1852 SEA OATS DR RES23-0076 spray foam evalution reportOriginally Issued: 02/04/2019 Revised: 02/26/2021
CARLISLE SPRAY FOAM INSULATION
:1.00 Enterprise Drive
Cartersville, GA 30120
(927) 767-9663
wsvw. carlis lesf.cotn
S.EALTITETAI PRO OCX
CSI Section:
07 2100 Thermal Insulation
1.0 RECOGNITION
SealTit6m PRO OCX spray -applied polyurethane foam
plastic insulation described in this report have been
evaluated for use as thermal insulation and for use in Types
I through V construction. The physical properties, thermal
resistance, surface burning characteristics, fire -resistance -
rating properties, alternative thermal barrier assemblies and
attic and crawl space installations were evaluated for
compliance with the following codes and regulations:
• 2018, 2015, 2012 2009, and 2006 International
Building Code' (IBC)
• 2018, 2015, 2012 2009, and 2006 International
Residential Code® (IRC)
• 2018, 2015, 2012 2009, and 2006 International
Energy Conservation Cade® (IECC)
2.0 LIMITATIONS
Use of SealTite PRO OCX spray -applied polyurethane
foam plastic insulation recognized in this report is subject
to the following limitations;
2.1 The insulation shall be installed in accordance with the
manufacturer's published installation instructions, this
evaluation report and the applicable code. If there are any
conflicts between the manufacturer's published installation
instructions and this report, the more restrictive shall
govern.
2.2 In accordance with Sections 4.5.1 and 4.5.2 of this
report, the insulation shall be separated from the interior of
the building by a code -complying thermal barrier or
ignition barrier as appropriate.
2.3 The insulation shall not exceed the nominal density and
thickness for the installation conditions described in this
report.
2.4 During installation the insulation and the surfaces to
which it is applied shall be protected from exposure to
weather.
615
Valid Through: 02/28/2022
2.5 The insulation shall be installed by professional spray
polyurethane foam installers approved by Carlisle Spray
Foam Insulation, or by the Spray Polyurethane Foam
Alliance (SPFA).
2.6 Use of the insulation in areas of "very heavy" termite
infestation probability shall be in accordance with 2018
and 2015 13C Section 2603.8, 2012 IBC Section 2603.9,
2009 or 2006 IBC Section 2603.8, or 2018, 2015, 2012 and
2009 IRC Section R318.4, or 2006 IRC Section R320.5, as
applicable.
2.7 When required by the applicable code, a vapor retarder
shall be installed.
2.8 Labeling andlobsite certification of the insulation and
coatings shall comply with the following code sections as
applicable:
• 2018, 2015, 2012 or 2009 IBC Section 2603,2
• 2018, 2015, 2012 or 2009 IRC Section R316.2
• 2018, 2015 IRC Section N1101,10.1.1
• 2012 IRC Section N1101.12,1.1
• 2009 IRC Section N1101.4.1
• 2018, 2015 or 2012 IECC Sections C303,1.1.1 or
8303.1.1.1
• 2009 IECC Section 303.1.1.1
2.9 Foam Plastic used in plenums as interior finish or
interior trim under the 2018 edition IBC shall comply with
Section 2603.7.
2.10 The insulation shall be produced by Carlisle Spray
Foam Insulation in Cartersville, Georgia.
3.0 PRODUCT USE
SealTite PRO OCX spray -applied polyurethane foam
plastic insulations comply with IBC Section 2603, IRC
Section R316,2012 IECC Sections C303, C402, R303, and
R402, 2009 IECC Sections 303 and 402, and 2006 IECC
Section 402. When installed in accordance with Section 4.0
of this report, the foam plastic insulation may be used in
wall cavities, floor assemblies or ceiling assemblies, and/or
in attics and crawl spaces as nonstructural thermal
insulation material. SealTite PRO OCX insulations are
used in Type V -B construction under the IBC and in one -
and two-family dwellings under the IRC.
SealTite PRO OCX insulations may also be used in Types
I, Il, III or IV construction when installed in accordance
with Section 4.5.3 of this report,
The product described in this Uniform Evaluation Service (UES) Report has been evaluated as an alternative material, design or method of construction In order to satisfy and comply with
the intentof the provision of the code, as noted in this report, and fora, least equivalence to that prescribed in the code in qualify, stren9lh, eh'ectAmness, fire resistance, durabdily and safely,
as applicable, in accordance with 19C Section 104.11. This document shall only be reproduced in its enfirety.
Copyrght Q Z )21 by lntemadonel Assoclabon of Plumbing and Mechanical Officials, All fights resa vad, Printed in the United Statas, Ph: 1-877.41ESRPr- Fax: 909.472.4171
web- www.uniforrn es.org • 4755 East Philadatphta Street, Ontario, California 91761-2816— USA
Page I of 6
lure
C.
el
tisosec,7065
V86
Originally Issued: 02/04/2019
4.0 PRODUCT DESCRIPTION
Revised: 02/26/2021 Valid Through: 02/28/2022
4.1 Properties: SealTite PRO OCX are open cell, spray -
applied polyurethane foam plastic insulations in
accordance with Section 3. 1.1 and Table 1 of AC377. The
insulation has a nominal in-place density of 0.5 pcf (8
kg/m'). The two -component spray foam plastic is produced
in the field by combining a polymeric isocyanate (A
component) and a polymeric resin (B component). The
liquid components shall be stored in 55 -gallon (208 L)
drums at temperatures between 65°F and 85°F (18°C and
290C). When Component A and Component B are stored
in factory -sealed containers at the recommended
temperatures, the maximum shelf life is six months.
4.2 Thermal Resistance (R -Values): SealTite PRO OCX
spray -applied polyurethane foam plastic insulations have
thermal resistance (R -Value) at a mean temperature of
75°F (24°C) as shown in Table 1 of this report.
Tat—Thennial Resistance
lues 1ThicknesR-Value
inch(°fzh1
3.7
4
14
7.5
27
11.541
For Sl: t inch = 2h.4 mm, 1 -F -W ha3tu =0.176 110 K-mr/W.
'R -Values are calculated based on tested K values at 1 -inch and 3.54nch
thicknesses.
4.3 Surface Burning Characteristics: At a maximum
thickness of 4 inches (102 mm) and a nominal density of
0.5 pcf (8.0 kg/m3), the SealTite PRO OCX insulations
yield a flame spread index of 25 or less and smoke -
developed index of 450 or less when tested in accordance
with ASTM E84. Greater thicknesses, depending on the
end use, are recognized when installed in accordance with
this report.
4.4 Fire- Protective Coatings and Coverings: Fire
protective coatings, for use as alternative thermal barriers
or ignition barriers, shall be in accordance with Tables 2
and 3 of this report, as applicable, and installed in
accordance with Section 4.5 of this report.
4.5 Installation: SealTite PRO OCX spray -applied
polyurethane foam plastic insulations shall comply with
one of the following requirements:
• 2018, 2015, 2012
(prescriptive)
• 2018, 2015, 2012
(prescriptive)
• 2009 IECC Sections
appropriate.
IECC Sections C402.1
IECC Section R402.1
402, 405, 502 or 506 as
The manufacturer's published installation instructions for
SealTite PRO OCX insulations and this report shall be
available on thejobsite during installation. Where conflicts
occur, the most restrictive governs.
SealTite PRO OCX insulation shall be spray -applied on the
jobsite using equipment specified in the manufacturer's
published installation instructions. The maximum in-
service temperature for all areas shall not exceed the
maximum temperature stated in the manufacturer's
published installation instructions. The insulation shall be
sprayed onto a substrate that is protected and clean from
any debris or weather-related conditions during and after
application and shall not be used in electrical outlets or
junction boxes or in contact with rain, water, or soil.
4.5.1 Thermal Barrier
4.5.1.1 Application with a Prescriptive Thermal
Barrier: SealTite PRO OCX Spray -Applied Polyurethane
Foam Plastic Insulation, of any thickness, shall be
separated from the interior by an approved thermal barrier
of minimum ''/a inch thick (12.7 mm) gypsum wallboard or
equivalent 15 -minute thermal barrier. The thermal barrier
shall comply with and be installed in accordance with the
2018, 2015, 2012, 2009 and 2006 editions IBC Section
2603.4, or the 2018, 2015, 2012 and 2009 IRC Section
8316.4 or 2006 IRC Section 314.4, as applicable.
4.5.1.2 Alternative Thermal Barrier Assemblies:
SealTite PRO OCX spray applied foam plastic insulation
may be installed without a prescriptive thermal barrier as
defined in Section 4.5.1.1 of this report when installed in
accordance with Table 2 of this report.
4.5.2 Installation in Attics or Crawl Spaces: SealTite
PRO OCX Spray -applied Polyurethane Foam Plastic
Insulation may be installed in atticg or crawl spaces in
accordance with this section (Section 4.5),
When installed in attics or crawl spaces where entry is
made only for the service of utilities, SealTite PRO OCX
insulations may be installed in accordance with this
section. SealTite PRO OCX insulations need not be
surfaced with a thermal barrier, however, such attic and
crawl space areas shall be separated from the interior of the
building by a ignition barrier in accordance with Section
4.5.2.1, 4.5.2.2, and 4.5.2.3 of this report.
4.5.2.1 Installation Using a Prescriptive Ignition
Barrier: When installed within attics or crawl spaces
where entry is made only for the service of utilities,
SealTite PRO OCX spray -applied polyurethane foam
plastic insulation, at a maximum of 11.5 inches (292 nun)
thick shall be covered with a prescriptive ignition barrier in
accordance with 2018, 2015, 2012, 2009 or 2006 IBC
Section 2603.4.1.6, 2018, 2015, 2012 or 2009 IRC Sections
R316.5.3 and R316.5.4 or 2006 IRC Sections R314.53 and
8314.5.4, as applicable.
Page 2 of 6
Originally Issued: 02/04/2019
Revised: 02/26/2021 Valid Through: 02/28/2022
Exception: The prescriptive ignition barrier may be
omitted when installed in accordance with Section
4.5.2.2, 4.5.2.3 or 4.5.2.4 of this report.
4.5.2.2 Installation Using an Alternative Ignition
Barrier Assembly: Spray -Applied Polyurethane Foam
Plastic Insulation may be installed in attics and crawl
spaces using an alternative ignition barrier assembly
provided:
a. Entry is only to service utilities in the attic or
crawl space and no storage is permitted.
b. Attic or crawl space areas cannot be
interconnected.
C. Air from the attic or crawl space cannot be
circulated to other parts of the building.
d. Attic ventilation is provided as required by the
2018 edition IBC Section 1202 or 2018 edition
IRC Section R806 except where air -impermeable
insulation is permitted in unvented attics and shall
comply with the following code sections as
applicable:
For Unvented Attics:
• 2018 IBC Section 1202.3
• 2015 IBC Section 1203.3
• 2018, 2015 and 2012 IRC Section
R806.5
• 2009 IRC Section R806.4
Crawl space ventilation is provided as required by
the following code sections as applicable:
• 2018 BBC Section 1202.4
• 2015 IBC Section 1203.4
• 2012, 2009 and 2006 IBC Section
1203.3
0 2018, 2015, 2012, 2009 and 2006 IRC
Section R408.1
e. The foam plastic insulation is limited to the
maximum thickness and density tested.
f. In accordance with Uniform Mechanical Code
((UMC) Section 701.1 or IMC (International
Mechanical Codee) Section 701, [2006 IMC
Sections 701 and 703], combustion air is
provided.
g. The installed coverage rate or thickness of
coatings, if part of the insulation system, shall be
equal to what is described in Section 4.5.2.3 of
this report.
4.5.2.3 Installation Using an Alternative Ignition
Barrier with Application of Fire -Protective Coatings:
SealTite PRO OCX Spray -Applied Polyurethane Foam
Plastic Insulations may be spray -applied in attics to the
underside of roof sheathing or roof rafters, and vertical
surfaces; and may be spray -applied in crawl spaces to the
underside of floors and vertical surfaces as described in this
section. Coating thickness shall be in accordance with
Table 3 of this report.
The coating shall be applied over the insulation using
airless spray equipment, roller, or a brush in accordance
with the coaling manufacturer's published installation
instructions and this report. The ambient and substrate
temperatures shall be minimum 50OF (100C), and the
surface shall be dry, clean, free of dirt and loose debris, and
any other substance that could interfere with adhesion of
the coating.
4.5.2.4 Application without a Fire -protective Coating:
SealTiteTm PRO OCX spray foam insulations may be
spray -applied without a prescriptive ignition barrier to the
underside of the roof deck and underside of floors in crawl
space to thicknesses not exceeding 11.5 inches (292 nun)
and/or vertical surfaces in attics or crawl spaces to
thicknesses not exceeding 7.5 inches (190 mm), as
described in this section, When SealTiteTM PRO OCX is
installed as described in this section and Section 4.5.2.2, no
ignition barrier or coating is required.
4.5.2.5 Use on Attic Floors: SealTite PRO OCX insulations
may be installed exposed (no coating), without an ignition
barrier up to a maximum thickness of 11 %x inches (292 mm)
between and over the joist in attic floors. The insulation shall
be separated from the interior of the building by an approved
thermal barrier complying with IBC Section 2603.4 or 2015,
2012 and 2009 IRC Section R316.4 (2006 IRC Section
314.4). The ignition barrier required by BBC Section 2603.4
and 2015, 2012 and 2009 BRC Section R316.5.3 (2006 IRC
Section R314.5.3) may be omitted in this case.
4.5.3 Exterior Walls of Types I, U, III or IV
Construction (IBC)
4.5.3.1 General: When SealTite PRO OCX insulation is
used in exterior walls of Types 1, II, III or IV construction
of any height, the insulation shall comply with IBC Section
2603.5 and this section.
4.5.3.2 Complying Exterior Wall Assemblies: Wall
assemblies that comply with Section 2603.5 of the IBC and
this report that may be used in exterior walls of buildings of
Type 1, II, III or IV construction of any height are described
in Table 4 of this report.
Page 3 of 6
W
Originally Issued: 02104/2019
5.0 IDENTIFICATION
Revised: 02/26/2021
The spray foam insulation is identified with the following:
a. Manufacturer's name (Carlisle Spray Foam
Insulation).
b. address and telephone number,
c. the product trade name (SealTite PRO OCX)
d. use instructions
e. density, flame -spread and smoke -development
indices
f. date of manufacture or batch/run number
g. thermal resistance values
h. the evaluation report number (ER -615)
i. the name or logo of the inspection agency
Either mark of conformity may be used as shown below:
IApMO UES
ES
W® or
IAPMO UES ER -615
6.0 SUBSTANTIATING DATA
6.1 Data in accordance with the ICC -ES Acceptance Criteria
for Spray -applied Foam Plastic Insulation, AC377, dated
April 2016, including Appendix X (Editorially Revised in
April 2018).
6.2 Reports of room corner fire testing in accordance with
NFPA 286.
6.3 Reports on fire propagation characteristics tests in
accordance with NFPA 285.
6.4 Test reports are from Laboratories in conformance
with ISO/IEC 17025.
Page 4 of 6
3
Valid Through: 02/28/2022
7.0 STATEMENT OF RECOGNI'T'ION
This evaluation report describes the results of research
completed by IAPMO Uniform Evaluation Service on
SealTite PRO OCX to assess its conformance to the codes
and standards shown in Section 1.0 of this report and
documents the product's certification. Products are
manufactured at locations noted in Section 2.10 of this
report under a quality control program with periodic
inspections under the supervision of IAPMO UES.
For additional information about this evaluation report please visit
2Ms ,uniformcs.orn or email us at info�%um`form_es ore
Originally Issued: 02/04/2019 Revised: 02/26/2021
2 -
IYra MINIMUM
THEORETICAL
THICKNESS
APPLICATION
mils
RATE
DC315' 14 WFT
f9 IIFT)
2
115 ft/gal.
WALLS ANI
VERTICAL
8.5
615
Valid Through: 02/28/2022
;FILING AND
OVERHEAD
14
Control 60- 20 WIT I 80 ft2/gal I 7,5
60A (13 DFT) 11.5
For SI I mch = 25.4 mm, I gallon 3.785 L, 1 ft 0.0929 mr
' Fire -protective coatings and coverings shall be applied over all exposed SPF surfaces in accordance with the
coatingtcovering manufacturer's instructions and this report.
' International Fireproof Technology, Inc, recognized in IAPMO UES ER499.
Flame Control Coatings, recognized in IAPMO UES ER -596.
FIRE -PROTECTIVE COATING/COVERAGE' I MAXIMUM SPF THICKNESS
inch
IMUM THEORETICAL WALLS �D
CEILINGS
TYPKNESS APPLICATION VERTICAL
AND
ils) RATE SURFACES
;DC311DFT
OVERHEAD
WFT
SURFACES
400 112/gal 7.5
11.5
For SI: 1 inch = 25.4 mm, I gallon = 3.785 L, I ft= 0.0929 m�
' Firaprotective coatings and coverings must be applied over all exposed SPF surfaces in accordance with the
i oatin&oveting manufacturer's instructions and this report.
International Fireproof Technology, Inc, recognized in IAPMO UES ER499
Page 5 of 6
SES
Originally Issued: 02/0412019
Revised: 02/26/2021
615
Valid Through: 0212812022
TABLE 4 - NFPA 285 COMPLYING EXTERIOR WALL ASSEMBLIES
FOAMSULATE 220= APPLIED TO EXTERIOR OF WALL ASSEMBLY WITH FOAMSULATE 2202, SEALTITET^r
DDA Alv iwr pis .
SI: 1 inch = 25.4 mm; 1 pcf=16.0 kg/ms; 1 Btu/ll =0.01128 mJ/m2
r Fireblocking per Section 718 of the 2018, 2015 or2012113C and thermal barrier material requirements per Section 2603.4 of
the 2018, 2015 or 2012 IBC shall be met for Base Wall Systems 1 and 2, as required by specific wall construction details when a
combustible concealed space is created on interior side of exterior wall assembly.
2 Foamsulate 220 in accordance with IAPMO UES ER -352.
Page 6 of 6
v,,n ui rreaUU J 1 Ull UA V I I
MATERIAL DESCRH'TION
I — concrete wall
7"ver.
2 — concrete masonry wall
—1 layer of 5/8 -inch thick Type X gypsum wallboard installed on the interior
ide of minimum 35/s -inch deep minimum No. 20 -gauge steel studs spaced a
aximum or 24 inches on center. Lateral bracing installed minimum every 4 feet
tically
ertically or as required. Wall stud cavities shall be filled ateach floor line with
minimum 4 pcf density mineral wool (e.g. Thermafiber) friction fit between steel
wall studs.
Perimeter Fire Barrier
System
Perimeter fire barrier system complying with Section 715.4 of the 2018, 2015 or
2012 IBC shall be installed as applicable, to fill fire void created at the
Interior Insulation
intersection of the exterior curtain wall assembl and the concrete floor slab.
1—None
Use either 1, 2, 3, 4 or 5; or
combination of 3 and 4; or
2 —Maximum 35 /s -inch thickness of SealTite PRa X open -cell SPF insulation
applied to the interior surface of BWS 1 or 2 abo
combination of 3 and 5
3 — SealTite PRO OCX insulation applied to the pth of the wall stud cavity,
or less, with exterior gypsum sheathing (see BWS 3 above) as the substrate
covering the width of the cavity and the inside of the steel wall stud framin
flange'.4 g
4 —Fiberglass batt insulation (faced or unfaced)
Exterior Sheathing
5 — Mineral wool insulation faced or unfaced
1—None (for BWS 1 or 2 above)
Use either 1 or 2
Exterior Insulation
Maximum 4 -inch thickness of Foamsulate 2202 insulation
2 —'%-inch thick exterior sum sheathingfor BWS 3 aJAsecondary
Exterior Wall Covering=
Use either 1, 2, 3, 4 or 5
1— Brick: Standard type brick veneer anchors, installed at um 24 -inches
on center, vertically on each stud with maximum 1 -inch aietween exterior
insulation and brick. Brick to be standard nominal 4 -inch tay brick installed
Ia running bond pattern using Type S mortar.
2 — Stucco: Minimum'/4-inch thick, exterior cement plasteth. A secondarywater-resistive
barrier (WRB) may be installed between thor insulation andthe
lath. The secondary WRB shall not be full -coverage asbutyl-basedself-adhered
membranes.
3 — Natural Stone: Minimum 2 -inch thick natural stone (grmestone,marble,
sandstone). Any standard non-openjointed installahnique may be
used.
4 — CMU and others: Minimum 2 -inch thick concrete masonry unit (CMU), pre-
cast concrete or artificial cast stone. Any standard non -open jointed installation
method maybe used.
5 —Terra Cotta: Minimum I V44 -inch thick Terra Cotta non -open jointed. Any
'ointed
Flashing of window, door
standard non-Q installation method may be used.
As an option, flash around windows, doors and other
and other exterior wall
exterior penetrationI
limited amounts of maximum 12 -inch wide flashing tape (acrylic, asphaltpenetrations
based) or liquid -applied membrane material with or without fiber mesh
reinforcements.
SI: 1 inch = 25.4 mm; 1 pcf=16.0 kg/ms; 1 Btu/ll =0.01128 mJ/m2
r Fireblocking per Section 718 of the 2018, 2015 or2012113C and thermal barrier material requirements per Section 2603.4 of
the 2018, 2015 or 2012 IBC shall be met for Base Wall Systems 1 and 2, as required by specific wall construction details when a
combustible concealed space is created on interior side of exterior wall assembly.
2 Foamsulate 220 in accordance with IAPMO UES ER -352.
Page 6 of 6
MW
SPRAY FOAM /NSULAT/ON
OPEN CELL FOAM
SealTite PRO OCX
SealTite PRO OCX is a two component, light density, one to one by volume spray -applied polyurethane foam that
complies with AC -377 Appendix X and can be installed in attics and crawl spaces without a prescriptive ignition barrier
or intumescent coating. SealTite PRO OCX is an insulation system designed for use in commercial and residential
applications. Use in lieu of more traditional forms of insulating materials such as fiberglass, cellulose or other loose fill
Products. Typical areas where SealTite PRO OCX is applied are exterior and interior walls, vented attics, unvented attic
assemblies and between floors. SealTite PRO OCX contains +/-14% bio, renewable, recycled and sustainable content
and ZERO ozone depleting blowing agents.
TYPICAL PHYSICAL PROPERTIES:
100 Enterprise Drive • Cartersville, GA 30120 - 844.922.2355
www.carlislesfi.com
R -Value
3.7 Q 1" ASTM C 518
Core Density
0.5 LB / Cubic Foot ASTM D 1622
Open Cell Content
> 95% ASTM D 6226
Sound Transmission Coefficient
50
ASTM E 90
Air Impermeable
<0.02 (Us -m') Q 3.5" ASTM E 283
Tensile Strength (PSI)
3.71 ASTM D1623
ODimensional
stability
<15% ASTM D2126
Building .. -
-
aa�
. Data
Dim
Evaluation Service Report
IAPMO
UES 675
Building Types
Approved I, II, III, IV, V -B:
Insulation material
Flame Spread
--Nonstructural
ASTM E84 Class I < o
mini
Smoke Development
ASTM E84 Class I < 300
■
NFPA 259
Pass: Standard fire test method for evaluation of fire propagation characteristics of exterior non-
load bearing wall assemblies coniaining combustible components.
NEPA 285
Pass: Standard fire test method for evaluation of fire propagation charactens8cs of exterior non -
load bearing wall assemblies containing combustible components
NFPA 286
Pass: Can be used without a 15 -minute thermal barrier when covered with one of the approved
Intumescent coatings as shown on page 2.
NFPA 286
AC377 Appendix X
Pass: Complies with the applicable requirements of ICC -ES AC377 Appendix X for use in attics
and Crawlspaces without the use of a prescriptive ignition barrier or intumescent coating.
UL Listing
FWFx.R38039 Exterior Wall System Components
UL UsHng
FWFO.EWS0013 Exterior Wall Systems
Greenguard
Certified: UL 2818 - 2013 Standard for Chemical Emissions for Building Materials, Finishes and
100 Enterprise Drive • Cartersville, GA 30120 - 844.922.2355
www.carlislesfi.com
i
SPPTAY FOAM /NSCJLAT/ON
THERMAL BARRIER:
Current International Building Code (IBC) and International Residential Code
(IRC) require that spray polyurethane foam be separated from the building
interior by a code prescribed 15 -minute thermal barrier or a code -approved
alternative. Gypsum board at a minimum thickness of t/2" is a code
Prescribed 15 -minute thermal barrier. The following intumescent coatings
when installed per manufacturer specifications are approved as thermal
barrier ahematives for SealTite PRO OCX:
Approved Intumescent Coatings:
DC315' manufactured by: International Application Rates:
Fireproof Technology, Inc 14 Wet MIS - 9 Dry Mils
IGNITION BARRIER:
SealTite PRO OCX meets the requirements of ICC -ES AC377 Appendix X
for use in attics and crawlspace without a prescriptive ignition barrier or
intumescent coatings when the following conditions are met:
a I miry 1s only to service utilities In the attic or crawlspace and no
b I Attic or crawlspace areas cannot be connected.
c IRif nom me artic or crawlspace cannot be circulated to other parts of
Jthe building.
d In accordance with IBC Section 1203.3 or IRC Section R408.1, under
floor (crawispace) ventilation is provided as applicable.
a I In accordance with IBC 1203.2 or IRC Section R806, attic ventilation is
In accordance with 2012 and 2009 IMC (International Mechanical
I
Codee) Section 701, or 2006 IMC Sections 701 and 703, combustion
air is provided.
g IThe foam plastic insulation is limited to the maximum thickness and
density tested.
In IThe installed coverage rate of coatings, if part of the insulation system
shall be equal or greater than that tested.
GENERAL PROPERTIES: Searrde PRO OCX is a low viscosity, 0.5 pcf
density open cell insulating material. SealTite PRO OCX is designed to
Provide significant control of air Infiltration along with a high R -value
per inch. When properly installed by a professional application company
SealTite PRO OCX quickly expands to fill the cracks, crevices, gaps and
voids that exist in every structure. In addition, SealTite PRO OCX will
conform to the curves, irregular surfaces and spaces to form a superior
thermal envelope around your entire structure.
EQUIPMENT AND COMPONENT RATIOS: The mix ratio is 1 to 1 by volume.
The pre -heater temperatures should be set between 115°F -140°F and
able to maintain +/- 5°F
VAPOR RETARDER: Open cell foam insulation is vapor permeable and will
allow some diffusion of moisture through the product. Consult local building
code officials for specific requirements. Climate zone tables are available in
current IBC and IRC publications.
r,
tlIrkppt III p e-^'llif M/
SealTite PRO OCX
APPLICATION GUIDELINES: Polyurethane foam systems should be
Processed through commercially available spray equipment designed for
that purpose by a qualified professional applicator. Consult the current
Carlisle Spray Foam Insulation application guidelines for SealTite PRO OCX
prior to installation. it is the responsibility of the professional applicator
to thoroughly understand all equipment technical information and safe
operating procedures that pertain to a spray polyurethane foam application.
MATERIAL HANDLING: Due to the reactive nature of these components
respiratory protection is mandatory. The vapors and liquid aerosols present
during application and for a short period thereafter must be considered —
and appropriate protective measures taken — to minimize potential risks
from overexposure through inhalation, skin, or eye contact These protective
measures include adequate ventilation, safety training for installers and
other workers, use of appropriate personal protective equipment, and a
medical surveillance program. It is imperative that the applicator read and
become familiar with all available information on proper use and handling
of spray polyurethane foam. Additional information is available at www.
carlislesfi.com or by contacting the Technical Services department of
Carlisle Spray Foam Insulation,
PROPER STORAGE OF RAW MATERIALS: Shelf life is six (6) months
from date of manufacture when stored indoors, in the original unopened
containers and between the temperatures of 50°F - 80°F.
TECHNICAL ASSISTANCE: For additional assistance please contact the
Technical Services department of Carlisle Spray Foam Insulation at
(844) 922-2355.
DISCLAIMER: To the best of our knowledge, all technical data contained
herein is true and accurate as of the date of issuance and subject to
change without prior notice. User must contact Carlisle Spray Foam
Insulation to verify correctness before specifying or ordering. We guarantee
our products to conform to the quality control standards established by
Carlisle Spray Foam Insulation. We assume no responsibility for coverage,
performance or Injuries resulting from use. Liability, if any, is limited to
replacement of the product. NO OTHER WARRANTY OR GUARANTEE OF
ANY KIND IS MADE BY CARLISLE SPRAY FOAM INSULATION EXPRESSED OR
IMPLIED; STATUTORY, BY OPERATION OF LAW, OR OTHERWISE, INCLUDING
MERCHANTABILITYAND FITNESS FOR A PARTICULAR PURPOSE.
111030 runuaAA (UMV)
S
100 Enterprise Drive • Cartersville, GA 30120 - 844.922.2355
www.carlislesfi.com
® 2019 Carible. 10.09.19 CSFI-10153 - ^SeaITRe PRO OCX Technical Oat, Sheet'
ca,raW and <.aITRa 1- bptly„uma nf,,,W