376 10th ST RES21-0373 Manual J and S.Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-07 11:44:45Right-Suite® Universal 2021 21.0.08 RSU12269 Page 1...Lucerno Res 376 Tenth St\Lucerno Res 2598 N.rup Calc = MJ8 Front Door faces: E 376 10th St.Job:Project Summary 12/6/2021Date:First Floor AC Stewart FranklinBy: McGowan's Heating & Air Conditioning 11320 E. Phillips Parkway Dr., Jacksonville, FL 32256 Phone: 904-278-0339 Fax: 904-278-0366 Email: sfranklin@mcgowansac.com Web: www.mcgowansac.com License: CM... Project Information Mike Smiley, Ashlar Home Builders LLCFor:5295 CR 209 SOUTH, Green Cove Springs, FL 32043Phone: (904) 742-0102Email: mike@ashlar-homes.comLucerno Residence 376 10th St. Notes: Design Information Jacksonville NAS, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F34 Outside db °F99Inside db °F70 Inside db °F75Design TD °F36 Design TD °F24Daily range LRelative humidity %50Moisture difference gr/lb56 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh19749 Structure Btuh17891DuctsBtuh2486DuctsBtuh1898Central vent (28 cfm)1114 Btuh Central vent (28 cfm)Btuh750Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh23350 Use manufacturer's data yRate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh20539 Method Latent Cooling Equipment Load SizingBlower doorShielding / stories 3 (partial) / 250 Pa / 3455 cfmPressure / AVF Structure Btuh3040DuctsBtuh470Central vent (28 cfm)Btuh1078 CoolingHeating Outside air13321332Area (ft²)Equipment latent load Btuh45881331013310Volume (ft³)Air changes/hour 0.340.58 Equipment Total Load (Sen+Lat)Btuh25127Equiv. AVF (cfm)75128 Req. total capacity at 0.70 SHR ton2.4 Heating Equipment Summary Cooling Equipment Summary Make Trane Make TraneTradeTRANETradeTRANEModel4TWR6030H1Cond4TWR6030H1AHRI ref 7562380 Coil TEM6A0B30H21AHRI ref 7562380Efficiency9 HSPF Efficiency 13.0 EER, 16 SEERHeating input Sensible cooling Btuh20020Heating output Btuh @ 47°F27800 Latent cooling Btuh8580Temperature rise °F27 Total cooling Btuh28600Actual air flow cfm953 Actual air flow cfm953Air flow factor cfm/Btuh0.043 Air flow factor cfm/Btuh0.048Static pressure in H2O0.50 Static pressure in H2O0.50Space thermostat Load sensible heat ratio 0.82Capacity balance point = 30 °F Backup:Input = 9 kW, Output = 30893 Btuh, 100 AFUE Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Dec-07 11:44:45Right-Suite® Universal 2021 21.0.08 RSU12269 Page 2...Lucerno Res 376 Tenth St\Lucerno Res 2598 N.rup Calc = MJ8 Front Door faces: E 376 10th St.Job:Project Summary 12/6/2021Date:Second Floor AC Stewart FranklinBy: McGowan's Heating & Air Conditioning 11320 E. Phillips Parkway Dr., Jacksonville, FL 32256 Phone: 904-278-0339 Fax: 904-278-0366 Email: sfranklin@mcgowansac.com Web: www.mcgowansac.com License: CM... Project Information Mike Smiley, Ashlar Home Builders LLCFor:5295 CR 209 SOUTH, Green Cove Springs, FL 32043Phone: (904) 742-0102Email: mike@ashlar-homes.comLucerno Residence 376 10th St. Notes: Design Information Jacksonville NAS, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F34 Outside db °F99Inside db °F70 Inside db °F75Design TD °F36 Design TD °F24Daily range LRelative humidity %50Moisture difference gr/lb56 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh18770 Structure Btuh17330DuctsBtuh1576DuctsBtuh1056Central vent (43 cfm)1679 Btuh Central vent (43 cfm)Btuh1130Outside air Outside airHumidificationBtuh0Blower Btuh0PipingBtuh0Equipment load Btuh22025 Use manufacturer's data yRate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh21916 Method Latent Cooling Equipment Load SizingBlower doorShielding / stories 3 (partial) / 250 Pa / 3455 cfmPressure / AVF Structure Btuh4975DuctsBtuh498Central vent (43 cfm)Btuh1624 CoolingHeating Outside air12661266Area (ft²)Equipment latent load Btuh46971624816248Volume (ft³)Air changes/hour 0.400.69 Equipment Total Load (Sen+Lat)Btuh26613Equiv. AVF (cfm)110188 Req. total capacity at 0.70 SHR ton2.6 Heating Equipment Summary Cooling Equipment Summary Make Trane Make TraneTradeTRANETradeTRANEModel4TWR6030H1Cond4TWR6030H1AHRI ref 7562380 Coil TEM6A0B30H21AHRI ref 7562380Efficiency9 HSPF Efficiency 13.0 EER, 16 SEERHeating input Sensible cooling Btuh20020Heating output Btuh @ 47°F27800 Latent cooling Btuh8580Temperature rise °F27 Total cooling Btuh28600Actual air flow cfm953 Actual air flow cfm953Air flow factor cfm/Btuh0.047 Air flow factor cfm/Btuh0.052Static pressure in H2O0.50 Static pressure in H2O0.50Space thermostat Load sensible heat ratio 0.73Capacity balance point = 28 °F Backup:Input = 6 kW, Output = 20029 Btuh, 100 AFUE Job #: 376 10th St. Performed by Stewart Franklin for: Mike Smiley 5295 CR 209 SOUTH Green Cove Springs, FL 32043 Phone: (904) 742-0102 mike@ashlar-homes.com McGowan's Heating & Air Conditioning 11320 E. Phillips Parkway Dr. Jacksonville, FL 32256 Phone: 904-278-0339 Fax: 904-278-0366 www.mcgowansac.com sfranklin@mcgowansac.com Scale: 1 : 106 Page 1 Right-Suite® Universal 2021 21.0.08 RSU12269 2021-Dec-07 11:45:22 ... Tenth St\Lucerno Res 2598 N.rup N First Floor Garage Entry. Mikes Bath Kitchen Office Stair Pantry Bath1 Entry ACU O.Bath Dining F FF 10 x 6 14 x 6 Great 5 " 10 x 6 10 x 6 10 x 6 6 " 6 " 6 " 8 " 12 x 12 24 x 18 8 x 4 4 " 10 x 6 12 x 6 8 x 4 10 x 6 5 " 7 " 10 " 6 " 4 " 12 "14 " 16 " T Job #: 376 10th St. Performed by Stewart Franklin for: Mike Smiley 5295 CR 209 SOUTH Green Cove Springs, FL 32043 Phone: (904) 742-0102 mike@ashlar-homes.com McGowan's Heating & Air Conditioning 11320 E. Phillips Parkway Dr. Jacksonville, FL 32256 Phone: 904-278-0339 Fax: 904-278-0366 www.mcgowansac.com sfranklin@mcgowansac.com Scale: 1 : 106 Page 2 Right-Suite® Universal 2021 21.0.08 RSU12269 2021-Dec-07 11:45:22 ... Tenth St\Lucerno Res 2598 N.rup N Second Floor Hall 2 Bed 2 Master M Bath Closet MWC HERS Bed1 M WIC HIS Hall Laundry Stairs ACU2 Bath2 F F 10 x 6 8 x 4 10 x 6 8 x 4 Open To below 6 " 12 x 6 F 14 x 1414 x 6 14 " 8 x 4 16 x 16 10 x 6 12 x 12 10 x 6 10 x 6 10 x 6 16 x 16 12 " 9 " 8 x 4 4 " 12 x 6 7 " 5 "4 " 6 " 4 " 6 " 10 x 6 12 " 5 " 5 " 5 " 7 " 4 " 8 "10 " T 14 " 6 " 12 " 6 " 2021-Dec-07 11:44:45 Right-Suite® Universal 2021 21.0.08 RSU12269 Page 1 ...Lucerno Res 376 Tenth St\Lucerno Res 2598 N.rup Calc = MJ8 Front Door faces: E 376 10th St.Job:Manual S Compliance Report 12/6/2021Date:First Floor AC Stewart FranklinBy: McGowan's Heating & Air Conditioning 11320 E. Phillips Parkway Dr., Jacksonville, FL 32256 Phone: 904-278-0339 Fax: 904-278-0366 Email: sfranklin@mcgowansac.com Web: www.mcgowansac.com License: CM... Project Information Mike Smiley, Ashlar Home Builders LLCFor: 5295 CR 209 SOUTH, Green Cove Springs, FL 32043 Phone: (904) 742-0102 Email: mike@ashlar-homes.com Cooling Equipment Design Conditions °F76.1Entering coil DB:Btuh20539Sensible gain:°F99.1Outdoor design DB: °F63.4Entering coil WB:Btuh4588Latent gain:°F79.4Outdoor design WB: Btuh25127Total gain:°F75.0Indoor design DB: cfm953Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ASHPEquipment type: 4TWR6030H1+TEM6A0B30H21Model:TraneManufacturer: cfm953Actual airflow: % of load111Btuh22851Sensible capacity: % of load109Btuh5022Latent capacity: %82SHR:% of load111Btuh27873Total capacity: Heating Equipment Design Conditions °F68.5Entering coil DB:Btuh23350Heat loss:°F34.2Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Split ASHPEquipment type: 4TWR6030H1+TEM6A0B30H21Model:TraneManufacturer: cfm953Actual airflow: °F30Capacity balance:% of load119Btuh27800Output capacity: °F-99Economic balance:Btuh0Supplemental heat required: Elec stripBackup equipment type: Model:Manufacturer: cfm953Actual airflow: °F29Temp. rise:% of load132kW9.1Output capacity: Meets all requirements of ACCA Manual S. 2021-Dec-07 11:44:45 Right-Suite® Universal 2021 21.0.08 RSU12269 Page 2 ...Lucerno Res 376 Tenth St\Lucerno Res 2598 N.rup Calc = MJ8 Front Door faces: E 376 10th St.Job:Manual S Compliance Report 12/6/2021Date:Second Floor AC Stewart FranklinBy: McGowan's Heating & Air Conditioning 11320 E. Phillips Parkway Dr., Jacksonville, FL 32256 Phone: 904-278-0339 Fax: 904-278-0366 Email: sfranklin@mcgowansac.com Web: www.mcgowansac.com License: CM... Project Information Mike Smiley, Ashlar Home Builders LLCFor: 5295 CR 209 SOUTH, Green Cove Springs, FL 32043 Phone: (904) 742-0102 Email: mike@ashlar-homes.com Cooling Equipment Design Conditions °F76.2Entering coil DB:Btuh21916Sensible gain:°F99.1Outdoor design DB: °F63.6Entering coil WB:Btuh4697Latent gain:°F79.4Outdoor design WB: Btuh26613Total gain:°F75.0Indoor design DB: cfm953Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ASHPEquipment type: 4TWR6030H1+TEM6A0B30H21Model:TraneManufacturer: cfm953Actual airflow: % of load100Btuh21856Sensible capacity: % of load100Btuh4675Latent capacity: %82SHR:% of load100Btuh26531Total capacity: Heating Equipment Design Conditions °F68.3Entering coil DB:Btuh22025Heat loss:°F34.2Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Split ASHPEquipment type: 4TWR6030H1+TEM6A0B30H21Model:TraneManufacturer: cfm953Actual airflow: °F28Capacity balance:% of load126Btuh27800Output capacity: °F-99Economic balance:Btuh0Supplemental heat required: Elec stripBackup equipment type: Model:Manufacturer: cfm953Actual airflow: °F50Temp. rise:% of load91kW5.9Output capacity: Meets all requirements of ACCA Manual S. 2021-Dec-07 11:44:45 Right-Suite® Universal 2021 21.0.08 RSU12269 Page 1 ...Lucerno Res 376 Tenth St\Lucerno Res 2598 N.rup Calc = MJ8 Front Door faces: E 376 10th St.Job:Duct System Summary 12/6/2021Date:First Floor AC Stewart FranklinBy: McGowan's Heating & Air Conditioning 11320 E. Phillips Parkway Dr., Jacksonville, FL 32256 Phone: 904-278-0339 Fax: 904-278-0366 Email: sfranklin@mcgowansac.com Web: www.mcgowansac.com License: CM... Project Information Mike Smiley, Ashlar Home Builders LLCFor: 5295 CR 209 SOUTH, Green Cove Springs, FL 32043 Phone: (904) 742-0102 Email: mike@ashlar-homes.com CoolingHeating External static pressure in H2O0.50in H2O0.50 Pressure losses in H2O0.11in H2O0.11 Available static pressure in H2O0.39in H2O0.39 Supply / return available pressure 0.242 / 0.148 in H2O in H2O0.242 / 0.148 Lowest friction rate in/100ft0.123in/100ft0.123 Actual air flow cfm953cfm953 Total effective length (TEL)ft317 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st3140.013.0VlFx0x04.00.1585461113cBath1 st3160.035.0VlFx0x08.00.1241722265284hDining st3140.017.0VlFx0x05.00.15465791832hEntry st3145.011.2VlFx0x06.00.1551091162699hKitchen st3160.027.0VlFx0x06.00.1301091162699hKitchen-B st3150.018.5VlFx0x06.00.1441091162699hKitchen-C st4150.028.5VlFx0x07.00.136130782709cMikes Bath st4160.037.2VlFx0x04.00.1231332738hO.Bath st4155.042.0VlFx0x06.00.123871353154hOffice st4150.029.5VlFx0x05.00.135107512220cPantry Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st3 Peak AVF 658 616 0.124 615 14.0 0x0 VinlFlx st4 Peak AVF 295 337 0.123 429 12.0 0x0 VinlFlx 2021-Dec-07 11:44:45 Right-Suite® Universal 2021 21.0.08 RSU12269 Page 2 ...Lucerno Res 376 Tenth St\Lucerno Res 2598 N.rup Calc = MJ8 Front Door faces: E Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb18 0x 3010 391 120.0 0.123 716 10.0 x0 0 VlFx rt2 rb16 0x 6520 562 62.5 0.236 467 16.0 x0 0 VlFx rt2 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2 Peak AVF 953 953 0.123 683 16.0 0x0 VinlFlx 2021-Dec-07 11:44:45 Right-Suite® Universal 2021 21.0.08 RSU12269 Page 3 ...Lucerno Res 376 Tenth St\Lucerno Res 2598 N.rup Calc = MJ8 Front Door faces: E 376 10th St.Job:Duct System Summary 12/6/2021Date:Second Floor AC Stewart FranklinBy: McGowan's Heating & Air Conditioning 11320 E. Phillips Parkway Dr., Jacksonville, FL 32256 Phone: 904-278-0339 Fax: 904-278-0366 Email: sfranklin@mcgowansac.com Web: www.mcgowansac.com License: CM... Project Information Mike Smiley, Ashlar Home Builders LLCFor: 5295 CR 209 SOUTH, Green Cove Springs, FL 32043 Phone: (904) 742-0102 Email: mike@ashlar-homes.com CoolingHeating External static pressure in H2O0.50in H2O0.50 Pressure losses in H2O0.11in H2O0.11 Available static pressure in H2O0.39in H2O0.39 Supply / return available pressure 0.207 / 0.183 in H2O in H2O0.207 / 0.183 Lowest friction rate in/100ft0.112in/100ft0.112 Actual air flow cfm953cfm953 Total effective length (TEL)ft348 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk st2155.027.5VlFx0x05.00.11340651379hBath2-A st2150.031.7VlFx0x08.00.1142062515357hBed 2 st1140.025.0VlFx0x07.00.125123802368cBed1-A st2150.016.8VlFx0x04.00.12466120cCloset-A st1145.028.4VlFx0x05.00.11940681458hHERS-A st1145.018.9VlFx0x04.00.12666112cHIS-A st2150.020.4VlFx0x05.00.121941132407hLaundry st1145.021.0VlFx0x04.00.1252537789hM Bath-A st2150.024.9VlFx0x05.00.11855401064cM WIC-A st1145.027.3VlFx0x04.00.1201624520hMWC st1145.028.5VlFx0x06.00.11986681654cMaster-A st1145.022.8VlFx0x06.00.12386681654cMaster-B st1145.019.4VlFx0x06.00.12686681654cMaster-C st2155.029.5VlFx0x07.00.11285611632cStairs-A Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st1 Peak AVF 418 467 0.119 437 14.0 0x0 VinlFlx st2 Peak AVF 535 486 0.112 681 12.0 0x0 VinlFlx 2021-Dec-07 11:44:45 Right-Suite® Universal 2021 21.0.08 RSU12269 Page 4 ...Lucerno Res 376 Tenth St\Lucerno Res 2598 N.rup Calc = MJ8 Front Door faces: E Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk rb15 0x 1770 134 134.8 0.136 226 12.0 x0 0 VlFx rt1 rb2 0x 1100 116 163.5 0.112 593 6.0 x0 0 VlFx rt1 rb6 0x 2970 267 76.4 0.240 544 10.0 x0 0 VlFx rb7 0x 1730 179 83.0 0.221 405 9.0 x0 0 VlFx rb9 0x 1960 256 141.1 0.130 326 12.0 x0 0 VlFx rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 484 507 0.112 474 14.0 0x0 VinlFlx