163 Belvedere St RES21-0345 ARCH DWGS REVIS 3-6-23_11ST LEVEL FLOOR PLAN
SCALE: 1/4" = 1'-0"
TEMP GLASS AS REQUIRED.
CONTRACTOR MUST VERIFY ALL DIMENSIONS.
IF SHOWER HAS GLASS ENCLOSURE,
SAFETY GLAZING REQUIRED PER
FBC R-308.4.5
REF
2ND LEVEL FLOOR PLAN
SCALE: 1/4" = 1'-0"
33'
20'13'
10'10'55'51'4'5'-11"5'-11"11'-10"6'5'-2"16'-2"55'6'4'36'5'4'2'-4"11'-8"2'-4"8'-10"7'-2"3'-8"33'
13'-2"19'-10"
9'-11"9'-11"6'-4"6'-10"
6'-10"
2-3060 TWIN SH
2-3060 TEMP TWIN SH 6080 FRENCH TEMP
3060 SH3060 SH2-3060 TWIN SHOHC
RANGE
5-SH
208
0
OHC OHCDW SINK5-SHOHC2880
CURB
WH
HB
16070 OHD
4050 SH TEMP2880OPEN UNDER STAIRSHANDRAIL2'-4"5'-6"
3'-6"2'-4"14'-2"2'-4"1'-10"4'-6"1'-2"10'-6"5'-6"
7'-6"1'-8"3'-10"3'-8"2'3'-10"55'10'41'4'2'-6"2'-10"4'-5"2'-4"2'10'-10"11'-4"33'55'9'1'41'4'3'-5"10'3'-5"2'6'-8"12'-2"3'-4"3'-8"
33'
3050 SH
1'R&S26682668
2068R&S2668AHU 26681668
5-SH
2668HANDRAIL2668
R&S
6068
3050 SH2x6 WALL2x6 WALL2668 R&S5-SHR&SR&SR&S
R&S
GUARDRAIL
GUARDRAIL2'8'3'-4"3'-6"5'-2"4'-2"5'-8"3'-6"5'-4"2'-4"26684'-2"3'2'-4"5'-4"6'1'-8"1'8'3'-4"2068
2068
LINE OF WALL BELOW
LINE OF WALL BELOW3050 SH3050 SHA/C
LANAI
19'-10"X9'-0"
10' CLG.
DINING
13'-0"X11'-2"
10' CLG.
GREAT ROOM
19'-4"X15'-8"
10' CLG.
KITCHEN
13'-10"X11'-6"
10' CLG.
20 MINUTE FIRE
RATED DOOR
GARAGE
19'-4"X20'-10"
10' CLG.
ENTRY
13'-0"X4'-0"
10' CLG.
3068
DECK
19'-10"X4'-0"
MASTER BEDROOM
14'-0"X16'-2"
TRAY CLG.
BEDROOM #2
11'-10"X12'-6"
9' CLG..
BEDROOM #3
13'-0"X11'-0"
9' CLG..
BEDROOM #4
12'-10"X11'-0"
9' CLG..
GUARDRAIL
MASTER BATH
10'-2"X13'-10"
9' CLG..
1/2 WALL WITH
1X CAP
BAR TOP AT
COUNTER HEIGHT
3050 TEMP SH
EGRESS
3050 SH
EGRESS 3050 SHEGRESS5070 SGD
30"x22"
ATTIC
ACCESS
WALL TO 42" WITH
GLASS ABOVE
2'-6"3'-4"6068OPTIONAL
DOG DOOR
1668PEDESTAL
SINK
3050 TEMP SH
2'-5"4'-11"4'-11"2'-5"
ON/OFF
VALVE
2880OPTIONAL2868 BARNDOOROPTIONAL2668 BARNDOOR28803'-6"4'-4"5'-8"15'-8"
3'-2"10'-2"
2'-4"
2'-8"4'-6"3'-2"3'-2"
3'-10"13'-4"13'-6"
12'-2"
14'-8"7'-10"
10'-6"
6'-2"
19'-10"13'-2"
9'-11"9'-11"
W D
9'-2"
2030 TEMP SH
20684040 SH OBS TEMP4'-9"9'-6" CLG.
9' CLG..
HALLWAY
9' CLG..2'0" TEMP5'-4"12'-10"48" VANITY
48" VANITY
2'-2"2'-7"1'-10"2'-7"60" VANITY
6'-2"
1'-10"6'
4'-8"1'-6"
4'-4"
4'-4"
HB
6"PANTRY
10' CLG.
LAUNDRY
10'-2"X5'-6"
10' CLG.POWDER
5'-2"X5'-2"
10' CLG.6"2'-2"2'-6"3'-6"GUARDRAIL9'2'-10"3'-10"9'-3"6'-3"
4"X4" COLUMN
WRAPPED TO
6"X6" (TYP.)
2'10'6'-6"4'-6"
4'1'-6"6'-7"
4"X4" COLUMN WITH
STONE TAPERED
COLUMN WRAP (TYP.)
1'-4"
3050 TEMP SH
GARAGE
19'-4"X20'-10"
10' CLG.
19
18
17
16
15
14
13
12
11
10
9
8
7
1234
5
6
7
8
9
10
11
1ST FLOOR HEATED AREA
2ND FLOOR HEATED AREA
TOTAL
GARAGE
FRONT ENTRY
LANAI
TOTAL UNDER ROOF
DECK
BUILDING AREAS
1,033 SF
1,314 SF
2,347 SF
424 SF
52 SF
176 SF
2,999 SF
139 SF
CONDITIONED SPACE = 22,156 CF
OPTIONAL
2880
6"
6"
6"6"DateSheet
Job
Scale
DateNo.RevisionsBy7654321AMERICAN CLASSIC HOMES, LLC4550 St. Augustine RoadJacksonville, FL 32207(904) 351-0308COPYRIGHT WARNING!CTHESE PLANS AND SPECIFICATIONS ARE THE SOLE ANDEXCLUSIVE PROPERTY OF AMERICAN CLASSIC HOMES. THEUSE OF THESE PLANS AND SPECIFICATIONS OR ANYPORTION THEREOF OR REPRODUCTION OF SAME WITHOUTTHE PRIOR WRITTEN CONSENT OF AMERICAN CLASSICHOMES IS STRICTLY PROHIBITED AND WILL BE PROSECUTEDTO THE FULLEST EXTENT OF THE LAWA1.1
2353R-10/9
03-10-21
AS SHOWN2 STORY RESIDENCE1ST AND 2ND LEVEL FLOOR PLANSJACKSONVILLE, FLSHEET NUMBER SHEET NAME
CODE INFORMATION
BUILDING CODE:
CONSTRUCTION TYPE:
OCCUPANCY CLASS:
2020 FLORIDA BUILDING CODE RESIDENTIAL 7TH ADDITION
2020 FLORIDA BUILDING CODE PLUMBING
2020 FLORIDA BUILDING CODE MECHANICAL
2017 NEC
5B
R-3
DRAWING INDEX
NOTE:
A FOUNDATION SURVEY SHALL BE PERFORMED AND A COPY
OF THE SURVEY SHALL BE ON THE SITE FOR THE BUILDING
INSPECTORS USE PRIOR TO FRAMING INSPECTION.
A1.1
A1.2
A1.3
A2.1
A3.1
1ST AND 2ND LEVEL FLOOR PLANS
FOUNDATION AND ROOF PLANS
1ST AND 2ND LEVEL ELECTRIC PLANS
ELEVATIONS
DETAIL SHEET
TEMP
163 Belvedere Street, Atlantic Beach, FL 32233
Architectural Drawing page A1.1, Master BathVerify width of tempered shower door opening is 2'0".
1
1. Revision to verify Master Bath width of tempered shower door opening as 2'0"2/27/23
ROOF PLAN
SCALE: 1/4" = 1'-0"6' OFF-RIDGE VENTIF SOFFIT EXTENDS LESS THAN 3' OF PROPERTY LINE, FIRE BLOCK THIS AREA (SEE DETAIL SHEET)IF SOFFIT EXTENDS LESS THAN 3' OF PROPERTY LINE, FIRE BLOCK THIS AREA (SEE DETAIL SHEET)4' OFF-RIDGE VENT1'-4" OVERHANG
(TYP.)
12
5
12
5 125125RIDGERIDGE12
5
RIDGE12
5
HIP 125HIPHIPHI
P
VALLEYVALLEY1ST FLOOR WALL
BELOW (TYP.)
1'-4" OVERHANG
(TYP.)
FOUNDATION PLUMBING PLAN
SCALE: 1/4" = 1'-0"
33'-10"
8'-1"4'-9"55'-4"4'-4"24'-6"13'-10"33'-4"
9'-9"9'-9"
12'-10"46'4'-4"5'36'4'-10"5'-2"5'19'-4"
8'14'-4"18'2'-6"10'SEE ENGINEERING FOR DETAILS AND NOTES
-4"
-4"
-4"
WH
14'-6 3/4"
17'-2"
2'-4"
4'-5"
1'-10"3'-7"10"2" SLOPE4"
20'-6"
6"6"3'-10"6"3'-10"1'1'
13'-10"
1'-10 1/2"
16'-3" X 9-1/2" RECESS 1'-10 1/2"
A/C
3'
3'X9' STOOP 9'3'3'
VENT CALCULATIONS
VENTED SOFFIT
VENTILATED ATTIC AREA: 1,314 SQ. FT.
1,314 / 300 = 4.38 SQ. FT.
4.38 SQ. FT. X 144 = 631 SQ. IN. TOTAL NET FREE VENT AREA
631 X 50% = 315.5 SQ. IN. NET FREE
SOFFIT REQUIREMENT = 6.55 SQ. IN. NET FREE PER LF
315.5 / 6.55 = 48 LF VENTED SOFFIT REQUIRED
OFF-RIDGE VENTS
VENTILATED ATTIC AREA: 1,314 SQ. FT.
1,314 / 300 = 4.38 SQ. FT.
4.38 SQ. FT. X 144 = 631 SQ. IN. TOTAL NET FREE VENT AREA
631 X 50% = 315.5 SQ. IN. NET FREE
(1) 6' OFF-RIDGE VENT REQUIRED (216 SQ. IN. EACH)
(1) 4' OFF-RIDGE VENT REQUIRED (144 SQ. IN. EACH)DateSheet
Job
Scale
DateNo.RevisionsBy7654321AMERICAN CLASSIC HOMES, LLC4550 St. Augustine RoadJacksonville, FL 32207(904) 351-0308COPYRIGHT WARNING!CTHESE PLANS AND SPECIFICATIONS ARE THE SOLE ANDEXCLUSIVE PROPERTY OF AMERICAN CLASSIC HOMES. THEUSE OF THESE PLANS AND SPECIFICATIONS OR ANYPORTION THEREOF OR REPRODUCTION OF SAME WITHOUTTHE PRIOR WRITTEN CONSENT OF AMERICAN CLASSICHOMES IS STRICTLY PROHIBITED AND WILL BE PROSECUTEDTO THE FULLEST EXTENT OF THE LAWA1.2
2353R-10/9
03-10-21
AS SHOWN2 STORY RESIDENCEFOUNDATION AND ROOF PLANSJACKSONVILLE, FL163 Belvedere Street, Atlantic Beach, FL 32233
1ST LEVEL ELECTRIC PLAN
SCALE: 1/4" = 1'-0"
REF
2ND LEVEL ELECTRIC PLAN
SCALE: 1/4" = 1'-0"
DW
WH
AHU
A/C
OPTIONAL COACH
LIGHTS
OPTIONAL FLOOD
LIGHT
OPTIONALFLOOD
LIGHT
OPTIONAL RECESSED
LIGHTS
W D
GFCIGFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI GFCI
WP/GFCI
WP/GFCI
WP/GFCI
GFCI GFCI
WP/GFCI
WP/GFCI
GFCI
GFCI
GFCI
GFCI
BELOW
3
3
3 3
3
3
CEILING
10'12'GFCI
LIGHT FIXTURE / EXHAUST FAN
GFCI
WALL MOUNTED LIGHT FIXTURE
(2) 110V OUTLETS
SINGLE POLE SWITCH
(2) 110V WATERPROOF GFCI OUTLETS (INTERIOR)
(1) 220V DISCONNECT
LEGEND
THREE WAY SWITCH3
PRE-WIRE AND BRACE FOR CEILING FAN
WP/GFCI (2) 110V WATERPROOF GFCI OUTLETS (EXTERIOR)
SMOKE/CARBON MONOXIDE DETECTOR
OPTIONAL FLOOD LIGHT
PENDANT LIGHTING
1'X4' FLOURESCENT LIGHT
CEILING MOUNTED LIGHT FIXTURE
RECESSED LIGHT FIXTURE
NOTES:
1. ELECTRICAL LAYOUT MUST MEET STATE AND LOCAL
CODES. ELECTRICIAN TO VERIFY.
2. ALL FIXTURES TO BE CFL OR LED.
3. ALL OUTLETS THAT ARE NOT GFI TO BE AFCI PROTECTED.
CABLE OUTLET
PHONE OUTLET DateSheet
Job
Scale
DateNo.RevisionsBy7654321AMERICAN CLASSIC HOMES, LLC4550 St. Augustine RoadJacksonville, FL 32207(904) 351-0308COPYRIGHT WARNING!CTHESE PLANS AND SPECIFICATIONS ARE THE SOLE ANDEXCLUSIVE PROPERTY OF AMERICAN CLASSIC HOMES. THEUSE OF THESE PLANS AND SPECIFICATIONS OR ANYPORTION THEREOF OR REPRODUCTION OF SAME WITHOUTTHE PRIOR WRITTEN CONSENT OF AMERICAN CLASSICHOMES IS STRICTLY PROHIBITED AND WILL BE PROSECUTEDTO THE FULLEST EXTENT OF THE LAWA1.3
2353R-10/9
03-10-21
AS SHOWN2 STORY RESIDENCE1ST AND 2ND LEVEL ELECTRIC PLANSJACKSONVILLE, FL163 Belvedere Street, Atlantic Beach, FL 32233
FRONT ELEVATION
SCALE: 1/4" = 1'-0"
12
5
12
5
FIBERGLASS SHINGLES
(TYP.)
0'-0" FINISHED FLOOR
HARDIEBOARD LAP
SIDING (TYP.)
4" HARDIE TRIM (TYP.)
10'-1 1/8" BEARING HEIGHT
11'-5 1/8" 2ND FLOOR
27'-9 5/8" TOP OF ROOF
20'-6 1/4" BEARING HEIGHT
4"X4" COLUMN WITH
STONE TAPERED
COLUMN WRAP (TYP.)
LEFT SIDE ELEVATION
SCALE: 1/4" = 1'-0"
12
5
12
5
FIBERGLASS SHINGLES
(TYP.)
4" HARDIE TRIM (TYP.)
0'-0" FINISHED FLOOR
4' OFF-RIDGE VENT
HARDIEBOARD T-111
SIDING; OPTIONAL LAP
SIDING (TYP.)
HARDIEBOARD LAP
SIDING (TYP.)
4"X4" COLUMN
WRAPPED TO 6"X6"
10'-1 1/8" BEARING HEIGHT
11'-5 1/8" 2ND FLOOR
27'-9 5/8" TOP OF ROOF
20'-6 1/4" BEARING HEIGHT
RIGHT SIDE ELEVATION
SCALE: 1/4" = 1'-0"
12
5
12
5
FIBERGLASS SHINGLES
(TYP.)
HARDIEBOARD T-111
SIDING; OPTIONAL LAP
SIDING (TYP.)
4" HARDIE TRIM (TYP.)
6' OFF-RIDGE VENT
4"X4" COLUMN
WRAPPED TO 6"X6"
0'-0" FINISHED FLOOR
10'-1 1/8" BEARING HEIGHT
11'-5 1/8" 2ND FLOOR
27'-9 5/8" TOP OF ROOF
20'-6 1/4" BEARING HEIGHT
REAR ELEVATION
SCALE: 1/4" = 1'-0"
12
5
12
5
FIBERGLASS SHINGLES
(TYP.)
4" HARDIE TRIM (TYP.)
0'-0" FINISHED FLOOR
HARDIEBOARD T-111
SIDING; OPTIONAL LAP
SIDING (TYP.)
4"X4" COLUMN
WRAPPED TO 6"X6"
(TYP.)
10'-1 1/8" BEARING HEIGHT
11'-5 1/8" 2ND FLOOR
27'-9 5/8" TOP OF ROOF
20'-6 1/4" BEARING HEIGHT
DateSheet
Job
Scale
DateNo.RevisionsBy7654321AMERICAN CLASSIC HOMES, LLC4550 St. Augustine RoadJacksonville, FL 32207(904) 351-0308COPYRIGHT WARNING!CTHESE PLANS AND SPECIFICATIONS ARE THE SOLE ANDEXCLUSIVE PROPERTY OF AMERICAN CLASSIC HOMES. THEUSE OF THESE PLANS AND SPECIFICATIONS OR ANYPORTION THEREOF OR REPRODUCTION OF SAME WITHOUTTHE PRIOR WRITTEN CONSENT OF AMERICAN CLASSICHOMES IS STRICTLY PROHIBITED AND WILL BE PROSECUTEDTO THE FULLEST EXTENT OF THE LAWA2.1
2353R-10/9
03-10-21
AS SHOWN2 STORY RESIDENCEELEVATIONSJACKSONVILLE, FL163 Belvedere Street, Atlantic Beach, FL 32233
TYPICAL WALL SECTION
SCALE : 1" = 1'-0"
DRYWALL OR OTHER FINISH
MATERIAL IF APPLICABLE
SEE ELEVATIONS FOR
EXTERIOR FINISH MATERIAL
R13 INSULATION
10'R-30
INSULATION
5/8" GYP. BOARD
BEARING HEIGHT
1'-4"
16" FLOOR TRUSS
DRYWALL OR OTHER FINISH
MATERIAL IF APPLICABLE
R13 INSULATION
9'2ND FLOOR
2"X4" FRAMING (TYP.)
2"X4" FRAMING (TYP.)
FASCIA STYLE
PER BUILDER
VINYL SOFFIT (TYP.)
FIBERGLASS SHINGLES OR APPROVED
EQUAL
PRE-ENGINEERED TRUSS ROOF SYSTEM
R-38
INSULATION
TYPE "X" 5/8" GYPSUM
BOARD
12
RP SEE
ELEV.
DOUBLE 2X TOP PLATE WITH
APPROVED HURRICANE
ANCHOR AT ENDS OF EACH
TRUSS
*IF WITHIN 3' OF PROPERTY LINE, FIRE
BLOCK AND FIRE CAULK BETWEEN
TRUSSES TO BOTTOM OF ROOF DECK
FIRE CAULKED*
2X BLOCKING*
NOTE: THIS WALL SECTION IS FOR
AESTHETIC PURPOSES ONLY. VERIFY
ALL CONDITIONS SHOWN WITH
BUILDER. SEE STRUCTURAL PLANS
FOR CONNECTIONS AND TIE DOWN
INFORMATION.SECTION A-A
THROUGH WINDOW JAMB
1
FLASHING
SEALANT BEAD
BEHIND MOUNTING
FLANGE.
JAMB FLASHING4
STEPS
2
3
4
WEATHER RESITIVE BARRIER (WRB) APPLIED PRIOR TO THE WINDOW INSTALLATION.
FLASHING APPLIED OVER THE FACE OF THE MOUNTING FLANGE.
SECURE WRB
AT HEAD
HEAD FLASHING
A
61 8 12"A
JAMB FLASHING
6
6
3
IN WATER SHEDDING FASHION, STARTING AT THE
BASE OF THE WALL & WORKING TOWARDS THE TOP,
INSTALL THE WRB TO THE FACE OF THE SHEATHING.
CUT AT INVERTED "Y".
CUT
LINE
INSTALL 6" WIDE SELF ADHESIVE SILL FLASHING THAT
EXTENDS 4" BEYOND OPENING.
9"
SHIM AND ADJUST WINDOW TO ACHIEVE SQUARE,
PLUMB, AND LEVEL CONDITION. USE CORROSION
RESISTANT FASTENERS. FASTEN WINDOWS PER
WINDOW MANUFACTURER SPECIFICATIONS.
SILL FLASHING
9"
1
9"135°
1
SEALANT
WINDOW INSTALLATION
SCALE: N.T.S.
5
APPLY A 4" SELF ADHESIVE JAMB FLASHING OVERLAPPING THE
WINDOW FLANGE EXTENDED 4" PAST THE ROUGH OPENING.
APPLY BEAD OF SEALANT AT BACK OF WINDOW
FLANGE & SET WINDOW USING PAN HEAD SCREWS
TO FACILITATE INSPECTION.
REMOVE PREVIOUSLY APPLIED TAPE,
ALLOWING WRB TO LAY FLAT OVER HEAD
FLASHING. APPLY NEW SHEATHING TAPE
OVER DIAGONAL CUT - SEE DIAGRAM.
FLASHING AT HEAD EXTENDS
1" BEYOND JAMB FLASHING.
5
6
EXTEND JAMB FLASHING TO
OVERLAP SILL FLASHING. EXTEND
JAMB FLASHING 8-1/2" ABOVE
ROUGH OPENING AT HEAD. TUCK
TOP OF JAMB FLASHING UNDER
THE FLAP OF WRB AT THE HEAD.
SEE DIAGRAM.
INTERIOR VIEW
TOP LEFT CORNER OF WINDOW
APPLY CONT. SELF ADHESIVE FLASHING THAT
EXTENDS AT LEAST 4" BEYOND ROUGH OPENING.
EMBED BOTTOM OF THE HEAD FLASHING
AGAINST THE PREVIOUSLY APPLIED
SEALANT (FLASHING GOES OVER SEALANT).
EXTEND HEAD FLASHING BEYOND EACH
JAMB FLASHING. FASTEN IN PLACE.
AT A 45 DEGREE ANGLE,
CAREFULLY CUT THE BARRIER ON
A DIAGONAL. GENTLY RAISE THE
TOP EDGE OF THE BARRIER UP AND
TAPE THE TOP CORNERS AND
CENTER TO THE EXTERIOR WRB
SURFACE ABOVE.
APPLY A 4" SELF ADHESIVE HEAD FLASHING OVERLAPPING THE
WINDOW FLANGE EXTENDED 4" PAST THE ROUGH OPENING.
WEATHER RESISTANT BARRIER (WRB)
5
FLASHING DETAILS AND SHINGLE INFORMATION
SCALE : 3" = 1'-0"
SHINGLES:
UL CLASS A FIRE RATING: ASTM D 3018, TYPE I
VALLEY FLASHING:
26 GA. GALVANIZED, 18" WIDE
FASTENING:
(4) 11 OR 12 GAUGE NAILS 1-1/4" LONG WITH 3/8" Ø HEAD
UL WIND RESISTANCE:
UASTM D 3161, TYPE I (MODIFIED TO 110 MPH)2-1/2"2-3/4"
26 GAUGE GALVANIZED
2-1/2" METAL DRIP EDGEA
5"5"26 GAUGE GALVANIZED
5"X5" ANGLE FLASHINGB 32 GAUGE GALVANIZED
"Z" FLASHINGC1/2"2-1/8"3/8" OR 5/8"
PIPE BOOT
GALVANIZED METAL FLANGE
PLUMBING STACK FLASHING DETAIL
NOT TO SCALE
OFF RIDGE VENT DETAIL
NOT TO SCALE
FIBERGLASS SHINGLE ROOFING OVER
UNDERLAYMENT
INSTALL SHINGLES OVER ORV VENT
FLANGE AT HEAD
GALVANIZED METAL ORV WITH BAFFLE SET IN
PLASTIC ROOF CEMENT OR SEALANT
SCREEN
INSTALL ORV FLANGE OVER
SHINGLES AT BASE
7/16" OSB OVER
PRE-ENGINEERED WOOD
TRUSSES
OVER PRE-ENGINEERED
WOOD TRUSSES
VALLEY FLASHING DETAIL
NOT TO SCALE
24" WIDE METAL VALLEY
FLASHING OVER 15# FELT
OVER 7/16" OSB
VALLEY SHINGLE INSTALLATION:
INSTALL SHINGLES USING WEAVE METHOD
1. EXTEND (1) FULL END SHINGLE MINIMUM 12" PAST CENTER
LINE OF VALLEY. SEE MANUFACTURERS WRITTEN
INSTRUCTIONS FOR ADDITIONAL INSTALL INFORMATION.
2. DO NOT NAIL MINIMUM 6" FROM VALLEY CENTER LINE.
DOOR FLASHING INSTALLATION AND DETAIL
SCALE: N.T.S.
APPROVED WEATHER BARRIER OVER USB
CUT WEATHER BARRIER IN AND
AROUND JAMBS
SET THRESHOLD IN BED OF
SEALANT
INSTALL 4" WIDE SELF-ADHERING
MEMBRANE FLASHING OVERLAPPING DOOR
FRAME BY 1/4" AND 1" BEYOND DOOR JAMB
INSTALL 4" WIDE SELF-ADHERING
MEMBRANE FLASHING OVERLAPPING
DOOR FRAME BY 1/4"
R703.8 FLASHING:
APPROVED CORROSION-RESISTANT FLASHING SHALL BE APPLIED
SHINGLE-FASHION IN SUCH A MANOR TO PREVENT ENTRY OF WATER INTO THE
WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING STRUCTURAL
FRAMING COMPONENTS. THE FLASHING SHALL EXTEND TO THE SURFACE OF THE
EXTERIOR WALL FINISH. APPROVED ANTI-CORROSION RESISTANT FLASHING SHALL
BE INSTALLED AT ALL OF THE FOLLOWING LOCATIONS:
1. AT THE INTERSECTION OF CHIMNEYS OR OTHER MASONRY CONSTRUCTION WITH
FRAME OR STUCCO WALLS, WITH PROJECTING LIPS ON BOTH SIDES UNDER STUCCO
COPINGS.
2. UNDER AND AT THE ENDS OF MASONRY, WOOD OR METAL COPINGS AND SILLS.
3. CONTINUOUSLY ABOVE ALL PROJECTING WOOD TRIM.
4. WHERE EXTERIOR PORCHES, DECKS OR STAIRS ATTACH TO A WALL OR FLOOR
ASSEMBLY OR WOOD FRAMED CONSTRUCTION.
5. AT ALL WALL AND ROOD INTERSECTIONS.
6. AT BUILT IN GUTTERS.
GUARDRAIL NOTE:
DEPENDING ON FIELD CONDITIONS, DIMENSIONS MAY VARY BUT MUST COMPLY WITH FLORIDA BUILDING
CODES R312.1-R312.2 FOR GUARDRAIL REQUIREMENTS AND OPENINGS.
*HEIGHT SHALL BE 36" MIN. WHEN PORCH, BALCONY OR RAISED FLOOR EXCEEDS 30" ABOVE FLOOR OR
GRADE AND SHALL BE 34" ON OPEN SIDES OF STAIRS THAT EXCEED 30" OR MORE ABOVE FLOOR OR
GRADE.
*OPENINGS SHALL HAVE INTERMEDIATE RAILS OR CLOSURES WHICH DO NOT ALLOW PASSAGE OF
SPHERE 4" OR GREATER IN DIAMETER. REQUIRED GUARD RAILS ON THE SIDES OF STAIR TREADS SHALL
NOT ALLOW SPHERE GREATER THAN 4-3/8" IN DIAMETER TO PASS THROUGH.
GENERAL NOTES:
1. PARKING BUMPER (IF REQUIRED) MUST BE INSTALLED BEFORE C.O.
2. 5/8" TYPE "X' GYP. BOARD REQUIRED ON CEILING OF GARAGE WHERE HABITAL SPACE IS
ABOVE PER FBC R302.6.
3. HVAC PENETRATING RATED ASSEMBLIES TO COMPLY WITH FBC R302.5.
4. UNDER STAIR PROTECTION TO COMPLY WITH FBC R302.7 (IF ACCESSIBLE).
HANDRAIL NOTE:
DEPENDING ON FIELD CONDITIONS, DIMENSIONS MAY VARY BUT MUST COMPLY WITH FLORIDA BUILDING
CODES R311.5.6-R311.5.6.3 FOR HANDRAIL HEIGHT CONTINUITY AND SIZE.
*HEIGHT: MUST BE BETWEEN 34-38" MEASURED VERTICALLY FROM SLOPED PLANE.
*CONTINUITY: HANDRAIL MUST BE CONTINUOUS THROUGH FULL LENGTH OF FLIGHT FROM POINT
DIRECTLY ABOVE HIGHEST RISER TO POINT DIRECTLY ABOVE LOWEST RISER. HANDRAIL ENDS SHOULD
TERMINATE IN NEWEL POSTS OR SAFETY TERMINAL OR RETURN TO WALL. HANDRAILS SHALL BE
ALLOWED TO BE INTERRUPTED BY NEWEL POSTS.
*SIZE: SHALL HAVE OUTSIDE DIAMETER BETWEEN 1-1/4"-2" IF CIRCULAR. SHALL HAVE BETWEEN 4-6"
PERIMETER IF NOT CIRCULAR.
STAIR NOTE:
DEPENDING ON FIELD CONDITIONS, DIMENSIONS MAY VARY BUT MUST COMPLY WITH FLORIDA BUILDING
CODES R311.5.1-R311.5.5 FOR TREAD DEPTH, RISER HEIGHTS AND STAIR WIDTHS.
*RISERS: 7-3/4" MAXIMUM WITH NO MORE THAN 3/8" DIFFERENCE BETWEEN HIGHEST AND LOWEST
RISER.
TREADS: 10" MINIMUM DEPTH WITH NO MORE THAN 3/8" DIFFERENCE BETWEEN LONGEST AND
SHORTEST TREAD. THE SUM OF 2 TREADS AND 1 RISER TO BE NOT LESS THAN 24" AND NOT MORE THAN
25".
*WIDTH: 36" MINIMUM CLEAR WIDTH ABOVE HANDRAIL AND 31-1/2" BELOW HANDRAIL.
GUARDRAIL DETAIL
SCALE : 1 1/2" = 1'-0"3'TO REJECT PASSAGEOF 2" SPHERETO REJECT PASSAGE
OF 4" SPHERE
TOP OF FINISH FLOOR
8" CMU; SEE STRUCTURAL
CONCRETE FOOTING; SEE
STRUCTURAL
DRYWALL OR OTHER FINISH
MATERIAL IF APPLICABLE
SEE ELEVATIONS FOR
EXTERIOR FINISH MATERIAL
NOTE: THIS WALL SECTION IS FOR
AESTHETIC PURPOSES ONLY. VERIFY
ALL CONDITIONS SHOWN WITH
BUILDER. SEE STRUCTURAL PLANS
FOR CONNECTIONS AND TIE DOWN
INFORMATION.
TYPICAL WALL SECTION
(STEM WALL OPTION)
SCALE : 1" = 1'-0"
10" MIN.7-3/4" MAX.STAIR DETAIL
SCALE : 1 1/2" = 1'-0"34"-38"DateSheet
Job
Scale
DateNo.RevisionsBy7654321AMERICAN CLASSIC HOMES, LLC4550 St. Augustine RoadJacksonville, FL 32207(904) 351-0308COPYRIGHT WARNING!CTHESE PLANS AND SPECIFICATIONS ARE THE SOLE ANDEXCLUSIVE PROPERTY OF AMERICAN CLASSIC HOMES. THEUSE OF THESE PLANS AND SPECIFICATIONS OR ANYPORTION THEREOF OR REPRODUCTION OF SAME WITHOUTTHE PRIOR WRITTEN CONSENT OF AMERICAN CLASSICHOMES IS STRICTLY PROHIBITED AND WILL BE PROSECUTEDTO THE FULLEST EXTENT OF THE LAWA3.1
2353R-10/9
03-10-21
AS SHOWN2 STORY RESIDENCEDETAIL SHEETJACKSONVILLE, FL4 1/4"
STONE APPLICATION DETAIL
SCALE: N.T.S.
EXTERIOR WALLS SHALL HAVE THE EXT.
SHEATHING RAISED OFF OF THE
CONCRETE FOUNDATION AND ALIGNED
WITH THE FACE OF THE FOUNDATION
STONE OVER LATH & BARRIER
TERMINATE STONE AT BASE OF WOOD
STRUCTURE PER ASTM C-929 A2.2.2
DRIP SCREED PER ASTM 1063-03CONCRETE
SLAB
P.T. 2x4 SILL
PLATE W/ SEAL
BRICK @ FOUNDATION DETAIL
SCALE: N.T.S.
1" AIRSPACE
RUBBER FLASHING MEMBRANE
WEEPHOLE @ 32" O.C.
GROUT SOLID
163 Belvedere Street, Atlantic Beach, FL 32233