482 Stewart St MECH23-0008 COAB Permit Form with ConditionsOWNER:ADDRESS:CITY:STATE:ZIP:
BBT INVESTORS LLC 2251 ST JOHNS BLUFF RD S JACKSONVILLE FL 32246-2309
COMPANY:ADDRESS:CITY:STATE:ZIP:
WAYNE AUTOMATIC FIRE
SPRINKLERS, INC.222 CAPITOL CT OCOEE FL 34761
TYPE OF
CONSTRUCTION:
REAL ESTATE
NUMBER:ZONING:BUILDING USE
GROUP:SUBDIVISION:
172327 0050 SECTION LAND
JOB ADDRESS:PERMIT TYPE:DESCRIPTION: VALUE OF WORK:
482 STEWART ST MECHANICAL COMMERCIAL
SEPARATE PLANS OTHER FIRE SPRINKLER SYSTEM $2450.00
FEES
DESCRIPTION ACCOUNT QUANTITY PAID AMOUNT
FIRE SPRINKLER SYSTEM 455-0000-322-1000 0 $0.00
FIRE SPRINKLER SYSTEM 455-0000-322-1000 0 $20.00
MECHANICAL BASE FEE 455-0000-322-1000 0 $55.00
STATE DBPR SURCHARGE 455-0000-208-0700 0 $2.00
STATE DCA SURCHARGE 455-0000-208-0600 0 $2.00
LIST OF CONDITIONS
Roll off container company must be on City approved list . Container cannot be placed on City right-of-way.
NOTICE: In addition to the requirements of this permit, there may be additional restrictions applicable to this property
that may be found in the public records of this county, and there may be additional permits required from other
governmental entities such as water management districts, state agencies, or federal agencies.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT
IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. A NOTICE OF
COMMENCEMENT MUST BE RECORDED AND POSTED ON THE JOB SITE BEFORE THE FIRST
INSPECTION. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN
ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.
MUST CALL INSPECTION PHONE LINE (904) 247-5814 BY 4 PM FOR NEXT DAY INSPECTION.
ALL WORK MUST CONFORM TO THE CURRENT 6TH EDITION (2017) OF THE FLORIDA BUILDING
CODE, NEC, IPMC, AND CITY OF ATLANTIC BEACH CODE OF ORDINANCES .
ALL CONDITIONS OF PERMIT APPLY, PLEASE READ CAREFULLY.
1 of 2Issued Date: 6/22/2023
PERMIT NUMBER
MECH23-0008
ISSUED: 6/22/2023
EXPIRES: 12/19/2023
MECHANICAL COMMERCIAL
SEPARATE PLANS PERMIT
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
TOTAL: $79.00
2 of 2Issued Date: 6/22/2023
PERMIT NUMBER
MECH23-0008
ISSUED: 6/22/2023
EXPIRES: 12/19/2023
MECHANICAL COMMERCIAL
SEPARATE PLANS PERMIT
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
MECH23-0008
PendentUpright
Note: Not all versions of the product are shown.
Features
• Standard coverage, standard-response sprinklers
• Upright, pendent, horizontal sidewall, and vertical sidewall
deflectors
• Robust solder capsule thermal element
• Available in a wide variety of finishes
Product Description
Reliable Model G Series sprinklers are standard-response
standard spray automatic sprinklers using a solder capsule
thermal element. The solder is captured in the cylinder of the
capsule by a stainless steel ball. When the solder melts, the ball
moves into the cylinder allowing the thermal element to fall away
from the sprinkler. When this occurs, the compressed strut and
lever spring free from the sprinkler. System pressure then clears
the waterway of all operating parts allowing the deflector to
evenly distribute water.
Pendent and horizontal sidewall sprinklers may be installed
exposed or surface mounted using escutcheons such as the
Reliable Models B, C, or HB (reference Technical Bulletin 204).
When installed recessed, the Model G Series sprinklers are
specifically listed with and may only be installed with listed
Reliable escutcheons. Refer to the technical information on the
following pages for specific listings for recessed installations and
Figures 6 and 7 for dimensional information.
www.reliablesprinkler.com
Model G Series
Standard-Response Sprinklers
Bulletin 110 January 2023
Sprinkler Summary
Model K-Factor gpm/psi1/2
(lpm/bar1/2)Listings & Approvals Threads Sprinkler Identification
Number (SIN)
G Upright
2.8 (40)UL, FM 1/2” NPT, ISO 7-R1/2 R1021
4.2 (60)UL 1/2” NPT, ISO 7-R1/2 R1023
5.6 (80)UL, FM, LPCB, EC, UKCA 1/2” NPT, ISO 7-R1/2 R1025
8.0 (115)UL, FM 1/2” NPT, ISO 7-R1/2 R1026
8.0 (115)UL, FM, LPCB, EC, UKCA 3/4” NPT, ISO 7-R3/4 R1027
G Upright
Intermediate
5.6 (80)UL, FM 1/2” NPT, ISO 7-R1/2 R1425
8.0 (115)UL, FM 3/4” NPT, ISO 7-R3/4 R1427
G Pendent
2.8 (40)UL, FM 1/2” NPT, ISO 7-R1/2 R1011
4.2 (60)UL 1/2” NPT, ISO 7-R1/2 R1013
5.6 (80)UL, FM, LPCB, EC, UKCA 1/2” NPT, ISO 7-R1/2 R1015
8.0 (115)UL, FM 1/2” NPT, ISO 7-R1/2 R1016
8.0 (115)UL, FM, LPCB, EC, UKCA 3/4” NPT, ISO 7-R3/4 R1017
G Horizontal
Sidewall
2.8 (40)UL 1/2” NPT, ISO 7-R1/2 R1231
4.2 (60)UL 1/2” NPT, ISO 7-R1/2 R1233
5.6 (80)UL, FM, LPCB 1/2” NPT, ISO 7-R1/2 R1235
8.0 (115)UL 1/2” NPT, ISO 7-R1/2 R1236
8.0 (115)UL 3/4” NPT, ISO 7-R3/4 R1237
G Vertical Sidwall 5.6 (80)FM, LPCB, EC, UKCA 1/2” NPT, ISO 7-R1/2 R1285
Table A
When fitted with an approved water shield, these sprinklers may
considered intermediate sprinklers for use in racks, below grated
walkways, and other areas where intermediate level sprinklers are
required.
Model G Upright Sprinkler
Technical Specifications
Style: Upright
Threads: (see Table B)
Nominal K-Factor: (See Table B)
Max. Working Pressure:
175 psi (12 bar)
Material Specifications
Thermal Sensor: Solder capsule
Sprinkler Frame: Brass Alloy
Cap: Bronze Alloy with PTFE
Load Screw: Brass Alloy
Deflector: Brass Alloy
Sprinkler Finishes
(See Table F)
Sensitivity
Standard response
Temperature Ratings
135°F (57°C)
165°F (74°C)
212°F (100°C)
286°F (141°C)
Guards & Shields
D-1 Guard (UL)
C-1 Guard (FM)
C-3 Guard with Shield (UL, FM on R1025,
R1026, and R1027 only)
Sprinkler Wrench
Model W2
Listings and Approvals
(See Table B)
Model G Upright Sprinkler Components and Dimensions Figure 1
SIN K-factor (US)K-factor (Metric)Threads Approvals
R1021 2.8 40 1/2” NPT, ISO 7-R1/2 UL, FM
R1023 4.2 60 1/2” NPT, ISO 7-R1/2 UL
R1025 5.6 80 1/2” NPT, ISO 7-R1/2
UL, FM, LPCB,
EC: 1438-CPR-0053
UKCA: 0832-UKCA-
CPR-S5104
R1026 8.0 115 1/2” NPT, ISO 7-R1/2 UL, FM
R1027 8.0 115 3/4” NPT, ISO 7-R3/4
UL, FM, LPCB,
EC: 1438-CPR-0053
UKCA: 0832-UKCA-
CPR-S5104
Model G Upright Sprinklers Table B
Bulletin 110
January 2023
Page 2 of 10
www.reliablesprinkler.com
Model G Intermediate Upright Sprinkler
Technical Specifications
Style: Intermediate Upright
Threads: (See Table C)
Nominal K-Factor: (See Table C)
Max. Working Pressure:
175 psi (12 bar)
Material Specifications
Thermal Sensor: Solder Capsule
Sprinkler Frame: Brass Alloy
Cap: Bronze Alloy with PTFE
Load Screw: Brass Alloy
Deflector: Brass Alloy
Sprinkler Finishes
Bronze (Only)
Sensitivity
Standard response
Temperature Ratings
135°F (57°C)
165°F (74°C)
212°F (100°C)
286°F (141°C)
Guards & Shields
Factory Water Shield (cULus, FM)
Sprinkler Wrenches
Model W2
Listings and Approvals
(See Table C)
Model G Intermediate Upright Sprinkler Components and Dimensions Figure 2
SIN K-factor (US)K-factor (Metric)Threads Approvals
R1425 5.60 80 1/2” NPT, ISO 7-R1/2 UL, FM
R1427 8.00 115 3/4” NPT, ISO 7-R3/4 UL, FM
Model G Intermediate Upright Sprinklers Table C
Bulletin 110
January 2023
Page 3 of 10
www.reliablesprinkler.com
Model G Pendent Sprinkler
Technical Specifications
Style:
Pendent
Recessed Pendent
Threads: (See Table D)
Nominal K-Factor: (See Table D)
Max. Working Pressure:
175 psi (12 bar)
Material Specifications
Thermal Sensor: Solder Capsule
Sprinkler Frame: Brass Alloy
Cap: Bronze Alloy with PTFE
Load Screw: Brass Alloy
Deflector: Brass Alloy
Sprinkler Finishes
(See Table F)
Sensitivity
Standard response
Temperature Ratings
135°F (57°C)
165°F (74°C)
212°F (100°C)
286°F (141°C)(1)
Recessed Escutcheons
G (cULus, all SIN)
G (FM, SIN R1015 only)(2)
F1 (cULus, all SIN)
F1 (LPCB, SIN R1015 only)
Guards & Shields(3)
D-1 Guard (UL)
D-5 Guard and Shield (UL, R1015, R1016, and
R1017)
C-1 Guard (FM)
C-5 Guard with Shield (FM on R1015 and R1017
only)
S-1 (1/2”) Shield (cULus, FM, R1015 only)
S-2 (3/4”) Shield (cULus, FM, R1017 only)
Sprinkler Wrenches
Model W2 (non-recessed pendent)
Model RC1 (recessed pendent)
Listings and Approvals
(See Table D)
Model G Pendent Sprinkler Components and Dimensions Figure 3
SIN K-factor (US)K-factor (Metric)Threads Approvals
R1011 2.8 40 1/2” NPT, ISO 7-R1/2 UL, FM
R1013 4.2 60 1/2” NPT, ISO 7-R1/2 UL
R1015 5.6 80 1/2” NPT, ISO 7-R1/2
UL, FM, LPCB,
EC: 1438-CPR-0053
UKCA: 0832-UKCA-
CPR-S5104
R1016 8.0 115 1/2” NPT, ISO 7-R1/2 UL, FM
R1017 8.0 115 3/4” NPT, ISO 7-R3/4
UL, FM, LPCB,
EC: 1438-CPR-0053
UKCA: 0832-UKCA-
CPR-S5104
Model G Pendent Sprinklers Table D
Bulletin 110
January 2023
Page 4 of 10
www.reliablesprinkler.com
Notes:
1. 286°F (141°C) temperature rated sprinklers not approved for recessed installations.
2. FM Approval of Model G Recessed sprinkler for ordinary and extra hazard occupancies is limited to wet pipe systems only.
3. Not suitable for recessed installations.
Model G Horizontal Sidewall Sprinkler
Technical Specifications
Style: Horizontal Sidewall
Threads: (See Table E)
Nominal K-Factor: See Table E
Max. Working Pressure:
175 psi (12 bar)
Material Specifications
Thermal Sensor: Solder Capsule
Sprinkler Frame: Brass Alloy
Cap: Bronze Alloy with PTFE
Load Screw: Brass Alloy
Deflector: Brass Alloy
Sprinkler Finishes
(See Table F)
Sensitivity
Standard response
Temperature Ratings
135°F (57°C)
165°F (74°C)
212°F (100°C)
286°F (141°C)
Recessed Escutcheons(1)(2)
F1 (UL)
Guards & Shields(3)
D-1 Guard (UL, all SIN)
C-1 Guard (FM, SIN R1235 only)
Sprinkler Wrenches
Model W2 (non-recessed sidewall)
Model RC-1 (recessed sidewall)
Listings and Approvals(4)
(See Table E)
Notes:
1. Listed for use with 135°F (57°C) temperature rated sprinkler only.
2. Listed for Light Hazard ONLY when installed recessed.
3. Not suitable for recessed horizontal sidewall installations.
4. Listed for light hazard only, except for SIN R1235 is cULus Listed for ordinary hazard when exposed or surface mounted.
Model G Horizontal Sidewall Sprinkler Components and Dimensions Figure 4
Bulletin 110
January 2023
Page 5 of 10
www.reliablesprinkler.com
Note: Please refer to Figure 7 for recessed installation.
SIN K-factor (US)K-factor (Metric)Threads Approvals
R1231 2.8 40 1/2” NPT, ISO 7-R1/2 UL
R1233 4.2 60 1/2” NPT, ISO 7-R1/2 UL
R1235 5.6 80 1/2” NPT, ISO 7-R1/2 UL, FM, LPCB
R1236 8.0 115 1/2” NPT, ISO 7-R1/2 UL
R1237 8.0 115 3/4” NPT, ISO 7-R3/4 UL
Model G Horizontal Sidewall Sprinklers Table E
Model G Vertical Sidewall Sprinkler SIN R1285
Technical Specifications
Style:
Upright Vertical Sidewall
Pendent Vertical Sidewall
Threads: 1/2” NPT or ISO 7-R1/2
Nominal K-Factor: 5.6 (80 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Thermal Sensor: Solder Capsule
Sprinkler Frame: Brass Alloy
Cap: Bronze Alloy with PTFE
Load Screw: Brass Alloy
Deflector: Brass Alloy
Sprinkler Finishes
(See Table F)
Sensitivity
Standard response
Temperature Ratings
135°F (57°C)
165°F (74°C)
212°F (100°C)
286°F (141°C)
Guards & Shields
C-1 Guard (FM)
Sprinkler Wrenches
Model W2
Listings and Approvals(1)
FM Approved
LPCB
EC (1438-CP-0055)
UKCA: 0832-UKCA-CPR-S5104
Notes:
1. Listed and approved for Light Hazard ONLY.
Model G Vertical Sprinkler Components and Dimensions Figure 5
Bulletin 110
January 2023
Page 6 of 10
www.reliablesprinkler.com
Recessed Installation: Pendent Sprinklers Figure 6
Bulletin 110
January 2023
Page 7 of 10
www.reliablesprinkler.com
Recessed Installation: G Horizontal Sidewall Sprinklers Figure 7
MODEL G HORIZONTAL SIDEWALL SPRINKLER
WITH MODEL F1 RECESSED ESCUTCHEON
3/4" [19mm]
Escutcheon
Adjustment
Hole in Ceiling
Recommended
2 1/4" [57mm]
1 7/8" [48mm]
Turn collar tight
to wrench boss
2 7/8" [72mm]
1/4" [6mm] Min
1" [25mm] Max
1-1/4" [32mm] Min
2" [51mm] Max
Face of fitting
to ceiling
110RECHSW
Reducing
Fitting
(TOP VIEW)
G Escutcheon F1 Recessed
Bulletin 110
January 2023
Page 8 of 10
www.reliablesprinkler.com
Maintenance
Reliable Model G series sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25, as well
as the requirements of any authorities having jurisdiction.
Prior to installation, sprinklers should remain in the original
cartons and packaging until used. This will minimize the potential
for damage to sprinklers that could cause improper operation or
non-operation.
Do not clean sprinklers with soap and water, ammonia liquid or
any other cleaning fluids. Remove dust by gentle vacuuming
without touching the sprinkler.
Replace any sprinkler which has been painted (other than factory
applied). A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprinklers.
Failure to properly maintain sprinklers may result in inadvertent
operation or non-operation during a fire event.
Standard Finishes Special Application Finishes
Sprinkler G and F1 Recessed
Escutcheons Sprinkler G and F1 Recessed
Escutcheons
Bronze Brass Bright Brass(5)Bright Brass
Chrome Chrome Satin Chrome Satin Chrome
White Polyester(3)(4)White Polyester Custom Color Polyester(3)(4)Custom Color Polyester
Lead Plated(6)(7)
Wax Coated(6)(7)(8)
Wax Over Lead(6)(7)(8)
Notes:
1. Other finishes and colors are available on special order. Consult your Reliable sales representative for details.
2. Paint or any other coating applied over the factory finish will void all approvals and warranties.
3. The Model G Recessed assembly consists of a sprinkler mounted in a galvanized steel cup with a finished trim ring.
4. Only frame and deflector are coated, operating parts are chrome plated.
5. For 212°F (100°C) maximum temperature rated sprinklers only.
6. Not suitable for use with recessed installations.
7. cULus Listed as corrosion resistant.
8. Clear wax used on ordinary temperature rated sprinklers; brown wax used on intermediate temperature rated sprinklers. Brown wax may be used on
high temperature rated sprinklers where the ambient temperature does not exceed 150°F (66°C).
Finishes(1)(2)Table F
Wrenches
Model W2 (upright, pendent, sidewall)
Model RC1 (recessed)
Application
Model G Series standard spray upright and pendent sprinklers
having K-factors of 5.6 (80) and higher are permitted to be used
in all occupancy classifications and building construction types
unless otherwise noted.
Model G Series standard spray upright and pendent sprinklers
having K-factors less than 5.6 (80) are limited to light hazard
occupancies.
Model G Series sidewall sprinklers shall only be installed in
light hazard occupancies with smooth, horizontal or sloped, flat
ceilings unless otherwise noted.
Bulletin 110
January 2023
Page 9 of 10
www.reliablesprinkler.com
P/N 9999970005Bulletin 110
January 2023
Page 10 of 10
www.reliablesprinkler.com
Installation
Model G Series sprinklers must be installed in accordance with
NFPA 13 and the requirements of all applicable authorities having
jurisdiction
Model G Series sprinklers must be installed with the Reliable
sprinkler installation wrench identified in this Bulletin. Any other
wrench may damage the sprinkler. A leak tight sprinkler joint
can be obtained with a torque of 8 to 18 lb-ft (11 - 24 N.m) for
1/2” sprinklers and a torque of 14-20 lb-ft (19 - 27 N.m) for 3/4”
sprinklers after applying appropriate thread sealant.
Do not tighten sprinklers over the maximum recommended
installation torque. Exceeding the maximum recommended
installation torque may cause leakage or impairment of the
sprinkler.
Guarantee
For the guarantee, terms, and conditions, visit
www.reliablesprinkler.com.
Ordering Information
Specify the following when ordering:
Model
• G
Deflector/Orientation
• Upright
• Upright Intermediate
• Pendent
• G Recessed
• Horizontal Sidewall
• Vertical Sidewall
Temperature Rating
• See sprinkler technical specifications
Sprinkler Finish
• See Table F
Recessed Escutcheon*
• G
• F1
Escutcheon Finish
• See Table F
Sprinkler Wrench
• Model W2 (upright, non-recessed pendent, and sidewall)
• Model RC1 (recessed)
Guards and Shields
• See sprinkler technical specifications
*Note: 286°F (141°C) sprinklers are not listed to be used recessed.