1600 Selva Marina Dr MECH23-0009 COAB Permit Form with ConditionsOWNER:ADDRESS:CITY:STATE:ZIP:
ATLANTIC BEACH
COUNTRY CLUB INC 1600 SELVA MARINA DR ATLANTIC BEACH FL 32233
COMPANY:ADDRESS:CITY:STATE:ZIP:
BENDER & MODLIN FIRE
SPRINKLER 170 -G C COLLEGE DR ORANGE PARK FL 32065
TYPE OF
CONSTRUCTION:
REAL ESTATE
NUMBER:ZONING:BUILDING USE
GROUP:SUBDIVISION:
172000 0010 SELVA MARINA UNIT 05
JOB ADDRESS:PERMIT TYPE:DESCRIPTION: VALUE OF WORK:
1600 SELVA MARINA DR MECHANICAL COMMERCIAL
SEPARATE PLANS OTHER
Fire Sprinkler Modification
(Fire Prevention)$10000.00
FEES
DESCRIPTION ACCOUNT QUANTITY PAID AMOUNT
FIRE DEPARTMENT FEE 45500002080800 0 $150.00
FIRE SPRINKLER SYSTEM 455-0000-322-1000 0 $36.40
MECHANICAL BASE FEE 455-0000-322-1000 0 $55.00
STATE DBPR SURCHARGE 455-0000-208-0700 0 $2.00
LIST OF CONDITIONS
Roll off container company must be on City approved list . Container cannot be placed on City right-of-way.
NOTICE: In addition to the requirements of this permit, there may be additional restrictions applicable to this property
that may be found in the public records of this county, and there may be additional permits required from other
governmental entities such as water management districts, state agencies, or federal agencies.
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT
IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. A NOTICE OF
COMMENCEMENT MUST BE RECORDED AND POSTED ON THE JOB SITE BEFORE THE FIRST
INSPECTION. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN
ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.
MUST CALL INSPECTION PHONE LINE (904) 247-5814 BY 4 PM FOR NEXT DAY INSPECTION.
ALL WORK MUST CONFORM TO THE CURRENT 6TH EDITION (2017) OF THE FLORIDA BUILDING
CODE, NEC, IPMC, AND CITY OF ATLANTIC BEACH CODE OF ORDINANCES .
ALL CONDITIONS OF PERMIT APPLY, PLEASE READ CAREFULLY.
1 of 2Issued Date: 9/27/2023
PERMIT NUMBER
MECH23-0009
ISSUED: 9/27/2023
EXPIRES: 3/25/2024
MECHANICAL COMMERCIAL
SEPARATE PLANS PERMIT
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
STATE DCA SURCHARGE 455-0000-208-0600 0 $2.00
TOTAL: $245.40
2 of 2Issued Date: 9/27/2023
PERMIT NUMBER
MECH23-0009
ISSUED: 9/27/2023
EXPIRES: 3/25/2024
MECHANICAL COMMERCIAL
SEPARATE PLANS PERMIT
CITY OF ATLANTIC BEACH
800 SEMINOLE ROAD
MECH23-0009
DECK
425
STORAGE 2
423
RESTROOM
422
RESTROOM
421
21 3
A
B
PLATFORM
LIFT
407
DUMB
WAITER
410
VESTIBULE
420
UPSTAIRS
BAR
424
9' - 11 1/2"
9' - 11 1/2"
9' - 11 1/2"
9' - 11 1/2"
13' - 9"
1. TOTAL AREA PART OF CONTRACT
1ST FLOOR DRY SYSTEM ±1782 SQ FT
2ND FLOOR DRY SYSTEM ±1,674 SQ FT
2. ALL PIPE FOR DRY SYSTEM 1" - 112" SCH 40
BLACK PIPE.
3. ALL PIPE FOR DRY SYSTEM 2" AND UP SCH
10 BLACK PIPE.
4. ALL WORK TO BE PERFORMED AS PER
NFPA 13.
DRAWING NOTES
DENOTES NEW PIPE
DENOTES EXISTING PIPE TO REMAIN
DENOTES RELOCATED/ADDED FIRE
SPRINKLER HEAD
DENOTES FIRE SPRINKLER HEAD TO
BE RELOCATED
DENOTES EXISTING PIPE TO
DENOTES FIRE SPRINKLER HEAD TO
BE REMOVED
DENOTES EXISTING FIRE SPRINKLER
HEAD TO REMAIN
27
DENOTES NEW CONNECTION
DENOTES HYDRAULIC NODE POINT
DENOTES PLUG
DENOTES CAP
DENOTES FIRE RISER LOCATION
SYMBOLS LEGEND
BE REMOVED
A
X
R R
X
DINING
400
KITCHEN
401FIRE RISER
408
PLATFORM
LIFT
407
STORAGE 1
412
WATER
HEATER
CLOSET
405
MEN'S
404
VESTIBULE
403
WOMEN'S
402
21 3
A
B
COOLER
406
MECHANICAL
409
9' - 11 1/2"
8' - 0"
9' - 11 1/2"
9' - 11 1/2"
9' - 11 1/2"
8' - 6"8' - 6"
8' - 6"
8' - 6"
X
X X X X
X X X
X
XX
XX
X X X X X
XXXX
X X X
X
FIRE PROTECTION 1ST FLOOR DEMO PLAN FIRE PROTECTION 1ST FLOOR PLAN
DINING
400
KITCHEN
401FIRE RISER
408
PLATFORM
LIFT
407
STORAGE 1
412
WATER
HEATER
CLOSET
405
MEN'S
404
VESTIBULE
403
WOMEN'S
402
21 3
A
B
COOLER
406
MECHANICAL
409
9' - 11 1/2"
8' - 0"
9' - 11 1/2"
9' - 11 1/2"
9' - 11 1/2"
8' - 6"8' - 6"
8' - 6"
8' - 6"
X
X X X X
X X X
X
X
X X X X X
XXXX
X X X
STORAGE 2
413
FIRE PROTECTION 2ND FLOOR PLAN
DECK
425
STORAGE 2
423
RESTROOM
422
RESTROOM
421
21 3
A
B
PLATFORM
LIFT
407
DUMB
WAITER
410
VESTIBULE
420
UPSTAIRS
BAR
424
9' - 11 1/2"
9' - 11 1/2"
9' - 11 1/2"
9' - 11 1/2"
13' - 9"
X
X
X
X
X
X
X
2021
2223
24
1 2
3
4
5
6
7
898S
252627
32 31
30
29S
28
21S
4S
25S26S27S
6S
29
106
100D
100101
101D
102
102D103D
107D 106D
105
105D
110D
110
104104D
108
108D
107
109
109D
99D
99
98D 98
97D
97
11
1213
13S
20S
28S
FIRE PROTECTION 2ND FLOOR DEMO PLAN
BM 24x36HFIRE SPRINKLER, INC.
1. TOTAL AREA PART OF CONTRACT
1ST FLOOR DRY SYSTEM ±1782 SQ FT
2ND FLOOR DRY SYSTEM ±1,674 SQ FT
2. ALL PIPE FOR DRY SYSTEM 1" - 112" SCH 40
BLACK PIPE.
3. ALL PIPE FOR DRY SYSTEM 2" AND UP SCH
10 BLACK PIPE.
4. ALL WORK TO BE PERFORMED AS PER
NFPA 13.
DRAWING NOTES
DENOTES NEW PIPE
DENOTES EXISTING PIPE TO REMAIN
DENOTES RELOCATED/ADDED FIRE
SPRINKLER HEAD
DENOTES FIRE SPRINKLER HEAD TO
BE RELOCATED
DENOTES EXISTING PIPE TO
DENOTES FIRE SPRINKLER HEAD TO
BE REMOVED
DENOTES EXISTING FIRE SPRINKLER
HEAD TO REMAIN
27
DENOTES NEW CONNECTION
DENOTES HYDRAULIC NODE POINT
DENOTES PLUG
DENOTES CAP
DENOTES FIRE RISER LOCATION
SYMBOLS LEGEND
BE REMOVED
A
X
R R
X
ATLAN
T
I
C
B
E
A
C
H
D
R
I
V
E
S.=
0
.
3
5
%
PETE'S TURN
4" DCDA BACKFLOW
PREVENTER
8" X 4" TAPPING SLEEVE
AND TAPPING VALVE
EXISTING STORM
YARD DRAIN (SEE
NOTE 3)UG1
BOR
BKFL
UG2
TEST
FIRE PROTECTION SITE PLAN (FOR HYRAULIC REFERENCE ONLY)
RETURN BEND DETAIL
MAXIMUM DISTANCE BETWEEN HANGERS
HORIZ. WOOD SCREW
FIRE PROTECTION GENERAL NOTES
VERTICAL WOOD SCREW
FLOW TEST DATA
FIRE RISER DETAIL
TOR
BOR
BM 24x36HFIRE SPRINKLER, INC.
As the leading supplier of steel sprinkler pipe, we understand that there are no second chances in fire suppression. You
need products of enduring quality and exceptional strength—plus reliable service. You need Bull Moose.
SCHEDULE 10 & 40 ADVANTAGES:
• UL listed (US & Canada) and FM approved
• ASTM A135 and A795 Type E, Grade A Certified
• Complies with NFPA-13, 13R and 14
• Industry-leading hydraulic characteristics
• CRR of 1.0 and greater
• All pipe NDT weld tested
OTHER BENEFITS/SERVICES:
• We have the most stocking locations in the industry,
for best delivery and availability
• Plain end or roll groove
• Eddy Guard II™ bacterial-resistant internal coating
• Custom length options
• Hot dipped galvanization
• Reddi-Pipe® red or black pipe eliminates field painting
• Compatible for use in wet, dry, preaction and deluge
sprinkler systems
• The only maker with EPDs (to help earn LEED points).
Always ready to protect your most valuable assets.
SCHEDULE 10 & 40
Exclusive maker of Reddi-Pipe®
RED OR BLACK PAINTED PIPE.
800.325.4467
sales@BullMooseIndustries.com
BullMooseTube.com
Nominal Pipe Size (Inches)1"1-1/4" 1-1/2"2"2-1/2"3"4"6"8"
O.D. (in)1.315 1.660 1.900 2.375 2.875 3.500 4.500 6.625 8.625
I.D. (in)1.097 1.442 1.682 2.157 2.635 3.260 4.260 6.357 8.249
Empty Weight (lb/ft)1.410 1.810 2.090 2.640 3.530 4.340 5.620 9.290 16.940
Water Filled Weight (lb/ft)1.820 2.518 3.053 4.223 5.893 7.957 11.796 23.038 40.086
C.R.R.15.27 9.91 7.76 6.27 4.92 3.54 2.50 1.158 1.805
Pieces per Lift 91 61 61 37 30 19 19 10 7
Lift Weight (lbs) 21' lengths 2,695 2,319 2,677 2,051 2,224 1,732 2,242 1,951 2,490
Lift Weight (lbs) 24' lengths 3,079 2,650 3,060 2,344 2,542 1,979 2,563 2,230 2,848
Lift Weight (lbs) 25' lengths 3,208 2,760 3,187 2,442 2,648 2,062 2,670SCHEDULE 10NPS (In.)1"1-1/4" 1-1/2"2"2-1/2"3"4"
1.315 1.660 1.900 2.375 2.875 3.500 4.500
1.049 1.380 1.610 2.067 2.469 3.068 4.026
1.680 2.270 2.720 3.660 5.800 7.580 10.800
2.055 2.918 3.602 5.114 7.875 10.783 16.316
1.00 1.00 1.00 1.00 1.00 1.00 1.00
70 51 44 30 30 19 19
2,470 2,431 2,513 2,306 3,654 3,024 4,309
2,822 2,778 2,872 2,635 4,176 3,456 4,925
2,940 2,894 2,992 2,745 4,350 3,601 5,130SCHEDULE 40Bull Moose Fire Sprinkler Pipe Product Information
Grooved End Fittings Rev.20230502
Grooved End Fittings
For pressure rating, listing, and approval information, refer to
Data Sheet B-42 or visit SHURJOINT website,
www.shurjoint.com for details or contact your SHURJOINT
Representative
Shurjoint ductile iron grooved-end fittings are made of ductile
iron per ASTM A536 Gr. 65-45-12. C-E dimensions are
manufacturer’s standard.
Shurjoint wrought steel grooved-end fittings are available from
10” (250 mm) through 24” (600 mm) pipe sizes in a variety of
styles. Fittings are fabricated with the carbon steel pipe to
ASTM A234 Gr. WPB, standard weight (0.375” or 9.5 mm), or
segmentally welded carbon steel of the same or equivalent
grade. C-E dimensions conform to ANSI B16.9. Other styles not
listed are available upon request.
Fitting pressure ratings are equivalent to the pressure ratings
of the coupling used to install them. Coupling pressure ratings
are pipe wall thickness dependent.
material specification
Fitting Body:
Ductile Iron castings to ASTM A536, Gr. 65-45-12, min.
tensile strength 65,000 psi (448 MPa).
Fabricated with the carbon steel pipe to ASTM A234 Gr.
WPB, standard weight (0.375” or 9.5 mm), or segmentally
welded carbon steel of the same or equivalent grade.
Surface Finish:
Orange color painted or red RAL3000 color painted.
o Hot dip galvanized (optional).
o Epoxy coated in red RAL3000 or other colors
(optional)
Grooved End Fittings Rev.20230502 Grooved End Fittings
Models 901 / 903
Nominal Pipe
Size
Pipe
O.D.
901
SR 90° Elbow
903
SR Straight Tee
C-E Weight C-E Weight
in in in lbs in lbs
mm mm mm kg mm kg
2 2.375 2.75 1.5 2.75 2.2
50 60.3 70 0.7 70 1.0
2½ 2.875 3.00 2.0 3.00 2.9
65 73.0 76 0.9 76 1.3
76.1
3.000 3.00 2.5 3.00 2.9
76.1 76 1.1 76 1.3
3 3.500 3.38 3.1 3.38 4.4
80 88.9 86 1.4 86 2.0
4 4.500 4.00 4.9 4.00 7.9
100 114.3 102 2.2 102 3.6
139.7
5.500 4.88 7.9 4.88 11.1
139.7 124 3.6 124 5.1
5 5.563 4.88 7.9 4.88 10.1
125 141.3 124 3.6 124 4.6
165.1
6.500 5.50 12.9 5.50 16.5
165.1 140 5.9 140 7.5
6 6.625 5.50 12.9 5.50 17.2
150 168.3 140 5.9 140 7.8
8 8.625 6.94 23.4 6.94 36.3
200 219.1 176 10.6 176 16.5
Grooved End Fittings Rev.20230502 Grooved End Fittings
MODEL 7110 / 7111 / 7112 / 7113 ELBOWS
Normal
Size
Pipe
O.D.
#7110 90° Elbows #7111 45° Elbows #7112 22.5° Elbows #7113 11.25° Elbows
C-E weight C-E weight C-E weight C-E weight
in in in lbs in lbs in lbs in lbs
mm mm mm kg mm kg mm kg mm kg
1 1.315 2.25 0.7 1.75 0.5 -- -- 1.38 0.4
25 33.4 57 0.3 45 0.2 -- -- 35 0.2
1¼ 1.660 2.75 1.1 1.75 0.7 1.75 0.7 1.38 0.7
32 42.2 70 0.5 45 0.3 45 0.3 35 0.3
1½ 1.900 2.75 1.3 1.75 0.9 1.75 1.1 1.38 0.7
40 48.3 70 0.6 45 0.4 45 0.5 35 0.3
2 2.375 3.25 2.0 2.00 1.5 1.88 1.6 1.38 1.0
50 60.3 83 0.9 51 0.7 48 0.7 35 0.4
2½ 2.875 3.75 2.6 2.25 2.1 2.01 2.6 1.50 1.6
65 73.0 95 1.2 57 0.9 51 1.2 38 0.7
76.1
3.000 3.75 3.1 2.25 2.1 2.01 2.5 1.50 1.7
76.1 95 1.4 57 0.9 51 1.1 38 0.8
3 3.500 4.25 4.3 2.50 2.9 2.25 3.1 1.50 1.8
80 88.9 108 2.0 64 1.3 57 1.4 38 0.8
101.6
4.000 4.50 5.5 -- -- -- -- -- --
101.6 114 2.5 -- -- -- -- -- --
108.0
4.250 5.00 5.5 3.00 4.4 -- -- -- --
108.0 127 2.5 76 2.0 -- -- -- --
4 4.500 5.00 6.9 3.00 4.4 2.88 4.4 1.75 2.2
100 114.3 127 3.1 76 2.0 73 2.0 45 1.0
133.0
5.250 5.50 9.0 3.25 5.9 -- -- -- --
133.0 140 4.1 83 2.7 -- -- -- --
139.7
5.500 5.50 9.5 3.25 6.4 2.88 6.5 2.00 4.5
139.7 140 4.3 83 2.9 73 2.9 51 2.0
5 5.563 5.50 11.0 3.25 6.6 2.88 6.8 2.00 4.5
125 141.3 140 5.0 83 3.0 73 3.1 51 2.1
90o 45o 22½o 11¼o
Grooved End Fittings Rev.20230502 Grooved End Fittings
MODEL 7110 / 7111 / 7112 / 7113 ELBOWS
Normal
Size
Pipe
O.D.
#7110 90° Elbows #7111 45° Elbows #7112 22.5° Elbows #7113 11.25° Elbows
C-E weight C-E weight C-E weight C-E weight
in in in lbs in lbs in lbs in lbs
mm mm mm kg mm kg mm kg mm kg
159.0
6.250 6.50 13.2 3.50 8.4 -- -- -- --
159.0 165 6.0 89 3.8 -- -- -- --
165.1
6.500 6.50 12.5 3.50 8.9 3.12 10.7 2.00 5.5
165.1 165 5.7 89 4.0 79 4.9 51 2.5
6 6.625 6.50 12.8 3.50 8.9 3.12 9.3 2.00 5.5
150 168.3 165 5.8 89 4.0 79 4.2 51 2.5
8 8.625 7.75 28.7 4.25 19.0 3.88 17.8 2.00 10.1
200 219.1 197 13.0 108 8.6 98 8.1 51 4.6
10 10.750 9.00 53.1 4.75 34.2 4.38 39.0 2.13 22.1
250 273.0 229 24.1 121 15.5 111 17.7 54 10.0
12 12.750 10.00 81.0 5.25 49.5 4.88 43.0 2.25 27.3
300 323.9 254 36.7 133 22.5 124 19.5 57 12.4
200 JIS
8.516 7.75 27.2 4.25 18.5 3.88 13.9 2.00 9.3
216.3 197 12.4 108 8.4 98 6.3 51 4.2
250 JIS
10.528 9.00 52.8 4.75 34.2 4.38 22.5 2.13 22.1
267.4 229 24.0 121 15.5 111 10.2 54 10.0
300 JIS
12.539 10.00 77.0 5.25 49.5 4.88 33.7 2.25 27.3
318.5 254 35.0 133 22.5 124 15.3 57 12.4
Grooved End Fittings Rev.20230502 Grooved End Fittings
7120 Tee 7135 Cross
Model 7120 TEE / 7135 CROSS
Nominal
Size
Pipe
O.D.
#7120
Tee
#7135
Cross
C - E Weight C-LE Weight
in in in lbs in lbs
mm mm mm kg mm kg
1 1.315 2.25 0.9 2.25 ---
25 33.4 57 0.4 57 ---
1¼ 1.660 2.75 1.5 2.75 ---
32 42.2 70 0.7 70 ---
1½ 1.900 2.75 2.0 2.75 ---
40 48.3 70 0.9 70 ---
2 2.375 3.25 2.9 3.25 2.7
50 60.3 83 1.3 83 1.2
2½ 2.875 3.75 4.8 3.75 6.6
65 73.0 95 2.2 95 3.0
76.1
3.000 3.75 5.1 3.75 6.6
76.1 95 2.3 95 3.0
3 3.500 4.25 6.8 4.25 6.8
80 88.9 108 3.1 108 3.1
4 4.500 5.00 9.9 5.00 11.5
100 114.3 127 4.5 127 5.2
108.0
4.250 5.00 9.0 --- ---
108.0 127 4.1 --- ---
133.0
5.250 5.50 13.2 --- ---
133.0 140 6.0 --- ---
139.7
5.500 5.50 14.3 5.50 13.0
139.7 140 6.5 140 5.9
5 5.563 5.50 14.3 5.50 13.0
125 141.3 140 6.5 140 5.9
159.0
6.250 6.50 18.9 --- ---
159.0 165 8.6 --- ---
Grooved End Fittings Rev.20230502 Grooved End Fittings
* Segmentally welded carbon steel fitting with roll groove. Sold as “W” series item.
Model 7120 TEE / 7135 CROSS
Nominal
Size
Pipe
O.D.
#7120
Tee
#7135
Cross
C - E Weight C-LE Weight
in in in lbs in lbs
mm mm mm kg mm kg
165.1
6.500 6.50 21.7 6.50 32.0
165.1 165 9.9 165 14.5
6 6.625 6.50 22.0 6.50 32.0
150 168.3 165 10.0 165 14.5
8 8.625 7.75 44.0 7.75 44.1
200 219.1 197 20.0 197 20.0
10 10.750 9.00 68.2 8.50* 72.7
250 273.0 229 31.0 216 33.0
12 12.750 10.00 96.7 10.00* 96.9
300 323.9 254 43.9 254 44.0
200 JIS
8.516 7.75 44.0 7.75 44.1
216.3 197 20.0 197 20.0
250 JIS
10.528 9.00 68.2 --- ---
267.4 229 31.0 --- ---
300 JIS
12.539 10.00 96.7 --- ---
318.5 254 43.9 --- ---
14* 14.000 11.00 110.2 11.00 121.0
350 355.6 279.4 50.0 279 54.9
16* 16.000 12.00 145.4 12.00 146.4
400 406.4 304.8 66.1 305 66.4
18* 18.000 13.50 169.8 13.50 185.4
450 457.2 342.9 77.0 343 84.1
20* 20.000 15.00 209.4 15.00 229.1
500 508.0 381.0 95.0 381 103.9
22* 22.000 16.50 277.2 --- ---
550 558.8 419.1 126.0 --- ---
24* 24.000 17.00 267.9 17.00 298.7
600 609.6 431.8 121.5 432 135.5
Grooved End Fittings Rev.20230502 Grooved End Fittings
1”~12”
Models 7160 End Cap / 7160P End Cap with Plug
Nominal Pipe
Size
Pipe
O.D.
7160
End Cap 7160P
Plug Size
E-E weight
in in in lbs in
mm mm mm kgs mm
1 1.315 0.87 0.2 ---
25 33.4 22 0.1 ---
1¼ 1.660 1.00 0.3 ---
32 42.2 25 0.2 ---
1½ 1.900 1.00 0.4 ---
40 48.3 25 0.2 ---
2 2.375 1.00 0.7 ½
50 60.3 25 0.3 15
2½ 2.875 1.00 0.9 ½
65 73.0 25 0.4 15
76.1
3.000 1.00 0.9 ½
76.1 25 0.4 15
3 3.500 1.00 1.5 ½
80 88.9 25 0.7 15
108.0
4.250 1.00 2.4 ---
108.0 25 1.1 ---
4 4.500 1.00 2.2 1
100 114.3 25 1.0 25
133.0
5.250 1.00 3.7 ---
133.0 25 1.7 ---
139.7
5.500 1.00 3.7 1
139.7 25 1.7 25
5 5.563 1.00 3.7 1
125 141.3 25 1.7 25
159.0
6.250 1.00 5.1 ---
159.0 25 2.3 ---
165.1
6.500 1.00 6.0 1
165.1 25 2.7 25
Grooved End Fittings Rev.20230502 Grooved End Fittings
* Segmentally welded carbon steel fitting with roll groove. Sold as “W” series item.
Models 7160 End Cap / 7160P End Cap with Plug
Nominal Pipe
Size
Pipe
O.D.
7160
End Cap 7160P
Plug Size
E-E weight
in in in lbs in
mm mm mm kgs mm
6 6.625 1.00 6.0 1
150 168.3 25 2.7 25
8 8.625 1.18 10.1 1½
200 219.1 30 4.6 40
10 10.750 1.25 15.4 1½
250 273.0 32 7.0 40
12 12.750 1.25 22.0 1½
300 323.9 32 10.0 40
200 JIS
8.516 1.18 10.1 ---
216.3 30 4.6 ---
250 JIS
10.528 1.25 15.4 ---
267.4 32 7.0 ---
300 JIS
12.539 1.25 22.0 ---
318.5 32 10.0 ---
14* 14.000 6.50 35.0 ---
350 355.6 165.0 15.9 ---
16* 16.000 7.00 44.0 ---
400 406.4 178.0 20.0 ---
18* 18.000 8.00 56.1 ---
450 457.2 203.0 25.5 ---
20* 20.000 9.00 70.0 ---
500 508.0 229.0 31.8 ---
22* 22.000 10.00 85.4 ---
550 558.8 254.0 38.8 ---
24* 24.000 10.50 99.2 ---
600 609.6 267.0 45.1 ---
•
•
o
•
o
o
•
•
•
•
•
•
•
•
Project InformatIon :aPProval Stam P:
Project:
Date:Phone:
Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
Rev. 03.03.06-00
For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
go to www.anvilstar.com or contact your local AnvilStar representative
Submittal Sheet
SPF Cast & Ductile Iron Fittings
®
Material Specification S
Ductile iron threaded fittings are UL & ULC Listed &
Factory Mutual Approved for 500 psi service.
Ductile iron per ASTM A536 Class 65-45-2.
Dimensions conform to ASMe B6.3 Class 50.
Threads are NPT per ANSI/ASMe B.20..
Notice: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile
iron fittings should be tightened three turns beyond hand tight, but no more than four turns.
reducing coupling
Nominal Size Anvil Item Number Universal Number Max. Working Pressure DimensionsA Approx. Wt. Each
In. (mm)PSI (kPa)In. (mm)Lbs. (kg)
1 x 1⁄2 840010755 DRC031 500 1.69 0.39
25 x 15 3450 42.92 0.18
1 x 3⁄4 840010763 DRC032 500 1.69 0.53
25 x 20 3450 42.92 0.24 A
reducing couplling
Ductile Iron
PROJECT INFORMATION APPROVAL STAMP
Project:q Approved
Address:q Approved as noted
Contractor:q Not approved
Engineer:Remarks:
Submittal Date:
Notes 1:
Notes 2:
NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe.
Therefore, over tightening can cause damage to pipe threads which may cause
leakage. Ductile iron fittings should be tightened approximately three turns beyond
hand tight, but no more than four turns.
SPF/DI-5.16
DUCTILE IRON THREADED FITTINGS
Dimensions: ASME B16.14
Material: ASTM A536 Grade 65-45-12
Finish: Black
Threads: NPT per ASME B1.20.1
Agency Approvals: All ductile iron threaded fittings are
UL/ULC Listed and FM Approved.
MATERIAL SPECIFICATIONS
s Pressure - Temperature Ratings in accordance with ASME B16.3 Class 150
FIG. 3388
Cored Plug
For Listings/Approval Details and Limitations,
visit our website at www.anvilintl.com or
contact an Anvil® Sales Representative.
A
FIGURE 3388 - CORED PLUG
Nominal Size Maximum
Working Pressures
Dimension A Approx. Wt. Each
In. (mm)PSI (kPa)In. (mm)Lbs. (kg)
1⁄2*500 0.94 0.10
15 3450 23.87 0.05
3⁄4 500 1.07 0.17
20 3450 27.17 0.08
1 500 1.25 0.28
25 3450 31.75 0.13
11⁄4 500 1.36 0.44
32 3450 34.54 0.20
11⁄2 500 1.45 0.62
40 3450 36.83 0.28
2 500 1.56 0.91
50 3450 39.62 0.41
s – Working Pressure Ratings are for reference only and based on Sch. 40 pipe. For the
latest UL/ULC, and FM pressure ratings versus pipe schedule, please visit anvilintl.com or
contact your local Anvil Representative.
* Part supplied as Solid Plug.
Project InformatIon :aPProval Stam P:
Project:
Date:Phone:
Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
Rev. 03.03.06-003
For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
go to www.anvilstar.com or contact your local AnvilStar representative
Submittal Sheet
SPF Cast & Ductile Iron Fittings
®
Material Specification S
Ductile iron threaded fittings are UL & ULC Listed &
Factory Mutual Approved for 500 psi service.
Ductile iron per ASTM A536 Class 65-45-2.
Dimensions conform to ASMe B6.3 Class 50.
Threads are NPT per ANSI/ASMe B.20..
Notice: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile
iron fittings should be tightened three turns beyond hand tight, but no more than four turns.
Straight tee
Nominal Size Anvil Item Number Universal Number Max. Working Pressure
Dimensions Approx. Wt. Each
A B
In. (mm)PSI (kPa)In. (mm)In. (mm)Lbs. (kg)
1 840003164 DT333 500 1.50 1.50 0.85
25 3450 38.10 38.10 0.39
11⁄4 840003172 DT444 500 1.75 1.75 1.22
32 3450 44.45 44.45 0.55
11⁄2 840003180 DT555 500 1.94 1.94 1.55
40 3450 49.27 49.27 0.70
2 840003198 DT666 500 2.25 2.25 2.45
50 3450 57.15 57.15 1.11
B
AA
Straight tee
Ductile Iron
Project InformatIon :aPProval Stam P:
Project:
Date:Phone:
Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
Rev. 03.03.06-004
For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
go to www.anvilstar.com or contact your local AnvilStar representative
Submittal Sheet
SPF Cast & Ductile Iron Fittings
®
Material Specification S
Ductile iron threaded fittings are UL & ULC Listed &
Factory Mutual Approved for 500 psi service.
Ductile iron per ASTM A536 Class 65-45-2.
Dimensions conform to ASMe B6.3 Class 50.
Threads are NPT per ANSI/ASMe B.20..
Notice: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile
iron fittings should be tightened three turns beyond hand tight, but no more than four turns.
reducing tee
Nominal Size Anvil Item Number Universal Number
Max. Working Pressure
Dimensions Approx. Wt. EachABC
In. (mm)PSI (kPa)In. (mm)In. (mm)In. (mm)Lbs.(kg)
11⁄2 x 11⁄4 x 1 840004428 DT543 500 1.65 1.58 1.80 1.2540 x 32 x 25 3450 41.91 40.13 45.72 0.5711⁄2 x 11⁄4 x 2 840004436 DT546 500 2.16 2.10 2.02 1.9040 x 32 x 50 3450 54.86 53.34 51.30 0.8611⁄2 x 11⁄2 x 1⁄2 840004444 DT551 500 1.41 1.41 1.16 1.1540 x 40 x 15 3450 35.81 35.81 29.46 0.5211⁄2 x 11⁄2 x 3⁄4 840004451 DT552 500 1.52 1.52 1.75 1.2440 x 40 x 20 3450 38.61 38.61 44.45 0.5611⁄2 x 11⁄2 x 1 840004469 DT553 500 1.65 1.65 1.80 1.3040 x 40 x 25 3450 41.91 41.91 45.72 0.5911⁄2 x 11⁄2 x 11⁄4 840004477 DT554 500 1.82 1.82 1.88 1.4840 x 40 x 32 3450 46.23 46.23 47.75 0.6711⁄2 x 11⁄2 x 2 840004485 DT556 500 2.16 2.16 2.02 1.9840 x 40 x 50 3450 54.86 54.86 51.30 0.902 x 1 x 2 840004493 DT636 500 2.25 2.02 2.25 2.1550 x 25 x 50 3450 57.15 51.31 57.15 0.982 x 11⁄4 x 2 840004501 DT646 500 2.25 2.10 2.25 2.3050 x 32 x 50 3450 57.15 53.34 57.15 1.042 x 11⁄2 x 1⁄2 840004519 DT651 500 1.49 1.41 1.88 1.5050 x 40 x 15 3450 37.85 35.81 47.75 0.682 x 11⁄2 x 3⁄4 840004527 DT652 500 1.60 1.52 1.97 1.6250 x 40 x 20 3450 40.64 38.61 50.04 0.732 x 11⁄2 x 1 840004535 DT653 500 1.73 1.65 2.02 1.6450 x 40 x 25 3450 43.94 41.91 51.31 0.742 x 11⁄2 x 11⁄4 840004543 DT654 500 1.90 1.82 2.10 1.8050 x 40 x 32 3450 48.26 46.23 53.34 0.822 x 11⁄2 x 11⁄2 840004550 DT655 500 2.02 1.94 2.16 2.0050 x 40 x 40 3450 51.31 49.28 54.86 0.912 x 11⁄2 x 2 840004568 DT656 500 2.25 2.16 2.25 2.3550 x 40 x 50 3450 57.15 54.86 57.15 1.072 x 2 x 1⁄2 840004576 DT661 500 1.49 1.49 1.88 1.6050 x 50 x 15 3450 37.85 37.85 47.75 0.732 x 2 x 3⁄4 840004584 DT662 500 1.60 1.60 1.97 1.6850 x 50 x 20 3450 40.64 40.64 50.04 0.762 x 2 x 1 840004592 DT663 500 1.73 1.73 2.02 1.8550 x 50 x 25 3450 43.94 43.94 51.31 0.842 x 2 x 11⁄4 840004600 DT664 500 1.90 1.90 2.10 2.0450 x 50 x 32 3450 44.45 42.42 44.45 0.932 x 2 x 11⁄2 840004618 DT665 500 2.02 2.02 2.16 2.1850 x 50 x 40 3450 44.45 42.42 44.45 0.992 x 2 x 21⁄2 -DT667 500 2.60 2.60 2.39 3.6150 x 50 x 65 3450 44.45 42.42 44.45 1.6421⁄2 x 2 x 3⁄4 -DT762 500 1.74 1.60 2.32 2.2865 x 50 x 20 3450 44.45 42.42 44.45 1.03
reducing tee
Nominal Size Anvil Item Number Universal Number
Max. Working Pressure
Dimensions Approx. Wt. EachABC
In. (mm)PSI (kPa)In. (mm)In. (mm)In. (mm)Lbs.(kg)
1 x 1⁄2 x 1 840004196 DT313 500 1.50 1.36 1.50 0.6425 x 15 x 25 3450 38.10 34.54 38.10 0.291 x 3⁄4 x 1 840004204 DT323 500 1.50 1.45 1.50 0.7325 x 20 x 25 3450 38.10 36.83 38.10 0.331 x 1 x 1⁄2 840004212 DT331 500 1.26 1.26 1.36 0.7125 x 25 x 15 3450 32.00 32.00 34.54 0.321 x 1 x 3⁄4 840004220 DT332 500 1.37 1.37 1.45 0.7625 x 25 x 20 3450 34.80 34.80 36.83 0.341 x 1 x 11⁄4 840004238 DT334 500 1.67 1.67 1.58 0.9825 x 25 x 32 3450 42.41 42.41 40.13 0.441 x 1 x 11⁄2 840004246 DT335 500 1.80 1.80 1.65 1.1625 x 25 x 40 3450 45.72 45.72 41.91 0.5311⁄4 x 1 x 1⁄2 840004253 DT431 500 1.34 1.26 1.53 0.8232 x 25 x 15 3450 34.04 32.00 38.86 0.3711⁄4 x 1 x 3⁄4 840004261 DT432 500 1.45 1.37 1.62 0.9032 x 25 x 20 3450 36.83 34.80 41.15 0.4111⁄4 x 1 x 1 840004279 DT433 500 1.58 1.50 1.67 1.0032 x 25 x 25 3450 40.13 38.10 42.42 0.4511⁄4 x 1 x 11⁄4 840004287 DT434 500 1.75 1.67 1.75 1.0832 x 25 x 32 3450 44.45 42.42 44.45 0.4911⁄4 x 1 x 11⁄2 840004295 DT435 500 1.88 1.80 1.82 1.4232 x 25 x 40 3450 47.75 45.72 46.22 0.6411⁄4 x 11⁄4 x 1⁄2 840004303 DT441 500 1.34 1.34 1.53 0.8632 x 32 x 15 3450 34.04 34.04 38.86 0.3911⁄4 x 11⁄4 x 3⁄4 840004311 DT442 500 1.45 1.45 1.62 0.9232 x 32 x 20 3450 36.83 36.83 41.15 0.4211⁄4 x 11⁄4 x 1 840004329 DT443 500 1.58 1.58 1.67 0.9532 x 32 x 25 3450 40.13 40.13 42.42 0.4311⁄4 x 11⁄4 x 11⁄2 840004337 DT445 500 1.88 1.88 1.82 1.4532 x 32 x 40 3450 47.75 47.75 46.22 0.6611⁄4 x 11⁄4 x 2 840004345 DT446 500 2.10 2.10 1.90 1.7532 x 32 x 50 3450 53.34 53.34 48.26 0.7911⁄2 x 1 x 1⁄2 840004352 DT531 500 1.41 1.34 1.66 0.9540 x 25 x 15 3450 35.81 34.04 42.16 0.4311⁄2 x 1 x 3⁄4 840004360 DT532 500 1.52 1.37 1.75 1.1440 x 25 x 20 3450 38.61 34.80 44.45 0.5211⁄2 x 1 x 1 840004378 DT533 500 1.65 1.50 1.80 1.1740 x 25 x 25 3450 41.91 38.10 45.72 0.5311⁄2 x 1 x 11⁄4 840004386 DT534 500 1.82 1.67 1.88 1.3440 x 25 x 32 3450 46.23 42.42 47.75 0.6111⁄2 x 1 x 11⁄2 840004394 DT535 500 1.94 1.80 1.94 1.4540 x 25 x 40 3450 49.28 45.72 49.28 0.6611⁄2 x11⁄4 x 1⁄2 840004402 DT541 500 1.41 1.34 1.66 1.0540 x 32 x 15 3450 35.81 34.04 42.16 0.4811⁄2 x11⁄4 x 3⁄4 840004410 DT542 500 1.52 1.45 1.75 1.1540 x 32 x 20 3450 38.61 36.83 44.45 0.52
C
BA
reducing tee
Ductile Iron
Project InformatIon :aPProval Stam P:
Project:
Date:Phone:
Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
Rev. 03.03.06-000
For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
go to www.anvilstar.com or contact your local AnvilStar representative
Submittal Sheet
SPF Cast & Ductile Iron Fittings
®
Material Specification S
Ductile iron threaded fittings are UL & ULC Listed &
Factory Mutual Approved for 500 psi service.
Ductile iron per ASTM A536 Class 65-45-2.
Dimensions conform to ASMe B6.3 Class 50.
Threads are NPT per ANSI/ASMe B.20..
Notice: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile
iron fittings should be tightened three turns beyond hand tight, but no more than four turns.
90° elbow
Nominal Size Anvil ItemNumber Universal Number
Max. Working Pressure
Dimensions- In.(mm)Approx. Wt. Each
A B
In. (mm)PSI (kPa)In. (mm)In. (mm)Lbs. (kg)
1 840000004 DB90033 500 1.50 1.50 0.62
20 3450 38.10 38.10 0.28
11⁄4 840000012 DB90044 500 1.75 1.75 0.90
32 3450 44.45 44.45 0.41
11⁄2 840000020 DB90055 500 1.94 1.94 1.20
40 3450 49.276 49.276 0.54
2 840000038 DB90066 500 2.25 2.25 1.85
50 3450 57.15 57.15 0.84
B
A
90° elbow
Ductile Iron
Project InformatIon :aPProval Stam P:
Project:
Date:Phone:
Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
Rev. 03.03.06-002
For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
go to www.anvilstar.com or contact your local AnvilStar representative
Submittal Sheet
SPF Cast & Ductile Iron Fittings
®
Material Specification S
Ductile iron threaded fittings are UL & ULC Listed &
Factory Mutual Approved for 500 psi service.
Ductile iron per ASTM A536 Class 65-45-2.
Dimensions conform to ASMe B6.3 Class 50.
Threads are NPT per ANSI/ASMe B.20..
Notice: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile
iron fittings should be tightened three turns beyond hand tight, but no more than four turns.
reducing 90° elbow
Nominal Size Anvil Item Number Universal Number
Max. Working Pressure
Dimensions Approx. Wt. Each
A B
In. (mm)PSI (kPa)In. (mm)In. (mm)Lbs. (kg)
1 x 1⁄2 840001036 DB90031 500 1.26 1.36 0.44
25 x 15 3450 32.00 34.54 0.20
1 x 3⁄4 840001044 DB90032 500 1.37 1.45 0.52
25 x 20 3450 34.79 36.83 0.24
11⁄4 x 1⁄2 840001051 DB90041 500 1.34 1.53 0.64
32 x 15 34550 34.03 38.86 0.29
11⁄4 x 3⁄4 840001069 DB90042 500 1.45 1.62 0.72
32 x 20 3450 36.83 41.14 0.33
11⁄4 x 1 840001077 DB90043 500 1.58 1.67 0.75
32 x 25 3450 40.13 42.41 0.34
11⁄2 x 1 840001085 DB90053 500 1.65 1.80 0.92
40 x 25 3450 41.91 45.72 0.42
11⁄2 x 11⁄4 840001093 DB90054 500 1.82 1.88 1.08
40 x 32 3450 46.22 47.75 0.49
2 x 1⁄2 840001101 DB90061 500 1.49 1.88 1.08
50 x 15 3450 37.84 47.75 0.49
2 x 3⁄4 840001119 DB90062 500 1.60 1.97 1.24
50 x 20 3450 40.64 50.03 0.56
2 x 1 840001127 DB90063 500 1.73 2.02 1.40
50 x 25 3450 43.94 51.30 0.64
2 x 11⁄4 840001135 DB90064 500 1.90 2.10 1.52
50 x 32 3450 48.26 53.34 0.70
2 x 11⁄2 840001143 DB90065 500 2.02 2.16 1.65
50 x 40 3450 51.30 54.86 0.75
A
B
reducing 90° elbow
Ductile Iron
Project InformatIon :aPProval Stam P:
Project:
Date:Phone:
Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
Rev. 03.03.06-00
For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
go to www.anvilstar.com or contact your local AnvilStar representative
Submittal Sheet
SPF Cast & Ductile Iron Fittings
®
Material Specification S
Ductile iron threaded fittings are UL & ULC Listed &
Factory Mutual Approved for 500 psi service.
Ductile iron per ASTM A536 Class 65-45-2.
Dimensions conform to ASMe B6.3 Class 50.
Threads are NPT per ANSI/ASMe B.20..
Notice: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile
iron fittings should be tightened three turns beyond hand tight, but no more than four turns.
45° elbow
Nominal Size Anvil Item Number Universal Number Max. Working Pressure
Dimensions-Approx. Wt. Each
A B
In. (mm)PSI (kPa)In. (mm)In. (mm)Lbs. (kg)
1 840002133 DB45033 500 1.12 1.12 0.46
25 3450 28.44 28.44 0.21
11⁄4 840002141 DB45044 500 1.29 1.29 0.73
32 3450 32.76 32.76 0.33
11⁄2 840002158 DB45055 500 1.43 1.43 0.92
40 3450 36.32 36.32 0.42
2 840002166 DB45066 500 1.68 1.68 1.50
50 3450 42.67 42.67 0.68
A B45° elbow
Ductile Iron
Project InformatIon :aPProval Stam P:
Project:
Date:Phone:
Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
Rev. 03.03.06-00
For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
go to www.anvilstar.com or contact your local AnvilStar representative
Submittal Sheet
SPF Cast & Ductile Iron Fittings
®
Material Specification S
Ductile iron threaded fittings are UL & ULC Listed &
Factory Mutual Approved for 500 psi service.
Ductile iron per ASTM A536 Class 65-45-2.
Dimensions conform to ASMe B6.3 Class 50.
Threads are NPT per ANSI/ASMe B.20..
Notice: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile
iron fittings should be tightened three turns beyond hand tight, but no more than four turns.
capS
Nominal Size Anvil Item Number Universal Number
Max. Working Pressure
Dimensions A Approx. Wt. Each
In. (mm)PSI (kPa)In. (mm)Lbs. (kg)
1 840005615 DCP003 500 1.16 0.32
25 3450 29.46 0.15
11⁄4 840005623 DCP004 500 1.28 0.43
32 3450 32.51 0.20
11⁄2 840005631 DCP005 500 1.33 0.60
40 3450 33.78 0.27
2 840005649 DCP006 500 1.45 0.91
50 3450 36.83 0.41
A
cap
Ductile Iron
Project InformatIon :aPProval Stam P:
Project:
Date:Phone:
Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
Rev. 03.03.06-0020
For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
go to www.anvilstar.com or contact your local AnvilStar representative
Submittal Sheet
SPF Cast & Ductile Iron Fittings
®
Material Specification S
Ductile iron threaded fittings are UL & ULC Listed &
Factory Mutual Approved for 500 psi service.
Ductile iron per ASTM A536 Class 65-45-2.
Dimensions conform to ASMe B6.3 Class 50.
Threads are NPT per ANSI/ASMe B.20..
Notice: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile
iron fittings should be tightened three turns beyond hand tight, but no more than four turns.
bu ShingS
Nominal Size Anvil Item Number Universal Number
Dimensions Style Approx. Wt. Each
A B C
In. (mm)In. (mm)In. (mm)In. (mm)Lbs. (kg)
1 x 1⁄2 840600001 DBUSH31 0.75 0.25 1.42 Outside 0.22
25 x 15 19.05 6.35 36.06 0.10
1 x 3⁄4 840600019 DBUSH32 0.75 0.25 1.42 Outside 0.17
25 x 20 19.05 6.35 36.06 0.08
11⁄4 x 1 840600027 DBUSH43 0.80 0.28 1.76 Outside 0.28
32 x 25 20.32 7.11 44.70 0.13
11⁄2 x 1 840600035 DBUSH53 0.83 0.31 2.00 Outside 0.45
40 x 25 21.08 7.874 50.80 0.20
11⁄2 x 11⁄4 840600043 DBUSH54 0.83 0.31 2.00 Outside 0.30
40 x 32 21.08 7.874 50.80 0.14
2 x 1 840600050 DBUSH63 0.88 0.41 1.95 Inside 0.67
50 x 25 22.35 10.414 49.53 0.30
2 x 11⁄4 840600068 DBUSH64 0.88 0.34 2.48 Outside 0.73
50 x 32 22.35 8.636 62.99 0.33
2 x 11⁄2 840600076 DBUSH65 0.88 0.34 2.48 Outside 0.61
50 x 40 22.35 8.636 62.99 0.28
A
B
C
A
B
C
Inside Head
Outside Head
buShingS
Ductile Iron
MICROFAST® QUICK
RESPONSE UPRIGHT SPRINKLER VK327 (K4.2)
TECHNICAL DATA
Page 1 of 3
Form No. F_061514 21.03.05 Rev 21.1
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
1. DESCRIPTION
The Viking Microfast® Quick Response Upright Sprinkler VK327 is a small,
thermosensitive, glass-bulb spray sprinkler available in several different finishes
and temperature ratings to meet design requirements. The special Polyester and
Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where
colors are desired. In addition, these coatings have been investigated for installation
in corrosive environments and are listed/approved as indicated in the Approval
Chart(s).
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
Refer to Approval Chart(s) and Design Criteria for cULus Listing requirements
that must be followed.
3. TECHNICAL DATASpecifications:
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: 175 psi (12 bar) wwp.
Factory tested hydrostatic rating: 500 psi (34.5 bar)
Thread size: 1/2” NPT, 15 mm BSPT
Nominal K-Factor: 4.2 U.S. (57 metric**)
Glass-bulb fluid temperature rating: -65 °F (-55 °C)
Overall Length: 2-1/4” (58 mm)
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
Covered by the following US Patent No.: 4,831,870Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Brass UNS-C23000 or Copper UNS-C19500
Bushing: Brass UNS-C36000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw-ENT Plated, Pip Cap-ENT CoatedOrdering Information: (Also refer to the current Viking price list.)
Order Viking Microfast® Quick Response Upright Sprinkler VK327 by first adding the appropriate suffix for the sprinkler finish and
then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffixes: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B and ENT = JN
Temperature Suffixes: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, and 286 F° (141 °C) = G
For example, sprinkler VK327 with a 1/2” NPT thread, Brass finish and a 155 °F (68 °C) temperature rating = Part No. 06719BAB
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the current Viking price list.)
Sprinkler Wrench: Standard Wrench: Part No. 21475M/B (available since 2017)
Sprinkler Cabinets:A. Six-head capacity: Part No. 01724A (available since 1971)B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATIONRefer to appropriate NFPA Installation Standards.
Replaces Form F_061514 Rev 20.1
(Removed bushed part numbers)
MICROFAST® QUICK
RESPONSE UPRIGHT SPRINKLER VK327 (K4.2)
TECHNICAL DATA
Page 2 of 3
Form No. F_061514 21.03.05 Rev 21.1
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCERefer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Microfast® Quick Response Upright Sprinkler VK327 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEEFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating1
Maximum Ambient
Ceiling Temperature2 Bulb Color
Ordinary 135 °F (57 °C)100 °F (38 °C)Orange
Ordinary 155 °F (68 °C)100 °F (38 °C)Red
Intermediate 175 °F (79 °C)150 °F (65 °C)Yellow
Intermediate 200 °F (93 °C)150 °F (65 °C)Green
High 286 °F (141 °C)225 °F (107 °C)Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester and ENT3,4
Corrosion-Resistant Coatings: White Polyester, Black Polyester and ENT3,4
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards.
3 The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart(s). These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfac-es only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated.
4 cULus Listed as corrosion resistant.
Figure 1:
Standard Sprinkler Wrench 21475M/B
Protective Sprinkler Cap
Wrench Flat
MICROFAST® QUICK
RESPONSE UPRIGHT SPRINKLER VK327 (K4.2)
TECHNICAL DATA
Page 3 of 3
Form No. F_061514 21.03.05 Rev 21.1
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Approval Chart
Microfast® Quick Response
Upright Sprinkler VK327
Maximum 175 PSI (12 bar) WWP
Base Part
Number1 SIN Thread Size Nominal K-Factor Overall Length Listings and Approvals3
NPT BSPT U.S.metric2 Inches mm cULus
21269 VK327 1/2”15 mm 4.2 57 2-3/16 56 A1, B2
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and
286 °F (141°C)
B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C)
Approved Finishes
1 - Brass, Chrome, White Polyester5,6, and Black Polyester5,6
2 - ENT6
Footnotes
1 Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4 Listed by Underwriters Laboratories Inc. for us in the U.S. and Canada
5 Other colors are available on request with the same Listings and Approvals as the standard colors.
6 cULus Listed as corrosion resistant.
DESIGN CRITERIA
(Also refer to Approval Chart 1 above.)
cULus Listing Requirements:
The Viking Microfast® Quick Response Upright Sprinkler VK327 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the
latest edition of NFPA 13 for standard spray sprinklers.
• Small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet sys-
tems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally
galvanized.
• The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page F_080614 for
general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking Technical Data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza-
tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Replaces Form F_061514 Rev 20.1
(Removed bushed part numbers)
MIRAGE® QUICK RESPONSE
CONCEALED PENDENT
SPRINKLER VK465 (K4.2)TECHNICAL DATA
Form No. F_032107 Rev 01 April 2023
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Page 1 of 5
1. DESCRIPTIONViking Mirage® Quick Response Concealed Pendent Sprinkler VK465 is a thermo-sensitive glass-bulb spray sprinkler designed for installation on concealed pipe systems where the appearance of a smooth ceiling is desired.The sprinkler is pre-assembled with a threaded adapter for installation with a low-profile cover assembly that provides up to ½” (13 mm) of vertical adjustment. The two-piece design allows installation and testing of the sprinkler prior to installation of the cover plate. The The “push-on” and “thread-on” designs of the concealed cover plate assemblies allow easy installation of the cover plate after the system has been tested and the ceiling finish has been applied. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive environments and is listed and approved as indicated in the Approval Charts. The ENT finish is only available for the sprinkler assembly, the cover plate is not plated.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
Refer to the Approval Chart and Design Criteria for cULus Listing requirements that must be followed.
3. TECHNICAL DATA
Specifications:Minimum Operating Pressure: 7 psi (0.5 bar). Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).Thread size: 1/2” (15 mm) NPTNominal K-Factor: 4.2 U.S. (57 metric*)
* Metric K-factor measurement is shown in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.Glass-bulb fluid temperature rated to -65 °F (-55 °C)Patents Pending
Material Standards:Sprinkler Body: Brass UNS-C84400Deflector: Copper UNS-C19500Deflector Pins: Stainless Steel UNS-S30300Bulb: Glass, nominal 3 mm diameterPip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400Button: Brass UNS-C36000 Screws: 18-8 Stainless SteelBelleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE TapeYoke: Phosphor Bronze UNS-C51000Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Cover Assembly Materials:Cover: Copper UNS-C11000Base: Brass UNS-C26000 or UNS-C26800Springs: Nickel AlloySolder: Eutectic
Ordering Information: The sprinkler and cover plate must be ordered separately. Refer to Tables 1 and 2.
4. INSTALLATIONRefer to appropriate NFPA Installation Standards.
5. OPERATIONDuring fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter, releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCERefer to NFPA 25 for Inspection, Testing and Maintenance requirements.
For Light Hazard Occupancies Only
Replaces Form No. F_032107 Rev 21.1
(Adding venting statement (s))
MIRAGE® QUICK RESPONSE
CONCEALED PENDENT
SPRINKLER VK465 (K4.2)TECHNICAL DATA
Form No. F_032107 Rev 01 April 2023
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Page 2 of 5
7. AVAILABILITYViking Mirage® Concealed Pendent Sprinkler VK465 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEEFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
TABLE 1: SPRINKLER ORDERING INFORMATION
Instructions:
(1) Select a Sprinkler Base Part Number
(2) Add the suffix for the desired Finish
(3) Add the suffix for the desired Sprinkler Temperature Rating
(4) Order a cover plate (refer to Table 2)
Example: 21274AE = 200 °F (93 °C) Temperature Rated Sprinkler with a standard Brass finish.
SIN
Sprinkler
Base Part
Number
Size 1: Finishes 2: Temperature Ratings
NPT
Inch
BSPT
mm Description Suffix1
Sprinkler
Temperature
Classification
Nominal Rating Bulb Color
Max. Ambient
Ceiling
Temperature2
Suffix
VK465 21274 1/2 15 Brass A Ordinary 155 °F (68 °C)Red 100 °F (38 °C)B
ENT 3,4 JN Intermediate 175 °F (79 °C)Yellow 150 °F (65 °C)D
Intermediate 200 °F (93 °C)Green 150 °F (65 °C)E
Accessories
Sprinkler Wrenches and tools (see Figure 1):
A. Heavy Duty Part Number: 14047W/B5 (available since 2006)
B. Head Cabinet Wrench Part Number: 140316 (available since 2006)
C. Optional Concealed Cover Plate Installer Tool Part Number: 144127 (available since 2007)
D. Optional Large Concealed Cover Plate Installer Tool Part No. 148677 (available since 2007)
Sprinkler Cabinet:Holds up to 6 sprinklers: Part number 01731A (available since 1971).
Footnotes
1. Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
2. Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards.
3. cULus Listed as corrosion resistant.
4. The corrosion resistant and corrosion proofing coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
5. Requires a ½” ratchet (not available from Viking).
6. Also optional for removal of the protective cap. Ideal for sprinkler cabinets.
7. The installer tool is for push-on style cover plates only.
MIRAGE® QUICK RESPONSE
CONCEALED PENDENT
SPRINKLER VK465 (K4.2)TECHNICAL DATA
Form No. F_032107 Rev 01 April 2023
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Page 3 of 5
TABLE 2: COVER PLATE ORDERING INFORMATION
Instructions:
(1) Select a Cover Plate Base Part Number
(2) Add the suffix for the desired Finish
(3) Add the suffix for the required Cover Plate Nominal Rating.
Example: 23190MC/W = 165 °F (74 °C) Temperature Rated, 2-3/4” (70 mm) diameter, Thread-On style Round Cover Plate with a Painted White finish.
1: Select a Cover Plate Base Part Number3
2: Select a FinishThread-On Style Push-On Style
Base Part
Number
Size
Inch (mm)Type Base Part
Number
Size
Inch (mm)Type Description Suffix5
23190 2-3/4 (70)Round 23447 2-3/4 (70)Round Polished Chrome F
23174 3-5/16 (84)Round 23463 3-5/16 (84)Round Brushed Chrome F-/B
23179 3-5/16 (84)Square 23482 3-5/16 (84)Square Bright Brass B
Antique Brass B-/A
Brushed Brass B-/B
Brushed Copper E-/B
Painted White M-/W
Painted Ivory M-/I
Painted Black M-/B
3: Temperature Rating Matrix1,2
Cover Plate Nominal
Rating (Required)
Temperature
Classification Sprinkler Nominal Rating Sprinkler Maximum Ambient
Ceiling Temperature2 Suffix
UL: 135 °F (57 °C)Ordinary 155 °F (68 °C)100 °F (38 °C)A
165 °F (74 °C)Intermediate 175 °F (79 °C)150 °F (65 °C)C
165 °F (74 °C)Intermediate 200 °F (93 °C)150 °F (65 °C)C
Footnotes
1. The sprinkler temperature rating is stamped on the deflector.
2. Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific
installation standards.
3. Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
4. Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
5. Square cover plates 23179 and 23482 cULus Listing is for the 135 °F (57 °C) temperature rated cover plate only. Refer to the Approval Chart.
Figure 1: Identification of Custom Paint for Concealed Covers
All custom color painted cover
plates will have an identifying label
affixed to the inside of the cover that
indicates the custom color and will
have a representative sample (a
paint dot) of the paint on the label.
Figure 2: Square Cover Assembly
3-5/16” (84 mm)FACTORY APPLIE D CUSTO
M
P
A
I
NT COLOR
MIRAGE® QUICK RESPONSE
CONCEALED PENDENT
SPRINKLER VK465 (K4.2)TECHNICAL DATA
Form No. F_032107 Rev 01 April 2023
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Page 4 of 5
DESIGN CRITERIA
(Also refer to the Approval Chart )
cULus Listing Requirements:
Mirage® Quick Response Concealed Pendent Sprinkler VK465 is cULus Listed as a quick response sprinkler for installation in accordance with the
latest edition of NFPA 13 for standard coverage pendent spray sprinklers as indicated below:
• Limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems, or
hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized.
• Maximum spacing allowed is 15 ft. (4.6 m).
• Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13.
• Minimum distance from walls is 4 in. (102 mm).
• Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
• The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed.
• Venting is required.
• Concealed sprinklers must NOT be installed in positive pressure plenums.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080416
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the lat-
est edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, Assemblee Pleniere, VdS or other
similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Approval Chart
Mirage® Quick Response Concealed Pendent Sprinkler VK465 For Light Hazard Occupancies Only; Maximum 175 PSI (12 bar) WWP
Sprinkler
Base Part
Number1
SIN
NPT Thread
Size
Nominal
K-Factor
Overall Length
(Sprinkler Body)
Listings and Approvals3
(Refer also to Design Criteria on page 64d.)
Inch mm U.S.metric2 Inches mm cULus4 FM NYC VdS LPCB
21274JN8 VK465 1/2”15 4.2 57 2-3/16”56 AW1, BX1 --See Footnote 5.--------
21274A VK465 1/2”15 4.2 57 2-3/16”56 AW1, BX1 --See Footnote 5.--------
Sprinkler Temperature Ratings
A - 155 °F (68 °C)
B - 175 °F (79 °C) and 200 °F (93 °C)
Cover Plate Assembly Temp. Ratings6
W - 135 °F (57 °C) cover, 231901, 234471 231741, 234631
(large diameter), or 231791, 23482 1 (square cover plate)
X - 165 °F (74 °C) cover 231901, 234471, or 231741, 234631
(large diameter)
Finishes of the Cover Plate Assembly7
1 - Polished Chrome, Brushed Chrome, Bright
Brass, Antique Brass, Brushed Brass,
Brushed Copper, Painted White, Painted
Ivory, or Painted Black
Footnotes
1. Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2. Metric K-factor measurement is shown in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3. This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals.
4. Listed by Underwriter’s Laboratories for use in the U.S. and Canada.
5. Meets New York City requirements, effective July 1, 2008.
6. The 135 °F (57 °C) cover has an orange label. The 165 °F (74 °C) cover has a white label.
7. Standard painted finishes consist of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
8. cULus Listed as corrosion resistant.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
MIRAGE® QUICK RESPONSE
CONCEALED PENDENT
SPRINKLER VK465 (K4.2)TECHNICAL DATA
Form No. F_032107 Rev 01 April 2023
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Page 5 of 5
Sprinkler and Adapter Assembly
• Protective cap
removed
• Use wrench
14047W/B**
Step 1:
Carefully slide the
wrench sideways around
the deflector and pins
Sprinkler Wrench
Part No. 14047W/B**
** A 1/2” ratchet is required (Not available from Viking)
2-1/4” (57 mm)
diameter opening
required in the
ceiling.
Step 2:
Carefully press the wrench upward and
turn slightly to ensure engagement with
the sprinkler wrench flats.
Figure 3: Sprinkler Installation and Proper Wrench Usage
NEVER install the sprinkler by applying the installation
wrench across the frame arms. DO NOT overtighten.
Use only the designated sprinkler wrenches, Viking
Part Numbers 14047W/B** or 14031**. A leak tight seal should be achieved by turning the sprinkler clockwise
1 to 1-1/2 turns beyond finger tight.
Sprinkler
wrench flat
Sprinkler
frame arms
Figure 4: Sprinkler Dimensions and Cover Installation
1/2” (15 mm) NPT
2-3/16”(55 mm)2-3/4” (70 mm)Maximum 2-1/4” (57 mm)Minimum
2-3/4” (70 mm) or
3-5/16” (84 mm)NOTE: Upon sprinkler activation, the deflector descends
to approximately 13/16” (21 mm) below the sprinkler body.
Replaces Form No. F_032107 Rev 21.1
(Adding venting statement (s))
MICROFAST® QUICK
RESPONSE HORIZONTAL
SIDEWALL SPRINKLER
VK305 (K5.6)
TECHNICAL DATA
Page 1 of 6
Form No. F_060914 19.11.21 Rev 19.2
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
1. DESCRIPTION
The Viking Microfast® Quick Response Horizontal Sidewall Sprinkler VK305 is a
small thermosensitive glass bulb spray sprinkler available with various finishes and
temperature ratings to meet design requirements. The special Polyester and Electroless
Nickel PTFE (ENT) coatings can be used in decorative applications where colors are
desired. In addition, these coatings have been investigated for installation in corrosive
atmospheres and are listed/approved as corrosion resistant as indicated in Approval
Charts.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Class 2020
China Approval: Approved according to China GB Standard
Refer to Approval Charts and Design Criteria for listing and approval requirements that must
be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)
Rated to 175 psi (12 bar) water working pressure
Factory tested hydrostatically to 500 psi (34.5 bar)
Nominal K-Factor: 5.6 U.S. (80.6 metric*)
* Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in
kPa, divide the metric K-factor shown by 10.0.
Overall Length: 2-3/4” (68 mm)
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Copper UNS-C19500
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT Coated Sprinklers: Belleville Spring - Exposed, Screw and Pip cap - ENT plated.
Ordering Information: (Also refer to the current Viking price list.)
Order Viking Microfast® Quick Response Horizontal Sidewall Sprinkler VK305 by first adding the appropriate suffix for the sprin-
kler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN
Temperature Suffix: 135 °F / 57 °C = A, 155 °F / 68 °C = B, 175 °F / 79 °C = D, 200 °F / 93 °C = E, and 286 °F / 141 °C = G
For example, sprinkler 12997 with a Brass finish and a 155 °F / 68 °C temperature rating = Part No. 12997AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the Viking website.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 21475M/B (available since 2017).
B. Wrench for recessed and/or wax coated sprinklers: Part No. 13655W/B** (available since 2006)
**A ½” ratchet is required (not available from Viking).
Replaces form F_060914 Rev. 19.1
(Revised China approval.)
MICROFAST® QUICK
RESPONSE HORIZONTAL
SIDEWALL SPRINKLER
VK305 (K5.6)
TECHNICAL DATA
Page 2 of 6
Form No. F_060914 19.11.21 Rev 19.2
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive fusible link disengages, the pip cap and spring are released, and the waterway is opened.
Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control
the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Microfast® Quick Response Horizontal Sidewall Sprinkler VK305 is available through a network of domestic and interna-
tional distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
Figure 1:
Standard Sprinkler Wrench 21475M/B
Wrench Flat
MICROFAST® QUICK
RESPONSE HORIZONTAL
SIDEWALL SPRINKLER
VK305 (K5.6)
TECHNICAL DATA
Page 3 of 6
Form No. F_060914 19.11.21 Rev 19.2
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Figure 2: Wrench 13655W/B for Recessed Sprinklers
Step 1: Carefully slide the
wrench sideways around
the deflector, ensuring en-
gagement with the sprinkler
wrench flats.
Sprinkler wrench 13655W/B**
must be used for installing
wax coated sprinklers.
** A 1/2” ratchet is required
(not available from Viking)Step 2: Carefully press the wrench onto the
sprinkler wrench flats.
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating1
Maximum Ambient
Ceiling Temperature2 Bulb Color
Ordinary 135 °F (57 °C)100 °F (38 °C)Orange
Ordinary 155 °F (68 °C)100 °F (38 °C)Red
Intermediate 175 °F (79 °C)150 °F (65 °C)Yellow
Intermediate 200 °F (93 °C)150 °F (65 °C)Green
High 286 °F (141 °C)225 °F (107 °C)Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion-Resistant Coatings3: White Polyester, Black Polyester, and ENT
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-
ible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only.
For ENT coated sprinklers, the waterway is coated. Note that the spring is exposed on sprinklers with Polyester, and ENT coatings.
MICROFAST® QUICK
RESPONSE HORIZONTAL
SIDEWALL SPRINKLER
VK305 (K5.6)
TECHNICAL DATA
Page 4 of 6
Form No. F_060914 19.11.21 Rev 19.2
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1.)
cULus Listing Requirements:
Quick Response Horizontal Sprinkler VK305 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of
NFPA 13 for sidewall standard spray sprinklers.
• Designed for use in Light and Ordinary Hazard occupancies.
• Locate with the deflector 4” to 12“ (102 mm to 305 mm) below the ceiling.
• Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13.
• Minimum spacing allowed is 6 ft. (1.8 m).
• Align the top of the deflector parallel with the ceiling.
• Locate no less than 4” (102 mm) from end walls.
• Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall.
• The sprinkler installation and obstruction rules contained in NFPA 13 for sidewall standard spray sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Bulletin Form No.
F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with
the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organiza-
tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Approval Chart 1 (UL)
Microfast® Quick Response Horizontal Sidewall Sprinkler VK305
For Light or Ordinary Hazard Occupancies
Maximum 175 PSI (12 Bar) WWP
Deflector must be located 4” to 12” (102 mm to 305 mm) below the ceiling.
Sprinkler
Base Part
Number1
SIN Thread Size Nominal K-Factor Overall Length Listings and Approvals3
(Refer also to UL Design Criteria.)
NPT BSPT U.S.metric2 Inches mm cULus4 China Approval
12997 VK305 1/2”15 mm 5.6 80.6 2-11/16 68 A1W, B1X, C2W, D2Z --
197827 VK305 1/2”--5.6 80.6 2-11/16 68 E3 E3
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
12121 VK305 1/2”15 mm 5.6 80.6 2-11/16 68 A1W, B1X, C2W, D2Z --
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C),
200 °F (93 °C), and 286 °F (141 °C)
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C),
and 200 °F (93 °C)
C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C),
and 286 °F (141 °C)
D - 155 °F (68 °C), 175 °F (79 °C), and 200 °F
(93 °C)
E - 155 °F (68 °C)
Approved Finishes
1 - Brass, Chrome, White Poly-ester5,6,
and Black Polyester5,6
2 - ENT5
3 - Chrome
Approved Escutcheons
W - Installed with standard surface-mounted escutcheons
X - Installed with standard surface-mounted escutch-
eons or recessed with the Viking Micromatic® Model
E-1, E-2, or G-1 Recessed Escutcheon
Z - Installed with standard surface-mounted escutch-
eons or recessed with the Viking Micromatic Model
E-1
Footnotes
1 Base part number shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5 cULus Listed as corrosion-resistant.
6 Other colors are available on request with the same Listings and Approvals as the standard colors.
7 Approved according to China GB Standard.
MICROFAST® QUICK
RESPONSE HORIZONTAL
SIDEWALL SPRINKLER
VK305 (K5.6)
TECHNICAL DATA
Page 5 of 6
Form No. F_060914 19.11.21 Rev 19.2
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)
FM Approval Requirements:
Horizontal Sidewall Sprinkler VK305 is FM Approved as a quick response Non-Storage sidewall sprinkler as indicated in the FM Approval Guide. For
specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM
Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling
slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Bulletin Form No.
F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with
the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar
organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Approval Chart 1 (FM)
Microfast® Quick Response Sidewall Sprinklers
Maximum 175 PSI WWP
Sprinkler
Base Part
Number1
SIN Thread Size Nominal K-Factor Overall Length FM Approvals3,4
(Refer also to Design Criteria below.)NPT BSPT U.S.metric2 Inches mm
12997 VK305 1/2”15 mm 5.6 80.6 2-11/16 68 A1Y, B1X
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
12121 VK305 1/2”15 mm 5.6 80.6 2-11/16 68 A1W, B1X, C2W, D2Z --
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79
°C), 200 °F (93 °C), and 286 °F (141 °C)
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C),
and 200 °F (93 °C)
Approved Finishes
1 - Brass
Approved Escutcheons
X - Installed with standard surface-mounted escutch-
eons or recessed with the Viking Micromatic® Model
E-1, E-2, E-3, or G-1 Recessed Escutcheon
Y - Installed with standard surface-mounted escutch-
eons
Footnotes
1 Base part number shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This table shows the FM Approvals available at the time of printing. Other approvals may be in process.
4 Viking vertical sidewall sprinklers may be installed pendent or upright.
5 Approved according to China GB Standard.
MICROFAST® QUICK
RESPONSE HORIZONTAL
SIDEWALL SPRINKLER
VK305 (K5.6)
TECHNICAL DATA
Page 6 of 6
Form No. F_060914 19.11.21 Rev 19.2
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Figure 4: Sidewall Sprinkler VK305 Dimensions with the Model E-1 and E-2 Recessed Escutcheons
Figure 3: Sidewall Sprinkler Dimensions with a Standard Escutcheon
2-3/4”
(68 mm)2-7/16”
(62 mm)
Installed with a Standard
1/8” Surface-Mounted
Escutcheon
Wall Opening Size:
2-5/16” (58.7 mm) minimum
2-1/2” (63.5 mm) maximum
1-5/8”
(41 mm)
Installed with the
Threaded Model E-2
Recessed Escutcheon
Wall Opening Size:
2-5/16” (58.7 mm) minimum
2-1/2” (63.5 mm) maximum
2-1/8” (54 mm)
2-1/4”
(57 mm)
Maximum
Minimum
2-1/8” (54 mm)
2-5/8”
(67 mm)
Maximum
1-3/4”
(45 mm)
Minimum
Installed with the
Micromatic Model E-1
Recessed Escutcheon
Replaces form F_060914 Rev. 19.1
(Revised China approval.)
QUICK RESPONSE
DRY PENDENT SPRINKLERSTECHNICAL DATA
Form No. F_031793 19.10.14 Rev 19.2
Page 1 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
1. DESCRIPTION
Viking Quick Response Dry Pendent Sprinklers are thermosensitive spray sprinklers
suitable for use in areas subject to freezing. The sprinklers are designed for dry sys-
tems and preaction systems where it is necessary to prevent water or condensation
from entering the drop nipple before sprinkler operation. They may also be installed
in spaces subject to freezing and supplied from a wet system in an adjacent heated
area.
Viking Quick Response Dry Pendent Sprinklers are available in various finishes
and temperature ratings to meet design requirements. The special Polyester and
Electroless Nickel PTFE (ENT) coatings have been investigated for installation in
corrosive atmospheres and are listed/approved as corrosion resistant as indicated
in the Approval Charts. (Note: FM Global has no approval classification for Polyester
coatings as corrosion resistant.)
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Classes 2013 and 2015
NYC Approved: MEA 89-92-E Volume 15
Refer to Approval Chart 1 and Design Criteria on page 105d for cULus Listing requirements, and refer to Approval Chart 2
and Design Criteria on page 105e for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)
Maximum Working Pressure: 175 psi (12 bar).
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1” NPT or 25 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric*) for all listed and approved lengths.
* Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown
by 10.0.
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Covered by the following U.S. Patents: 8,636,075 and 10,220,231
Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Brass UNS-C26000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Compression Screw: Brass UNS-C36000
Pip Cap: Brass UNS-C31400 or UNS-C31600
Pip Cap Adapter: Brass UNS-C36000
Orifice: Copper UNS-C22000 or UNS-C11000
Tube: ERW Hydraulic Steel Tube
Support (Internal): Stainless Steel UNS-S30400
Barrel: Steel Pipe UNS-G10260, Electrodeposited Epoxy Base finish
Barrel End and Threads: QM Brass
Sleeve (for Adjustable Standard style only): Brass UNS-C26000 or UNS-C26800
Escutcheon Materials:
Adjustable Standard Dry Escutcheons: Brass UNS-C26000 or UNS-C26800
Recessed Dry Escutcheons: Cold Rolled Steel UNS-G10080
ENT Coated Adjustable and Recessed Escutcheons: Stainless Steel UNS-S30400
Ordering Information: (Also refer to the current Viking price list.)
Replaces Form F_031793 Rev. 19.1
(Added ENT; updated FM language.)
QUICK RESPONSE
DRY PENDENT SPRINKLERSTECHNICAL DATA
Form No. F_031793 19.10.14 Rev 19.2
Page 2 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Order Quick Response Dry Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish, the appropriate suffix
for the temperature rating, and then the suffix for the length (“A” dimension) to sprinkler base part number. Order in a specific
length noted as the “A” dimension. The “A” dimension is the distance from the face of the fitting (tee) to the desired finished
surface of the ceiling.
These sprinklers are listed and approved in lengths from 1-1/2” to 45-1/2” (38.1 mm to 1,156 mm) for the adjustable standard style, 3” to
47” (76.2 mm to 1,194 mm) for the plain barrel style, and 3-1/4” to 47-1/2” (82.5 mm to 1,207 mm) for the adjustable recessed style.
Lengths exceeding the standard lengths are available, with no approvals, on a “made-to-order” basis: Recessed Dry Pendent up to
65-1/2” (1,664 mm). Adjustable Standard Dry Pendent up to 63-1/2” (1,613 mm). Plain Barrel Dry Pendent up to 65” (1,651 mm).
Contact the manufacturer for more information.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, and ENT = JN
Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G
For example, sprinkler VK176 with a Chrome finish and a 155 °F (68 °C) temperature rating, and “A” length of 10” = Part No.
08383UFB10.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the “Sprinkler Accessories” section of the
Viking data book.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 07297W/B (available since 1991)
B. Wrench for recessed sprinklers: Part No. 07565W/B**
(available since 1991)
**A ½” ratchet is required (not available from Viking).
Sprinkler Guard: Chrome, with no listings or approvals, for installation
on dry pendent sprinklers made after May 1994 only (Part No. 08954).
Replacement Escutcheons:
A. Adjustable Standard Dry Escutcheon: Base Part No. 07741
B. Recessed Dry Escutcheon Cup: Base Part No. 05459A
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in
the glass bulb expands, causing the glass to
shatter, releasing the internal parts to open the
waterway. Water flowing through the sprinkler
orifice strikes the sprinkler deflector, forming a
uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS & MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and
Maintenance requirements.
7. AVAILABILITY
The Viking Quick Response Dry Pendent Sprink-
ler is available through a network of domestic
and international distributors. See The Viking
Corporation web site for the closest distributor
or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current
list price schedule or contact Viking directly.
Figure 1: Standard Sprinkler Wrench 07297W/B
Figure 2: Wrench 07565W/B for Adjustable Recessed Dry Pendent Sprinklers
QUICK RESPONSE
DRY PENDENT SPRINKLERSTECHNICAL DATA
Form No. F_031793 19.10.14 Rev 19.2
Page 3 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating1
Maximum Ambient
Ceiling Temperature2 Bulb Color
Ordinary 155 °F (68 °C)100 °F (38 °C)Red
Intermediate 175 °F (79 °C)150 °F (65 °C)Yellow
Intermediate 200 °F (93 °C)150 °F (65 °C)Green
High 286 °F (141 °C)225 °F (107 °C)Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, and ENT
Corrosion-Resistant Coating3,4: White Polyester and ENT in all temperature ratings
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3 The corrosion-resistant Polyester and ENT coatings have passed the standard corrosion test required by the approving agencies indicated
in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Note: These coatings are NOT cor-
rosion proof. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environ-
ment. Polyester and ENT coatings are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with
Polyester and ENT coatings.
4 When installed in some corrosive environments, the Polyester finish may change color. This natural discoloration over time is not in itself
an indication of corrosion and should not be treated as such. All sprinklers installed in corrosive environments should be replaced or
tested as described in NFPA 25 on a more frequent basis.
Figure 3: Adjustable Standard Dry Pendent Sprinkler
QUICK RESPONSE
DRY PENDENT SPRINKLERSTECHNICAL DATA
Form No. F_031793 19.10.14 Rev 19.2
Page 4 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Approval Chart 1 (UL)
Quick Response Dry Pendent Sprinklers
Maximum 175 PSI (12 bar) WWP
Sprinkler
Base Part No.1 SIN Style Thread Size Nominal K-Factor2 Order Length Increment Listings and Approvals4
(Refer also to Design Criteria below.)
NPT BSP U.S.metric3 Inches mm cULus5 NYC6 VdS LPCB
08383U VK176 Adjustable
Standard
1”--5.6 80.6 1/2”12.7 A1, A5 A1 --------
16457U --25 mm --80.6 1/2”12.7 A1, A5 ----------
08385U VK180 Adjustable
Recessed
1”--5.6 80.6 1/4”6.35 B2, B6 B2 --------
16453U --25 mm --80.6 1/4”6.35 B2, B6 ----------
08387U VK172 Plain
Barrel
1”--5.6 80.6 1/2”12.7 A3 A4 --------
16455U --25 mm --80.6 1/2”12.7 A3 ----------
Approved Temperature Ratings
A - 155 °F (68 °C), 175 °F (79°C), 200 °F (93 °C),
and 286 °F (141 °C)
B - 155 °F (68 °C), 175 °F (79°C), and 200 °F
(93 °C)
Approved Finishes and “A” Dimensions
1 - Chrome or White Polyester7 sprinkler with a Chrome or White Polyester Sleeve and Escutcheon
with “A” dimensions 1-1/2” to 45-1/2” (38.1 mm to 1,156 mm)
2 - Chrome or White Polyester7 with “A” dimensions 3-1/4” to 47-1/2” (82.5 mm to 1,207 mm)
3 - Chrome, Brass, White Polyester7, or ENT 7 with “A” dimensions 3” to 47” (76.2 mm to 1,194 mm)
4 - Chrome or Brass with “A” dimensions 3” to 47” (76.2 mm to 1,194 mm)
5 - ENT7 sprinkler with an ENT7 Sleeve and Escutcheon with “A” dimensions 1-1/2” to 45-1/2”
(38.1 mm to 1,156 mm)
6 - ENT7 with “A” dimensions 3-1/4” to 47-1/2” (82.5 mm to 1,207 mm)
Footnotes
1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 K-Factor applies for standard lengths (“A” Dimensions indicated above).
3 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0.
4 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any
additional approvals.
5 Listed by Underwriter’s Laboratories for use in the U.S. and Canada.
6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 15.
7 cULus Listed as corrosion resistant.
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1 above.)
NOTE: When using CPVC fittings with Viking dry sprinklers, use only new Nibco Model 5012-S-Bl tees. When selecting other CPVC fittings,
contact Viking Technical Services.
cULus Listing Requirements:
Standard Dry Pendent Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for
standard spray sprinklers.
• Designed for use in Light and Ordinary Hazard occupancies.
• The sprinkler installation and obstruction rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form
F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS
or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards,
whenever applicable.
QUICK RESPONSE
DRY PENDENT SPRINKLERSTECHNICAL DATA
Form No. F_031793 19.10.14 Rev 19.2
Page 5 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.comApproval Chart 2 (FM)
Quick Response Dry Pendent Sprinklers Maximum 175 PSI (12 bar) WWP
Sprinkler Base
Part No.1 SIN Style Thread Size Nominal K-Factor2 Order Length Increment FM Approvals4
(Refer also to Design Criteria below.)NPT BSP U.S.metric3 Inches mm
08383U VK176 Adjustable Standard 1”--5.6 80.6 1/2”12.7 A1
16457U --25 mm --80.6 1/2”12.7 A1
08385U VK180 Adjustable Recessed 1”--5.6 80.6 1/4”6.35 B2
16453U --25 mm --80.6 1/4”6.35 B2
08387U VK172 Plain Barrel 1”--5.6 80.6 1/2”12.7 A3
16455U --25 mm --80.6 1/2”12.7 A3
Approved Temperature Ratings
A - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C),
and 286 °F (141 °C)
B - 155 °F (68 °C), 175 °F (79°C), and 200 °F (93 °C)
Approved Finishes and “A” Dimensions
1 - Brass, Chrome, White Polyester, or ENT5 sprinkler with a Brass, Chrome, White Polyester, or
ENT5 Sleeve and Escutcheon with “A” dimensions 1-1/2” to 45-1/2” (38.1 mm to 1,156 mm)
2 - Brass, Chrome, White Polyester, or ENT5 with “A” dimensions 3-1/4” to 47-1/2” (82.5 mm to 1,207 mm)
3 - Brass, Chrome, White Polyester, or ENT5 with “A” dimensions 3” to 47” (76.2 mm to 1,194 mm)
Footnotes
1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 K-Factor applies for standard lengths (“A” Dimensions indicated above).
3 Metric K-Factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
4 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any ad-ditional approvals.
5 FM approved as corrosion resistant.
Figure 4: Adjustable Recessed Dry Pendent Sprinkler Figure 5: Plain Barrel Dry Pendent Sprinkler
DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)
NOTE: When using CPVC fittings with Viking dry sprinklers, use only new Nibco Model 5012-S-Bl tees. When selecting other CPVC fittings, contact Viking Technical Services.
FM Approval Requirements:
The Dry Pendent Sprinklers in the Approval Chart above are FM Approved as quick response Non-storage standard spray sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (includ-ing 2-0) and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
QUICK RESPONSE
DRY PENDENT SPRINKLERSTECHNICAL DATA
Form No. F_031793 19.10.14 Rev 19.2
Page 6 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Figure 6: Dry Pendent Sprinkler Required Minimum Barrel Length Based on Ambient Temperature in the Protected Area
(Adjustable Standard Dry Pendent Sprinkler is Shown)
Figure 7: Dry Sprinkler Seal (Adjustable Standard Dry Pendent Sprinkler is Shown)
Replaces Form F_031793 Rev. 19.1
(Added ENT; updated FM language.)
PROJECT INFORMATION APPROVAL STAMP
Project: Approved
Address: Approved as noted
Contractor: Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
SS-01.18 page 1 SS-SUB-92-v01 20220505
Anvil® Beam Clamps
Universal C-type Clamp (Standard Throat)
Fig. 92 (Formerly Afcon Fig. 100)
Dimensions (In) - Load (Lbs) - Torque (In-Lbs) - Weight (Lbs)
Rod SizeA
Set Screw Size
Torque Value
Max Loads Weight C D E F G HTopBottom
In.In.In.-Lbs.Lbs.Lbs.Lbs.In.In.In.In.In.In.
3/8 3/8 60 500 250 0.34 1 5/16 1 9/16 9/16 13/16 3/8 1/2
1/2 1/2 125 950 760 0.63 1 3/8 1 13/16 1/2 1 1/16 7/16 23/32
Material Specifications
Size Range
3/8" and 1/2"
Material
Ductile iron, hardened steel cup point set screw
and locknut.
Finish
Plain
Zinc Plated (Hot-Dip Galvanized optional)
Service
Recommended for use under roof installations with
bar joist type construction, or for attachment to the
top or bottom flange of structural shapes where
the vertical hanger rod is required to be offset from
the edge of the flange and where the thickness of
joist or flange does not exceed 3/4".
Approvals
Complies with Federal Specification
A-A-1192A (Type 19 & 23), WW-H-171-E (Type 23),
ANSI/MSS SP-69 and MSS SP-58 (Type 19 & 23).
UL, ULC Listed and FM Approved.
How to size
Size of clamp is determined by size of rod to be used.
Installation
Follow recommended set screw torque values
per MSS-SP-69.
Features
• They may be attached to horizontal flanges
of structural members in either the top beam
or bottom beam positions.
• Secured in place by a cup-pointed Set Screw
tightened against the flange. A Jam Nut is
provided for tightening the Set Screw against
the Body Casting.
• Thru tapping of the body casting permits
extended adjustment of the threaded rod.
• Can be used with Fig 89X retaining clip for
seismic applications.
Ordering
Specify rod size, figure number, name of clamp
and finish.
Available with oversized tapped rod hole for Hot
Dip Galvanized finish.
Note:
Maximum temperature of 450° F
Threaded Accessories
116688 All dimensions in charts and on drawings are in inches. Dimensions shown in
parentheses are in millimeters unless otherwise specified.
FFiigguurree BB33220055 TThhrreeaaddeedd RRoodd ((rriigghhtt--hhaanndd tthhrreeaaddss -- bbootthh eennddss))
((AAvvaaiillaabbllee wwiitthh rriigghhtt && lleefftt--hhaanndd tthhrreeaaddss aass BB33220055LL--ssiizzee))
MMaatteerriiaall::Steel
SSttaannddaarrdd FFiinniisshh:: Plain or Electro-Plated
SSeerrvviiccee:: Designed for use in pipe hanger
assemblies.
OOrrddeerriinngg:: Specify part number, length and
finish. (B3205L for left hand threads on one end)
MMaatteerriiaall::Steel
SSttaannddaarrdd FFiinniisshh:: Plain or Electro-Plated
SSeerrvviiccee:: Designed for use in pipe hanger assemblies.
SSttaannddaarrdd LLeennggtthhss ‘‘LL’’:: 36” (91.4cm), 72” (182.9cm),
120” (304.8cm), 144” (365.7cm)
OOrrddeerriinngg:: Specify part number, length and finish.
''AA''
TThhrreeaadd SSiizzee
''TTLL''
''TTLL''
SSppeecciiffyy ''LL''
SSttaannddaarrdd DDeessiiggnn LLooaadd
TThhrreeaadd SSiizzee TThhrreeaadd LLeennggtthh 665500°°FF ((334433°°CC))775500°°FF ((339999°°CC))
PPaarrtt NNoo..''AA''''TTLL''LLbbss..kkNN LLbbss..kkNN
BB33220055--33//88 xx ''LL''33//88""--1166 2211//22""((6633..55))773300 ((33..2255))557722 ((22..5544))
BB33220055--11//22 xx ''LL''11//22""--1133 2211//22""((6633..55))11335500 ((66..0000))11005577 ((44..7700))
BB33220055--55//88 xx ''LL''55//88""--1111 2211//22""((6633..55))22116600 ((99..6611))11669922 ((77..5522))
BB33220055--33//44 xx ''LL''33//44""--1100 33""((7766..22))33223300 ((1144..3377))22553300 ((1111..2255))
BB33220055--77//88 xx ''LL''77//88""--99 3311//22""((8888..99))44448800 ((1199..9933))33550088 ((1155..6600))
BB33220055--11 xx ''LL''11""--88 44""((110011..66))55990000 ((2266..2244))44662200 ((2200..5555))
BB33220055--1111//88 xx ''LL''1111//88""--77 4411//22""((111144..33))77445500 ((3333..1144))55883300 ((2255..9933))
BB33220055--1111//44 xx ''LL''1111//44""--77 55""((112277..00))99550000 ((4422..2255))77444400 ((3333..0099))
BB33220055--1111//22 xx ''LL''1111//22""--66 66""((115522..44))1133880000 ((6611..3388))1100880077 ((4488..0077))
BB33220055--1133//44 xx ''LL''1133//44""--55 77""((117777..88))1188660000 ((8822..7733))1144556666 ((6644..7799))
BB33220055--22 xx ''LL''22""--4411//22 88""((220033..22))2244660000 ((110099..4422))1199662255 ((8877..2299))
BB33220055--2211//44 xx ''LL''2211//44""--4411//22 99""((222288..66))3322330000 ((114433..6677))2255229955 ((111122..5511))
BB33220055--2211//22 xx ''LL''2211//22""--44 1100""((225544..00))3399880000 ((117777..0033))3311116699 ((113388..6644))
BB33220055--2233//44 xx ''LL''2233//44""--44 1111""((227799..44))4499440000 ((221199..7733))3388668877 ((117722..0088))
BB33220055--33 xx ''LL''33""--44 1122""((330044..88))6600110000 ((226677..3322))4477006666 ((220099..3355))
BB33220055--3311//44 xx ''LL''3311//44""--88UUNN 1133""((333300..22))7711990000 ((331199..8811))5566330077 ((225500..4455))
BB33220055--3311//22 xx ''LL''3311//22""--88UUNN 1144""((335555..66))8844770000 ((337766..7744))6666333311 ((229955..0044))
BB33220055--3333//44 xx ''LL''3333//44""--88UUNN 1155""((338811..00))9988550000 ((443388..1133))7777113399 ((334433..1111))Threaded AccessoriesPPaarrtt NNoo..TThhrreeaaddss RReeccoommmmeennddeedd LLooaadd WWtt..//CC FFtt..
&& SSiizzee PPeerr IInncchh LLbbss..kkNN LLbbss..kkgg
AATTRR 11//44”” xx ‘‘LL’’2200 224400 ((11..0077))1122 ((55..4444))
AATTRR 55//1166”” xx ‘‘LL’’1188 440000 ((11..7788))1199 ((88..6622))
AATTRR 33//88”” xx ‘‘LL’’1166 773300 ((33..2244))2299 ((1133..1155))
AATTRR 11//22”” xx ‘‘LL’’1133 11335500 ((66..0000))5533 ((2244..0044))
AATTRR 55//88”” xx ‘‘LL’’1111 22116600 ((99..6600))8899 ((4400..3377))
AATTRR 33//44”” xx ‘‘LL’’1100 33223300 ((1144..3377))112233 ((5555..7799))
AATTRR 77//88”” xx ‘‘LL’’99 44448800 ((1199..9933))117700 ((7777..1111))
AATTRR 11”” xx ‘‘LL’’88 55990000 ((2266..2244))222255 ((110022..0066))
BLine_160-175 7/24/06 5:17 PM Page 168
PROJECT INFORMATION APPROVAL STAMP
Project: Approved
Address: Approved as noted
Contractor: Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
Pipe Hangers & Supports
SS-01.18 page 1 SS-SUB-69-v01 20220325
Adjustable Swivel Ring
Fig. 69 Size Range: ¾" through 8"
Material: Carbon steel
Finish: Strap is Pre-Galvanized
Zinc Material. Nut is Zinc Plated.
Service: Recommended for suspension of
non-insulated stationary pipe line.
Maximum Temperature: 450° F
Approvals: Complies with Federal
Specification A-A-1192A (Type 10),
WW-H-171-E (Type 10), and
ANSI/MSS SP-58 (Type 10).
UL Listed and FM Approved (Sizes ¼" - 8").
Features:
• ¾" - 2" sizes designed for use with steel
and CPVC piping and manufactured with
FBC System Compatible oil.
• Threads are countersunk so that they
cannot become burred or damaged.
• Knurled swivel nut provides vertical
adjustment after piping is in place.
• Captured swivel nut in the 1⁄2" through 6"
sizes. The capture is permanent in the
bottom portion of the band, allowing the
hanger to be opened during installation
if desired, but not allowing the nut to fall
completely out.
Ordering:
Specify size, figure number and name.
Non-captured nut also available
upon request.
Fig. 69: Dimensions (in) • Loads (lbs) • Weight (lbs)
Pipe Size Max Load Weight Rod Size A B C F G Width
1⁄2
300
0.10
3⁄8
27⁄8 2 19⁄16
5⁄8
3⁄4 0.10 23⁄4 17⁄8 15⁄16
1 0.10 29⁄16 111⁄16 1
11⁄4 0.10 25⁄8 13⁄4 7⁄811⁄2 0.10 23⁄4 17⁄8
2 0.11 31⁄4 23⁄8 11⁄8
21⁄2 525 0.20 4 23⁄4 15⁄16
3⁄4
3 0.20 313⁄16 215⁄16 13⁄16
4 650 0.30 411⁄16 313⁄16 19⁄165
1,000
0.54
1⁄2
55⁄16 43⁄8
6 0.65 611⁄16 59⁄16 21⁄4
8 1.00 89⁄16 79⁄16 31⁄4
21/2" through 8" pipe1/2" through 1" pipe 11/4" through 2" pipe
B
C
F
CL
G
A
B
C
CL
G
A
F
A
BCF
CL
G
1/2" through 2" SizeRounded Edge Design 21/2" through 8" Size