330 Sargo Rd RES23-0018 - BLOWER DOOR TESTF L O R I D A
`= BLOWER
DOOR
Permit#:kES`a3,pptg
Blower Door Test Form
Job Information
Builder: Mathieu Builders
Community: Lot #:
Address: 330 Sargo Rd Unit #:
City, State, Zip: Atlantic Beach, FL 32233
Air Infiltration Test Results
CFM(50) = 1058 Volume = 17198
ACH(50)={CFM(50) X 60 / Volume = 3.69
J Pass ❑ Fail Passing results must be 7 ACH(50) or less
Certification of Test Results
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes
per hour in Climate Zones 1 and 2, 3 air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with a blower door at a
pressure or 0.2 inches w.g. (50 Pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7),F.S. or
individuals licensed as set forth in Section 489.105(3)(9, (g), or (h) or an approved third party. A written report of the results of the test
shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of
all penetrations of the building thermal envelope.
Authorized Third Partv
I hereby certify the above results and that I hold the below certification:
Class A or B A/C contractor or Mechanical contractor License No.
RESNET approved HERS Rater or Residential Field Inspector Certification No.
✓ BPI approved Building Analyst, Energy Auditor, & IDL Certification No. 5020420
Professional Engineer License No.
Mechanical ventilation has been added: Yes No
Signature:
f
Printed Name: Christian Hernandez Date: 08/08/2023