2ND REVIEW COMMENTS, ACC22-0036, 8.15.2022
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
(904) 247-5800
BUILDING REVIEW COMMENTS
Date: 8/15/2022
Permit #: RESO22-0036 Site Address: 343 PLAZA
Review Status: DENIED RE#: 170003 0000
Applicant:Property Owner: LOVE NANCY J
Email: Email: nancy@coastaladvantagerealty.com
Phone: Phone: 9045536266
THIS REVIEW IS ONE OF MULTIPLE DEPARTMENT REVIEWS.
Revisions may not be submitted until ALL departments have completed their respective reviews.
Revisions submitted MUST respond to EACH department review. Submittals that respond to only one or a
few correction items will not be accepted.
Correction Comments:
1.The energy form R402-2020 was not filled out making it incomplete. Please fill out the needed information
and sign the last page. Ceiling and wall insulation R-Values needed of the existing building. If not insulated it
will have to be. The ceiling will have to be R38 unless it is flat, then if will have to be at least R19. Stick frame
wall insulation shall be a minimum of R13, if exterior walls are cmu blockwork the walls shall be inslulated to
th
an R6 value. 7 Edition of the FBC-Existing Building Code; Section R503 ALTERATIONS; R503.2 Change in
space conditioning. Also SECTION R505 CHANGE IN OCCUPANCE OR USE.
2.Resubmittals may generate other review comments.
Mike Jones
Building Inspector/Plans Examiner
City of Atlantic Beach
800 Seminole Road
Atlantic Beach, FL 32233
(904) 247-5844
Email:mjones@coab.us
Resubmittal Notes:
All revisions and changes shall clearly stand out from the rest of the drawing on the sheet as a
revision by way of completely encircling the change with “clouding”. The revision shall also be identified as to the
sequence of revision by indicating a triangle with the revision sequence number within it and located adjacent to the
cloud. The revision date and revision sequence number shall also be indicated in a conspicuous location in the title block
for each sheet on which a revision for that sequence occurs. For projects still in the initial review stage and permit
pending, all sheets with revisions shall be inserted into each set of drawings. The original sheets must be clearly marked
“VOID” but are to be left within the set of drawings. Complete new sets of drawings will not be accepted. ADDITIONAL
ITEMS MAY BE REQUIRED DEPENDING UPON NEW INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR
REVIEW.