Loading...
725 ATLANTIC BLVD - FIRE COMMENTS 7/10/18 Gx.SONV, V 9FSCUE.DieP Office of the Fire Marshal Plans Review Permit Number: Comm 18-0019 Architectural Plans: Interior Buildout 725 Atlantic Blvd Unit 4 Atlantic Beach, Florida 1. Return for Corrections The plans submitted have been returned for corrections. Please correct or provide the proceeding requested information to obtain plans approval. When resubmitting corrected sheets, please provide a written narrative letter responding to our comments and directing the plans reviewer to the sheets the changes have taken place. Failure to provide response letter"WILL"result in an immediate return for corrections plans review submission. Revised sheets should be clouded clearly showing areas were changes or corrections have occurred and re-inserted with the original set of drawings with old sheets removed. 2. Key Plan Provide key plan of building showing adjacent occupancy type with required separation of occupancies per 6th Edition FFPC,NFPA 101 Table 6.1.14.1.4. 3. Fire Code Specific Code Summary The building code and fire code differ on occupancy types and uses and can make the proper application of the code difficult. Please provide in addition to normal building code summary a fire code specific summary based off the Florida Fire Prevention Code(current edition)to include all the following information listed below. Failure to provide accurate fire code summary may delay plans review approvals as we return plans for corrections and clarifications. • Occupancy type sub-classification(per NFPA 101 6.1) • Building construction type(per NFPA 101 8.2.1) -. 1, r-. F �. • Gross square footage � „� L_ I , •Number of stories • Building height • Interior wall and ceiling finish requirements JUL 1 0 2018 •Allowable dead end limits •Allowable Common path of travel limits •Allowable travel distance limits Building Department •Any fire protection systems(sprinkler, fire alarm,etc.) City of Atlantic Beach, FL • Statement from architect or engineers that their design to the best of their knowledge complies • with the 6th Edition Florida Fire Prevention Code(FFPC). Also all existing building must provide classification of rehabilitation work categories per NFPA 101 43.1 cx,SON v�l(F FIRE tit Liv0 Z CTI9FSCUE 0�4 Office of the Fire Marshal Plans Review 4. Life Safety Plan: Please provide a Life Safety Plan to include all the following information. • Dead end corridors measurements. • Common path of travel measurements. • Total travel distance to exits. • Lock/Latch details: Panic Hardware, Thumb turn lock, Key Lock with indicator and required signage. •All required exits shall terminate at a"public way". Access to the public way shall be via a stable, firm, and slip resistant conveyance such as a concrete sidewalk with a min. 5'x5' landing and 44"walkway. • Main Electrical disconnects access/location. • Exit signs to include tactile exits signage. *(The plans reflect only two marked exits located at each door). NFPA 101, 38.2.10 Marking of Means of Egress. Means of egress shall have signs in accordance with Section 7.10. Kind Regards, Captain Charles R Johnson NFPA Certified Fire Plans Examiner Fire Prevention Bureau—Certificates of Use City of Jacksonville I Fire and Rescue Department 214 N Hogan Street Jacksonville, FL 32202 Office: 904.255.8560