HAVING JURISDICTION. C. CONFORM TO REQUIREMENTS OF llTIUTY COMPANY. PART 2 PRODUCTS 2.1 ENCLOSED SWITCHES A. MANUFACTIURERS: 1. SQUARE D 2. EATON-CUTLER HAMMER 3. GE B. ENCLOSED SWITCH ASSEMBLIES: NEMA KS 1; TYPE HD. 1. FUSE CUPS: DESIGNED TO ACCOMMODATE CLASS R OR J FUSES C. ENCLOSURES: TYPE 1 FOR INTERIOR LOCATIONS, TYPE 3R FOR EXTERIOR LOCATIONS. 2.2 FUSES A. MANUFACTIURERS: 1. FERRAZ-SHAWMUT 2. BUSSMAN B. FUSES 600 AMPERES AND LESS: CURRENT LIMmNG, ONE-TIME FUSE, 250 VOLT, UL CLASS RK 1, RK 5 OR J. 2.3 PANELBOARDS A. MANUFACTIURERS: 1. GE 2. SIEMENS 3. EATON-CUTLER HAMMER B. PANELBOAROS: NEMA PB 1 ; CIRCUIT BREAKER TYPE. 1. ENCLOSURE: TYPE 1 2. PROVIDE SURFACE OR FLUSH CABINET FRONT WITH SCREW COVER. HINGED DOOR AND DOOR-IN-DOOR CONSTRUCTION. 3. BUS: COPPER. 4. GROUND BUS: COPPER. 5. VOLTAGE: AS SHOWN 6. MINIMUM INTEGRATED EQUIPMENT RATING: AS INDICATED ON DRAWINGS. 7. BREAKERS SHALL BE BOLT-ON TYPE. 8, MINIMUM INTEGRATED EQUIPMENT RATING; AS INDICATED ON DRAWINGS. PART 3 EXECllTION 3.1 EXAMINATION AND PREPARATION A MAKE ARRANGEMENTS WITH llTIUTY COMPANY TO OBTAIN PERMANENT ELECTRIC SERVICE TO THE PROJECT. B. PROVIDE CONCRETE PAD FOR llTIUTY TRANSFORMER. PROVIDE PAD DIMENSIONS AND DETAILS TO llTIUTY REQUIREMENTS. 3.2 INSTALLATION A. INSTALL EQUIPMENT IN ACCODRANCE WITH MANUFACTIURER'S INSTRUCTIONS. B. INSTALL PROPER FUSES IN EACH FUSED SWITCH. C. INSTALL PANELBOAROS AND LOAD CENTERS TO NEMA PB 1. 1. 3.3 CLEANING A. CLEAN EQUIPMENT FINISHES TO REMOVE PAINT AND CONCRETE SPLATTERS. SECTION 265100 INTERIOR WMINAIRES PART 1 GENERAL 1.1 SECTION INCLUDES A. INTERIOR/EXTERIOR WMINAIRES AND ACCESSORIES. B. DRIVERS C. LED LAMPS D. WMINAIRE ACCESSORIES. 1.2 REFERENCES A. ANSI C78.379 -ELECTRIC LAMPS -INCANDESCENT AND HIGH-INTENSllY DISCHARGE REFLECTOR LAMPS -CLASSIFICATION OF BEAM PATTERNS. B. MANUFACTIURER'S INSTRUCTIONS: AND LIMITATIONS OF USE STIPULATED BY PRODUCT TESTING AGENCY SPECIFIED UNDER REGULATORY REQUIREMENTS. C. MANUFACTIURER'S INSTRUCTIONS: STORAGE, HANDLING, PROTECTION, EXAMINATION, PREPARATION, AND INSTALLATION OF PRODUCT. 1.3 QUAIJFICATIONS A. MANUFACTIURER: COMPANY SPECIALIZING IN PRODUCTS SPECIFIED IN THIS SECTION WITH MINIMUM THREE YEARS DOCUMENTED EXPERIENCE. 1.4 REGULATORY REQUIREMENTS A. CONFORM TO REQUIREMENTS OF ANSI/NFPA 70 B. CONFORM TO REQUIREMENTS OF NFPA 101. C. FURNISH PRODUCTS LISTED AND CLASSIFIED BY UL AS SUITABLE FOR PURPOSE SPECIFIED AND SHOWN. D. LUMINAIRES SHALL BE UL 1598 LISTED AND DLC LISTED. PART 2 PRODUCTS 2.1 WMINAIRES A. FURNISH PRODUCTS AS SPECIFIED IN SCHEDULE ON DRAWINGS. B. SUBSTlTlUTlONS: MAY INCUR ADDmONAL FEES TO REVIEW AND/OR CAN BE SUBSTITUTED AT CONTRACTOR'S RISK/RESPONSIBILITY. C. INSTALL DRIVERS, LAMPS, AND SPECIFIED ACCESSORIES AT FACTORY. PART 3 EXECllTION 3.1 EXAMINATION A. EXAMINE SUBSTRATE AND SUPPORTING GRIDS FOR LUMINAIRES. B. EXAMINE EACH LUMINAIRE TO DETERMINE SUITABILITY FOR LAMPS SPECIFIED (EX: T-LED LAMPS). 3.2 INSTALLATION A. INSTALL IN ACCORDANCE WITH MANUFACTIURERS INSTRUCTIONS. B. INSTALL SUSPENDED LUMINAIRES USING PENDANTS SUPPORTED FROM SWIVEL HANGERS. PROVIDE PENDANT LENGTH REQUIRED TO SUSPEND WMINAIRE AT INDICATED HEIGHT. C. INSTALL SURFACE MOUNTED WMINAIRES AND EXIT SIGNS PWMB AND ADJUST TO ALIGN WITH BUILDING LINES AND WITH EACH OTHER. SECURE TO PROHIBIT MOVEMENT. D. INSTALL WALL MOUNTED WMINARIES AS SCHEDULED. E. INSTALL ACCESSORIES FURNISHED WITH EACH LUMINAIRE. F. EACH RECESSED FIXI\JRE SHALL HAVE TWO STEEL WIRE SUPPORTS FASTENED TO THE STRUCTURE ABOit.. AT DIAGONALLY OPPOSITE CORNERS OF THE FIXI\JRE. G. SEE ARCHITECTURAL SHEETS FOR MOUNTING HEIGHTS AND RCP. H. EXIT SIGNS SHALL BE MOUNTED TO CONFORM TO NFPA 101 REQUIREMENTS. 3.3 FIELD QUALllY CONTROL A. OPERATE EACH WMINAIRE AFTER INSTALLATION. INSPECT FOR PROPER CONNECTION AND OPERATION. 3.4 ADJUSTING A. AIM AND ADJUST LUMINAIRES AS DIRECTED AND TO MEET PROJECT/DESIGN OBJECTIVES. B. ADJUST EXIT SIGN DIRECTIONAL ARROWS AS INDICATED. 3.5 CLEANING A. CLEAN LIGHTING FIXI\JRES AFTER COMPLETION OF INSTALLATION. B. TOUCH UP ANY VISIBLE DAMAGE. [ RECEIVED l GENERAL NOTES; 1. WIRING SHOWN IS DIAGRAMMATIC 2. NO FIRE PROTECTION DESIGN INCLUDED; PROVIDED BY OTHERS. 3. NO DATA/CATV/SECURITY DESIGN INCLUDED; PROVIDED BY OTHERS. ABBREVJATIONS: AC ABOVE COUNTER WP We.A THER PROOF TTB TELEPHONE/TELECOMM BACKBOARD LEGEND 0 4f' 20A, 120V, 3W DUPLEX RECEPTACLE 20A, 120V, 3W QUAD RECEPTACLE DUPLEX RECEPTACLE WITH GROUND FAULT INTERRUPTER, 20 AMP, 120 VOLT, 3W. DUPLEX ARC FAULT CIRCUIT INTERRUPTER RECEPTACLE, 20 AMP, 120 VOLT, 3W. PROTECTION CAN BE PROVIDED BY THE RECEPTACLE, OR A ARC FAULT INTERRUPTER BREAKER AT THE PANEL 20A, 120V, 3W DUPLEX RECEPTACLE, ASHRAE COMPLIANT / z (I) ... 0 ... CD +' C z + CD ... ::, +' = 0 CD +' N .c 0 ... al " ...... I"')"-oooC! ;J;.NNC: N ~ C: ~"'"':ii t~~ 0 L •-.., &V C <n ..! o·-...lt'. ~ 0, L C: CO a."' "" N <> ~ .Q, ---,.,.,,. \\\\\11111111,, \,,, "' T ,,,, / ,,,, ., I'"" . 9.,, ,.1,,, DATA PORT. DEFAULT IS 2 DATA DROPS (2D), CATS. INSTALL j~~~:i,c'i'iis;~r,,,;✓;;:; PATHWAY (CONDUIT/BASKET TRAY/J-HOOKS) BACK TO /;2~.·· \~":. \ BACKBOARD, CONDUIT MINIMUM 1 •. EACH DROP CONSISTS OF ( ~ * f No. 70825 \ * ~ 1 (1 )CATS WITH TERMINATION. = : * : = :: : : = I SPECIAL RECEPTACLE, NEMA STYLE. NEMA STYLE NUMBER SHALL\\~\. STATE OF ,,:'/1;.fj BE WRITTEN NEXT TO SYMBOL ON THE PLANS. 1,,~f t9.!!~.~1.~~1 J-BOX. PROVIDE SIZE TO MEET CONDUCTOR FILL. PHOTOCELL. 120V, 2000W TUNGSTEN, 1800VA BALLAST, 600VA LED TOGGLE SWITCH -SINGLE POLE -QUIET TYPE 20 AMP, 120/277V. $o SWITCH, LINE VOLTAGE, 0-10V DIMMING, 20 AMP, 120/277V SENSOR SWITCH SPODMRD OR EQUAL $D SWITCH, LINE VOLTAGE, OCCUPANCY SENSOR, 0-10V DIMMING oc SENSOR SWITCH WSX PDT D OR EQUAL. $, TOGGLE SWITCH -THREE WAY -QUIET TYPE 20 AMP, 120/277V. $~V LOW VOLTAGE, 3-WAY, LIGHT SWITCH. SENSOR SWITCH SPODM SA 3X OR EQUAL $re LOW VOLTAGE, DIMMER, 3-WAY, LIGHT SWITCH. SENSOR SWITCH SPODM SA 3X D OR EQUAL. $~v LOW VOLTAGE, DIMMER LIGHT SWITCH. SENSOR SWITCH SPODM SA D OR EQUAL. $2P SWITCH, LINE VOLTAGE, OCCUPANCY SENSOR, 2P (LIGHT&FAN) oc SENSOR SWITCH WSX PDT 2P OR EQUAL. $0C SWITCH, LINE VOLTAGE, OCCUPANCY SENSOR SENSOR SWITCH WSX PDT OR EQUAL. ~T ASTRAL TIMER WALLSWITCH. INTERMATIC El600-COLOR OR EQUAL. OCCUPANCY SENSOR, CEILING MOUNT, LINE VOLTAGE (120/277V). SENSOR SWITCH CMR-PDT-9 OR EQUAL. OCCUPANCY SENSOR, CEILING MOUNT, LOW VOLTAGE. SENSOR SWITCH CM-PDT-9 OR EQUAL. POWc.R PACK. SENSOR SWITCH PP-20 OR EQUAL. OCCUPANCY SENSOR, CEILING MOUNT, LOW VOLTAGE. SENSOR SWITCH CM-PDT-6 (HIGH BAY) OR EQUAL. 240/4BOV, 100-600A PANEL RECESSED PANEL 30A-6DA0 DISCONNECT. FRAME/FUSE/POLES/NEMA RATING. 100A c:::::JJ ~ () ENCLOSED CIRCUIT BREAKER. NEMA 3R FOR OUTDOOR BACKBOARD. 4'x8', FIRE RETARDANT PLYWOOD (NO PAINTING). WITH THE FOLLOWING INSTALLED; -GROUND BAR (PER SPEC. 2.16.3) CONNECTED TO SERVICE ENTRANCE GROUND BAR WITH #6 BONDING JUMPER -DEDICATED QUAD RECEPTACLE (SEE PANEL SCHEDULE). CATV OUTLET. COORDINATE REQUIREMENTS WITH PROVIDER. MINIMUM SINGLE GANG BOX WITH RG6 CONNECTOR WITH WALL PLATE AND RG6 CABLE HOME RUN TO BACKBOARD. PROVIDE (1)3-FOOT LOOP OF CABLE AT BACKBOARD. MOTOR. CONDUIT UP /DOWN 111' _,-.,:'ONA\..'-":;,,, ,,,, 11 ,,,, -!!.!_1 ft I J 1111 \ \~ I w I-<( _J 0 u 0 :r: uz 0 ::::) (/) Zz W<( ~ (l_ <Cx :::;;:w CX) 0 N w ~ I-N <( 0 ON 1-w (/) .. ~ Wu ::::) w (/) :r: (/) u (/) w l-o z 0 z w 0 w 0 _J z " -(/) 3: u <( w O'.'. (l_ 0 (/) w n n N N n o_J >LL _J -m:r: u U<C -w 1-m z <Cu _J_ I-I-<CZ <( LO _J Of-f',. <( POWER INTEGRATION, LLCELECTRICAL ENGINEERING CONSULTANTCA#31167PH: 904.307.9077EMAIL: sukutb@comcast.netSukumaran T BaskaranDigitally signed by Sukumaran T Baskaran Date: 2022.04.08 18:37:51 -04'00'I NOTE 2 ' I I I I I I PANEL P32 EXISTING\: \ I / I I L ____ _ / EXISTING UNIT 32 METER AND SERVICE ENTRANCE BREAKER I / r-' ' ' ' ' \ : I IINOTE 111 0 IINOTE 111 I / iNOTE 11 UNIT 32 ' \ I _____ J ELECTRICAL -DEMOLITION GENERAL NOTES: A. DEMOLISH ALL CIRCUITS BACK TO SOURCE. B. COORDINATE WITH OWNER FOR ANY ITEMS TO BE SALVAGED. C. DASHED ITEMS REPRESENT ITEMS WITHIN SCOPE OF DEMOLITION. KEYED NOTES: 1. COORDINATE DEMOLITION EFFORT IN THIS SPACE WITH NEW WORK. 2. DEMOLISH EXISTING SERVICE ENTRANCE FOR UNIT 32. THIS INCLUDES FROM WEATHERHEAD, METER CAN/BREAKER, CONDUIT/CONDUCTOR, UP TO AND INCLUDING EXISTING PANEL P32. SEE SHEET ES FOR NEW SERVICE ENTRANCE. I / z rn .... 0 .... (D -C z + (D .... ::, -= 0 (D -N .c 0 .... al I' VI"')"-oooC! '<tNN C l::11:::N .-C -"'"'~ ~~~ 0 L •-+-' •V C (I)~ 0 ·-...l£ ~ 0, LC CO Q. "' -"' N <> ~ .Q, -/1,,, ,,\,, --!!_I I/ I J 1111 \ \~ ~ n n N N I n w o_J I->LL <( _J • _J m:r: 0 u u U<C 0 -w :r: I-IIl uz z 0 <Cu :::) (/) _J_ 1-1-Zz <CZ W<( <( ~ (l_ I[) _J <Cx 01-~w I'--<( CX) 0 N ~ w ~ I-N <( 0 ON I-w (/) .. ~ Wu :::) w (/) :r: (/) u z 0 I-_J 0 ~ w 0 I z .. <( ('.) _J z (l_ -O::'. ~o <( 0 O::'. _J 0 LL N w POWER INTEGRATION, LLCELECTRICAL ENGINEERING CONSULTANTCA#31167PH: 904.307.9077EMAIL: sukutb@comcast.netSukumaran T BaskaranDigitally signed by Sukumaran T Baskaran Date: 2022.04.08 18:38:44 -04'00'I NEW PANEL P32 ,------\ 2P 0C --r -, I '-' I I RESTROOM 108 Im \ HALL I 109 I / /. l;3 I D I J WP DISH 111 iCKT#1II L-R1 TEMPERING I / I L ____ _ RESTR OM / I STO AGE 06 110 __ J '-\ I -----'.l Ill! I~ □ PATIO 114 NOTE 3 S1 0 ~ □ MELANGER ROOM 113 DINING 102 FRONTCOUN 101 S1 D D D '-\ I _____ J I / Liohtin Schedule SyMbol Label Ma.nufo.cturer Catalog NuMber □ EXISTING EXISTING EXl 0 EXISTING EXISTING EX2 I STARTEK NOV2D-16-L-SD-35K-Pw'-SM-U Ll I STARTEK NOV2D-9-L-SD-35K-Pw'-SM-U L2 I STARTEK NOV2D-3-L-SD-35K-Pw'-SM-U L3 0 BOVER TANET S/43 -26101210158U Pl I MARK ARCHITECTURAL SL4L LOP BFT FLP FL BOCRI 35K BOOLMF MIN! 120 ZT Pw'S Rl I MARK ARCHITECTURAL SL4L LOP 12FT FLP FL BOCRI 35K R2 0 LOUIS POULSEN RIPLS 12.2IN 35K Sl ~ LITHONIA ELCC□MB□2Rw'BB EX <bd> LITHONIA EU2LM12 EM ELECTRICAL -LIGHTING GENERAL NOTES: A. ALL EMERGENCY FIXTURES REQUIRE AN UNSWITCHED HOT CONNECTION; CONNECT TO CLOSEST CIRCUIT WITHIN THE SAME SPACE. B. ALL CIRCUITS TO PANEL P32 U.N.O. C. NO BACK TO BACK J-BOXES. KEYED NOTES: 1. PROVIDE PHENOLIC NAMEPLATE ABOVE SWITCH BANK DESCRIBING WHAT SWITCH CONTROLS WHAT. 2. ROOF MOUNTED, WEATHER PROOF, J-BOX FOR SIGN. COORDINATE WITH OWNER FOR LOCATION. PHOTOCELL CONTROLLED. 3. RUN CIRCUIT THROUGH PHOTOCELL; ALL OUTDOOR LIGHTING IN THIS SPACE SHALL BE PHOTOCELL CONTROLLED. 15W/J-BOX IS ALLOWANCE FOR OWNER SUPPLIED LIGHTING. COORDINATE MOUNTING WITH PATIO COVERING. IF CONDUIT RUN EXPOSED; PAINT TO MATCH. NO EXPOSED PVC CONDUIT. ELECTRICAL LIGHTING CONTROL NOTES: -10000140833 ALL SPACES EXCEPT FOR RESTROOM: TIMER CLOCK ON/TIMER CLOCK OFF (SEE THIS SHEET) HALLWAYS, RESTROOMS: AUTO ON/AUTO OFF AFTER 20 MINUTES. OUTDOOR LIGHTING/SIGN: PHOTOCELL ON/PHOTOCELL OFF (DUSK TO DAWN OPERATION) PROVIDE LIGHTING CONTROL COMMISSIONING PAPERWORK PER FBC TO OWNER UPON COMPLETION. 24-HOUR, 7-DAY PROGRAMMABLE TIMER UNSWITCHED BOOLMF MIN! 120 ZT Pw'S Description EXISTING EXISTING SURFACE-MOUNTED LINEAR LUMINAIRE SURFACE-MOUNTED LINEAR LUMINAIRE SURFACE-MOUNTED LINEAR LUMINAIRE w'OVEN COTTON THREAD SCREEN PENDANT LUMINAIRE RECESSED LINEAR LUMINAIRE RECESSED LINEAR LUMINAIRE VALL SCONCE EXIT /LIGHT COMB□; REQUIRES UNSIJITCHED HOT EMERGENCY w'ALL PACK; REQUIRES UNSIJITCHED HOT CIRCUITS FROM EMERGENCY LTG PANEL 120V I I I I [i] -C TIMER SWITCH: MAXIMUMUM 2 HOUR OVERRIDE. IN TERM ATTIC El235W OR EQUAL N PAN EL 32 TiMER CONTROL DIAGRAM NOTES: 1. COORDINATE WITH OWNER FOR OPERATING HOURS AND PROGRAM TIMER ACCORDINGLY. 2. COORDINATE LOCATION OF OVERRIDE SWITCH WITH OWNER. PROVIDE MINIMUM ALLOWANCE OF 50' OF 1/2" EMT CONDUIT WITH 12/2 CONDUCTOR FOR REMOTE LOCATION OF OVERRIDE SWITCH FROM TIME CLOCK/CONT ACTOR. I 1) _i _i _i -- ------T T T I I _i T 3 2 OA/6P 40V R ATINGS: 6A LED 1 2 OA 1\JNGSlEN ELEClRICALL Y HELD CONTACTOR ASHRAE LTG I Toto.l Lo.Mp Lo.Mp w'attage I ' EX 3654 30,9971 EX 1553 25,3 LED 2058 16,8 LED 4374 33 LED 4374 33 LED 490 14,3 LED 2936 31.46 LED 2936 31.46 LED 1076 13 LED -1 LED -1 z rn .... 0 .... (D -C z + (D .... ::, -= 0 (D -N .c 0 .... al I' VI"')"-oooC! '<tNN C l::11:::N .-C -"'"'~ ~~~ 0 L •-+-' •V C (I)~ 0 ·-...l£ ~ 0, LC CO Q. "' "" N <> ~ .Q, -w I-<( _J 0 u 0 I uz 0 :::) (/) Zz W<( ~ (l_ <Cx ~w CX) 0 N ~ w ~ I-N <( 0 ON 1--w (/) .. ~ Wu :::) w (I) I (/) u (.'.) z I-I (.'.) _J I z .. <( (.'.) _J z (l_ ~ i5 <( 0 0::: _J 0 LL n w n n N N n o_J >LL _J • mI u U<C -w !z IIl <( u _J_ I-1--<CZ <( I[) _J 0 I-I'--<( / POWER INTEGRATION, LLCELECTRICAL ENGINEERING CONSULTANTCA#31167PH: 904.307.9077EMAIL: sukutb@comcast.netSukumaran T BaskaranDigitally signed by Sukumaran T Baskaran Date: 2022.04.08 18:39:47 -04'00' POWER INTEGRATION, LLCELECTRICAL ENGINEERING CONSULTANTCA#31167PH: 904.307.9077EMAIL: sukutb@comcast.netSukumaran T BaskaranDigitally signed by Sukumaran T Baskaran Date: 2022.04.08 18:41:04 -04'00'