660 MAYPORT RD COMM23-0012 Brewery - MEP Plans REVISION 3-17-23_11. REMOVE EXISTING PLUMBING FIXTURES, EQUIPMENT, AND EQUIPMENT PADS TOTHE EXTENT INDICATED ON THE PLUMBING AND ARCHITECTURAL DEMOLITIONDRAWINGS.2. REMOVE EXISTING WATER PIPING TO THE EXTENT INDICATED ON THE DRAWINGS.POINTS OF DISCONNECTION/RECONNECTION ON DRAWINGS ARE BASED BESTAVAILABLE INFORMATION AND SHALL BE FIELD LOCATED AND ADJUSTEDACCORDINGLY. UNLESS OTHERWISE INDICATED, INACCESSIBLE EXISTINGUNDER-SLAB PIPING NOT INTERFERING WITH NEW CONSTRUCTION MAY BEABANDONED IN PLACE AFTER COMPLETELY DISCONNECTING FROM NEW SYSTEM,DRAINING, CUTTING AND CAPPING BELOW GRADE.3. REMOVE EXISTING SANITARY, WASTE, & VENT PIPING SYSTEMS TO THE EXTENTINDICATED ON THE DRAWINGS. POINTS OF DISCONNECTION/RECONNECTION ONPLANS ARE BASED BEST AVAILABLE INFORMATION AND SHALL BE FIELD LOCATEDAND ADJUSTED ACCORDINGLY. INACCESSIBLE EXISTING UNDER-SLAB PIPING NOTINTERFERING WITH NEW CONSTRUCTION MAY BE ABANDONED IN PLACE AFTERCOMPLETELY DISCONNECTING FROM NEW SYSTEM, DRAINING, CUTTING ANDCAPPING BELOW GRADE. EXISTING VTR'S OF REQUIRED SIZE AND ACCEPTABLECONDITION MAY BE RE-USED.4. EXISTING PIPING TO BE RE-USED IS SHOWN FADED.5. RECOVER ALL REFRIGERANT IN ACCORDANCE WITH ALL FEDERAL, STATE ANDLOCAL REQUIREMENTS.6. PROPERLY DISPOSE OF ALL REMOVED MATERIAL OFFSITE.7. ALL EQUIPMENT BEING REUSED SHALL BE INSPECTED FOR PROPER OPERATIONAND REASONABLE CONDITION AND SHALL BE PRESSURE TESTED WITH THE NEWSYSTEM. ALL PIPING BEING REUSED SHALL BE VISUALLY INSPECTED FORREASONABLE CONDITION, SLOPE AND INVERT, AS APPLICABLE; AND SHALL BEFLUSHED AND PRESSURE TESTED.8. EXISTING PLUMBING SYSTEM, WHERE INDICATED, ARE BASED ON BEST AVAILABLEINFORMATION. CONTRACTOR SHALL VISIT SITE PRIOR TO BIDDING AND FIELDCONFIRM EXTENT OF DEMOLITION, EXISTING INVERTS, ETC. CONTRACTOR SHALLCONFIRM ALL EXISTING CONDITIONS AS DEMOLITION OCCURS. REFER TO ORIGINALCONSTRUCTION DRAWINGS WHERE AVAILABLE FOR ADDITIONAL INFORMATION OFEXISTING CONDITIONS.1. SANITARY, WASTE AND VENT PIPE AND FITTINGS SHALL BE SOLID CORE DWV SCH 40 PVC, WITH A SOLID CELLULAR CORE, OR COMPOSITEWALL MATERIAL AS SPECIFIED, UNLESS STATED OTHERWISE BY LOCAL CODES AND REGULATIONS; ASTM D2665; ASTM F891; ASTM F1488; CSAB181.2. PROVIDE APPROVED FIRE RATED JACKET WHERE PIPE PASSES THROUGH RETURN AIR PLENUM.2. OFFSET VENT THRU ROOF'S (VTR'S) AS REQUIRED TO PENETRATE ROOF AT LOCATION AT LEAST 10' FROM AIR CONDITIONING UNIT INTAKESAND TERMINATE A MINIMUM OF 12" (INCHES) AWAY FROM ANY VERTICAL SURFACE. COORDINATE EXACT LOCATION OF AIR CONDITIONINGUNITS WITH MECHANICAL CONTRACTOR AND ADJUST AS NECESSARY. EXISTING VTR'S MAY BE RE-USED WHERE SUITABLE.3. REFER TO RISERS FOR PIPE SIZES NOT SHOWN ON PLAN. REFER TO SCHEDULE FOR SANITARY DRAIN, DOMESTIC WATER AND INDIVIDUALVENT CONNECTION SIZES.4. REFER TO ARCHITECTURAL PLANS TO CONFIRM LOCATION OF FIRE RATED WALLS, SMOKE BARRIERS, AND SMOKE PARTITIONS. ALLPENETRATIONS OF RATED WALLS SHALL BE MADE WITH FIRE STOPPING MATERIALS IN ACCORDANCE WITH THE 2020 FLORIDA BUILDING CODEREQUIREMENTS. PENETRATIONS OF ALL FIRE RATED ASSEMBLIES SHALL BE MADE IN ACCORDANCE WITH THE FIRE RATED ASSEMBLY'S ULLISTING, AS APPROVED BY THE AUTHORITY HAVING JURISDICTION.5. SLEEVE ALL FLOOR/WALL PENETRATIONS THAT ARE NOT CORE BORED.6. POTABLE WATER PIPING AND FITTINGS SHALL BE CPVC WITH COMPATIBLE CPVC FITTINGS AND SOLVENT CEMENT, MATERIAL AS SPECIFIED.OR POTABLE WATER PIPING AND FITTINGS SHALL BE TYPE K COPPER BELOW GRADE AND TYPE L COPPER ABOVE GRADE AS SPECIFIED.PROVIDE APPROVED FIRE RATED JACKET WHERE PIPE PASSES THROUGH RETURN AIR PLENUM.7. INSULATE ALL HOT WATER PIPING, AND COLD WATER PIPING IN EXPOSED LOCATIONS, AS SPECIFIED.8. REFER TO WATER HEATER DETAIL FOR EMERGENCY DISCHARGE, DRAIN PAN, AND OTHER PIPING REQUIREMENTS.9. ISOLATION AND SHUTOFF VALVES AND STOP VALVES SHALL BE GATE VALVES, BALL VALVES OR ANGLE STOPS, RATED FOR 150 PSI AT 180°F.REFER TO SPECIFICATIONS.10. PROVIDE WATER HAMMER ARRESTORS FOR ALL FIXTURES IN ACCORDANCE WITH PDI 201 GUIDELINES.11. PROVIDE TRAP PRIMERS FOR ALL FLOOR DRAINS AND/OR FLOOR SINKS. PROVIDE ADA COVERING OVER TRAP PRIMERS INSTALLED UNDERADA LAVATORIES AND SINKS.12. ALL WATER PIPE SHALL BE RUN CONCEALED IN CHASE, WALL, OR ABOVE CEILING EXCEPT IN MECHANICAL ROOMS OR AS OTHERWISENOTED.13. PRIOR TO ORDERING FIXTURES, CONFIRM DIMENSIONAL FIT-UP REQUIREMENTS FOR DWV PIPING LAYOUTS, FRAMING/MILLWORK, FAUCETTRIM HOLES, ETC. AND COORDINATE ANY REQUIRED ADJUSTMENTS FOR PROPER FIT FORM AND FUNCTION OF EACH FIXTURE.14. PROVIDE ALL REQUIRED FITTINGS FOR COMPLETE INSTALLATION OF EACH FIXTURE INCLUDING, BUT NOT LIMITED TO, 3/8" FLEXIBLESUPPLIES, ESCUTCHEON PLATES, STOP VALVES, DRAINS, TRAPS, MOUNTING HARDWARE, ETC. ALL EXPOSED HARDWARE SHALL BE POLISHEDBRASS OR CHROME FINISH.15. INSTALL ALL FIXTURES IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, PLUMB AND LEVEL, PROPERLY SECURED ANDSEALED TO WALL OR FLOOR.16. ALL PLUMBING FIXTURES AND MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2020 FLORIDA PLUMBING CODE AND ENERGYCONSERVATION CODE, LATEST EDITION ADOPTED BY AUTHORITY HAVING JURISDICTION.17. ALL PLUMBING FIXTURES AND MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH 2020 FLORIDA ACCESSIBILITY CODE. ENSURESANITARY ROUGH-INS ARE LOCATED TO MAINTAIN ADA CLEARANCES AFTER FIXTURES ARE INSTALLED. REFER TO ARCHITECTURAL DRAWINGSFOR EXACT DIMENSIONS.18. REVIEW PLANS TO CONFIRM ADEQUATE CHASE AND/OR WALL CAVITY CLEARANCE EXISTS PRIOR TO INITIATION OF WORK.19. ALL PIPING, MATERIALS AND EQUIPMENT ARE NEW UNLESS OTHERWISE NOTED.20. REVIEW BUY AMERICA(N) REQUIREMENTS WITH GENERAL CONTRACTOR. IF RELEVANT TO THIS CONTRACT, CONFIRM ALL EQUIPMENTPROVIDED MEETS THESE REQUIREMENTS, REGARDLESS OF MAKE/MODEL INDICATED ON BASIS OF DESIGN EQUIPMENT SCHEDULES.21. ALL WORK AND MATERIAL SHALL BE PERFORMED AND INSTALLED IN COMPLIANCE WITH THE 2020 FLORIDA BUILDING CODE AND ALLCURRENT AMENDMENTS. NOTHING IN THESE DRAWINGS IS TO BE CONSTRUED TO PERMIT WORK NOT CONFORMING TO THESE CODES.22. ALL PLUMBING WORK SHALL BE INSTALLED TO AVOID INTERFERENCES WITH ELECTRICAL, MECHANICAL AND STRUCTURAL FRAMING.23. EXACT LOCATIONS AND MOUNTING HEIGHTS OF PLUMBING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL DRAWINGS.24. BEFORE COMMENCEMENT OF WORK, CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS, ELEVATIONS, AND CHARACTERISTICS OF ALLUTILITIES AND PIPING. IMMEDIATELY NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES.25. ALL WASTE AND VENT PIPING SHALL SLOPE AT 1/8" PER FOOT OR 1/4" PER FOOT UNLESS INDICATED OTHERWISE.26. REMOVE ALL FACTORY MARKINGS ON EXPOSED PVC PIPING. USE ACETONE, XYLENE, MEK OR ANOTHER APPROPRIATE SOLVENT.27. ALL FLOOR DRAINS; CLEANOUTS; FLOOR SINKS AND TROUGHS SHALL BE INSTALLED FLUSH TO FINISHED FLOOR, NO DISHING PERMITTED.28. ALL VENT PIPING SHALL BE FULL LINE SIZE IF A WALL CLEAN-OUT IS SHOWN OR AS INDICATED.29. FLOOR DRAIN LINE SIZE AND VENTING IN ACCORDANCE WITH THE 2020 FLORIDA PLUMBING CODE INCLUDING LATEST REVISIONS,COMBINATION WASTE AND VENT SYSTEM.30. ALL VENT PIPING SHALL BE LOCATED WITHIN MASONRY WALLS AND OTHER WALL CONSTRUCTION THAT MAY BE USED TO ENCLOSE THEVENT PIPING. PIPING SHOWN ON DRAWINGS MAY NOT REFLECT THIS INSTALLATION METHOD BECAUSE OF THE DEGREE OF DETAILINCONSISTENT WITH 1/8" PLANS. IF PIPING CANNOT BE INSTALLED WITHIN THESE STRUCTURES, APPROVAL OF THE ENGINEER OF ANOTHERINSTALLATION METHOD IS REQUIRED. ALL EXPOSED VENT PIPING SHALL BE ATTACHED TO WALL NO FURTHER THAN 3" AWAY.31. PLUMBING FIXTURE DESCRIPTION SHALL TAKE PRECEDENCE WHEN EXISTS A CONFLICT WITH THE DESCRIPTION AND MODEL NUMBER.32. PLUMBING CONTRACTOR SHALL PROVIDE A PRESSURE REDUCING VALVE (PRV) WHERE WATER MAIN ENTERS BUILDING IF PRESSUREEXCEEDS 80 PSI. SET PRESSURE REDUCING VALVE TO 75 PSI.33. WHILE EVERY ATTEMPT HAS BEEN MADE IN THE PREPARATION TO THESE PLANS TO AVOID MISTAKES, THE DESIGNER AND COMPANYCANNOT GUARANTEE AGAINST ERROR OR UNFORESEEN FIELD CONDITIONS. THE CONTRACTOR OR BUILDER MUST CHECK ALL DIMENSIONSAND DETAILS AND REPORT ANY DISCREPANCIES.34. CONTRACTOR MUST CHECK EQUIPMENT NOT IN CONTRACT SO THAT THE SERVICE REQUIREMENTS ARE CORRECTLY TYPED, ADEQUATELYSIZED, AND ROUGHED-IN PROPERLY SO AS TO MINIMIZE THE AMOUNT OF MATERIALS AND FITTINGS NEEDED FOR FINAL HOOK-UP, RESULTINGIN A NEAT AND ORDERLY LOOKING INSTALLATION.35. COORDINATE WITH GENERAL CONTRACTOR AND ALL OTHER DISCIPLINES FOR CONNECTION REQUIREMENTS AND RUN LOCATIONS TOPREVENT CONFLICTS.36. LANDLORD TO APPROVE ALL ROOF PENETRATIONS. ALL ROOF WORK MUST BE BY LANDLORD'S APPROVED ROOFER.PLUMBING LEGENDPROJECT GENERAL NOTESABBREVIATIONSPIPINGPROJECT PIPING NOTES1. PROVIDE TRAPEZE PIPE HANGERS FOR PIPES 3 OR MORE. DOUBLE NUT U-BOLTS EVERY THIRD HANGER. U-BOLT SHALL BE LOOSELYFASTENED. INTENT IS NOT TO BIND OR HOLD PIPE, BUT ONLY TO PROVIDE LATERAL SEPARATION.2. PROVIDE 1" X 1" X 1/8" ANGLE WELDED TO BOTH SIDES OF PIPE OF BAR JOIST IF PIPE HANGAR IS MORE THAN 6" AWAY FROM PANEL POINTS.3. PROVIDE WATER HAMMER ARRESTORS FOR ALL GANG TOILET AREAS OR ANY OTHER SINGLE OR MULTIPLE WATER USING DEVICE.4. FASTEN ALL INSULATION PIPE SHIELDS TO PIPE INSULATION WITH ADHESIVE.5. ALL PIPE SUPPORT SYSTEMS SHALL NOT CRUSH THE INSULATION WHEN RESTING UPON THE SUPPORT. THE USE OF METAL SADDLES ISNECESSARY WHEN THE WEIGHT OF PIPE EXCEEDS THE WEIGHT SUPPORT LIMIT OF THE INSULATION.6. PIPE SIZES MAY BE SHOWN FOR THE SAME PIPING ON MORE THAN ONE PLAN. IN CASE OF PIPE SIZE DISCREPANCY, THE LARGER PIPE SIZESHALL BE CONSIDERED CORRECT DURING THE BIDDING AND DURING CONSTRUCTION UNLESS SPECIFICALLY APPROVED BY THEARCHITECT/ENGINEER OTHERWISE.7. PROVIDE SHUT-OFF VALVES FOR BOTH HOT AND COLD DOMESTIC WATER AT ALL RESTROOM LOCATIONS AND HEAT TRAPS FOR WATERHEATERS.8. PROVIDE 1" INSULATION ON HOT WATER PIPING. REFER TO TABLE C403.2.10 OF THE 2020 FLORIDA ENERGY CONSERVATION CODE.9. PIPE PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS SHALL BE INSULATED AND HAVE SPACE SEALED WITH FIRE STOP MATERIAL.10. PROVIDE A POSI-SET SYSTEM GAS CONNECTION SYSTEM FOR ALL GAS APPLIANCES.NOTE:NO PLUMBING, GAS, MECHANICAL OR ELECTRICAL CONNECTIONS OR INSTALLATIONSSHALL BE MADE UNTIL THE GENERAL CONTRACTOR, SUB-CONTRACTOR ANDOWNER/TENANT HAVE FIELD VERIFIED ALL EQUIPMENT REQUIREMENTS WITHEQUIPMENT SUPPLIER.NTSNOT TO SCALEWCOSRCOOGVTRFCOCOTYP.WHAEWCHBHWCWCLEAN-OUT ON GRADESANITARY RISERWALL CLEAN-OUTCLEAN-OUTFLOOR CLEAN-OUTVENT THRU ROOFELECTRIC WATER COOLERTYPICALWATER HAMMER ARRESTORCOLD WATER LINEHOT WATER LINEHOSE BIBBFLOOR DRAINFDFSFLOOR SINKAFFABOVE FINISHED FLOORHWPHOT WATER RECIRCULATION PUMPCNDCONDENSATE DRAINSANSANITARY LINEVVENT LINEASAQUASTATWMWATER METERABBREVIATIONSCFHCUBIC FEET PER HOURMBHTHOUSAND BTU'S PER HOURPSIPOUNDS PER SQUARE INCHWCWATER COLUMNWRWATER RISERETTHERMAL EXPANSION TANKBTUBRITISH THERMAL UNITAHJAUTHORITIES HAVING JURISDICTIONTMVTEMPERATURE MIXING VALVEGIGREASE INTERCEPTORLINT INTERCEPTORLIGPFGALLONS PER FLUSHGPMGALLONS PER MINUTETPVTRAP PRIMER VALVEWSVWASTE STACK VENTCACOMPRESSED AIRVSVENT STACKWSWASTE STACKACAIR COMPRESSORBTSBARRIER TYPE SEAL-TRAP PRIMEREWHELECTRIC WATER HEATERFUNNEL FLOOR DRAINFNDGRGAS REGULATORGWHGAS WATER HEATERHDHUB DRAININSTANTANEOUS WATER HEATERIWHICE MAKER VALVE BOXIVBPRVPRESSURE REDUCING VALVERVBREFRIGERATOR VALVE BOXRDROOF DRAINSDSHOWER DRAINSPSUMP PUMPTDTRENCH DRAINWVBCLOTHES WASHER VALVE BOXWALL HYDRANTHYYHYARD HYDRANTPOINT OF CONNECTION TOEXISTINGPOINT OF DISCONNECTIONFROM EXISTINGFORCE MAINFMRLRAIN LEADERELBOW (PLAN, UP, DOWN)SHUT-OFF VALVES (GATE/BALL VALVES)BRANCH CONNECTIONS (TOP, BOTTOM, SIDE)TEE (PLAN, UP, DOWN)TRAP, PLAN VIEWHOT WATERSANITARYVENTCOLD WATERSTRAINERGASGASNATURAL GAS/PROPANEEXISTING SANITARY (FADED)EXISTING COLD WATER (FADED)EXISTING HOT WATER (FADED)EXISTING HOT WATER RETURN (FADED)CAP FOR FUTURE CONNECTIONGAS BALL OR PLUG VALVEDIRECTION OF FLOWCIRCUIT BALANCING VALVE WITH MEMORY STOPPRESSURE REDUCING VALVEUNIONCLEANOUT IN FLOORCLEANOUT ON END OF PIPEHOSE BIBBFLOOR DRAIN, FLOOR SINKGLOBE VALVEEXISTING VENT (FADED)AACOMPRESSED AIRTEMPERED WATER MIXING VALVEDEMOLITIONREDUCED PRESSURE BACKFLOW PREVENTERHOT WATER RECIRCULATION PUMPPCHECK VALVEAAVAIR ADMITTANCE VALVEHOT WATER RETURN LINEHWRGWGREASE WASTE LINEWATER METERMCONTINUATIONBFGBELOW FINISHED GRADEBFFBELOW FINISHED FLOORECOEXTERIOR CLEAN-OUTGASGAS LINECLCENTER LINEDNDOWNEXEXISTINGGCGENERAL CONTRACTORHIHAIR INTERCEPTORNICNOT IN CONTRACTOWOIL WASTE SANITARY LINEOWSOIL WASTE SEPARATORTWTEMPERED WATER LINEVBVACUUM BREAKERPROJECT DEMOLITION NOTESFWFILTERED WATER LINEASME PRESSURE/TEMP RELIEF VALVEHOT WATER RETURNGREASE WASTEFILTERED COLD WATERWATER HEATER RELIEFBUTTERFLY VALVENOTE:CONTRACTORS SHALL VISIT THE SITE TOFAMILIARIZE WITH BUILDING CONDITIONS PRIOR TOSUBMITTING BID.PLUMBING LEGEND AND PROJECT NOTES P-1SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:MJSCMDREVISIONDATE 03-16-23370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23 PLUMBING SCHEDULES P-2SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:MJSCMDREVISIONDATE 03-16-23370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23 OUTDOORSEATING000DECK000BAR000EXISTINGRESTROOM000EXISTINGSTORAGE000EXISTINGSTORAGE000EXISTINGRESTROOM000WALK-INCOOLER000EXISTINGROOM000EXISTINGRESTROOM000RESTROOM000STAGE000DININGAREA000.ATTIC000SECONDFLOOR000ATTIC000EXISTINGBATH000EXISTINGSTORAGE000SANITARY AND GREASE WASTE PLAN P-3SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:MJSCMDREVISIONDATE 03-16-23370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23SCALE: 1/4" = 1'-0"02'4'8'SCALE:1/4"=1'-0"FIRST FLOOR SANITARY AND GREASE WASTE PLANSCALE:1/4"=1'-0"SECOND FLOOR SANITARY AND GREASE WASTE PLAN OUTDOORSEATING000DECK000BAR000EXISTINGRESTROOM000EXISTINGSTORAGE000EXISTINGSTORAGE000EXISTINGRESTROOM000WALK-INCOOLER000EXISTINGROOM000EXISTINGRESTROOM000RESTROOM000STAGE000DININGAREA000CHMCHM EXISTINGSTORAGE000ATTIC000SECONDFLOOR000ATTIC000EXISTINGBATH000DOMESTIC WATER PLAN P-4SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:MJSCMDREVISIONDATE 03-16-23370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23SCALE: 1/4" = 1'-0"02'4'8'SCALE:1/4"=1'-0"FIRST FLOOR DOMESTIC WATER PLANSCALE:1/4"=1'-0"SECOND FLOOR DOMESTIC WATER PLAN STUDOR - AIR ADMITTANCEVALVE (AAV); MUST BEINSTALLED IN UPRIGHTPOSITION ONLYP-5SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:MJSCMDREVISIONDATE 03-16-23370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23SCALE:N.T.S.FLOOR DRAIN DETAIL (FD)SCALE:N.T.S.WALL CLEANOUT DETAIL (WCO)SCALE:N.T.S.FLOOR SINK DETAIL (FS)PLUMBING DETAILS SCALE:N.T.S.TYPICAL PIPE SLEEVE THRU WALL DETAILSCALE:N.T.S.AIR ADMITTANCE VALVE DETAIL (AAV)SCALE:N.T.S.UNDERGROUND GREASE TRAP DETAIL (GT) P-5.1SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:MJSCMDREVISIONDATE 03-16-23370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23PLUMBING DETAILSSCALE:N.T.S.3-COMPARTMENT SINK PIPING DETAILSCALE:N.T.S.ANTI-SCALD DEVICE DETAIL (TMV-P)SCALE:N.T.S.TRAP PRIMER DETAIL (TPV)SCALE:N.T.S.WATER HAMMER ARRESTOR DETAILSCALE:N.T.S.ELECTRIC WATER HEATER DETAIL (EWH) .SANITARY AND GREASE WASTE RISER DIAGRAM P-6SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:MJSCMDREVISIONDATE 03-16-23370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M. DOHERTY, P.E. FL. P.E. #-55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23SCALE:N.T.S.SANITARY RISER DIAGRAMSCALE:N.T.S.GREASE WASTE RISER DIAGRAM 1.ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN DUCTS, & TRANSITIONS AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST. MAINTAIN MANUFACTURER'S RECOMMENDED CLEARANCES. LOCATION OF DUCTWORK IS APPROXIMATE. PRIOR TO FABRICATING DUCTWORK, CONTRACTOR SHALL VERIFY ALL DIMENSIONS & CLEARANCES AND REPORT ANY DISCREPANCIES BETWEEN DRAWINGS & ACTUAL FIELD CONDITIONS TO THE ENGINEER. PRIOR TO INSTALLING EQUIPMENT, CONTRACTOR SHALL ENSURE EQUIPMENT CLEARANCES WILL BE MAINTAINED. 2.FABRICATE & INSTALL DUCTWORK IN ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS, LATEST EDITION. 3.CONDENSATE DISPOSAL SHALL BE IN ACCORDANCE WITH 2020 FMC INCLUDING ALL LATEST REVISIONS. 4.CONDENSATE PIPING SHALL BE TRAPPED AND SIZED PER MANUFACTURER'S RECOMMENDATIONS. 5.INDOOR & OUTDOOR UNITS SHALL HAVE SINGLE POINT OF CONNECTION. 6.PROVIDE CONICAL TAKE-OFFS FOR ALL ROUND TAPS INTO RECTANGULAR DUCTWORK WITH VOLUME DAMPERS AT EACH TAKE-OFF FOR CFM ADJUSTMENT. 7.COORDINATE DIFFUSER BOXES, SUPPLY, & RETURN GRILLES & OTHER MECHANICAL DEVICES WITH LIGHT FIXTURES, SPRINKLER PIPING & PLUMBING. 8.PROVIDE LOW AMBIENT CONTROLS AS NECESSARY TO ALLOW COOLING AT TEMPERATURES DOWN TO 45°F. 9.HORSEPOWER RATINGS ON MOTORS ARE BASED ON SCHEDULED EQUIPMENT & DESIGN CONDITIONS. ACTUAL FIELD CONDITIONS OR SUBSTITUTIONS FROM SCHEDULED EQUIPMENT MAY REQUIRE DIFFERENT HORSEPOWER. IF LARGER MOTOR SIZES ARE REQUIRED OR CHANGES OCCUR IN VOLTAGES, COORDINATE ELECTRICAL SERVICE TO ENSURE PROPER WIRE SIZES & DEVICES AT NO ADDITIONAL COMPENSATION (DUE TO THESE CHANGES) ASKED FOR OR REQUESTED BY ANOTHER CONTRACTOR OR TRADE. 10.REFRIGERANT LINES FROM CU's TO AHU's SHALL BE SIZED PER MANUFACTURER'S RECOMMENDATIONS. 11.ALL FAN MOTORS SHALL HAVE THERMAL OVERLOAD & CURRENT PROTECTION. 12.PROVIDE SMOKE DETECTORS IN SUPPLY DUCT FOR ALL AHU's THAT DELIVER GREATER THAN 2000 CFM OF SUPPLY AIR FOR UNIT SHUTDOWN. CONTRACTOR SHALL PROVIDE AUDIBLE & VISUAL ALARM IN A CONSTANTLY OCCUPIED LOCATION. ALARM SHALL BE LABELED "DUCT TROUBLE". 13.PROVIDE AHU's WITH PROGRAMMABLE THERMOSTATS. 14.PROVIDE UNITS WITH 1" DISPOSABLE FILTER & FILTER HOUSING, TIME DELAY RELAY & LOCKOUT RELAY. 15.PROVIDE UNITS WITH A 5 YEAR WARRANTY FOR COMPRESSORS & ONE YEAR ON OTHER PARTS. 16.ALL DUCTWORK SHALL BE CONSTRUCTED WITH FIBERBOARD OR SHEET METAL PER LATEST SMACNA STANDARDS, & SHALL HAVE A MINIMUM R VALUE OF 6. 17.MECHANICAL CONTRACTOR TO PROVIDE TENANT WITH AIR BALANCE REPORT, EQUIPMENT AND LABOR WARRANTIES AND PROVIDE A COMPLETE, OPERATIONAL MECHANICAL SYSTEM IN COMPLIANCE WITH ALL APPLICABLE CODES. 18.OUTSIDE AIR DUCTS SHALL INCLUDE INSTALLATION OF A MOTORIZED, 2-POSITION DAMPER TO ALLOW THE SCHEDULED AMOUNT OF OUTSIDE AIR TO FLOW THROUGH THE UNIT, AND CLOSE UPON UNIT SHUTDOWN. 19.ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE 2020 FLORIDA MECHANICAL CODE (INCLUDING ALL LATEST REVISIONS), NFPA 90A, ASHRAE 62.1-2016, AND ASHRAE 90.1. 20.PROVIDE ENGINEER OF RECORD WITH HVAC EQUIPMENT CUT SHEETS. CUT SHEETS SHALL BE APPROVED PRIOR TO INSTALLATION. 21.THE MECHANICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID FOR THE PROJECT. THE MECHANICAL CONTRACTOR SHALL COORDINATE DUCTWORK LOCATIONS DESIGNED BY THE MECHANICAL ENGINEER AND FIELD VERIFY ANY OBSTACLES OR CONFLICTS AND NOTE THEM IMMEDIATELY TO THE ENGINEER. NO DUCTWORK SHALL BE FABRICATED PRIOR TO FIELD VERIFYING ALL EXISTING CONDITIONS. NOTE: SOME SYMBOLS SHOWN DO NOT PERTAIN TO THIS PROJECT THERMOSTAT/SENSOR SUPPLY AIRFLOW RETURN/ EXHAUST AIRFLOW DEHUMIDISTAT AIR DEVICE TYPE CFM AMOUNT SMOKE DETECTOR DUCT TEMPERATURE SENSOR CEILING RETURN AIR GRILLE CEILING EXHAUST AIR GRILLE MANUAL VOLUME DAMPER FLEX DUCT (INSIDE DIMENSION) NEW ROUND DUCT (INSIDE DIMENSION) EXISTING DUCT TO REMAIN EXISTING DUCT TO BE REMOVED CONNECT NEW DUCT TO EXISTING DUCT TRUNCATE DUCT - LIMIT OF DEMOLITION VANED ELBOW RADIUS ELBOW TRANSITION - CONCENTRIC TRANSITION - ECCENTRIC SQUARE TEE SUPPLY DUCT (UP & DOWN) RETURN DUCT (UP & DOWN) EXHAUST DUCT (UP & DOWN) ROUND DUCT (UP & DOWN) STANDARD BRANCH TAKE-OFF DUCT / WALL MOUNTED SUPPLY REGISTER / GRILLE DUCT / WALL MOUNTED RETURN/ EXHAUST REGISTER / GRILLE MECHANICAL GENERAL NOTES SYMBOL LEGEND ABBREVIATIONS CEILING SUPPLY AIR DIFFUSERNEW RECTANGULAR DUCT (INSIDE DIMENSIONS; WIDTH X DEPTH) ABV ABOVE AFF ABOVE FINISH FLOOR AHU AIR HANDLING UNIT BDD BACKDRAFT DAMPER BHP BRAKE HORSEPOWER BTU BRITISH THERMAL UNIT CFM CUBIC FEET PER MINUTE CIRC CIRCULAR CU CONDENSING UNIT DCI DUCTLESS CEILING-CASSETTE INDOOR DCO DUCTLESS CEILING-CASSETTE OUTDOOR DN DOWN DWI DUCTLESS WALL-MOUNTED INDOOR DWO DUCTLESS WALL-MOUNTED OUTDOOR EAT ENTERING AIR TEMPERATURE EDB ENTERING DRY-BULB (TEMPERATURE) EER ENERGY EFFICIENCY RATIO EF EXHAUST FAN ESP EXTERNAL STATIC PRESSURE EWB ENTERING WET-BULB (TEMPERATURE) EX EXISTING FD FIRE DAMPER FF FLY FAN (AIR CURTAIN) FLA FULL LOAD AMPS FPM FEET PER MINUTE FT FEET GPM GALLON PER MINUTE HE HEATER HP HEAT PUMP HP HORSEPOWER HUM HUMIDIFIER IN INCHES IRH INFRARED HEATERS KEF KITCHEN EXHAUST FAN KW KILOWATT L LOUVER LAT LEAVING AIR TEMPERATURE MBH THOUSANDS BTUs PER HOUR MCA MINIMUM CIRCUIT AMPS MOCP MAXIMUM OVER CURRENT PROTECTION MOD MOTOR OPERATED CONTROL DAMPER MUA MAKE-UP AIR UNIT NA NOT APPLICABLE NC NOISE CRITERIA NC NORMALLY CLOSED NO NORMALLY OPEN NTS NOT TO SCALE OA OUTSIDE AIR OD OUTSIDE DIAMETER PSI POUNDS PER SQUARE INCH RA RETURN AIR RECT RECTANGULAR RH RELATIVE HUMIDITY RLA RUN LOAD AMPERE RTU ROOFTOP AIR HANDLING UNIT RPM REVOLUTION PER MINUTE SA SUPPLY AIR SEER SEASONAL ENERGY EFFICIENCY RATIO SF SUPPLY FAN SS STAINLESS STEEL SP STATIC PRESSURE TYP TYPICAL UC UNDERCUT DOOR UNO UNLESS NOTED OTHERWISE UTR UP THROUGH ROOF V/PH VOLTS/PHASE VCD VOLUME CONTROL DAMPER VAV VARIABLE AIR VOLUME VD VOLUME DAMPER (MANUAL OPPOSED BLADE) VFD VARIABLE FREQUENCY DRIVE W WATTS WEF WALL EXHAUST FAN HEATER MECHANICAL NOTES, LEGEND AND ABBREVIATIONSM-1SHEET TITLE:SHEET DATE:NO.DRAWN BY: CHECKED BY:CMDREVISIONDATE 03-16-2023370 15th Ave S; Units A & BJacksonville Beach, FL 32250904.249.0698 pDOHERTY SOMMERSARCHITECTS ENGINEERS, INC.904.241.0691 fwww.dsae.netFlorida Certificate of Auth No: 00009393Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS. THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUT EXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E.FL. P.E. #55021CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THISITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDEREDSIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.25 WEST 6TH STREETATLANTIC BEACH, FLORIDA 32266TENANT BUILD-OUTMAYPORT BREWINGCOMPANY D/B/ABEDLAM BREWERY03-16-23 ABS BRANCH & FLEX DUCT SCHEDULE 0 - 160 CFM -6"Ø 165 - 250 CFM -8"Ø 255 - 380 CFM -10"Ø 385 - 470 CFM -12"Ø 475 - 700 CFM -14"Ø 705 - 1100 CFM -16"Ø NOTE : BRANCH RUNOUT SIZE REFLECTS SUPPLY DIFFUSER NECK SIZE UNLESS OTHERWISE NOTED. SPLIT SYSTEM COOLING UNIT SCHEDULE MARK TONS INDOOR FAN DATA COOLING CAPACITY SEER INDOOR FAN OUTDOOR FAN ELECTRICAL DATA BASIS OF DESIGNTOTAL FLOW (CFM) 0/A (CFM) ESP (W.G.) MOTOR (HP) EDB (°F) EWB (°F) AMBIENT (°F) TOTAL (BTU/HR) SENSIBLE (BTU/HR) MCA (A) MOCP (A) HEATER (kW) MCA (A) MOCP (A)VOLTS Hz PHASE AHU-1 /CU-1 5 1900 475 1 3/4 80 67 95 60,000 ----67.2 80 10 ----230 60 1 WBHL604AD01E AHU-2 /CU-2 2 750 175 0.9 1/3 80 67 95 24,000 ----33.1 35 5 ----230 60 1 WBHL244AB01 NOTES: 1. UNITS PROVIDED SHALL MEET ALL SCHEDULED VALUES REGARDLESS OF MODEL OR TYPE, UNLESS APPROVED BY THE ENGINEER. 2. PROVIDE EACH UNIT WITH A PROGRAMMABLE THERMOSTAT MOUNTED @ 48" AFF. 3. PROVIDE WATER-LEVEL DETECTION DEVICE INSIDE PRIMARY DRAIN PAN THAT WILL SHUT OFF UNIT WHEN THE PRIMARY DRAIN PAN BECOMES RESTRICTED. EXHAUST FAN SCHEDULE MARK SERVICE TOTAL AIR (CFM) E.S.P. (W.G)UNIT TYPE DRIVE FLA VOLTS/PH/HZ MANUFACTURER MODEL NUMBER NOTES EF-1,2,3 TOILET ROOM 70 0.13 CEILING DIRECT 0.27 115/1/60 GREENHECK SP-A70 1,2 NOTES: 1. INTERLOCK WITH LIGHT SWITCH. 2. PROVIDE BACKDRAFT DAMPER. AIR DISTRIBUTION DEVICE SCHEDULE MARK DESCRIPTION MOUNTING FACE SIZE BASIS OF DESIGN NOTES A CEILING SUPPLY LAY-IN 16" x 8" / 8" x 4"--1,2 B WALL SUPPLY WALL 12" x 8"--1,2 C CEILING RETURN LAY-IN 24"x 24"--2 D WALL RETURN WALL 36" x 16" / 16"x 16"--2 NOTES: 1. LOUVER FACE. 2. WITH OPTIONAL DAMPER.MECHANICAL SCHEDULESM-2SHEET TITLE:SHEET DATE:NO.DRAWN BY: CHECKED BY:CMDREVISIONDATE 03-16-2023370 15th Ave S; Units A & BJacksonville Beach, FL 32250904.249.0698 pDOHERTY SOMMERSARCHITECTS ENGINEERS, INC.904.241.0691 fwww.dsae.netFlorida Certificate of Auth No: 00009393Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS. THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUT EXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E.FL. P.E. #55021CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THISITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDEREDSIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.25 WEST 6TH STREETATLANTIC BEACH, FLORIDA 32266TENANT BUILD-OUTMAYPORT BREWINGCOMPANY D/B/ABEDLAM BREWERY03-16-23 ABS CU-1 CU-2 UNDER STAIR EF-1 EF-2 A 506"Ø6"ØA 50 A 50 A 350 D 750 C 675 A 350 A 350 A 350 A 35012"x12"18"Ø6"Ø8"Ø 8"Ø 6"Ø5"Ø9"Ø UP TO 2ND FLOOR 18"Ø UP TO 2ND FLOOR AHU-1CU-1 CU-2 CU-2 UNDER STAIR EF-3 14"x21"6"ØA 50 B 200 B 200 B 150 B 150 D 350 D 350 SUPPLY LOW ON WALL AND RETURN HIGH ON WALL 8"Ø O/A INLET AHU-28"Ø O/A INLET 14"x21"14"x14"16"Ø18"Ø DOWN TO FIRST FLOOR D REGISTER 10"Ø TYPICAL OF 5 9"Ø TO FIRST FLOOR RESTROOMS/ STRG 19"x21" RIGID 19"x21" RIGID 14"x14"14"x14"14"Ø10"Ø12"x12"8"Ø 8"Ø 8"Ø 8"Ø 4"Ø 12"Ø 12"Ø12"Ø9"ØMECHANICAL PLANM-3SHEET TITLE:SHEET DATE:NO.DRAWN BY: CHECKED BY:CMDREVISIONDATE 03-16-2023370 15th Ave S; Units A & BJacksonville Beach, FL 32250904.249.0698 pDOHERTY SOMMERSARCHITECTS ENGINEERS, INC.904.241.0691 fwww.dsae.netFlorida Certificate of Auth No: 00009393Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS. THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUT EXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E.FL. P.E. #55021CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THISITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDEREDSIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.25 WEST 6TH STREETATLANTIC BEACH, FLORIDA 32266TENANT BUILD-OUTMAYPORT BREWINGCOMPANY D/B/ABEDLAM BREWERY03-16-23 ABS SCALE: 3/8"= 1'-0" 1ST FLOOR MECHANCIAL PLAN SCALE: 3/8"= 1'-0" 2ND FLOOR MECHANCIAL PLAN MECHANICAL DETAILSM-4 SCALE:N.T.S. DUCT HANGER DETAIL SCALE:N.T.S. RADIUS ELBOW - RECT. DUCT SCALE:N.T.S. ELBOW DETAIL - RECT. DUCT SCALE:N.T.S. FLEX DUCT CONNECTION DETAIL SCALE:N.T.S. TOILET EXHAUST DETAIL SCALE:N.T.S. DUCT OFFSET SCALE:N.T.S. TYPICAL BRANCH TAKE-OFF DETAIL SCALE:N.T.S. AHU CONNECTION DETAIL SHEET TITLE:SHEET DATE:NO.DRAWN BY: CHECKED BY:CMDREVISIONDATE 03-16-2023370 15th Ave S; Units A & BJacksonville Beach, FL 32250904.249.0698 pDOHERTY SOMMERSARCHITECTS ENGINEERS, INC.904.241.0691 fwww.dsae.netFlorida Certificate of Auth No: 00009393Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS. THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUT EXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E.FL. P.E. #55021CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THISITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDEREDSIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.25 WEST 6TH STREETATLANTIC BEACH, FLORIDA 32266TENANT BUILD-OUTMAYPORT BREWINGCOMPANY D/B/ABEDLAM BREWERY03-16-23 ABS E-1ELECTRICAL LEGEND & PROJECT GENERAL NOTESSHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:CMDREVISIONDATE 03-16-2023370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23JAG R.R.R.R.STORAGER.RROOMSERVICE STATION FDBARDININGSTAGE4 PERSON TABLE4 PERSON TABLE4 PERSON TABLE4 PERSON TABLE6 PERSON TABLE6 PERSON TABLE6 PERSON TABLE6 PERSON TABLEBARDECKDECKDECKTOILET(20) EQ. TREADS @ 10"FDFSWALK-IN COOLERSTORAGEEF-1EF-2E-2SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:CMDREVISIONDATE 03-16-2023370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23JAGSCALE:1/4"=1'-0"LIGHTING PLAN - 1ST FLOORLIGHTING PLAN - 1ST FLOOR UPSECOND FLOOR-STORAGE-BATH-ATTIC-ATTIC-UPUP REFOPENEF-3E-2.1SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:CMDREVISIONDATE 03-16-2023370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23JAGSCALE:1/4"=1'-0"LIGHTING PLAN - 2ND FLOORLIGHTING PLAN - 2ND FLOOR R.R.R.R.STORAGER.RROOMSERVICE STATION FDBARDININGSTAGE4 PERSON TABLE4 PERSON TABLE4 PERSON TABLE4 PERSON TABLE6 PERSON TABLE6 PERSON TABLE6 PERSON TABLE6 PERSON TABLEBARDECKDECKDECKTOILET(20) EQ. TREADS @ 10"FDFSWALK-IN COOLERSTORAGECU-1CU-2E-3SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:CMDREVISIONDATE 03-16-2023370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23JAGSCALE:1/4"=1'-0"POWER PLAN - 1ST FLOORPOWER PLAN - 1ST FLOOR UPSECOND FLOOR-STORAGE-BATH-ATTIC-ATTIC-UPUP REFOPENAHU-1 AHU-2 E-3.1SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:CMDREVISIONDATE 03-16-2023370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23JAGSCALE:1/4"=1'-0"POWER PLAN - 2ND FLOORPOWER PLAN - 2ND FLOOR E-4SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:CMDREVISIONDATE 03-16-2023370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23JAGGENERAL NOTES:KEY NOTESSCALE: NTSPOWER RISER DIAGRAMPOWER RISER DIAGRAM E-5SHEET TITLE:SHEETDATE:NO.DRAWN BY:CHECKED BY:CMDREVISIONDATE 03-16-2023370 15th Ave S; Units A & B Jacksonville Beach, FL 32250 904.249.0698 p DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC. 904.241.0691 f www.dsae.net Florida Certificate of Auth No: 00009393 Florida License No.: AA26000952DESIGNER EXPRESSLY RESERVES HIS COPYRIGHT AND OTHER PROPERTY RIGHTS IN THESE DRAWINGS.THESE DRAWINGS, PLANS & DESIGNS ARE NOT TO BE REPRODUCED, COPIED OR USED IN ANY MANNER WITHOUTEXPRESSED WRITTEN PERMISSION AND CONSENT OF DOHERTY SOMMERS ARCHITECTS ENGINEERS, INC.THESE PLANS SHALL NOT BE DISTRIBUTED TO ANY PARTY WITHOUT SAID WRITTEN PERMISSION & CONSENT.CAREN M. DOHERTY, P.E. FL. P.E. #55021 CAREN M DOHERTY, STATE OF FLORIDA, PROFESSIONAL ENGINEER, LICENSE NO. 55021. THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY CAREN M DOHERTY, PE ON 03/16/23 USING A DIGITAL SIGNATURE. PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. 25 WEST 6TH STREET ATLANTIC BEACH, FLORIDA 32266 TENANT BUILD-OUT MAYPORT BREWING COMPANY D/B/A BEDLAM BREWERY 03-16-23JAGELECTRICAL SCHEDULES & DETAILSNOTES:SCALE: NTSTYPICAL DEVICE MOUNTING DETAILSCALE: NTSTYPICAL TELEPHONE AND DATA RISER