831BEACH AVE RES23-0016 Gulf Coast Metal Roofing REVISION 3-31-23_1GREEK TECHNICAL SERVICES, LLC EVALUATION REPORT FLORIDA BUILDING CODE, Manufacturer: GULF COAST SUPPLY & MANUFACTURING. LLC 14429 SW 2"" Place, Suite G30 Newberry, FL 32669 (352) 498-7852 www.gulfcoastsupply.com Manufacturing Locations: Alachua, FL Sebring, FL Montgomery, AL Quality Assurance: Keystone Certifications, Inc. (QUA1824) SCOPE Category: Subcategory: Code Sections: Properties: REFERENCES Roofing Metal Roofing 1504.3 Wind Resistance Entity Report No. Force Engineering & Testing (TST5328) 72 -0313T -06A -C Force Engineering & Testing (TST5328) 72 -0198T -07A -C Force Engineering & Testing (TST5328) 117-0033T-05 Force Engineering & Testing (TST5328) 117-0053T-05 Force Engineering & Testing (TST5328) 117 -0062T -07A -C Force Engineering & Testing (TST5328) 117 -0062T -07D -F Force Engineering & Testing (TST5328) 117 -0062T -07G-1 Force Engineering & Testing (TST5328) 117 -0062T -07J -K Force Engineering & Testing (TST5328) 117 -0065T -07A -C Force Engineering & Testing (TST5328) 117 -0076T -12A Force Engineering & Testing (TST5328) 117-0089T-05.1 Force Engineering & Testing (TST5328) 117-0089T-05.2 /Ssui CREEK TECHNICAL SERVICES, LLC Entity Force Engineering & Testing (TST5328) Force Engineering & Testing (TST5328) Force Engineering & Testing (TST5328) Force Engineering & Testing (TST5328) Force Engineering & Testing (TST5328) Force Engineering & Testing (TST5328) Force Engineering & Testing (TST5328) Force Engineering & Testing (TST5328) Force Engineering & Testing (TST5328) Force Engineering & Testing (TST5328) Force Engineering & Testing (TST5328) Force Engineering & Testing (TST5328) Intertek- West Palm Beach (an ATI company) (TST1527) Intertek- West Palm Beach (an ATI company) (TST1527) Intertek- West Palm Beach (an ATI company) (TST1527) Intertek- West Palm Beach (an ATI company) (TST1527) Intertek- West Palm Beach (an ATI company) (TST1527) PRI Construction Materials Technologies (TST5878) PRI Construction Materials Technologies (TST5878) PRI Construction Materials Technologies (TST5878) GULF COAST SUPPLY & Mi Report No. 117 -0285T -09A 117-0301 T -10A -C 117 -0330T -10A -B 117 -0331T -08A 117 -0331T -08B 117 -0331T -08D 117-0337T-10 117-0378T-11 A 117-0378T-11 B 117-0378T-11 C 117-0407T-09 117 -0407T -09A B9000.01-450-18 C0308.01-450-18 D0818.01-450-18 D11692.01-450-44 G7287.01-450-44 1272T0005 2292T0001 2292T0002 PRI Construction Materials Technologies (TST5878) 2292T00l l CREEK TECHNICAL SERVICES, LLC PRODUCT DESCRIPTION GulfLok GulfSeam Profile: Description: ................................................ Material: 1" GULF COAST SUPPLY & Mi 1 in. snap lock seam; Max. 16 in. coverage _Non-structural, snap lock standing seam roof panel with 7/8 in. Min. 26 ga. ASTM A792 AZ50 or ASTM A653 G90; Optional FIS finish; F, = min. 50 ksi; Shall conform with FBC Section 1507.4 Min. 0.032 in. ASTM 8209, 3105 H24 aluminum; Optional Fluro Fv = min. 24 ksi; Shall conform with FBC Section 1507.4.3 12" and 16" Coverage Profile: 1 3/4 in. snap lock seam; Max. 18 in. coverage ..........................;.. Description: Non-structural, snap lock standing seam roof panel ................................�... Material:= Min. 26 ga. ASTM A792 AZ50 or ASTM A653 G90; Optional FIS finish; Fy = min. 50 ksi; Shall conform with FBC Section 1507.4 Min. 0.032 -inch ASTM B209, 3105 H24 aluminum, Optional Flu Shall conform with FBC Section 1507.4.3 ...................................................................:.. . F, = min. 21 ksi; 1M. 14", 16", and 18" Coverage MegaLoc Profile: 2 in. mechanical seam, Max. 18 in. coverage Description:Non-structural, mechanical lock 1800 standing seam roof panel .........._. _. _....................... _. _..................... Material: Min. 24 ga. ASTM A792 AZ50 or ASTM A653 G90; Optional FIS finish; F. = min. 50 ksi; Shall conform with FBC Section 1507.4 CREEK TECHNICAL SERVICES, LLC GULF COAST SUPPLY & Mi VersaLoc Profile: 1.5 in. mechanical seam; Max. 18 in. coverage Description: Non-structural, mechanical lock 1800 standing seam roof panel Material: Min. 24 ga. ASTM A792 AZ50 or ASTM A653 G90; Optional FIL finish; F, =min. 50 ksi; Shall conform with FBC Section 1507.4 5V Crimp GulfPBR lid 16' • W C0vera96 Profile:7/16 in. ribs at 12 in. o.c.; 24 in. coverage Description: Non-structural, through fastened roof panel }_ Material:Min. 26 ga. ASTM A792 AZ50 or ASTM A653 G90; Optional FIS :finish; F, = min. 50 ksi; Shall conform with FBC Section 1507.4 r_ Min. 0.032 in. ASTM B209, 3105 H24 aluminum; Optional Fluro F� =min. 25 ksi; Shall conform with FBC Section 1507.4.3 7116 Profile: ............................... Description: 12„ 24" Coverage 1 1/4 in. ribs at 12 in. o.c.; 36 in. coverage Non-structural, through fastened roof panel Min. 26 ga. ASTM A792 AZ50 or ASTM A653 G90; Optional FIL finish; F, = min. 80 ksi; Shall conform with FBC Section 1507.4 CREEK TECHNICAL SERVICES, LLC GULF COAST SUPPLY & Mi GulfRib Profile: 3/4 in. ribs at 9 in. o.c.; 36 in. coverage Description: Non-structural, through fastened roof panel Material: Min. 29 ga. ASTM A792 AZ50 or ASTM A653 G90; Optional FIL ..... .. ....................................................._- finish: F� =min. 80 ksi: Shall conform with FBC Section 1507.4 3/4"t 36" Coverage GulfWave Profile: 3/4 in. corrugation; 29 in. coverage .............................................................. - Description: Non-structural, through fastened roof panel Material: Min. 26 ga. ASTM A792 AZ50 or ASTM A653 G90; Optional FIS finish: F� -min. 80 ksi; Shall conform with FBC Section 1507.4 ....................................................................� - -- -- - -- - -- 3/4' 29" Coverage CREEK TECHNICAL SERVICES, LLC LIMITATIONS GULF COAST SUPPLY & Mi 1. Fire classification is not within the scope of this evaluation. 2. This report is not for use in the HVHZ. 3. The roof deck and the roof deck attachment shall be designed by others to meet the mii established for components and cladding and in accordance with FBC requirements. 4. Roof slope shall be in accordance with FBC Section 1507.4.2. 5. Reroofing shall be in accordance with FBC Section 1511. Recovery versus replacemer in accordance with FBC Section 1511.3. 6. Installation of the evaluated products shall comply with this report, the FBC and published application instructions. Where discrepancies exist between these sources, and FBC compliant installation detail shall prevail. 7. All products listed in this report shall be manufactured under a quality assurance progran Rule 61 G20-3. COMPLIANCE STATEMENT The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with Code, 7t" Edition (2020) as evidenced in the referenced documents submitted by the named manL `G�p.RY No 74021 r - v — O'.. STATE OF .:441 This item has been digitally signed and sealed by Zachary R. Priest, PE, on 10/18/2021. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies. CERTIFICATION OF INDEPENDENCE 202 1�2 0:4 iiyw, •�1rn h •rw.ry w .n.r -04'1 Zachary R. Priest, P.E. Florida Registration No. 74021 Organization No. ANE9641 CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manuf products under this evaluation. CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distr this evaluation. Zachary R. Priest. P.E. does not have, nor will acquire, a financial interest in any company manufacturing c under this evaluation. Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the a product. APPi=mni _FC CREEK TECHNICAL SERVICES, LLC GULF COAST SUPPLY & Mi INSTALLATION Note - Refer to the APPROVED ROOF SYSTEMS section of this report for specific installation details o Unless otherwise specified in this report the following installation details shall be met for the name Component Product Installation Detail #9-15 HWH wood screw with sealing washer #9-15 HWH WoodZAC screw #10-12 Pancake Type A screw #10-14 HWH WoodTite Shall penetrate through the sheathing a minimum 3/8 in. E Fastener with sealing resistant in accordance with FBC section 1507.4.4. Fasteners washer #12-11 Pancake Type A screw #12-8 HWH Woodgrip XG screw with sealing washer Clips 1/4-14 HWH ZAC Impax Installed at panel side lap; Shall be corrosion resistant in a Lap screw section 1507.4.4. 24 ga. in -seam clip I • I I I GulfLok Clip 1,3J4' 18 ga. in -seam clip 3. Fixed Clip _ �� CREEK TECHNICAL SERVICES, LLC Component Product Installation Detail Clips (Cont'd) Sealants NC -33003-3 Sliding Clip 1500SC Sliding Clip TiteBond Weathermaster Metal Roof Sealant GULF COAST SUPPLY & Mi �— 4-114" 22 ga. top; 16 ga. base; in -seam clip (109.22; 3U (B E �. � z cr 0", C U a `L.:12 {10.18} C.40 Shall be applied in 1/4"- 5/16" continuous beads on the ma Fastening Details Nomenclature Attachment J GulfLok Type 1 (1) # 10-12 X 1 " TYPE A PANCAKE VV 1143 STAINLESS GULF LCK PANEL r STEEL RIVET @ 6- ibOVERLAP SIDE)— J C E CREEK TECHNICAL SERVICES, LLC GULF COAST SUPPLY & (1) �ff-A-1 .r-; x 1-1 /?" HWH w/.qPalinn Fastening Details Nomenclature Attachment _ -_ -- GulfLok"' CLIP 24 GA. - GulfLok Type 2 (1) #10-12 X 1" TYPE A PANCAKE -18 Ga. Fixed Clip GulfSeam Type 1 (2) #10-12 Pancake Type A Per Clip. MegaLoc Type 1 NC -33003 SLIDING CLIP (2) #10-12 x 1" per Clip VersaLoc Type 1 1500SC SLIDING CLIP (2) #12-11 x 1" Panhead per Clip (1) #9-15 x 1-1 /2" HWH w/Sealing 5V Type 1 1211 0 1211 At Panel Lap (1) �ff-A-1 .r-; x 1-1 /?" HWH w/.qPalinn CREEK TECHNICAL SERVICES, LLC GULF COAST SUPPLY & Fastening Details Nomenclature Attachment 1211 -1211 5V Type 3 At Panel L (1) #9-15 x 1-1 /2" HWH w/Sealing At P #1/4-14 x 7/8" Lap Screw @ 24" O.C. Max. - -12" 1211 12" - GulfPBR Type 1 I �(1) #9-15 x 1-1/2" #1 /4-14 x 7/8" Lap Screw @ 24" O.C. Max. GulfPBR Type 2 -511711 511 711 5 V11 711 �(1) #9-15 x 1-1/2" 9" 91' 9 s A GulfRib Type 1 (1) #9-15 x 1.1119- w/Sealer Washer CREEK TECHNICAL SERVICES, LLC GULF COAST SUPPLY & Fastening Details Nomenclature Attachment 911 911 911 or 911- GulfRib Type 3�_ #915 x 2' w/Sealer Washer 9" 9" 9" 6.5 GulfRib Type 4 (1) #12-8x 1-1/2' WoodGrip XG W/Seale Washer At Pay X01 8.. �5.� GulfWave Type 1 '�(1) #9-15 x 1-1 /2" HWH w/Sealing Washer :Es. LLC GULF COAST SUPPLY & MANUFACTURING, LLC Metal Roofing APPENDIX B served when using the assembly tables below. ;sure (MDP) was calculated using a 2:1 margin of safety per FBC Section 1504.9. nd sections of this evaluation when using the table(s) below. section of this report for installation detail when the information is not explicitly stated for the selected assembly. )acing given is the maximum allowable attachment spacing for the rated system. r gauge is the minimum allowable. !signed by others in accordance with FBC requirements and shall be minimum 22 ga (Fy = min.40 ksi) Wide Rb Deck (Type WR) DI-RD1.0 & FBC. esigned by others in accordance with FBC requirements and shall be minimum 15/32 -inch thick APA Span -Rated plywood i 24 -inch span. Roof System Numbers and Definitions Gulf Lok over Wood Deck (New or Existing) GulfSeam over Wood Deck (New or Existing) MegaLoc over Wood Deck (New or Existing) 1.5" VersaLoc over Wood Deck (new or Existin 5V Crimp over Wood Deck I GuIfPBR over Wood DecK (I Gulf Rib over Wood Deck GulfWave over Wood Deck ( New or Existing) Jew or Existing) aw or Existing) New or Existina) Approved Systems for GulfLok over Wood Deck (New or Existing) Fire Barrier Underlayment Roof Panel Panel Attachment MDP (psf) OPTIONAL Approved fire barrier As required per FBC Min. 0.032" Al GulfLok Guftok Type 1 attachment with #10-12 x 1" -65.5 or insulation Max. 16 -inch coverage Pancake Type A screws spaced 5-3/16 in. o.c. OPTIONALGuftok Type i attachment with #10-12 x 1" Approved fire barrier As required per FBC Min. 0.032" Al GulfLok Pancake Type A screws spaced 5-3/16 in. o.c. -� 16 or insulation Max. 16 -inch coverage Titebond Weathermaster Metal Roof Sealant applied to male rib. GULF COAST SUPPLY & MANUFACTURING, LLC Metal Roofing APPENDIX B Approved Systems for GulfLok over Wood Deck (New or Existing) Fire Barrier Underlayment Roof Panel Panel Attachment MDP (psf) OPTIONAL GulfLok Type 1 attachment with #10-12 x 1" (psf) Approved fire barrier As required per FBC 26 ga. GulfLok Pancake Type A screws spaced 5-3/16 in. o.c. -121.75 or insulation Max. 16 -inch coverage Titebond Weathermaster Metal Roof Sealant OPTIONAL Approved fire barrier As required per FBC Min. 0.032" Al GulfSeam applied to male rib. -75 or insulation OPTIONAL Approved fire barrier As required per FBC 26 ga., Grade 80 GulfLok GulfLok Type 1 attachment #10-12 x 1" -63.5 or insulation Max. 16 -inch coverage Pancake Type A p screws spaced 5-3/16 in. o.c OPTIONAL 26 ga., Grade 80 GulfLoK GulfLok Type 2 attachment with Approved fire barrier As required per FBC x. verage Max,6-inch co #10-12 x 1" Pancake Type A screws through -161 or insulation clip and spaced 5-3/16 in. o.c. OPTIONAL Approved fire barrier As required per FBC 24 ga. GuffLok GulfLok Type 1 attachment with #10-12 x 1" -81'75 or insulation Max. 16 -inch coverage Pancake Type A screws spaced 10-1/4 in. o.c. OPTIONAL Approved fire barrier As required per FBC 24 ga. GuffLok GulfLok Type 1 attachment with #10-12 x 1" -96.75 or insulation Max. 16 -inch coverage Pancake Type A screws spaced 5-1/8 in. o.c. Approved Systems for GulfSeam over Wood Deck (New or Existing) Fire Barrier Underlayment Roof Panel Panel Attachment MDP (psf) OPTIONAL Approved fire barrier As required per FBC Min. 0.032" Al GulfSeam GulfSeam Type 1 attachment -60 or insulation Max. 16 -inch coverage with stainless steel clips spaced 18 in. o.c. OPTIONAL Approved fire barrier As required per FBC Min. 0.032" Al GulfSeam GulfSeam Type 1 attachment -75 or insulation Max. 16 -inch coverage with stainless steel clips spaced 6 in. o.c. GULF COAST SUPPLY & MANUFACTURING, LLC Metal Roofing APPENDIX B Approved Systems for GulfSeam over Wood Deck (New or Existing) MDP Fire Barrier Underlayment Roof Panel Panel Attachment (psf) OPTIONAL Min. 26 ga. GulfSeam GulfSeam Type 1 attachment Approved fire barrier As required per FBC Max. 16 -inch coverage with clips spaced 18 in. o.c. -60 or insulation OPTIONAL Min. 26 ga. GulfSeam GulfSeam Type 1 attachment Approved fire barrier As required per FBC Max. 16 -inch coverage with clips spaced 6 in. o.c. -75 or insulation OPTIONAL Approved fire barrier As required per FBC Min, 24 ga. GulfSeam GulfSeam Type 1 attachment with clips spaced -93.5 or insulation Max. 16 -inch coverage 18 in. o.c. over wood purlins OPTIONAL Min. 24 ga. GulfSeam GulfSeam Type 1 attachment Approved fire barrier As required per FBC Max. 18 -inch coverage with clips spaced 24 in. o.c. -69.25 or insulation OPTIONAL Min. 24 ga. GulfSeam GulfSeam Type 1 attachment Approved fire barrier As required per FBC Max. 18 -inch coverage with clips spaced 12 in. o.c. -108.5 or insulation OPTIONAL Approved fire barrier As required per FBC Min. 24 ga. GulfSeam GulfSeam Type 1 attachment with clips spaced -114.25 or insulation Max. 18 -inch coverage 24 in. o.c. over wood purlins OPTIONAL Approved fire barrier As required per FBC Min. 24 ga. GulfSeam GulfSeam Type 1 attachment with clips spaced -159.25 — ;-- ,,-4;_- Max. 18 -inch coverage 12 in. o.c, over wood purlins GULF COAST SUPPLY & MANUFACTURING, LLC Metal Roofing APPENDIX B Approved Systems for MegaLoc over Wood Deck (New or Existing) Fire Barrier Underlayment Roof Panel Panel Attachment MDP (psf) OPTIONAL Approved fire barrier As required per FBC Min. 24 ga. MegaLoc MegaLoc Type 1 attachment -71 or insulation As required per FBC Max. 18 -inch coverage with clips spaced 24 in. o.c. -59.75 OPTIONAL Approved fire barrier As required per FBC Min, 24 ga. MegaLoc MegaLoc Type 1 attachment -108.5 or insulation As required per FBC Max. 18 -inch coverage with clips spaced 12 in. o.c. -123.5 Approved Systems for VersaLoc over Wood Deck (New or Existing) Fire Barrier Underlayment Roof Panel Panel Attachment MDP Insulation (psf) OPTIONAL Approved fire barrier As required per FBC Min. 24 ga. VersaLoc VersaLoc Type 1 attachment -59.75 or insulation Max. 16 -inch coverage with clips spaced 24 in. o.c. OPTIONAL Approved fire barrier As required per FBC Min. 24 ga. VersaLoc VersaLoc Type 1 attachment -123.5 or insulation Max. v . 16-inccoverage with clips spaced 6 in. o.c. Approved Systems for 5V Crimp over Wood Deck (New or Existing) Fire Barrier/ Underlayment Roof Panel Panel Attachment MDP Insulation (psf) OPTIONAL Approved fire barrier As required per FBC Min. 0.032" Al 5V Crimp 5V Crimp Type 1 attachment with #9-15 HWH wood -108.5 or insulation 24 -inch coverage screws with sealing washers spaced 12 in. o.c. ,ES GULF COAST SUPPLY & MANUFACTURING, LLC Metal Roofing APPENDIX B Approved Systems for 5V Crimp over Wood Deck (New or Existing) Fire Barrier/ Underlayment Roof Panel Panel Attachment MDP Insulation (psf) OPTIONAL Approved fire barrier As required per FBC Min. 26 ga. 5V Crimp 5V Crimp Type 3 attachment with #9-15 HWH wood -94.25 or insulation As required per FBC 24 -inch coverage screws with sealing washers spaced 16 in. o.c. -60.5 OPTIONAL Approved fire barrier As required per FBC Min. 26 ga. 5V Crimp 5V Crimp Type 1 attachment with #9-15 HWH wood -108.5 or insulation 24 -inch coverage screws with sealing washers spaced 12 in. o.c. OPTIONAL Approved fire barrier As required per FBC Min. 26 ga. 5V Crimp 5V Crimp Type 2 attachment with #9-15 HWH wood -131 or insulation As required per FBC 24 -inch coverage screws with sealing washers spaced 16 in. o.c, -100.5 OPTIONAL Min. 26 ga. 5V Crimp 5V Crimp Type 1 attachment with Approved fire barrier As required per FBC 24 inch coverage #9-15 HWH wood screws with sealing washers spaced 6 -156.5 or insulation in. o.c. Approved Systems for GulfPBR over Wood Deck (New or Existing) Fire Barrier/ Underlayment Roof Panel Panel Attachment MDP Insulation (psf) OPTIONAL GulfPBR Type 1 attachment with #9-15 15 HWH WoodZAC Approved fire barrier As required per FBC Min. 26 ga. GuIfPBR screws spaced 24 in. o.c. -60.5 or insulation 36 -inch coverage Laps fastened with 1/4-14 x 7/8" HWH ZAC Impax Lap screws spaced 24 in. o.c. OPTIONAL Gu1fPBR Type 1 attachment with #9-15 HWH WoodZAC Approved fire barrier As required per FBC Min. 26 ga. GuIfPBR . screws spaced 24 ino.c. into wood purlins -100.5 nr inci dntinn 36 -inch coverage Laps fastened with 1/4-14 x 7/8 ZAC Impax Lap screws ,ES GULF COAST SUPPLY & MANUFACTURING, LLC Metal Roofing APPENDIX B Approved Systems for GulfPBR over Wood Deck (New or Existing) Fire Barrier/ Underlayment Roof Panel Panel Attachment MDP Insulation (psf) OPTIONAL As required per FBC Min. 29 ga. Gulf Rib GulfPBR Type 2 attachment with #9-15 15 HWH -22.66 Approved fire barrier As required per FBC Min. 26 ga. GulfPBR WoodZAC screws spaced 12 in. o.c. into wood purlins _151.75 or insulation As required per FBC 36 -inch coverage Laps fastened with 1/4-14 x 7/8" HWH ZAC Impax Lap -56 or insulation 36 -inch coverage screws spaced 24 in. o.c. OPTIONAL As required per FBC Min. 29 ga. GulfRib GulfPBR Type 2 attachment with #9-15 HWH WoodZAC -71.75 Approved fire barrier As required per FBC Min. 26 ga. GuIfPBR screws spaced 12 in. o.c. -154.75 or insulation 36 -inch coverage Laps fastened with 1/4-14 x 7/8" HWH ZAC Impax Lap screws spaced 24 in. o.c. Approved Systems for GulfRib over Wood Deck (New or Existing) Fire Barrier/ Underlayment Roof Panel Panel Attachment MDP Insulation (psf) OPTIONAL Approved fire barrier As required per FBC Min. 29 ga. Gulf Rib GulfRib Type 4 attachment with #12-8 HWH Woodgrip XG -22.66 or insulation 36 -inch coverage wood screws with sealing washers spaced 24 in. o.c. OPTIONAL Approved fire barrier As required per FBC Min. 29 ga. Gulf Rib GuJfRib Type 3attachment with #9-15 HWH wood screws -56 or insulation 36 -inch coverage with sealing washers spaced 24 in. o.c. OPTIONAL Approved fire barrier As required per FBC Min. 29 ga. GulfRib GulfRib Type 1 attachment with # with #9-15 HWH -71.75 or insulation 36 -inch coverage WoodZAC screws spaced 24 in. o.c ,ES GULF COAST SUPPLY & MANUFACTURING, LLC Metal Roofing APPENDIX B Approved Systems for GulfRib over Wood Deck (New or Existing) Fire Barrier/ Underlayment Roof Panel Panel Attachment MDP Insulation (psf) OPTIONAL Min. 29 ga. Guff Rib GulfRib Type 1 attachment with #9-15 x 1 112" HWH wood Approved fire barrier As required per FBC 36 -inch coverage screws with sealing washers spaced 24 in. o.c. -101 or insulation into wood purlins OPTIONAL Approved fire barrier As required per FBC Min. 29 ga. Gulf Rib Gu/fRib Type 3attachment with #9-15 HWH wood screws -101 or insulation 36 -inch coverage with sealing washers spaced 12 in. o.c. OPTIONAL Approved fire barrier As required per FBC Min. 29 ga. Gulf Rib Gu/fRib Type 4 attachment with #12-8 HWH Woodg rip XG -116.0 or insulation 36 -inch coverage wood screws with sealing washers spaced 6 in. o.c. OPTIONAL Min. ga.h GulfRb Gu/fRib Type 2attachment with #9-15 x 1 1/2" HWH wood Approved fire barrier As required per FBC coverage 36-incnc e screws with sealing washers spaced 24 in. o.c. -123.5 or insulation into wood purlins OPTIONAL Approved fire barrier As required per FBC Min. 29 ga. Gulf Rib GulfRib Type 2attachment with #9-15 HWH wood screws -146.0 or insulation 36 -inch coverage with sealing washers spaced 12 in. o.c. OPTIONAL Approved fire barrier As required per FBC Min. 26 ga. Gulf Rib Gulf% Type 1 attachment with #9-15 HWH WoodZAC -106.75 or insulation 36 -inch coverage screws spaced 24 in. o.c. into wood purlins ,ES GULF COAST SUPPLY & MANUFACTURING, LLC Metal Roofing APPENDIX B Approved Systems for GulfRib over Wood Deck (New or Existing) Fire Barrier/ Underlayment Roof Panel Panel Attachment MDP Insulation (psf) OPTIONAL Approved fire barrier As required per FBC Min. 26 ga. GuffRib GulfRib Type 1 attachment with #9-15 HWH WoodZAC -164.25 or insulation As required per FBC 36 -inch coverage screws spaced 12 in. o.c, into wood purlins -78.5 Approved Systems for GulfWave over Wood Deck (New or Existing) Fire Barrier/ Underlayment Roof Panel Panel Attachment MDP Insulation (psf) OPTIONAL Min. 26 ga. GulfWave GulfWave Type 1 attachment with Approved fire As required per FBC 29 -inch coverage #9-15 HWH wood screws with sealing washers -78.5 barrier or insulation spaced 24 in. o.c. :Es. LLC GULF COAST SUPPLY & MANUFACTURING, LLC Metal Roofing APPENDIX C sign wind loads for components and cladding in accordance with Section 1609 of the FBC and ASCE 7-16 under the following ategory I, II, 111, and IV buildings shall be as defined in Section 1609 of the FBC. shall be as defined in section 1609 of the FBC. ided only for gable/hip roofs with roof slopes between 2:12 and 6.1:12 sed on an effective wind area of 10-ft2 or less. ich as escarpments or hills have been excluded from the analysis excluded from the analysis. tor, Kd = 0.85 les below. Design wind loads are calculated using Vasd = V,,,t-\�0.6 per 1609.3.1. ?one 2e, Zone 2n, and Zone 2r ?one 3e and Zone 3r )f heights greater than 60 -ft shall be evaluated by a licensed design professional I be defined as shown below. Dimension "a" shall be 10% of the least horizontal dimension or (0.4 x Mean Roof Height), whichever than either 4% of the least horizontal dimension or 3ft Hip 3 2 3 3 2 3 a 2 1 2 2 1 2 \r"3,1 2 1,301 a .Es. LLC GULF COAST SUPPLY & MANUFACTURING, LLC Metal Roofing APPENDIX C Gable/Hip Roofs in Exposure B (Roof slope between 2:12 and 12:12 Mean Basic Wind Speed (mph) Roof Height (ft) 120 130 140 150 160 170 180 190 200 20 -25.4 -29.8 -34.6 1 -39.7 -45.2 -51.0 -57.2 -63.7 -70.6 25 30 -27.5 -28.7 -32.2 -33.7 -37.4 -39.1 -42.9 -48.8 -55.1 -61.8 -68.8 -76.3 -44.8 -51.0 -57.6 -64.6 -71.9 -79.7 40 -31.2 -36.6 -42.4 -48.7 -55.4 -62.5 -70.1 -78.1 -86.5 50 -33.2 -34.8 -39.0 -40.9 -45.2 -47.4 -51.9 -59.0 -66.6 -74.7 -78.4 -83.2 -87.3 -92.2 -96.8 60 -54.4 -61.9 -69.9 20 -37.1 -43.5 -50.5 -57.9 -65.9 -74.4 -83.4 -92.9 -103.0 25 -40.1 -41.9 -45.4 -47.0 -49.1 -53.3 -54.5 -57.0 -61.9 -62.6 -65.4 -71.0 -71.2 -74.4 -80.8 -80.4 -84.0 -91.2 -90.1 -94.2 -102.2 -100.4 -104.9 -113.9 -111.3 -116.3 -126.2 30 40 50 -48.4 -56.8 -65.9 -75.7 -86.1 -97.2 -109.0 -121.4 -134.5 60 -50.8 -59.6 -69.2 -79.4 -90.3 1 -102.0 -114.3 -127.4 -141.2 20 -44.1 -51.7 -60.0 -68.8 -78.3 -88.4 -99.1 -110.5 -122.4 25 -47.6 -55.9 -64.8 -74.4 -84.7 -95.6 -107.1 -119.4 -132.3 30 -49.8 -58.4 -67.7 -77.7 -88.4 -99.8 -111.9 -124.7 -138.2 40 -54.0 -63.4 -73.5 -84.4 -96.0 -108.4 -121.5 -135.4 -150.0 50 -57.6 -67.6 -78.4 -90.0 -102.3 -115.5 -129.5 -144.3 -159.9 60 -60.4 -70.9 -82.2 -94.4 -107.4 -121.2 -135.9 -151.4 -167.8 20 -29.7 -32.1 -34.9 -37.7 -40.5 -43.7 -46.5 -50.2 -52.8 -57.1 -59.7 -64.5 -66.9 -72.3 -74.5 -80.5 -82.6 25 -89.2 30 -33.6 -39.4 -45.7 -52.4 -59.7 -67.4 -75.5 -84.1 -93.2 40 -36.4 -42.8 -49.6 -56.9 -64.8 -73.1 -82.0 -91.3 -101.2 50 -38.8 -45.6 -52.9 -60.7 -69.0 -77.9 -87.4 -97.4 -107.9 60 -40.8 -47.8 -55.5 -63.7 -72.4 -81.8 -91.7 -102.2 -113.2 20 -41.4 -48.6 -56.3 -64.7 -73.6 -83.1 -93.1 -103.7 -115.0 25 -44.7 -52.5 -60.9 -69.9 -79.5 -89.8 -100.6 -112.1 -124.2 30 -46.7 -54.8 -63.6 -73.0 -83.1 -93.8 -105.1 -117.1 -129.8 40 -50.7 -59.5 -69.0 -79.3 -90.2 -101.8 -114.1 -127.2 -140.9 50 -54.1 -56.7 An A -63.4 -66.6 LB n -73.6 -77.2 BL n -84.5 -88.6 -/e C -96.1 -100.9 ne A -108.5 -113.9 0%7 4 -121.6 -127.6 4nn n -135.5 -142.2 4A4 n -150.2 60 M -157.6 inI Lam. LLC GULF COAST SUPPLY & MANUFACTURING, LLC Metal Roofing APPENDIX C Gable/Hip Roofs in Exposure C (Roof slope between 2:12 and 12:12 Mean Basic Wind Speed (mph) Roof Height (ft) 120 130 140 150 160 170 180 190 200 20 -36.9 -43.3 -50.2 -57.6 -65.6 -74.0 -83.0 -92.5 -102.5 25 -38.5 -45.2 -52.4 -60.2 -68.5 -77.3 -86.7 -96.6 -107.0 30 -40.2 -47.1 -54.7 -62.8 -71.4 -75.8 -80.6 -85.6 -90.4-100.7 -95.9 -106.9 -111.6 -118.4 40 -42.6 -50.0 -58.0 -66.6 50 -44.7 -52.4 -60.8 -69.8 -79.4 -89.7 -100.5 -112.0 -124.1 60 -46.3 -54.4 -63.0 -72.4 -82.3 -93.0 -104.2 -116.1 -128.7 20 -53.8 -63.2 -73.2 -84.1 -95.7 -108.0 -121.1 -134.9 -149.5 25 -56.2 -66.0 -76.5 -87.8 -99.9 -112.8 -126.5 -140.9 -156.1 30 -58.6 -68.8 -79.8 -91.6 -104.2 -117.6 -131.8 -146.9 -162.8 40 -62.2 -73.0 -84.6 -97.2 -110.5 -124.8 -139.9 -155.9 -172.7 50 -65.2 -76.5 -88.7 -101.8 -115.9 -130.8 -146.6 -163.4 -181.0 60 -67.6 -79.3 -92.0 -105.6 -120.1 -135.6 -152.0 -169.4 -187.7 20 -64.0 -75.1 -87.1 -99.9 -113.7 -128.4 -143.9 -160.3 -177.7 25 -66.8 -78.4 -90.9 -104.4 -118.8 -134.1 -150.3 -167.5 -185.6 30 -69.7 -81.7 -94.8 -108.8 -123.8 -139.8 -156.7 -174.6 -193.5 40 -73.9 -86.7 -100.6 -115.5 -131.4 -148.3 -166.3 -185.3 -205.3 50 -77.5 -90.9 -105.4 -121.0 -137.7 -155.5 -174.3 -194.2 -215.2 60 -80.3 -94.3 -109.3 -125.5 -142.8 -161,2 -180.7 1 -201.3 -223.1 20 -43.2 -50.6 -58.7 -67.4 -76.7 -86.6 -97.1 -108.2 -119.9 25 -45.1 -52.9 -61.3 -70.4 -80.1 -83.5 -90.4 1-101.4 -94.3 -105.7 -113.0 -117.8 -125.2 -130.5 30 -47.0 -55.1 -64.0 -73.4 40 -49.9 -58.5 -67.9 -77.9 -88.6 -100.1 -112.2 -125.0 -138.5 50 -52.3 -54.2 -61.3 -63.6 -71,1 -73.7 -81.7 -84.7 -92.9 -96.3 -104.9 -108.7 -117.6 -121.9 -131.0 -135.8 -145.2 -150.5 60 20 -60.1 -70.5 -81.8 -93.9 -106.8 -120.6 -135.2 -150.6 -166.9 25 -62.7 -65.4 -69.4 -73.6 -76.8 -81.5 -85.4 -89.0 -94.5 -98.0 -102.2 -108.5 -111.5 -125.9 -141.2 -157.3 -174.3 30 -116.3 -131.3 -147.2 -164.0 -181.7 40 -123.4 -139.3 -156.2 -174.0 -192.8 50 -72.8 -85.4 -99.0-113.7 -129.3 -146.0 -163.7 -182.4 -202.1 60 -75.4 1 -88.5 -102.7 -117.8 -134.1 -151.4 -169.7 -189.1 -209.5 on 7n7 1 09A I nCC 1nn7 40wo 1Ar%n 1cOn 4712 r% 4nc4 LC' GULF COAST SUPPLY & MANUFACTURING, LLC Metal Roofing APPENDIX C Gable/Hip Roofs in Exposure D (Roof slope between 2:12 and 12:12) Mean Basic Wind Speed (mph) Roof Height (ft) 120 130 140 150 160 170 180 190 200 20 25 -44.3 -45.9 -52.0 -53.9 -60.3 -62.5 -69.2 -71.7 -78.7 -81.6 -88.8 -92.1 -99.6 -103.3 -111.0 -115.1 -123.0 -127.5 30 -47.5 -55.8 -64.7 -74.3 -84.5 -95.4 -107.0 -119.2 -132.1 40 -50.0 -58.7 -68.1 -78.1 -88.9 -100.4 -112.5 -125.4 -138.9 50 -52.1 -61.1 -70.9 -81.3 -92.5 -104.5 -117.1 -130.5 -144.6 60 -53.7 -63.0 -73.1 -83.9 -95.5 -107.8 -120.8 -134.6 -149.1 20 -64.6 -75.8 -87.9 -100.9 -114.8 -129.6 -145.3 -161.9 -179.4 25 -67.0 -78.6 -91.1 -104.6 -119.0 -134.4 -150.7 -167.9 -186.0 30 -69.4 -81.4 -94.4 -108.4 -123.3 -139.2 -156.0 -173.9 -192.6 40 -72.9 -85.6 -99.3 -114.0 -129.7 -146.4 -164.1 -182.9 -202.6 50 -75.9 -89.1 -103.3 -118.6 -135.0 -152.4 -170.8 -190.4 -210.9 60 -78.3 -91.9 -106.6 -122.4 -139.2 -157.2 -176.2 -196.3 -217.6 20 -76.8 -90.1 -104.5 -119.9 -136.5 -154.0 -172.7 -192.4 -213.2 25 -79.6 -93.4 -108.3 -124.4 -141.5 -159.7 -179.1 -199.5 -221.1 30 -82.4 -96.8 -112.2 -128.8 -146.6 -165.4 -185.5 -206.7 -229.0 40 -86.7 -101.8 -118.0 -135.5 -154.1 -174.0 -195.1 -217.4 -240.8 50 -90.3 -105.9 -122.8 -141.0 -160.5 -181.1 -203.1 -226.3 -250.7 60 -93.1 -109.3 -126.7 -145.5 -165.5 -186.8 -209.5 -233.4 -258.6 20 -51.8 -60.8 -70.5 -80.9 -92.1 -103.9 -116.5 -129.8 -143.8 25 -53.7 -63.0 -73.1 -83.9 -95.5 -107.8 -120.8 -134.6 -149.2 30 -55.6 -65.3 -75.7 -86.9 -98.9 -111.6 -125.1 -139.4 -154.5 40 -58.5 -68.7 1 -79.6 -91.4 -104.0 -117.4 -131.6 -146.6 -162.5 50 -60.9 -71.5 -82.9 -95.1 -108.2 -122.2 -137.0 -152.6 -169.1 60 -62.8 -73.7 -85.5 -98.1 -111.7 -126.0 -141.3 -157.5 -174.5 20 -72.1 -84.6 -98.1 -112.6 -128.2 -144.7 -162.2 -180.7 -200.2 25 -74.8 -87.7 -101.7 -116.8 -132.9 -150.0 -168.2 -187.4 -207.6 30 -77.4 -90.9 -105.4 -121.0 -137.6 -155.4 -174.2 -194.1 -215.1 40 -81.4 -95.6 -110.8 -127.2 -144.8 -163.4 -183.2 -204.1 -226.2 50 -84.8 -99.5 -115.4 -132.4 -150.7 -170.1 -190.7 -212.5 -235.5 60 -87.4 -102.6 -119.0 -136.6 -155.4 -175.5 -196.7 -219.2 -242.9 20 -84.3 -98.9 -114.7 -131.7 -149.8 -169.1 -189.6 -211.3 -234.1 nr n� • •nn n • •n n •nn r •rr • •ter • •nn n n•n • �•n �