1852 SEA OATS RES3-0076 GOODRICH RES ESHEET (2UNITS)- REV. 9-15-23_1FORM R405-2022 Supplement
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: GOODRICH RESIDENCE Builder Name: MARCO HEATING & AIR
Street:1852 SEA OATS DRIVE Permit Office: DUVAL CNTY
City, State, Zip: ATLANTIC BCH, FL, 32233 Permit Number:
Owner:GOODRICH RESIDENCE Jurisdiction: 261300
Design Location: FL, Jacksonville County: DUval(Florida Climate Zone 2)
1. New construction or existing New (From Plans)
2. Single family or multiple family Detached
3. Number of units, if multiple family 1
4. Number of Bedrooms 3
5. Is this a worst case?No
6. Conditioned floor area above grade (ft²)2490
Conditioned floor area below grade (ft²)0
7. Windows(492.0 sqft.) Description Area
a. U-Factor:Dbl, U=0.33 289.00 ft2
S H G C :SHGC=0.23
b. U-Factor:Dbl, U=0.55 203.00 ft2
S H G C :SHGC=0.27
c. U-Factor:N/A f t2
S H G C :
Area Weighted Average Overhang Depth: 2.000 ft
Area Weighted Average SHGC:0.247
8. Skylights Description Area
U - F a c t o r : ( A V G ) N/A N/A ft2
S H G C ( A V G ) : N/A
9. Floor Types I n s u l a t i o n Area
a. Slab-On-Grade Edge Insulation R= 0.0 2490.00 f t2
b. N/A R = f t2
c. N/A R = f t2
10. Wall Types(2727.0 sqft.) I n s u l a t i o n Area
a. Frame - Wood, Exterior R=13.0 2160.00 ft2
b. Interior Frame - Wood, Interior R=0.0 288.00 ft2
c. Frame - Wood, Adjacent R=13.0 279.00 ft2
d. N/A
11. Ceiling Types(2490.0 sqft.) I n s u l a t i o n Area
a. Flat ceiling under att (Vented) R=38.0 2490.00 ft2
b. N/A
c. N/A
12. Roof(Comp. Shingles, Vented) Deck R=0.0 2714 ft2
13. Ducts, location & insulation level R ft2
a. Sup: Attic, Ret: Attic, AH: Attic 6 270
b. Sup: Attic, Ret: Attic, AH: Attic 6 228
c .
14. Cooling Systems k B t u / h r Efficiency
a. Central Unit 23.6 SEER2:16.50
b. Central Unit 23.6 SEER2:16.50
15. Heating Systems k B t u / h r Efficiency
a. Electric Heat Pump 24.6 HSPF2:8.00
b. Electric Heat Pump 24.6 HSPF2:8.00
16. Hot Water Systems
a. Natural GasTankless Cap: 1 gallons
EF: 0.999
b. Conservation features
None
17. Credits CF, Pstat
Glass/Floor Area:0.198 Total Proposed Modified Loads: 54.79
Total Baseline Loads: 62.87 PASS
I hereby certify that the plans and specifications covered by Review of the plans and
this calculation are in compliance with the Florida Energy specifications covered by this
Code.calculation indicates compliance
with the Florida Energy Code.
PREPARED BY: _________________________________ Before construction is completed
this building will be inspected for
DATE: _________________________________________ compliance with Section 553.908
Florida Statutes.
I hereby certify that this building, as designed, is in compliance
with the Florida Energy Code.
OWNER/AGENT: __________________________________ BUILDING OFFICIAL: ____________________________
DATE: _________________________________________ DATE: _________________________________________
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.3.2.1.
- Default duct leakage does not require a Duct Leakage Test Report.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project
requires a PERFORMANCE envelope leakage test report with envelope leakage no greater than 7.00 ACH50 (R402.4.1.2).
8/22/2023 10:24:12 AMEnergyGauge® USA 7.5.00 - FlaRes2020 FBC 7th Edition (2022 Supplement) Compliant Software Page 1
09/13/23
FORM R405-2022S INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title:GOODRICH RESIDENCE Address type:Street Address
Building Type:Bedrooms:Lot #:User 3 ---
Owner:Conditioned Area:Block/SubDivision:GOODRICH RESIDENCE 2490 ---
Builder Home ID:Total Stories:PlatBook:1 ---
Builder Name:Worst Case:Street:MARCO HEATING & AIR No 1852 SEA OATS DRIVE
Permit Office:Rotate Angle:County:DUVAL CNTY 0 DUval
Jurisdiction:Cross Ventilation:City, State, Zip:261300 No ATLANTIC BCH,
Family Type:Whole House Fan: Detached No FL, 32233
New/Existing:Terrain: New (From Plans)Suburban
Year Construct:Shielding: 2023 Suburban
Comment:
CLIMATE
Design Design Temp Int Design Temp Heating Design Daily temp
Location Tmy Site 97.5%2.5%Winter Summer Degree Days Moisture Range
___ FL, Jacksonville FL_JACKSONVILLE_INTL_A 32 93 70 75 1281 49 Medium
BLOCKS
Number Name Area Volume
___ 1 (Rest of House)1348 12132 cu ft
___ 2 BED 1142 10278 cu ft
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms Finished Cooled Heated
___ 1 MAIN 853 7677 No 0 Yes Yes Yes
___ 2 KITHEN 495 4455 Yes 0 Yes Yes Yes
___ 3 BEDS 1142 10278 No 4 3 Yes Yes Yes
FLOORS (Total Exposed Area = 2490 sq.ft.)
#Floor Type Space Exposed Perim Perimeter R-Value Area U-Factor Joist R-Value Tile Wood Carpet
___ 1 Slab-On-Grade Edge Ins MAIN 56 0 853 ft 0.587 ---0.30 0.30 0.40
___ 2 Slab-On-Grade Edge Ins KITHEN 73 0 495 ft 0.587 ---0.30 0.30 0.40
___ 3 Slab-On-Grade Edge Ins BEDS 127 0 1142 ft 0.587 ---0.30 0.30 0.40
ROOF
Roof Gable Roof SolarRad SA Emitt Emitt Deck Pitch
#Type Materials Area Area Color Absor.Barr Tested Tested Insul.(deg)
___ 1 Hip Composition shingles 2714 ft²0 ft²Medium N 0.9 No 0.9 No 0 23.43
ATTIC
#Type Ventilation Vent Ratio (1 in)Area RBS IRCC
___ 1 Full attic Vented 300 2490 ft²N N
8/22/2023 10:24:12 AM Page 2EnergyGauge® USA 7.5.00 - FlaRes2020 FBC 7th Edition (2022 Supplement) Compliant Software
FORM R405-2022S INPUT SUMMARY CHECKLIST REPORT
CEILING (Total Exposed Area = 2490 sq.ft.)
#Ceiling Type Space R-Value Ins. Type Area U-Factor Framing Frac.Truss Type
___ 1 Flat ceiling under attic(Vented)MAIN 38.0 Blown 853.0ft²0.049 0.10 Wood
___ 2 Flat ceiling under attic(Vented)KITHEN 38.0 Blown 495.0ft²0.049 0.10 Wood
___ 3 Flat ceiling under attic(Vented)BEDS 38.0 Blown 1142.0ft²0.049 0.10 Wood
WALLS (Total Exposed Area = 2439 sq.ft.)
Adjacent Cavity Width Height Area U-Sheath Frm.Solar Below
#Ornt To Wall Type Space R-Value Ft In Ft In sq.ft.Factor R-Value Frac.Absor.Grade
___ 1 N Exterior Frame - Wood MAIN 13.0 24.0 0 9.0 0 216.0 0.094 0 0.23 0.01 0 %
___ 2 S Exterior Frame - Wood MAIN 13.0 16.0 0 9.0 0 144.0 0.094 0 0.23 0.01 0 %
___ 3 E BEDS Interior Fr. Wood MAIN 0.0 32.0 0 9.0 0 288.0 0.370 0 0.23 0.80 0 %
___ 4 N Exterior Frame - Wood MAIN 13.0 7.0 0 9.0 0 63.0 0.094 0 0.23 0.01 0 %
___ 5 S Exterior Frame - Wood MAIN 13.0 8.0 0 9.0 0 72.0 0.094 0 0.23 0.01 0 %
___ 6 W Garage Frame - Wood MAIN 13.0 9.0 0 9.0 0 81.0 0.094 0 0.23 0.01 0 %
___ 7 S Garage Frame - Wood MAIN 13.0 7.0 0 9.0 0 63.0 0.094 0 0.23 0.01 0 %
___ 8 N Exterior Frame - Wood KITHEN 13.0 15.0 0 9.0 0 135.0 0.094 0 0.23 0.01 0 %
___ 9 E Exterior Frame - Wood KITHEN 13.0 10.0 0 9.0 0 90.0 0.094 0 0.23 0.01 0 %
___ 10 W Exterior Frame - Wood KITHEN 13.0 33.0 0 9.0 0 297.0 0.094 0 0.23 0.01 0 %
___ 11 S Garage Frame - Wood KITHEN 13.0 15.0 0 9.0 0 135.0 0.094 0 0.23 0.01 0 %
___ 12 N Exterior Frame - Wood BEDS 13.0 22.0 0 9.0 0 198.0 0.094 0 0.23 0.01 0 %
___ 13 E Exterior Frame - Wood BEDS 13.0 57.0 0 9.0 0 513.0 0.094 0 0.23 0.01 0 %
___ 14 S Exterior Frame - Wood BEDS 13.0 23.0 0 9.0 0 207.0 0.094 0 0.23 0.01 0 %
___ 15 W Exterior Frame - Wood BEDS 13.0 25.0 0 9.0 0 225.0 0.094 0 0.23 0.01 0 %
DOORS (Total Exposed Area = 63 sq.ft.)
Width Height
#Ornt Adjacent To Door Type Space Storms U-Value Ft In Ft In Area
___ 1 S Exterior Wood MAIN None 0.39 3.00 0 7.00 0 21.0ft²
___ 2 N Exterior Wood BEDS None 0.39 3.00 0 7.00 0 21.0ft²
___ 3 N Exterior Wood MAIN None 0.35 3.00 0 7.00 0 21.0ft²
WINDOWS (Total Exposed Area = 492 sq.ft.)
Wall Total Same Width Height --Overhang--
#Ornt ID Frame Panes NFRC U-Factor SHGC Imp Storm Area Units (ft)(ft)Depth Sep.Interior Shade Screen
(ft²)(ft)(ft)
___ 1 N 8 Wood Low-E Double Y 0.33 0.23 N N 54.0 3 3.00 6.00 2.0 2.0 Drapes/blinds None
___ 2 E 9 Metal Low-E Double Y 0.55 0.27 N N 42.0 1 6.00 7.00 2.0 2.0 Drapes/blinds None
___ 3 W 10 Wood Low-E Double Y 0.33 0.23 N N 15.0 1 3.00 5.00 2.0 2.0 Drapes/blinds None
___ 4 W 10 Wood Low-E Double Y 0.33 0.23 N N 18.0 3 3.00 2.00 2.0 2.0 Drapes/blinds None
___ 5 N 1 Metal Low-E Double Y 0.55 0.27 N N 98.0 1 14.00 7.00 2.0 2.0 Drapes/blinds None
___ 6 N 1 Wood Low-E Double Y 0.33 0.23 N N 7.0 1 3.50 2.00 2.0 2.0 Drapes/blinds None
___ 7 N 1 Wood Low-E Double Y 0.33 0.23 N N 6.0 1 3.00 2.00 2.0 2.0 Drapes/blinds None
___ 8 S 2 Wood Low-E Double Y 0.33 0.23 N N 10.0 1 5.00 2.00 2.0 2.0 Drapes/blinds None
___ 9 S 2 Wood Low-E Double Y 0.33 0.23 N N 6.0 1 3.00 2.00 2.0 2.0 Drapes/blinds None
___ 10W 15 Wood Low-E Double Y 0.33 0.23 N N 18.0 1 3.00 6.00 2.0 2.0 Drapes/blinds None
___ 11N 12 Metal Low-E Double Y 0.55 0.27 N N 63.0 1 9.00 7.00 2.0 2.0 Drapes/blinds None
___ 12N 12 Wood Low-E Double Y 0.33 0.23 N N 20.0 2 2.00 5.00 2.0 2.0 Drapes/blinds None
___ 13E 13 Wood Low-E Double Y 0.33 0.23 N N 12.0 2 3.00 2.00 2.0 2.0 Drapes/blinds None
___ 14E 13 Wood Low-E Double Y 0.33 0.23 N N 20.0 1 4.00 5.00 2.0 2.0 Drapes/blinds None
___ 15E 13 Wood Low-E Double Y 0.33 0.23 N N 72.0 4 3.00 6.00 2.0 2.0 Drapes/blinds None
___ 16E 13 Wood Low-E Double Y 0.33 0.23 N N 24.0 4 3.00 2.00 2.0 2.0 Drapes/blinds None
___ 17S 2 Wood Low-E Double Y 0.33 0.23 N N 7.0 1 1.00 7.00 2.0 2.0 Drapes/blinds None
8/22/2023 10:24:12 AM Page 3EnergyGauge® USA 7.5.00 - FlaRes2020 FBC 7th Edition (2022 Supplement) Compliant Software
FORM R405-2022S INPUT SUMMARY CHECKLIST REPORT
INFILTRATION
#Scope Method SLA CFM50 ELA EqLA ACH ACH50 Space(s)Infiltration Test Volume
___ 1 Wholehouse Proposed ACH(50)0.00040 2615 143.44 269.29 0.1438 7.0 22410 cu ftAll
GARAGE
#Floor Area Roof Area Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation
___ 1 516 ft²516 ft²64 ft 8 ft 1
MASS
#Mass Type Area Thickness Furniture Fraction Space
___ 1 Default(8 lbs/sq.ft.)0 ft²0 ft 0.30 MAIN
___ 2 Default(8 lbs/sq.ft.)0 ft²0 ft 0.30 KITHEN
___ 3 Default(8 lbs/sq.ft.)0 ft²0 ft 0.30 BEDS
HEATING SYSTEM
#System Type Subtype/Speed AHRI #Efficiency Capacity ----Geothermal HeatPump----Ducts Block
kBtu/hr Entry Power Volt Current
___ 1 Electric Heat Pump Split/Single HSPF2: 8.00 24.6 0.00 0.00 0.00 sys#1 1
___ 2 Electric Heat Pump Split/Single HSPF2: 8.00 24.6 0.00 0.00 0.00 sys#2 2
COOLING SYSTEM
#System Type Subtype/Speed AHRI #Efficiency Capacity Air Flow SHR Duct Block
kBtu/hr cfm
___ 1 Central Unit Split/Single SEER2:16.5 23.6 787 0.70 sys#1 1
___ 2 Central Unit Split/Single SEER2:16.5 23.6 787 0.70 sys#2 2
HOT WATER SYSTEM
#System Type Subtype Location EF(UEF)Cap Use SetPnt Fixture Flow Pipe Ins.Pipe length
___ 1 Natural Gas Tankless Exterior 1.00 (1.00)1.00 gal 61 gal 120 deg Standard None 91___ 2 Natural Gas Tankless Exterior 1.00 (1.00)1.00 gal 61 gal 120 deg Standard None 91
Recirculation Recirc Control Loop Branch Pump DWHR Facilities Equal DWHR Other Credits
System Type length length power Connected Flow Eff
___ 1 No NA NA NA No NA NA NA None
___ 2 No NA NA NA No NA NA NA None
DUCTS
Duct ---------Supply------------------Return---------Air CFM 25 CFM 25 HVAC #
#Location R-Value Area Location R-Value Area Leakage Type Handler TOT OUT QN RLF Heat Cool
___ 1 Attic 6.0 270 ft²Attic 6.0 67 ft²Default Leakage Attic (Default)(Default)1 1
___ 2 Attic 6.0 228 ft²Attic 6.0 57 ft²Default Leakage Attic (Default)(Default)2 2
8/22/2023 10:24:12 AM Page 4EnergyGauge® USA 7.5.00 - FlaRes2020 FBC 7th Edition (2022 Supplement) Compliant Software
FORM R405-2022S INPUT SUMMARY CHECKLIST REPORT
TEMPERATURES
Programable Thermostat: Y Ceiling Fans: N
Cooling [ ] Jan [ ] Feb [ ] Mar [ ] Apr [ ] May [X] Jun [X] Jul [X] Aug [X] Sep [ ] Oct [ ] Nov [ ] Dec
Heating [X] Jan [X] Feb [X] Mar [ ] Apr [ ] May [ ] Jun [ ] Jul [ ] Aug [ ] Sep [ ] Oct [X] Nov [X] Dec
Venting [ ] Jan [ ] Feb [X] Mar [X] Apr [ ] May [ ] Jun [ ] Jul [ ] Aug [ ] Sep [X] Oct [X] Nov [ ] Dec
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
___ Cooling (WD)AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
___ Cooling (WEH)AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
___ Heating (WD)AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
___ Heating (WEH)AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
8/22/2023 10:24:12 AM EnergyGauge® USA 7.5.00 - FlaRes2020 FBC 7th Edition (2022 Supplement) Compliant Software Page 5
FORM R405-2022 Supplement
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 87
The lower the EnergyPerformance Index, the more efficient the home.
1852 SEA OATS DRIVE,ATLANTIC BCH,FL,32233
1. New construction or existing New (From Plans)
2. Single family or multiple family Detached
3. Number of units, if multiple family 1
4. Number of Bedrooms 3
5. Is this a worst case?No
6. Conditioned floor area above grade (ft²)2490
Conditioned floor area below grade (ft²)0
7. Windows**Description Area
a. U-Factor:Dbl, U=0.33 289.00 ft2
S H G C :SHGC=0.23
b. U-Factor:Dbl, U=0.55 203.00 ft2
S H G C :SHGC=0.27
c. U-Factor:N/A f t2
S H G C :
Area Weighted Average Overhang Depth: 2.000 ft
Area Weighted Average SHGC:0.247
8. Skylights Description Area
U - F a c t o r : ( A V G ) N/A N/A ft2
S H G C ( A V G ) : N/A
9. Floor Types I n s u l a t i o n Area
a. Slab-On-Grade Edge Insulation R= 0.0 2490.00 f t2
b. N/A R = f t2
c. N/A R = f t2
10. Wall Types(2727.0 sqft.) I n s u l a t i o n Area
a. Frame - Wood, Exterior R=13.0 2160.00 ft2
b. Interior Frame - Wood, Interior R=0.0 288.00 ft2
c. Frame - Wood, Adjacent R=13.0 279.00 ft2
d. N/A
11. Ceiling Types(2490.0 sqft.) I n s u l a t i o n Area
a. Flat ceiling under att (Vented) R=38.0 2490.00 ft2
b. N/A
c. N/A
12. Roof(Comp. Shingles, Vented) Deck R=0.0 2714 ft2
13. Ducts, location & insulation level R ft2
a. Sup: Attic, Ret: Attic, AH: Attic 6 270
b. Sup: Attic, Ret: Attic, AH: Attic 6 228
c .
14. Cooling Systems k B t u / h r Efficiency
a. Central Unit 23.6 SEER2:16.50
b. Central Unit 23.6 SEER2:16.50
15. Heating Systems k B t u / h r Efficiency
a. Electric Heat Pump 24.6 HSPF2:8.00
b. Electric Heat Pump 24.6 HSPF2:8.00
16. Hot Water Systems
a. Natural GasTankless Cap: 1 gallons
EF: 0.999
b. Conservation features
None
17. Credits CF, Pstat
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.
Builder Signature: ___________________________________ Date: _________________________
Address of New Home: 1852 SEA OATS DRIVE City/FL Zip: ATLANTIC BCH,FL,32233
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for
energy efficient mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the
Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
8/22/2023 10:24:19 AMEnergyGauge® USA 7.5.00 - FlaRes2020 FBC 7th Edition (2022 Supplement) Compliant Software Page 1 of 1
09/13/23
CHECK2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIAa
Project Name:GOODRICH RESIDENCE Builder Name:MARCO HEATING & AIR
Street:1852 SEA OATS DRIVE Permit Office:DUVAL CNTY
City, State, Zip:ATLANTIC BCH, FL, 32233 Permit Number:
Owner:GOODRICH RESIDENCE Jurisdiction:261300
Design Location:FL, Jacksonville County:DUval(Florida Climate Zone 2)
COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA
General A continuous air barrier shall be installed in the building envelope.Air-permeable insulation shall
requirements The exterior thermal envelope contains a continuous air barrier.not be used as a sealing material.
Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit
Ceiling/attic the insulation and any gaps in the air barrier shall be sealed.shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls The junction of the foundation and sill plate shall be sealed.Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity with
sealed.a material having a thermal resistance of R-3 per
Knee walls shall be sealed.inch minimum
Exterior thermal envelope insulation for framed walls
shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights The space between window/door jambs and framing, and
and doors skylights and framing shall be sealed.
Rim joists Rim joists shall include the air barrier.Rim joists shall be insulated.
Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to
(including insulation.maintain permanent contact with the underside of
above-garage subfloor decking, or floor framing cavity insulation
and cantilevered shall be permitted to be in contact with the top side
floors)of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls Exposed earth in unvented crawl spaces shall be covered Where provided instead of floor insulation, insulation
with a Class I vapor retarder with overlapping joints taped.shall be permanently attached to the crawlspace walls.
Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Narrow cavities Batts in narrow cavities shall be cut to fit, or narrow
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and
conditioned spaces.
Recessed lighting Recessed light fixtures installed in the building thermal Recessed light fixtures installed in the building
envelope shall be sealed to the finished surface.thermal envelope shall be air tight and IC rated.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
extend behind piping and wiring.
Shower/tub The air barrier installed at exterior walls adjacent to showers Exterior walls adjacent to showers and tubs shall
on exterior wall and tubs shall separate them from the showers and tubs.be insulated.
Electrical/phone box The air barrier shall be installed behind electrical or
on exterior walls communication boxes or air-sealed boxes shall be installed.
HVAC register boots HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub-floor, wall covering
or ceiling penetrated by the boot.
Concealed When required to be sealed, concealed fire sprinklers shall only
sprinklers be sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
voids between fire sprinkler cover plates and walls or ceilings.
a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400.
8/22/2023 10:24:28 AM EnergyGauge® USA 7.0 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction:261300 Permit #:
Job Information
Builder:MARCO HEATING & AIR Community:Lot:NA
Address:1852 SEA OATS DRIVE
City:ATLANTIC BCH State:FL Zip:32233
Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERI Method
PRESCRIPTIVE METHOD-The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air
changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones 1 and 2.
PERFORMANCE or ERI METHOD-The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding
the selected ACH(50) value, as shown on Form R405-2020 (Performance) or R406-2020 (ERI), section labeled as infiltration, sub-section ACH50.
ACH(50) specified on Form R405-2020-Energy Calc (Performance) or R406-2020 (ERI):7.000
_________ x 60 ÷ ______________ = ____________22410
CFM(50) Building Volume ACH(50)
PASS
When ACH(50) is less than 3, Mechanical Ventilation installation
must be verified by building department.
Method for calculating building volume:_____________________________
Retrieved from architectural plans
Code software calculated
Field measured and calculated
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals).
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
m e a s u r e s .
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: ______________________________________Phone: ________________________
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: ____________________________________Date of Test: ______________________
Printed Name of Tester: _________________________________
License/Certification #: _____________________________Issuing Authority: _________________________
8/22/2023 10:24:36 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
2023-Aug-22 09:06:08
Rig ht-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 1
...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Building Analysis Jan 31, 2023Date:Entire House By:
MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
Project Information
GOODRICH RESIDENCE, MATHIEU BUILDERSFor:
1852 SEA OATS DRIVE, ATLANTIC BCH, FL 32233
Design Conditions
Location:CoolingHeatingIndoor:
7570Indoor temp era ture (°F)Jacksonville Intl AP, FL, US
1838Design TD (°F)ft33Elevation:
5050Relative humidity (%)°N30Latitude:Outdoor:51.233.1Moisture difference (gr/lb)CoolingHeating
Infiltration:9333Dry bul b (°F)
SimplifiedMethod)M(18-Da ily ra nge (°F)
AverageConstruction quality77-We t bu lb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
Doors
Ceilings
Floors
Infiltration
% of loadBtuhBtuh/ft²Component
21.065713.5Walls
13.2412417.6Glazing
8.5266214.6Doors
9.529881.2Ceilings
34.8108964.44.4Floors
13.141042.4Infiltration
00Ducts
00Piping
00Humidification
00Ventilation0Adjustments
100.031345Total
Cooling
Walls
Glazing
Doors
Ceilings
Infiltration
Internal Gains
% of loadBtuhBtuh/ft²Component
6.622891.2Walls
17.5605725.9Glazing
6.2214411.8Doors
12.442791.7Ceilings
000Floors
2.89680.6Infiltration
00Ducts
00Ventilation
54.518820Internal gains
00Blower
0Adjustments
100.034557Total
Latent Cooling Load = 6430 Btuh
Overall U-va lue = 0.0 95 Btuh/ft²-°F, Windo w / Floor Area = 9.4 %
Data entries checked.
2023-Aug-22 09:06:08
Rig ht-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 2
...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Building Analysis Jan 31, 2023Date:(Rest of House)By:
MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
Project Information
GOODRICH RESIDENCE, MATHIEU BUILDERSFor:
1852 SEA OATS DRIVE, ATLANTIC BCH, FL 32233
Design Conditions
Location:CoolingHeatingIndoor:
7570Indoor temp era ture (°F)Jacksonville Intl AP, FL, US
1838Design TD (°F)ft33Elevation:
5050Relative humidity (%)°N30Latitude:Outdoor:51.233.1Moisture difference (gr/lb)CoolingHeating
Infiltration:9333Dry bul b (°F)
SimplifiedMethod)M(18-Da ily ra nge (°F)
AverageConstruction quality77-We t bu lb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
Doors
Ceilings
Floors
Infiltration
% of loadBtuhBtuh/ft²Component
20.932523.5Walls
6.8105817.6Glazing
15.1235514.6Doors
10.416181.2Ceilings
35.354914.14.1Floors
11.517872.4Infiltration
00Ducts
00Piping
00Humidification
00Ventilation0Adjustments
100.015559Total
Cooling
Walls
Glazing
Doors
Ceilings
Infiltration
Internal Gains
% of loadBtuhBtuh/ft²Component
6.711571.2Walls
7.2124420.7Glazing
10.9189611.8Doors
13.423161.7Ceilings
000Floors
2.44220.6Infiltration
00Ducts
00Ventilation
59.410300Internal gains
00Blower
0Adjustments
100.017335Total
Latent Cooling Load = 3154 Btuh
Overall U-va lue = 0.0 91 Btuh/ft²-°F, Windo w / Floor Area = 4.5 %
WARNING: window to floor area ratio = 4.5% - less than 5%.
2023-Aug-22 09:06:08
Rig ht-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 3
...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Building Analysis Jan 31, 2023Date:BED By:
MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
Project Information
GOODRICH RESIDENCE, MATHIEU BUILDERSFor:
1852 SEA OATS DRIVE, ATLANTIC BCH, FL 32233
Design Conditions
Location:CoolingHeatingIndoor:
7570Indoor temp era ture (°F)Jacksonville Intl AP, FL, US
1838Design TD (°F)ft33Elevation:
5050Relative humidity (%)°N30Latitude:Outdoor:51.233.1Moisture difference (gr/lb)CoolingHeating
Infiltration:9333Dry bul b (°F)
SimplifiedMethod)M(18-Da ily ra nge (°F)
AverageConstruction quality77-We t bu lb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
OtherCeilings
Floors
Infiltration
% of loadBtuhBtuh/ft²Component
21.033193.5Walls
19.4306717.6Glazing
1.930714.6Doors
8.713701.2Ceilings
34.254054.74.7Floors
14.723162.4Infiltration
00Ducts
00Piping
00Humidification
00Ventilation0Adjustments
100.015785Total
Cooling
Walls
Glazing
Other
CeilingsInfiltration
Internal Gains
% of loadBtuhBtuh/ft²Component
6.611321.2Walls
28.0483427.8Glazing
1.424711.8Doors
11.419621.7Ceilings
000Floors
3.25470.6Infiltration
00Ducts
00Ventilation
49.48520Internal gains
00Blower
0Adjustments
100.017243Total
Latent Cooling Load = 3277 Btuh
Overall U-va lue = 0.0 99 Btuh/ft²-°F, Windo w / Floor Area = 15 .2 %
Data entries checked.
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2023-Aug-22 09:06:08
Rig ht-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 1
...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Project Summary Jan 31, 2023Date:Entire House By:
MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
Project Information
GOODRICH RESIDENCE, MATHIEU BUILDERSFor:1852 SEA OATS DRIVE, ATLANTIC BCH, FL 32233
1) 2.0 TON
1) 2.0TON
Notes:
Design Information
Jacksonville Intl AP, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F33 Outside db °F93Inside db °F70 Inside db °F75
Design TD °F38 Design TD °F18Daily range M
Relative humidity %50Moisture difference gr/lb51
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh31345 Structure Btuh34557
Ducts Btuh0 Ducts Btuh0Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0
Humidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh31345 Use manufacturer's data n
Rate/swing multiplier 0.98InfiltrationEquipment sensible load Btuh33762
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh6430
Ducts Btuh0Central vent (0 cfm)Btuh0
CoolingHeating24902490Area (ft²)Equipment latent load Btuh6430
1867518675Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh40192
Equiv. AVF (cfm)50100 Req. total capacity at 0.70 SHR ton4.0
Heating Equipment Summary Cooling Equipment Summary
Make n/a Make n/aTraden/a Trade n/a
Model n/a Cond n/aAHRI ref n/a Coil n/a
AHRI ref n/aEfficiencyn/a Efficiency n/a
Heating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0
Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0
Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0
Space thermostat n/a Load sensible heat ratio 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2023-Aug-22 09:06:08
Rig ht-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 2
...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Project Summary Jan 31, 2023Date:(Rest of House)By:
MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
Project Information
GOODRICH RESIDENCE, MATHIEU BUILDERSFor:1852 SEA OATS DRIVE, ATLANTIC BCH, FL 32233
1) 2.0 TON
1) 2.0TON
Notes:
Design Information
Jacksonville Intl AP, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F33 Outside db °F93Inside db °F70 Inside db °F75
Design TD °F38 Design TD °F18Daily range M
Relative humidity %50Moisture difference gr/lb51
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh15559 Structure Btuh17335
Ducts Btuh0 Ducts Btuh0Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0
(none)(none)Humidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh15559 Use manufacturer's data n
Rate/swing multiplier 0.98InfiltrationEquipment sensible load Btuh16936
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh3154
Ducts Btuh0Central vent (0 cfm)Btuh0
CoolingHeating (none)13481348Area (ft²)Equipment latent load Btuh3154
1011010110Volume (ft³)Air changes/hour 0.130.26 Equipment Total Load (Sen+Lat)Btuh20090
Equiv. AVF (cfm)2243 Req. total capacity at 0.70 SHR ton2.0
Heating Equipment Summary Cooling Equipment Summary
Make Carrier Make CarrierTrade2-STAGE 17 SEER HP Trade 2-STAGE 17 SEER HP
Model GH7TAN42400AA0 Cond GH7TAN42400AA0AHRI ref 207867916 Coil FV4CNF002L
AHRI ref 207867916Efficiency8 HSPF2 Efficiency 12.5 EER2,16.5 SEER2
Heating input Sensible cooling Btuh16520Heating output Btu h @ 47°F24600 Latent cooling Btuh7080
Temperature rise °F28 Total cooling Btuh23600Actual air flow cfm787 Actual air flow cfm787
Air flow factor cfm/Btuh0.051 Air flow factor cfm/Btuh0.045Static pressure in H2O0 Static pressure in H2O0
Space thermostat Load sensible heat ratio 0.85Capacity ba lance po int = 23 °F
Backup:Input = 9 kW, Output = 30303 Btuh, 100 AFUE
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2023-Aug-22 09:06:08
Rig ht-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 3
...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Project Summary Jan 31, 2023Date:BED By:
MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
Project Information
GOODRICH RESIDENCE, MATHIEU BUILDERSFor:1852 SEA OATS DRIVE, ATLANTIC BCH, FL 32233
1) 2.0 TON
1) 2.0TON
Notes:
Design Information
Jacksonville Intl AP, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F33 Outside db °F93Inside db °F70 Inside db °F75
Design TD °F38 Design TD °F18Daily range M
Relative humidity %50Moisture difference gr/lb51
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh15785 Structure Btuh17243
Ducts Btuh0 Ducts Btuh0Central vent (0 cfm)Btuh0 Central vent (0 cfm)Btuh0
(none)(none)Humidification Btuh0 Blower Btuh0
Piping Btuh0Equipment load Btuh15785 Use manufacturer's data n
Rate/swing multiplier 0.98InfiltrationEquipment sensible load Btuh16846
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh3277
Ducts Btuh0Central vent (0 cfm)Btuh0
CoolingHeating (none)11421142Area (ft²)Equipment latent load Btuh3277
85658565Volume (ft³)Air changes/hour 0.200.39 Equipment Total Load (Sen+Lat)Btuh20123
Equiv. AVF (cfm)2856 Req. total capacity at 0.70 SHR ton2.0
Heating Equipment Summary Cooling Equipment Summary
Make CARRIER Make CARRIERTrade2-STAGE 17 SEER HP Trade 2-STAGE 17 SEER HP
Model GH7TAN42400AA0 Cond GH7TAN42400AA0AHRI ref 207867916 Coil FV4CNF002L
AHRI ref 207867916Efficiency8 HSPF2 Efficiency 16.5 SEER2
Heating input Sensible cooling Btuh0Heating output Btu h @ 47°F0 Latent cooling Btuh0
Temperature rise °F0 Total cooling Btuh0Actual air flow cfm785 Actual air flow cfm785
Air flow factor cfm/Btuh0.050 Air flow factor cfm/Btuh0.046Static pressure in H2O0 Static pressure in H2O0
Space thermostat Load sensible heat ratio 0.84Capacity ba lance po int = 0 °F
Backup:Input = 5 kW, Output = 15785 Btuh, 100 AFUE
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2023-Aug-22 09:06:08Right-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 1...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Right-J® W or ksheet Jan 31, 2023Date:Entire House By:MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
1 Room name Entire House BED
2 Exposed wall 256.0 ft 127.0 ft
3 Room height 9.0 ft 9.0 ft
4 Room dimensions
5 Room area 2490.0 f t²1142.0 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 15B11-0wc-215B11-0wc-2 0.0990.099 nn 3.443.44 1.111.11 549 358 1233 398 198 129 444 144
.GG 4A5-2ow4A5-2ow 0.4700.470 nn 17.6317.63 14.7514.75 72 0 1269 1062 48 0 846 708
.DD 11D011D0 0.3900.390 nn 14.6214.62 11.7811.78 119 119 1740 1402 21 21 307 247
.WW 15B11-0wc-215B11-0wc-2 0.0990.099 ee 3.493.49 1.181.18 603 479 1673 566 513 431 1510 516
1 1 GG 4A5-2ow4A5-2ow 0.4700.470 ee 17.6317.63 38.0538.05 82 0 1445 3120 82 0 1445 3120
DD 11D011D0 0.3900.390 ee 14.6214.62 11.7811.78 42 42 614 495 0 0 0 0
WW 15B11-0wc-215B11-0wc-2 0.0990.099 ss 3.493.49 1.181.18 351 274 956 322 207 175 613 210
GG 4A5-2ow4A5-2ow 0.4700.470 ss 17.6317.63 17.1717.17 56 0 987 961 32 0 564 549
DD 11D011D0 0.3900.390 ss 14.6214.62 11.7811.78 21 21 307 247 0 0 0 0
WW 15B11-0wc-215B11-0wc-2 0.0990.099 ww 3.533.53 1.231.23 522 498 1757 614 225 213 751 262
GG 4A5-2ow4A5-2ow 0.4700.470 ww 17.6317.63 38.0538.05 24 0 423 913 12 0 212 457
PP 12C-0sw12C-0sw 0.0910.091 --3.413.41 1.391.39 279 279 952 388 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --1.201.20 1.721.72 2490 2490 2988 4279 1142 1142 1370 1962
FF 22C-5tpm22C-5tpm 1.1351.135 --42.5642.56 0.000.00 2490 256 10896 0 1142 127 5405 0
6 c) AED excursion 0 0
Envelope loss/gain 27241 14768 13469 8176
12 a)Infiltration 4104 968 2316 547
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 4 920 4 920
Appliances/other 17900 7600
Subtotal (lines 6 to 13)31345 34557 15785 17243
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 31345 34557 15785 17243
15 Duct loads 0%0%0 0 0%0%0 0
Total room load 31345 34557 15785 17243
Air required (cfm)Air required (cfm)1572 1572 785 785
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2023-Aug-22 09:06:08Right-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 2...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Right-J® W or ksheet Jan 31, 2023Date:Entire House By:MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
1 Room name (Rest of House)
2 Exposed wall 129.0 ft
3 Room height 9.0 ft
4 Room dimensions
5 Room area 1348.0 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area Load
number (Bt uh/f t²-°F)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W 15B11-0wc-2 0.099 n 3.44 1.11 351 229 789 255
.G 4A5-2ow 0.470 n 17.63 14.75 24 0 423 354
.D 11D0 0.390 n 14.62 11.78 98 98 1433 1154
.W 15B11-0wc-2 0.099 e 3.49 1.18 90 48 162 49
1 1 G 4A5-2ow 0.470 e 17.63 38.05 0 0 0 0
D 11D0 0.390 e 14.62 11.78 42 42 614 495
W 15B11-0wc-2 0.099 s 3.49 1.18 144 99 342 112
G 4A5-2ow 0.470 s 17.63 17.17 24 0 423 412
D 11D0 0.390 s 14.62 11.78 21 21 307 247
W 15B11-0wc-2 0.099 w 3.53 1.23 297 285 1006 352
G 4A5-2ow 0.470 w 17.63 38.05 12 0 212 457
P 12C-0sw 0.091 -3.41 1.39 279 279 952 388
C 16B-30ad 0.032 -1.20 1.72 1348 1348 1618 2316
F 22C-5tpm 1.135 -42.56 0.00 1348 129 5491 0
6 c) AED excursion 21
Envelope loss/gain 13772 6613
12 a)Infiltration 1787 422
b)Room ventilation 0 0
13 Internal gains:Occupants @ 230 0 0
Appliances/other 10300
Subtotal (lines 6 to 13)15559 17335
Less external load 0 0
Less transfer 0 0
Redistribution 0 0
14 Subtotal 15559 17335
15 Duct loads 0%0%0 0
Total room load 15559 17335
Air required (cfm)787 787
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2023-Aug-22 09:06:08Right-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 3...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Right-J® W or ksheet Jan 31, 2023Date:(Rest of House)By:MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
1 Room name (Rest of House)MAIN
2 Exposed wall 129.0 ft 56.0 ft
3 Room height 9.0 ft 9.0 heat/coolft
4 Room dimensions ft853.0x1.0
5 Room area 1348.0 f t²853.0 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 15B11-0wc-215B11-0wc-2 0.0990.099 nn 3.443.44 1.111.11 351 229 789 255 216 118 400 123
.GG 4A5-2ow4A5-2ow 0.4700.470 nn 17.6317.63 14.7514.75 24 0 423 354 0 0 0 0
.DD 11D011D0 0.3900.390 nn 14.6214.62 11.7811.78 98 98 1433 1154 98 98 1433 1154
.WW 15B11-0wc-215B11-0wc-2 0.0990.099 ee 3.383.38 1.031.03 90 48 162 49 0 0 0 0
1 1 GG 4A5-2ow4A5-2ow 0.4700.470 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0
DD 11D011D0 0.3900.390 ee 14.6214.62 11.7811.78 42 42 614 495 0 0 0 0
WW 15B11-0wc-215B11-0wc-2 0.0990.099 ss 3.463.46 1.131.13 144 99 342 112 144 99 342 112
GG 4A5-2ow4A5-2ow 0.4700.470 ss 17.6317.63 17.1717.17 24 0 423 412 24 0 423 412
DD 11D011D0 0.3900.390 ss 14.6214.62 11.7811.78 21 21 307 247 21 21 307 247
WW 15B11-0wc-215B11-0wc-2 0.0990.099 ww 3.533.53 1.241.24 297 285 1006 352 0 0 0 0
GG 4A5-2ow4A5-2ow 0.4700.470 ww 17.6317.63 38.0538.05 12 0 212 457 0 0 0 0
PP 12C-0sw12C-0sw 0.0910.091 --3.413.41 1.391.39 279 279 952 388 144 144 491 200
CC 16B-30ad16B-30ad 0.0320.032 --1.201.20 1.721.72 1348 1348 1618 2316 853 853 1024 1466
FF 22C-5tpm22C-5tpm 1.1351.135 --42.5642.56 0.000.00 1348 129 5491 0 853 56 2384 0
6 c) AED excursion 21 -8
Envelope loss/gain 13772 6613 6804 3706
12 a)Infiltration 1787 422 730 172
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 10300 3400
Subtotal (lines 6 to 13)15559 17335 7534 7278
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 15559 17335 7534 7278
15 Duct loads 0%0%0 0 -0%0%0 0
Total room load 15559 17335 7534 7278
Air required (cfm)Air required (cfm)787 787 381 330
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2023-Aug-22 09:06:08Right-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 4...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Right-J® W or ksheet Jan 31, 2023Date:(Rest of House)By:MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
1 Room name KITHEN
2 Exposed wall 73.0 ft
3 Room height 9.0 heat/coolft
4 Room dimensions ft33.0x15.0
5 Room area 495.0 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area Load
number (Bt uh/f t²-°F)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 W 15B11-0wc-2 0.099 n 3.44 1.11 135 111 388 132
.G 4A5-2ow 0.470 n 17.63 14.75 24 0 423 354
.D 11D0 0.390 n 14.62 11.78 0 0 0 0
.W 15B11-0wc-2 0.099 e 3.38 1.03 90 48 162 49
1 1 G 4A5-2ow 0.470 e 0.00 0.00 0 0 0 0
D 11D0 0.390 e 14.62 11.78 42 42 614 495
W 15B11-0wc-2 0.099 s 3.46 1.13 0 0 0 0
G 4A5-2ow 0.470 s 17.63 17.17 0 0 0 0
D 11D0 0.390 s 14.62 11.78 0 0 0 0
W 15B11-0wc-2 0.099 w 3.53 1.24 297 285 1006 352
G 4A5-2ow 0.470 w 17.63 38.05 12 0 212 457
P 12C-0sw 0.091 -3.41 1.39 135 135 461 188
C 16B-30ad 0.032 -1.20 1.72 495 495 594 851
F 22C-5tpm 1.135 -42.56 0.00 495 73 3107 0
6 c) AED excursion 29
Envelope loss/gain 6967 2907
12 a)Infiltration 1058 250
b)Room ventilation 0 0
13 Internal gains:Occupants @ 230 0 0
Appliances/other 6900
Subtotal (lines 6 to 13)8025 10057
Less external load 0 0
Less transfer 0 0
Redistribution 0 0
14 Subtotal 8025 10057
15 Duct loads -0%0%0 0
Total room load 8025 10057
Air required (cfm)406 457
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2023-Aug-22 09:06:08Right-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 5...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Right-J® W or ksheet Jan 31, 2023Date:BED By:MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
1 Room name BED BEDS
2 Exposed wall 127.0 ft 127.0 ft
3 Room height 9.0 ft 9.0 heat/coolft
4 Room dimensions ft1142.0x1.0
5 Room area 1142.0 f t²1142.0 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 15B11-0wc-215B11-0wc-2 0.0990.099 nn 3.443.44 1.111.11 198 129 444 144 198 129 444 144
.GG 4A5-2ow4A5-2ow 0.4700.470 nn 17.6317.63 14.7514.75 48 0 846 708 48 0 846 708
.DD 11D011D0 0.3900.390 nn 14.6214.62 11.7811.78 21 21 307 247 21 21 307 247
.WW 15B11-0wc-215B11-0wc-2 0.0990.099 ee 3.503.50 1.201.20 513 431 1510 516 513 431 1510 516
1 1 GG 4A5-2ow4A5-2ow 0.4700.470 ee 17.6317.63 38.0538.05 82 0 1445 3120 82 0 1445 3120
DD 11D011D0 0.3900.390 ee 0.000.00 0.000.00 0 0 0 0 0 0 0 0
WW 15B11-0wc-215B11-0wc-2 0.0990.099 ss 3.513.51 1.201.20 207 175 613 210 207 175 613 210
GG 4A5-2ow4A5-2ow 0.4700.470 ss 17.6317.63 17.1717.17 32 0 564 549 32 0 564 549
DD 11D011D0 0.3900.390 ss 0.000.00 0.000.00 0 0 0 0 0 0 0 0
WW 15B11-0wc-215B11-0wc-2 0.0990.099 ww 3.533.53 1.231.23 225 213 751 262 225 213 751 262
GG 4A5-2ow4A5-2ow 0.4700.470 ww 17.6317.63 38.0538.05 12 0 212 457 12 0 212 457
PP 12C-0sw12C-0sw 0.0910.091 --0.000.00 0.000.00 0 0 0 0 0 0 0 0
CC 16B-30ad16B-30ad 0.0320.032 --1.201.20 1.721.72 1142 1142 1370 1962 1142 1142 1370 1962
FF 22C-5tpm22C-5tpm 1.1351.135 --42.5642.56 0.000.00 1142 127 5405 0 1142 127 5405 0
6 c) AED excursion 0 0
Envelope loss/gain 13469 8176 13469 8176
12 a)Infiltration 2316 547 2316 547
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 4 920 4 920
Appliances/other 7600 7600
Subtotal (lines 6 to 13)15785 17243 15785 17243
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 15785 17243 15785 17243
15 Duct loads 0%0%0 0 -0%0%0 0
Total room load 15785 17243 15785 17243
Air required (cfm)Air required (cfm)785 785 785 785
2023-Aug-22 09:06:08
Rig ht-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 1
...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Manual S Compliance Report Jan 31, 2023Date:(Rest of House)By:
MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
Project Information
GOODRICH RESIDENCE, MATHIEU BUILDERSFor:
1852 SEA OATS DRIVE, ATLANTIC BCH, FL 32233
Cooling Equipment
Design Conditions
°F75.0Entering coil DB:Btuh17335Sensible gain:°F92.7Outdoor design DB:
°F62.5Entering coil WB:Btuh3154Latent gain:°F77.1Outdoor design WB:
Btuh20488Total gain:°F75.0Indoor design DB:
cfm787Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ASHPEquipment type:
GH7TAN42400AA0+FV4CNF002LModel:CarrierManufacturer:
cfm787Actual airflow:
% of load109Btuh18873Sensible capacity:
% of load137Btuh4322Latent capacity:
%81SHR:% of load113Btuh23195Total capacity:
Heating Equipment
Design Conditions
°F70.0Entering coil DB:Btuh15559Heat loss:°F32.5Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Split ASHPEquipment type:
GH7TAN42400AA0+FV4CNF002LModel:CarrierManufacturer:
cfm787Actual airflow:
°F23Capacity balance:% of load119Btuh18493Output capacity:
°F-99Economic balance:Btuh0Supplemental heat required:
Elec stripBackup equipment type:
Model:Manufacturer:
cfm787Actual airflow:
°F50Temp. rise:% of load195kW8.9Output capacity:
Meets all requirements of ACCA Manual S.
2023-Aug-22 09:06:08
Rig ht-Su ite® U niv er sal 20 22 22 .0.07 RSU1 7889 Page 2
...LDERS\GOODRICH RESIDENCE\GOODRICH RESIDENCE.rup Calc = MJ8 Front Door faces: SW
Job:Manual S Compliance Report Jan 31, 2023Date:BED By:
MARCO HEATING & AIR
720 MILL CREEK DR, JACKSONVILLE, FL 32211 Phone: 904-743-3350 License: CAC1715711
Project Information
GOODRICH RESIDENCE, MATHIEU BUILDERSFor:
1852 SEA OATS DRIVE, ATLANTIC BCH, FL 32233
Cooling Equipment
Design Conditions
°F75.0Entering coil DB:Btuh17243Sensible gain:°F92.7Outdoor design DB:
°F62.5Entering coil WB:Btuh3277Latent gain:°F77.1Outdoor design WB:
Btuh20519Total gain:°F75.0Indoor design DB:
cfm785Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ASHPEquipment type:
GH7TAN42400AA0+FV4CNF002LModel:CARRIERManufacturer:
cfm785Actual airflow:
% of load109Btuh18873Sensible capacity:
% of load132Btuh4322Latent capacity:
%81SHR:% of load113Btuh23195Total capacity:
Heating Equipment
Design Conditions
°F70.0Entering coil DB:Btuh15785Heat loss:°F32.5Outdoor design DB:
°F70.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Split ASHPEquipment type:
GH7TAN42400AA0+FV4CNF002LModel:CARRIERManufacturer:
cfm785Actual airflow:
°F0Capacity balance:% of load117Btuh18493Output capacity:
°F0Economic balance:Btuh0Supplemental heat required:
Elec stripBackup equipment type:
Model:Manufacturer:
cfm785Actual airflow:
°F0Temp. rise:% of load100kW4.6Output capacity:
Meets all requirements of ACCA Manual S.
MATHIEU BUILDERS PLAN: GOODRICH
1
ADDRESS: _1852 SEA OATS DR ATLANTIC BCH., FL 32233
GOODMAN _2.0_ TON HEAT PUMP SYSTEM SEER: _16.5_ HSPF: _8. _
GOODMAN _2.0_ TON HEAT PUMP SYSTEM SEER: _16.5_ HSPF: _8. _
DESIGN COOL BTUH: _48000_ AVAILABLE STATIC PRESSURE: _1:1_
TOTAL CFM: _1390_ TOTAL EFFECTIVE LENGTH: _200__
PERFORMANCE METHOD: DUCT MATERIAL: R8 VINYL FLEX
SUPPLY BRANCH DETAIL TABLE
ROOM NAME COOLING CFM BRANCH SIZE LINEAR FT DUCT MATERIAL
DINING 150 CFM 7” 14’ VINYL FLEX
FAMILY ROOM (2) 150 CFM (2) 7” 25’ VINYL FLEX
KITCHEN 150 CFM 6” 10’ VINYL FLEX
LAUNDRY 35 CFM 4” 8’ VINYL FLEX
PANTRY 35 CFM 4” 10’ VINYL FLEX
BR2 150 CFM 7” 30’ VINYL FLEX
POWDER ROOM 35 CFM 4” 15’ VINYL FLEX
BR3 200 CFM 8” 22’ VINYL FLEX
MBR (2) 100 CFM (2) 6” 32’ VINYL FLEX
MBA 35 CFM 4” 20’ VINYL FLEX
MBR WIC 100 CFM 6” 15’ VINYL FLEX
MBA TOILET 35 CFM 4” 18’ VINYL FLEX
TOTALS 1390CFM 200 LN (FT)
SUPPLY TRUNK DETAIL TABLE
LOCATION DESIGN BTUH TRUNK SIZE DUCT MATERIAL