2337 Seminole Road Unit C ROOF23-0012 COAB Permit Form with ConditionsOWNER:ADDRESS:CITY:STATE:ZIP:
BOHR SARAH H 2337 SEMINOLE RD A ATLANTIC BEACH FL 32233-5931
COMPANY:ADDRESS:CITY:STATE:ZIP:
AMERICAN ROOFING OF
JACKSONVILLE 2117 University Blvd. S JACKSONVILLE FL 32216
TYPE OF
CONSTRUCTION:
REAL ESTATE
NUMBER:ZONING:BUILDING USE
GROUP:SUBDIVISION:
168846 5006 BLUFFS CLUSTER HOMES
COND
JOB ADDRESS:PERMIT TYPE:DESCRIPTION: VALUE OF WORK:
2337 SEMINOLE RD C ROOF NON SHINGLE FLAT ROOF , FL2533-R28
SYSTEM W104 $17707.00
LIST OF CONDITIONS
Roll off container company must be on City approved list . Container cannot be placed on City right-of-way.
1 BUILDING NOTICE OF COMMENCEMENT INFORMATIONAL
Notes:
No inspections may be scheduled until a copy a recorded Notice of Commencement has been submitted to the Building Department
NOTICE: In addition to the requirements of this permit, there may be additional restrictions applicable to this property
that may be found in the public records of this county, and there may be additional permits required from other
governmental entities such as water management districts, state agencies, or federal agencies.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT
IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. A NOTICE OF
COMMENCEMENT MUST BE RECORDED AND POSTED ON THE JOB SITE BEFORE THE FIRST
INSPECTION. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN
ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.
MUST CALL INSPECTION PHONE LINE (904) 247-5814 BY 4 PM FOR NEXT DAY INSPECTION.
ALL WORK MUST CONFORM TO THE CURRENT 6TH EDITION (2017) OF THE FLORIDA BUILDING
CODE, NEC, IPMC, AND CITY OF ATLANTIC BEACH CODE OF ORDINANCES .
ALL CONDITIONS OF PERMIT APPLY, PLEASE READ CAREFULLY.
1 of 2Issued Date: 4/18/2023
PERMIT NUMBER
ROOF23-0012
ISSUED: 4/18/2023
EXPIRES: 10/15/2023
ROOF NON SHINGLE PERMIT
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
FEES
DESCRIPTION ACCOUNT QUANTITY PAID AMOUNT
BUILDING PERMIT 455-0000-322-1000 0 $140.00
BUILDING PLAN CHECK 455-0000-322-1001 0 $70.00
STATE DBPR SURCHARGE 455-0000-208-0700 0 $3.15
STATE DCA SURCHARGE 455-0000-208-0600 0 $2.10
TOTAL: $215.25
2 BUILDING ROOF IN-PROGRESS INSPECTION REQUIRED INFORMATIONAL
Notes:
a.\tThe roof sheathing for all new construction must remain uncovered until the Roof Sheathing Inspection is approved.\r\r
b.\tAll roofing projects require an In-Progress Inspection.\r\r
c.\tSheathing installation and replacement guidelines per APA.\r\r
d.\tUnderlayment must conform to FBC-R Table 905.1.1\r\r
e.\tShingles must conform to ASTM D3161 G or H, or ASTM D7158 F\r\r
2 of 2Issued Date: 4/18/2023
PERMIT NUMBER
ROOF23-0012
ISSUED: 4/18/2023
EXPIRES: 10/15/2023
ROOF NON SHINGLE PERMIT
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
ATLANTIC BEACH, FL 32233
Building Permit Application Updated 10/9/18
City of Atlantic Beach Building Department ALL INFORMATION
800 Seminole Road, Atlantic Beach, FL 32233 HIGHLIGHTED IN GRAY
yJ'rt
IS REQUIRED.Phone: (904) 247-5826 Email: Building-Dept@coab.us
RC)0JobAddress: 2337 Seminole Rd, Unit C,Atlantic Beach, FL 32233 Permit Number: Z1'not Z,
Legal Description 37-2S-29E BLUFFS CLUSTER HOMES CONDOMINIUM UNIT C 0/R 4818-193 RE# 168846-5006
Valuation of Work(Replacement Cost)$ 17,707.50 Heated/Cooled SF 1,128 Non-Heated/Cooled 0
Class of Work: New Addition Alteration E Repair DMove Demo Pool Window/Door
Use of existing/proposed structure(s): Commercial IX Residential
If an existing structure,is a fire sprinkler system installed?: Yes No
Will tree(s)be removed in association with proposed prosect? Yes(must submit separate Tree Removal Permit) No
Describe in detail the type of work to be performed:
Complete tear off and replacement of roof system. '- )4 4,(:), .01.:,#./Y t,":6' 4 ShZ
Florida Product Approval#2„c, ..?—. ( " S /4.-7 l.(//(9 for multiple products use product approval form
Property Owner Information Install Certainteed Flintlastic flat roof system
Name Sarah H. Bohr Address 2337 Seminole Rd
City Atlantic Beach State FL Zip 32233 Phone 904.472.6252
E-Mail sarahbohr@aol.com
Owner or Agent(If Agent, Power of Attorney or Agency Letter Required)
Contractor Information
Name of Company American Roofing of Jacksonville, LLC Qualifying Agent Dan Kinkel
Address 222 River Hills Dr City Jacksonville State FL Zip 32233
Office Phone 904-385-4375 Job Site Contact Number 828.513.6930
State Certification/Registration# RC29027546 E-Mail admin@americanroofingiax.com
Architect Name&Phone# NA
Engineer's Name&Phone# NA
Workers Compensation Insurer 196-55865 OR Exempt 0 Expiration Date 8/25/2023
Application is hereby made to obtain a permit to do the work and installations as indicated.I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all the laws regulating
construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRICAL WORK, PLUMBING,SIGNS,
WELLS, POOLS, FURNACES, BOILERS, HEATERS,TANKS,and AIR CONDITIONERS,etc. NOTICE: In addition to the requirements of this
permit,there may be additional restrictions applicable to this property that may be found in the public records of this county,and
there may be additional permits required from other governmental entities such as water management districts,state agencies, or
federal agencies.
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all
applicable laws regulating construction and zoning.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY
RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND
TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMMENCEMENT. _
r
N
O
O Q Signature of Owner or Agent)Signature of Contractor)
LL m-c> mo
a m;o ed and sworn to(or affirme• •efore met /1 < day of d nd sw rn to(ora irmed)before me this day of
a o % ,, 2o.73 ,b -- G 6, 32 - b --, • / 'ley.
aa' EE
zoo Sig .tre of Notary)
lima• . N-71711-
V t
Z N t•
Y;;y TONT GINDLESPER ER I
oo 6=°jbo -rsonally Known OR Personally Known OR 1/r. 'c MY COMMISSION#GG 353178
roduced Identification l Produced Identificatic r.e: L / l EXPIRES:October 6,2023
yo,,,0 ,Tyr•of Identification: j `i1 L- Type of Identification: t `.i..-0`:", ., , - Nola Public Underwriters
NEMO I etc.
APPENDIX 1:ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE
TABLE DECK APPLICATION TYPE DESCRIPTION PAGE
1A Wood New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 6
1B Wood New or Reroof(Tear-Off) A-2 Mechanically Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 7-8
lc Wood New,Reroof(Tear-Off)or Recover B-1 Mechanically Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 9
to Wood New,Reroof(Tear-Off)or Recover C-1 Mechanically Attached Insulation,Bonded Roof Cover 9- 11
lE Wood New,Reroof(Tear-Off)or Recover D-2 Insulated,Mechanically Attached Base Sheet,Bonded Roof Cover 11-13
1F Wood New,Reroof(Tear-Off) E-2 Non-Insulated,Mechanically Attached Base Sheet,Bonded Roof Cover 13- 16
lo Wood New,Reroof(Tear-Off)or Recover E-2 Non-Insulated,Mechanically Attached Base Sheet,Bonded Roof Cover 16-18
1H Wood New or Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 18
2A Steel or Structural concrete New,Reroof(Tear-Off)or Recover B-1 Mechanically Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 19-21
2B Steel or Structural concrete New,Reroof(Tear-Off)or Recover C-1 Mechanically Attached Insulation,Bonded Roof Cover 22-25
2c Steel or Structural concrete New,Reroof(Tear-Off)or Recover D-2 Insulated,Mechanically Attached Base Sheet,Bonded Roof Cover 26-28
3A Structural concrete New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 29-37
3B Structural concrete New or Reroof(Tear-Off) A-3 Bonded Temp Roof/Vapor Barrier,Bonded Insulation,Bonded Roof Cover 37
3c Structural concrete New or Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 38
4A LWIC/steel New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 39-40
4B LWIC/structural concrete New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 41- 45
4c LWIC/structural concrete New,Reroof(Tear-Off) A-1 Bonded Vapor Barrier,Bonded Insulation,Bonded Roof Cover 46-47
40 LWIC/steel New or Reroof(Tear-Off) A-2 Mechanically Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 48-50
4E LWIC/steel or struct.conc.New or Reroof(Tear-Off) E-2 Non-Insulated,Mechanically Attached Base Sheet,Bonded Roof Cover 51-55
4F LWIC/steel Reroof(Tear-Off)or Recover E-2 Non-Insulated,Mechanically Attached Base Sheet,Bonded Roof Cover 56
4G LWIC/steel Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 56
5A Cementitious wood fiber New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 57-58
5B Cementitious wood fiber New or Reroof(Tear-Off)or Recover A-2 Mechanically Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 59
5c Cementitious wood fiber Reroof(Tear-Off)or Recover C-1 Mechanically Attached Insulation,Bonded Roof Cover 60
5o Cementitious wood fiber New,Reroof(Tear-Off)or Recover E-2 Non-Insulated,Mechanically Attached Base Sheet,Bonded Roof Cover 60
6A Existing gypsum Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 61- 62
6B Existing gypsum Reroof(Tear-Off) A-2 Mechanically Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 63
6c Existing gypsum Reroof(Tear-Off) C-1 Mechanically Attached Insulation,Bonded Roof Cover 64
6D Existing gypsum Reroof(Tear-Off) E-2 Non-Insulated,Mechanically Attached Base Sheet,Bonded Roof Cover 64
7A Various Recover A-1 Bonded Insulation,Bonded Roof Cover 65-70
7B Various Recover F Non-Insulated,Bonded Roof Cover 70
NEMO ETC,LLC Evaluation Report 3520.03.04-R29 for FL2533-R28
Certificate of Authorization#32455 7T"EDITION(2020)FBC NON-HVHZ EVALUATION(Method 10) Revision 29:04/14/2022
2019 NEMO ETC,LLC CertainTeed Flintlastic®Modified Bitumen Roof Systems,(610) 893-5400 Appendix 1,Page 1 of 70
NEMO I etc.
The following notes apply to the systems outlined herein:
1 The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having
Jurisdiction.
2 Unless otherwise noted,fasteners and stress plates shall be as follows. Fasteners shall be of sufficient length for the following engagements:
FASTENER/PLATE OPTIONS
DECK TYPE By FBC FILE PARTS MINIMUM ENGAGEMENT
Altenloh,Brinck and Co.U.S.,Inc. FL4500 Trufast#14 HD with Trufast 3"Metal Insulation Plates
Wood OMG,Inc. FL699 OMG#14 Roofgrip with AccuTrac Plates or OMG#14 Heavy Duty with OMG 3 in.Galvalume Steel Plate
Minimum'/.-inch plywood penetration or
minimum 1-inch wood plank embedment
SFS Group USA,Inc.FL20311 Dekfast DF-#14-PH3 with Dekfast PLT-H-2- 7/8 or Dekfast PLT-R-3.
Altenloh,Brinck and Co.U.S.,Inc. FL4500 Trufast#12 DP or Trufast#14 HD with Trufast 3"Metal Insulation Plates
Steel OMG,Inc. FL699
OMG#12 or#14 Roofgrip with AccuTrac Plates or OMG#12 Standard or OMG#14 Heavy Duty with Minimum%-inch steel penetration and engage the
OMG 3 in.Galvalume Steel Plate top flute of the steel deck
SFS Group USA,Inc.FL20311 Dekfast DF-#12-PH3 or DF-#14-PH3 with Dekfast PLT-H-2- 7/8 or Dekfast PLT-R-3.
Altenloh,Brinck and Co.U.S.,Inc. FL4500 Trufast#14 HD or Trufast Fluted Concrete Nail with Trufast 3"Metal Insulation Plates
Structural OMG#14 Roofgrip with AccuTrac Plates or OMG#14 Heavy Duty or CD-10 with OMG 3 in.Galvalume
Minimum 1-inch embedment. Fasteners installed
Concrete
OMG,Inc. FL699
Steel Plate
with a pilot hole in accordance with the fastener
manufacturer's published installation instructions
SFS Group USA,Inc.FL20311 Dekfast DF-#14-PH3 with Dekfast PLT-H-2-7/8 or Dekfast PLT-R-3.
3 Unless otherwise noted,insulation may be any one layer or combination of FBC Approved(Local or Statewide)board(s)that meet FBC 1505 and,for foam plastic,FBC Chapter 26,when installed with the roof
cover.
4 Minimum 200 psi,minimum 2-inch FBC Approved lightweight insulating concrete may be substituted for,or installed below,rigid insulation board for System Types B-1,C-1,C-2,D-1 or D-2,whereby fasteners
are installed through the lightweight insulating concrete to engage the structural deck. The structural deck shall be of equal or greater type,thickness and strength to the steel and structural concrete deck
listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. This is a wind uplift resistance allowance and does not purport
to address non-wind-uplift-related issues,such as deck venting or moisture levels within the Lightweight Concrete and the potential effect on overlying components.
5 Preliminary insulation attachment for System Type D:Unless otherwise noted,refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29(February 2020).
6 Unless otherwise noted,insulation adhesive application rates are as follows.
Ribbon or bead width is at the time of application;the ribbons/beads shall expand as noted in the manufacturer's published instructions.
When multiple layers(s)of insulation and/or coverboard are installed in ribbon-applied adhesive,board joints shall be staggered.
The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
INSULATION ADHESIVE REFERENCES
By FBC FILE ADHESIVE REFERENCE MINIMUM RATE NOTE
DuPont de Nemours,Inc. FL720 Insta Stik Quik Set Insta Stick Continuous 0.75 to 1 inch wide ribbons,12-inch o.c
H.B.Fuller Company FL1800 Millennium One Step Foamable Adhesive M-OSFA Continuous 0.25 to 0.5-inch wide ribbons,12-inch o.c.
H.B.Fuller Company FL1800 Millennium PG-1 Pump Grade Adhesive M-PG1 Continuous 0.5 to 0.75-inch wide ribbons,12-inch o.c.
ICP Construction,Inc. FL22256 Polyset Board-Max Polyset BM Continuous 3-inch wide ribbons,12-inch o.c.
ICP Construction,Inc. FL1365 Polyset Commercial Roofing Adhesive Polyset CRA _ Continuous 2.5 to 3-inch wide ribbons,12-inch o.c. Formerly Polyset CR-20
OMG,Inc. FL1608 OlyBond 500 Adhesive Fastener OB500 Continuous 0.75-inch wide ribbons,12-inch o.c. PaceCart,SpotShot or Canister dispensing
If applying hot asphalt to concrete deck,deck shall
Generic,ASTM D312,Type IV N/A hot asphalt N/A Full coverage at 25-30 lbs/square
be primed with ASTM D41 primer
NEMO ETC,LLC Evaluation Report 3520.03.04-R29 for FL2533-R28
Certificate of Authorization#32455 7T"EDITION(2020)FBC NON-HVHZ EVALUATION(Method 1D) Revision 29:04/14/2022
02019 NEMO ETC,LLC CertainTeed Flintlastic®Modified Bitumen Roof Systems,(610)893-5400 Appendix 1,Page 2 of 70
I
NEMO I etc.
7 Unless otherwise noted,all insulations are flat-stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following
Maximum Design Pressure(MDP)limitations. In no case shall these values be used to'increase'the MDP listings in the tables;rather if MDP listing below meets or exceeds that listed for a particular system in
the tables,then the thinner board listed below may be used as a drop-in for the equivalent thicker material listed in the table.
MDP LIMITATIONS FOR TAPERED POLYISOCYANURATE INSULATIONS
INSULATION MIN.TAPERED
ADHESIVE MDP(Psi')
LISTED PRODUCT FBC FILE THICKNESS(IN)
Insta Stik Any polyisocyanurate listed with adhesive herein Various 1.0 120.0
M-OSFA Any polyisocyanurate listed with adhesive herein Various 1.0 157.5
M-PG1 Any polyisocyanurate listed with adhesive herein Various 1.0 157.5
Polyset CRA Any polyisocyanurate listed with adhesive herein Various 1.0 117.5
OB500 Rmax Multi-Max FA3 FL11207 0.5 45.0
OB500 Hunter H-Shield FL5968 0.5 315.0
OB500 Johns Manville ENRGY 3 FL4205 0.5 315.0
OB500 Atlas Roofing ACFoam II FL17989 0.5 487.5
8 For adhered roof insulation and board-size: Unless otherwise noted,refer to Section 2.2.10.6.2 of FM Loss Prevention Data Sheet 1-29(February 2020).
9 For mechanically attached components or partially-bonded insulation,the maximum design pressure for the selected assembly shall meet or exceed at least the Zone 1 PRIME design pressure determined in
accordance with FBC Chapter 16. Elevated pressure zones shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are
ANSI/SPRI WD1,FM Loss Prevention Data Sheet 1-29,Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk'carry the limitations set forth in
Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29(February 2020)for Zone 2/3 enhancements.
10 For assemblies with all components fully bonded,the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No
rational analysis is permitted for these systems.
11 For mechanically attached components over existing decks,fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the
minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105.
12 For bonded insulation or membrane over existing substrates in a re-roof( tear off)or recover installation,the existing deck or existing roof surface shall be examined for compatibility with the adhesive to be
installed. If any surface conditions exist that bring system performance into question,field uplift testing shall be conducted on mock-ups of the proposed new roof assembly. For bonded insulation or membrane
over existing substrates in a recover installation,the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction,as
documented through field uplift testing. Field uplift testing shall be in accordance with ASTM E907,FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13 Refer to FBC 1511 for requirements and limitations regarding recover installations. For Structural Concrete Deck or Recover Applications using System Type C-1 the base insulation layer is optional and for System
Type C-2,D-1 or D-2,the insulation is optional. Alternatively,an FBC Approved insulation board or coverboard may be used as a separation layer. Board products shall be preliminarily attached prior to roof
cover installation(Note 5 herein). The separator component shall be documented as meeting FBC 1505 and,for foam plastic,FBC Chapter 26,when installed with the roof cover in Recover applications.
14 Lightweight insulating concrete(LWIC)shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWIC is referenced,refer to current
LWIC Product Approval for specific deck construction and limitations. Unless otherwise noted,for systems where specific LWIC is not referenced,the minimum design mix shall be 300 psi. In all cases,the
minimum top-coat thickness is 2-inches. For LWIC over structural concrete,reference is made to FBC Section 1917.4.1,Point 1. For"pre-existent"LWIC references,listings were established through testing over
lightweight concrete cast using only foaming agent(ASTM C896),water and Portland cement(ASTM C150),with no proprietary additives,in accordance with procedures adopted by Miami-Dade BCCO(FBC
CER1592). Use of these listings in new construction or re-roof( tear-off)applications is at the discretion of the Designer or Record and Authority Having Jurisdiction.
NEMO ETC,LLC Evaluation Report 3520.03.04-R29 for FL2533-R28
Certificate of Authorization#32455 7TH EDITION(2020)FBC NON-HVHZ EVALUATION(Method 1D) Revision 29:04/14/2022
02019 NEMO ETC,LLC CertainTeed Flintlastic®Modified Bitumen Roof Systems,(610)893-5400 Appendix 1,Page 3 of 70
NEMO I etc.
15 For bonded membrane applications,unless otherwise noted,refer to the following.
MEMBRANE/ADHESIVE COMBINATIONS
REFERENCE LAYER MATERIAL APPLICATION
Base Ply: Flintlastic Base 20,Flintlastic Poly SMS Base Sheet,Flintlastic Ultra Poly SMS Base
Note: Base ply cures overnight prior to application of the ply or cap ply. Karnak No.81 Cold Process Modified Bitumen Adhesive Brush GradeSBS-CAI
Ply: Flintlastic Base 20,Flintlastic Poly SMS Base Sheet,Flintlastic Ultra Poly SMS Base at 1 gal/square
Cap Ply: Flintlastic FR-P,Flintlastic FR-P CoolStar,Flintlastic Premium FR-P,Flintlastic Premium FR-P CoolStar,Flintlastic GMS
BP-CA2 Base Ply: Glasbase Base Sheet,All Weather/Empire Base Sheet,Flintlastic Base 20
Base Ply: Flintlastic Base 20,Flintlastic Poly SMS Base Sheet,Flintlastic Ultra Poly SMS Base
Henry#903 Adhesive at 1.5 gal/square.SBS-CA2 Ply: Flintlastic Base 20,Flintlastic Poly SMS Base Sheet,Flintlastic Ultra Poly SMS Base
Cap Ply: Flintlastic FR-P,Flintlastic FR-P CoolStar,Flintlastic Premium FR-P,Flintlastic Premium FR-P CoolStar,Flintlastic GMS
BP-CA3 Base Ply: Glasbase Base Sheet,All Weather/Empire Base Sheet,Flintlastic Base 20
Base Ply: Flintlastic Base 20,Flintlastic Poly SMS Base Sheet,Flintlastic Ultra Poly SMS Base HB Fuller"Millennium Hurricane Force Membrane Adhesive",beads
SBS-CA3 Ply: Flintlastic Base 20,Flintlastic Poly SMS Base Sheet,Flintlastic Ultra Poly SMS Base spaced 6-inch o.c.
Cap Ply: Flintlastic FR-P,Flintlastic FR-P CoolStar,Flintlastic Premium FR-P,Flintlastic Premium FR-P CoolStar,Flintlastic GMS
Base Ply: Flintlastic Base 20,Flintlastic Poly SMS Base Sheet,Flintlastic Ultra Poly SMS Base
Note: Base ply cures overnight prior to application of the ply or cap ply. FlintBond Brush or Tropical Roofing Products#216 ModifiedSBS-CA4
Ply: Flintlastic Base 20,Flintlastic Poly SMS Base Sheet,Flintlastic Ultra Poly SMS Base Bitumen Adhesive at 1 to 1.5 gal/square.
Cap Ply: Flintlastic FR-P,Flintlastic FR-P CoolStar,Flintlastic Premium FR-P,Flintlastic Premium FR-P CoolStar,Flintlastic GMS
Base Ply: Glasbase Base Sheet,All Weather/Empire Base Sheet,Flintlastic Base 20
BP-AA hot asphalt at 20-40 lbs/square
Ply: One or more Flintglas Ply 4
BP-AA2 Base Ply: Flintglas MS Cap(inverted) hot asphalt in 24-inch diameter spots in 30-inch grid pattern
BP-AA3 Base Ply: Flintglas MS Cap(inverted) hot asphalt in 9-inch diameter spots in grid pattern noted herein.
BP-AA4 Base Ply: Flintglas MS Cap(inverted) hot asphalt in 9-inch wide ribbons spaced as noted herein.
Base Ply: Flintlastic Base 20,Flintlastic Poly SMS Base Sheet,Flintlastic Ultra Poly SMS Base
SBS-AA Ply: One or more Flintlastic Base 20,Flintlastic Poly SMS Base Sheet,Flintlastic Ultra Poly SMS Base hot asphalt at 20-40 lbs/square
Cap Ply: Flintlastic FR-P,Flintlastic FR-P CoolStar,Flintlastic Premium FR-P,Flintlastic Premium FR-P CoolStar,Flintlastic GMS
Base Ply: Flintlastic Ultra Poly SMS Base Sheet,Flintlastic Base 20 TSBS-TA
Ply: One or more Flintlastic Ultra Poly SMS Base Sheet,Flintlastic Base 20 T
torch-applied
Base Ply: One or more Flintlastic APP Base T,Flintlastic STA,Flintlastic STA Plus
APP-TA Flintlastic STA,Flintlastic STA Plus,Flintlastic GTA,Flintlastic GTA CoolStar,Flintlastic GTA-FR,Flintlastic GTA-FR torch-applied
Cap Ply: CoolStar
SBS-SA-H Base Ply: Black Diamond Base Sheet,Flintlastic Ultra Glass SA self-adhering(activated by overlying membrane)
Base Ply: Flintlastic SA PlyBase,Flintlastic SA Mid Ply
SBS-SA Ply: Flintlastic SA PlyBase,Flintlastic SA Mid Ply self-adhering
Cap Ply: Flintlastic SA Cap,Flintlastic SA Cap CoolStar,Flintlastic SA Cap FR,Flintlastic SA Cap FR CoolStar
NEMO ETC,LLC Evaluation Report 3520.03.04-R29 for FL2533-R28
Certificate of Authorization#32455 7"EDITION(2020)FBC NON-HVHZ EVALUATION(Method 1D) Revision 29:04/14/2022
2019 NEMO ETC,LLC CertainTeed Flintlastic®Modified Bitumen Roof Systems,(610) 893-5400 Appendix 1,Page 4 of 70
04 NEMO I etc.
16 Vapor barrier options for use over structural concrete deck followed by bonded insulation carry the following MDP limitations. The lesser of the MDP listings below vs.that for the selected assembly from TABLE
3A applies.
VAPOR BARRIER OPTIONS,STRUCTURAL CONCRETE DECK,ADHERED INSULATION
VAPOR BARRIER INSULATION ADHESIVE
OPTION# PRIMER MDP(PSF)
TYPE ATTACH PER TABLE 3A
C-VB-1. FlintPrime QD Flintlastic SA PlyBase Self-adhering OB500,12-inch o.c.82.5
All Weather/Empire Base Sheet, 3-inch wide side laps and 6-inch wide end laps are HB Fuller"Millennium Hurricane Force
C-VB-2. None M-OSFA or M-PG1,12-inch o.c. -82.5
sealed with HB Fuller"HB Fuller"Millennium Hurricane Force Lap and Flashing Adhesive" Membrane Adhesive HS",max.6-inch o.c.
Flintlastic Ultra Poly SMS Base Sheet, 3-inch wide side laps and 6-inch wide end laps are
C-VB-3. None hot-air-welded,torch-welded or sealed with HB Fuller"HB Fuller"Millennium Hurricane
HB Fuller"Millennium Hurricane Force
M-OSFA or M-PG1,12-inch o.c. -82.5
Force Lap and Flashing Adhesive'
Membrane Adhesive HS",max.6-inch o.c.
C-VB-4. FlintPrime QD Black Diamond Base Sheet,Flintlastic Ultra Glass SA or Flintlastic SA Cap Self-adhering M-OSFA or M-PG1,12-inch o.c. -97.5
C-VB-S. FlintPrime QD Black Diamond Base Sheet,Flintlastic Ultra Glass SA or Flintlastic SA Cap Self-adhering M-OSFA or M-PG1,6-inch o.c. -315.0
C-VB-6. FlintPrime QD Flintlastic GTA Torch-applied M-OSFA or M-PG1,12-inch o.c. -420.0
C-VB-7. FlintPrime QD Flintlastic Base 20 T Torch-applied M-OSFA or M-PG1,12-inch o.c. -495.0
17 The following products are interchangeable within the scope of this Evaluation Report.
ACCEPTABLE ALTERNATES
SUB-CATEGORY MANUFACTURER FBC FILE LISTED PRODUCT HEREIN ALTERNATE
M-OSFA FlintFast QS Insulation Adhesive
Adhesives H.B.Fuller Company FL1800
M-PG1 FlintFast LV Insulation Adhesive
Trufast#12 DP FlintFast#12 Fastener
Trufast#14 HD FlintFast#14 Fastener
Roofing Altenloh,Brinck and Co.U.S.,
FL4500
Trufast#15 EHD FlintFast#15 EHD Fastener
Fasteners Inc. Trufast 2"Barbed Metal Seam Plate FlintFast 2"Barbed Seam Plate
Trufast 2.4"Barbed Metal Seam Plate FlintFast 2.4"Barbed Seam Plate
Trufast 3"Metal Insulation Plate FlintFast 3"Insulation Plate
ACFoam II FlintBoard ISO
Atlas Roofing FL17989
ACFoam III FlintBoard ISO Cold
Roofing
H-Shield FlintBoard"ISO
Insulation Hunter Panels FL5968
H-Shield CG FlintBoard"ISO Cold
Georgia-Pacific Gypsum,LLC FL1250 DensDeck Prime DensDeck StormX Prime Roof Board
18 "MDP"=Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads.Refer to FBC 1609 for determination of design wind loads.
NEMO ETC,LLC Evaluation Report 3520.03.04-R29 for FL2533-R28
Certificate of Authorization#32455 7T"EDITION(2020)FBC NON-HVHZ EVALUATION(Method 10) Revision 29:04/14/2022
2019 NEMO ETC,LLC CertainTeed Flintlastic'Modified Bitumen Roof Systems,(610)893-5400 Appendix 1,Page 5 of 70
NEMO I etc.
TABLE 1G: WOOD DECKS—NEW CONSTRUCTION,REROOF(TEAR-OFF)OR RECOVER
SYSTEM TYPE E-2: NON-INSULATED,MECHANICALLY ATTACHED BASE SHEET,BONDED ROOF COVER
System Deck Base Sheet Roof Cover(Note 15)MDP
No. Note 1) Base Fasteners Attach
Primer
Base Ply Cap Ply (psf)
Glasbase Base Sheet,Flintlastic
Min.15/32-inch
Base 20,All Weather/Empire Base
8-inch o.c.at 4-inch lap and 8- Optional)
W-97 plywood,24-inch
Sheet,Flintlastic Poly SMS Base Trufast#14 HD with Trufast 3"Metal
inch o.c.at three(3)equally None BP-AA,SBS- SBS-AA 97.5
span
Sheet,Flintlastic Ultra Poly SMS Insulation Plate
spaced,staggered center rows AA or SBS-TA
Base Sheet or Flintglas MS Cap
inverted)
Glasbase Base Sheet,Flintlastic
Min.19/32-inch Base 20,Flintlastic Poly SMS Base 7-inch o.c.at 3-inch lap and 7- BP-AA,SBS-
SBS-AA orW-98 plywood,24-inch Sheet,Flintlastic Ultra Poly SMS Note 2 inch o.c.in three(3),equally None AA,SBS-TA 105.0
span Base Sheet or Flintglas MS Cap spaced,staggered center rows or APP-TA
APP-TA
inverted)
Min.19/32-inch
Dekfast DF-#14-PH3 with PLT-H-2-7/8 or OMG 7-inch o.c.at 3-inch lap and 7-
W-99 plywood,24-inch Flintlastic APP Base T
14 HD with OMG 3 in.Round Metal Plate
inch o.c.in three(3),equally None APP-TA APP-TA 105.0
span spaced,staggered center rows
Glasbase Base Sheet,Flintlastic
Optional)
Min.15/32-inch Base 20,Flintlastic Poly SMS Base OMG#14 HD with OMG 3 in.Round Metal 6-inch o.c.at 4-inch lap and 6—BP—AA, SBS- SBS-AA orW-100 plywood,24-inch Sheet,Flintlastic Ultra Poly SMS Plate or Trufast#12 DP or#14 HD with Trufast inch o.c.in four(4),equally None 127.5
AA,SBS TA APP-TA
span Base Sheet or Flintglas MS Cap 3"Metal Insulation Plate spaced,staggered center rows
or APP-TA
inverted)
Min.15/32-inch
OMG#14 HD with OMG 3 in.Round Metal 6-inch o.c.at 4-inch lap and 6
W-101 plywood,24-inch Flintlastic APP Base T
Plates
inch o.c.in four(4),equally None APP-TA APP-TA 127.5
span spaced,staggered center rows.
COLD-APPLIED SYSTEMS:
Glasbase Base Sheet,Flintlastic
Base 20,All Weather/Empire Base
Min.15/32-inch
Sheet,Flintlastic PolySMS Base Trufast#12 DP or#14 HD with Trufast 3"8-inch o.c.at 4-inch lap and 8
W-102 plywood,24-inch inch o.c.in three(3),equally None
Optional)
SBS-CA1 52.5
span
Sheet,Flintlastic Ultra Poly SMS Metal Insulation Plate
spaced,staggered center rows
SBS-CA1
Base Sheet or Flintglas MS Cap
inverted)
TABLE 1H: WOOD DECKS—NEW CONSTRUCTION OR REROOF(TEAR-OFF)
SYSTEM TYPE F:NON-INSULATED,BONDED ROOF COVER
System Deck
Primer
Roof Cover(Note 15)
MDP(psf)
No.Note 1) Base Ply Ply Cap Ply
W-103
APA rated,min.7/16 CAT,0.418 in.,Exposure 1,
FlintPrime QD Flintlastic SA Mid Ply,self-adheringOSBsheathing,24-inch span
Y Optional)SBS-SA SBS-SA 90.0
W-104 Min.15/32-inch plywood,24-inch span FlintPrime QD SBS-SA-H Optional)SBS-TA,APP-TA SBS-TA,APP-TA 112.5
W-105 Min.15/32-inch plywood,24-inch span FlintPrime QD SBS-SA Optional)SBS-SA SBS-SA 127.5
NEMO ETC,LLC Evaluation Report 3520.03.04-R29 for FL2533-R28
Certificate of Authorization#32455 7"EDITION(2020)FBC NON-HVHZ EVALUATION(Method 10) Revision 29:04/14/2022
2019 NEMO ETC,LLC CertainTeed Flintlastic®Modified Bitumen Roof Systems,(610)893-5400 Appendix 1,Page 18 of 70